KPS1 DG Cable tray not covered. Diesel Generator KPS1-PWE-EG-001 Provide cable tray cover 1 No No
KPS1 DG Abandoned cable without protection. Diesel Generator KPS1-PWE-EG-001 Abandoned cables must be removed 1 No No
KPS1 DG Earthing conductor not connected to cable tray. Diesel Generator KPS1-PWE-EG-001 Cable tray earthing conductor to be connected 1 yes No
KPS1 Permanent tag is not provided for DG Diesel Generator KPS1-PWE-EG-001 Permanent tags need to be installed for DG and tank 1 No No
The DG set is not shown on the as-built drawings, 1All as-built drawings need to be updated to show
KPS1 Diesel Generator KPS1-PWE-EG-001 1 No No
specifically, electrical layout drawings. the actual location of the DG system
Lack of periodically inspection & preventative Provide periodic inspection and preventive
KPS1 Switchgears (MV & LV) KPS1-EEQ-MVS-001~030 1 No No
maintenance program. maintenance program.
Power Transformer protection (mechanical & electrical) must Inter-trip setting for transformer HV & LV sides
KPS1 trip both sides (HV & LV), inter-trip setting (wiring) between Switchgears (MV & LV) KPS1-EEQ-MVS-001~030 should be activated by completing wiring and 1 No No
transformer LV-HV feeders is missing. commissioning.
Lack of Synchro-check function (relay) which affects Synchro-check function need to be activated for the
system reliability, currently only one incomer can supply the
KPS1 Switchgears (MV & LV) KPS1-EEQ-MVS-001~030 MV switchgear to enable operation of both 1 No No
MV SWGR, the other incomer can not be operated because incomers.
of non-availability of the Synchro-check function.
The max. short circuit withstand voltage rating for the Underrate equipment need to be replaced. Value
KPS1 MV equipment is not enough for parallel operation as Switchgears (MV & LV) KPS1-EEQ-MVS-001~030 1 no no
engineering analysis is recommended.
illustrated in APPENDIX (short circuit calculations).
Wrong setting and configuration of some protection Relay coordination study need to be made correctly
KPS1 Switchgears (MV & LV) KPS1-EEQ-MVS-001~030 1 no no
functions, relay coordination is not done correctly. according to short circuit calculation.
VT supervision function is not enabled for all voltage Enable VT supervision function for voltage
KPS1 Switchgears (MV & LV) KPS1-EEQ-MVS-001~030 2 No No
protections. protection.
There is no duct for control wires inside 33KV Wiring ducts to be provided for control wires inside
KPS1 Switchgears (MV & LV) KPS1-EEQ-MVS-001~030 2 Yes No
switchgear control cubicle. cubicle.
Voltmeters are malfunctioning for both AVRs of 33 KV
KPS1 Switchgears (MV & LV) KPS1-EEQ-MVS-001~030 Replace both defected voltmeters of AVRs 1 Yes No
Power Transformers.
Setting of the AVR relays (TAPCON) need to be
KPS1 The setting of AVR relays (TAPCON) is not correct. Switchgears (MV & LV) KPS1-EEQ-MVS-001~030 1 No No
corrected and tested.
KPS1 AVR1 Tap indicator not working properly. Switchgears (MV & LV) KPS1-EEQ-MVS-001~030 Tap indicator need to be replaced. 2 Yes No
KPS1 As-built drawings not in line with actual installation. Switchgears (MV & LV) KPS1-EEQ-MVS-001~030 Update the as-built drawings. 1 No No
Meters including analogue meters, multifunction digital
KPS1 meters and energy counters are not calibrated. No calibration Switchgears (MV & LV) KPS1-EEQ-MVS-001~030 All meters need to be calibrated every single year 1 Yes No
stick or report is found.
Install 2 sets of 2.5 MVAR (Five steps for each)
Load Flow analysis revealed that reactive power is high,
KPS1 Switchgears (MV & LV) KPS1-EEQ-MVS-001~030 capacitor banks to compensate the reactive power 2 Yes Yes
approximately 5 MVAR. and to improve the station power factor
ATS is not available. ATS is required to achieve reliable Provide ATS controller and modify internal wiring
KPS1 Switchgears (MV & LV) KPS1-EEQ-MVS-001~030 1 Yes Yes
power supply. accordingly.
Regarding to this fact that LV circuit breakers are three Install an earth fault protection relay and modify
KPS1 poles a proper earth fault protection system must be Switchgears (MV & LV) KPS1-EEQ-MVS-001~030 1 Yes No
internal wiring accordingly.
provided.
Booster pumps are supplying from KPS1 while they are Supply booster pump from the station that they are
KPS1 Switchgears (MV & LV) KPS1-EEQ-MVS-001~030 1 yes N/A
located outside (in CPS1) and controlled from there. located in.
Lack of periodically inspection & preventative Provide periodic inspection and preventive
KPS1 Switchgears (MV & LV) KPS1-EEQ-MCBR-014~017 1 No No
maintenance program. maintenance program.
Power Transformer protection (mechanical & electrical) must Inter-trip setting for transformer HV & LV sides
KPS1 trip both sides (HV & LV), inter-trip setting (wiring) between Switchgears (MV & LV) KPS1-EEQ-MCBR-014~017 should be activated by completing wiring and 1 No No
transformer LV-HV feeders is missing. commissioning.
Lack of Synchro-check function (relay) which affects system Synchro-check function need to be activated for the
reliability, currently only one incomer can supply the MV
KPS1 Switchgears (MV & LV) KPS1-EEQ-MCBR-014~017 MV switchgear to enable operation of both 1 No No
SWGR, the other incomer can not be operated because of incomers.
non-availability of the Synchro-check function.
The max. short circuit withstand voltage rating for the Underrate equipment need to be replaced. Value
KPS1 MV equipment is not enough for parallel operation as Switchgears (MV & LV) KPS1-EEQ-MCBR-014~017 1 Yes No
engineering analysis is recommended.
illustrated in APPENDIX (short circuit calculations).
Wrong setting and configuration of some protection KPS1-EEQ-MCBR-014~017 Relay coordination study need to be made correctly
KPS1 Switchgears (MV & LV) 1 No No
functions, relay coordination is not done correctly. according to short circuit calculation.
There is no duct for control wires inside 33KV KPS1-EEQ-MCBR-014~017 Wiring ducts to be provided for control wires inside
KPS1 Switchgears (MV & LV) 2 Yes No
switchgear control cubicle. cubicle.
Voltmeters are malfunctioning for both AVRs of 33 KV
KPS1 Switchgears (MV & LV) KPS1-EEQ-MCBR-014~017 Replace both defected voltmeters of AVRs 1 Yes No
Power Transformers.
Setting of the AVR relays (TAPCON) need to be
KPS1 The setting of AVR relays (TAPCON) is not correct. Switchgears (MV & LV) KPS1-EEQ-MCBR-014~017 1 No No
corrected and tested.
KPS1 AVR1 Tap indicator not working properly. Switchgears (MV & LV) KPS1-EEQ-MCBR-014~017 Tap indicator need to be replaced. 2 Yes No
MV cables are connected to the switchgear without
KPS1 Switchgears (MV & LV) KPS1-EEQ-MCBR-014~017 remake MV cables by using cable glands . 1 Yes Yes
glands.
KPS1 As-built drawings not in line with actual installation. Switchgears (MV & LV) KPS1-EEQ-MCBR-014~017 Update the as-built drawings. 1 No No
Meters including analogue meters, multifunction digital
KPS1 meters and energy counters are not calibrated. No calibration Switchgears (MV & LV) KPS1-EEQ-MCBR-014~017 All meters need to be calibrated every single year 1 Yes No
stick or report is found.
Install 2 sets of 2.5 MVAR (Five steps for each)
Load Flow analysis revealed that reactive power is high,
KPS1 Switchgears (MV & LV) KPS1-EEQ-MCBR-014~017 capacitor banks to compensate the reactive power 2 Yes Yes
approximately 5 MVAR. and to improve the station power factor
Re-commission LV switchgear and prepare as-built
KPS1 LV Switchgear is not commissioned properly. Switchgears (MV & LV) KPS1-EEQ-MCBR-014~017 1 No No
drawing accordingly.
LV Switchgear needs another incoming for DG (Please
KPS1 Switchgears (MV & LV) KPS1-EEQ-MCBR-014~017 Add additional incomer to the LV Switchgear. 1 Yes Yes
refer to UniTech’s Recommended SLD)
Provide reliable power supply ( from existing UPS)
Multifunction meters of incomers (KPS1-EEQ-LDV-007 & Switchgears (MV & LV)
KPS1 KPS1-EEQ-MCBR-014~017 for SWG Control system including multifunction 1 Yes Yes
KPS1-EEQ-LDV-009) is out of service. meters.
ATS is not available. ATS is required to achieve reliable Provide ATS controller and modify internal wiring
KPS1 Switchgears (MV & LV) KPS1-EEQ-MCBR-014~017 1 Yes Yes
power supply. accordingly.
Regarding to this fact that LV circuit breakers are three Install an earth fault protection relay and modify
KPS1 poles a proper earth fault protection system must be Switchgears (MV & LV) KPS1-EEQ-MCBR-014~017 1 Yes No
internal wiring accordingly.
provided.
Booster pumps are supplying from KPS1 while they are KPS1-EEQ-MCBR-014~017 Supply booster pumplocated
from the station that they are
KPS1 Switchgears (MV & LV) 1 No No
located outside (in CPS1) and controlled from there. in.
Lack of periodically inspection & preventative Provide periodic inspection and preventive
KPS1 Switchgears (MV & LV) KPS1-EEQ-MCBR-018~030 1 No No
maintenance program. maintenance program.
Power Transformer protection (mechanical & electrical) must Inter-trip setting for transformer HV & LV sides
KPS1 trip both sides (HV & LV), inter-trip setting (wiring) between Switchgears (MV & LV) KPS1-EEQ-MCBR-018~030 should be activated by completing wiring and 1 No No
transformer LV-HV feeders is missing. commissioning.
Lack of Synchro-check function (relay) which affects Synchro-check function need to be activated for the
system reliability, currently only one incomer can supply the
KPS1 Switchgears (MV & LV) KPS1-EEQ-MCBR-018~030 MV switchgear to enable operation of both 1 No No
MV SWGR, the other incomer can not be operated because incomers.
of non-availability of the Synchro-check function.
The max. short circuit withstand voltage rating for the Underrate equipment need to be replaced. Value
KPS1 MV equipment is not enough for parallel operation as Switchgears (MV & LV) KPS1-EEQ-MCBR-018~030 1 no no
engineering analysis is recommended.
illustrated in APPENDIX (short circuit calculations).
Wrong setting and configuration of some protection KPS1-EEQ-MCBR-018~030 Relay coordination study need to be made correctly
KPS1 Switchgears (MV & LV) 1 No No
functions, relay coordination is not done correctly. according to short circuit calculation.
There is no duct for control wires inside 33KV KPS1-EEQ-MCBR-018~030 Wiring ducts to be provided for control wires inside
KPS1 Switchgears (MV & LV) 2 Yes No
switchgear control cubicle. cubicle.
Voltmeters are malfunctioning for both AVRs of 33 KV
KPS1 Switchgears (MV & LV) KPS1-EEQ-MCBR-018~030 Replace both defected voltmeters of AVRs 1 Yes No
Power Transformers.
Setting of the AVR relays (TAPCON) need to be
KPS1 The setting of AVR relays (TAPCON) is not correct. Switchgears (MV & LV) KPS1-EEQ-MCBR-018~030 1 No No
corrected and tested.
KPS1 AVR1 Tap indicator not working properly. Switchgears (MV & LV) KPS1-EEQ-MCBR-018~030 Tap indicator need to be replaced. 2 Yes No
MV cables are connected to the switchgear without
KPS1 Switchgears (MV & LV) KPS1-EEQ-MCBR-018~030 remake MV cables by using cable glands . 1 Yes Yes
glands.
KPS1 As-built drawings not in line with actual installation. Switchgears (MV & LV) KPS1-EEQ-MCBR-018~030 Update the as-built drawings. 1 no no
Meters including analogue meters, multifunction digital
KPS1 meters and energy counters are not calibrated. No calibration Switchgears (MV & LV) KPS1-EEQ-MCBR-018~030 All meters need to be calibrated every single year 1 Yes No
stick or report is found.
Install 2 sets of 2.5 MVAR (Five steps for each)
Load Flow analysis revealed that reactive power is high,
KPS1 Switchgears (MV & LV) KPS1-EEQ-MCBR-018~030 capacitor banks to compensate the reactive power 2 Yes Yes
approximately 5 MVAR. and to improve the station power factor
Re-commission LV switchgear and prepare as-built
KPS1 LV Switchgear is not commissioned properly. Switchgears (MV & LV) KPS1-EEQ-MCBR-018~030 1 No No
drawing accordingly.
LV Switchgear needs another incoming for DG (Please
KPS1 Switchgears (MV & LV) KPS1-EEQ-MCBR-018~030 Add additional incomer to the LV Switchgear. 1 Yes Yes
refer to UniTech’s Recommended SLD)
Provide reliable power supply ( from existing UPS)
Multifunction meters of incomers (KPS1-EEQ-LDV-007 & Switchgears (MV & LV)
KPS1 KPS1-EEQ-MCBR-018~030 for SWG Control system including multifunction 1 yes yes
KPS1-EEQ-LDV-009) is out of service. meters.
ATS is not available. ATS is required to achieve reliable Provide ATS controller and modify internal wiring
KPS1 Switchgears (MV & LV) KPS1-EEQ-MCBR-018~030 1 Yes Yes
power supply. accordingly.
Booster pumps are supplying from KPS1 while they are KPS1-EEQ-MCBR-018~030 Supply booster pumplocated
from the station that they are
KPS1 Switchgears (MV & LV) 1 NO NO
located outside (in CPS1) and controlled from there. in.
Lack of periodically inspection & preventative Provide periodic inspection and preventive
KPS1 Switchgears (MV & LV) KPS1-EEQ-MCBR-031~047 1 No No
maintenance program. maintenance program.
Power Transformer protection (mechanical & electrical) must Inter-trip setting for transformer HV & LV sides
KPS1 trip both sides (HV & LV), inter-trip setting (wiring) between Switchgears (MV & LV) KPS1-EEQ-MCBR-031~047 should be activated by completing wiring and 1 No No
transformer LV-HV feeders is missing. commissioning.
Lack of Synchro-check function (relay) which affects system Synchro-check function need to be activated for the
reliability, currently only one incomer can supply the MV
KPS1 Switchgears (MV & LV) KPS1-EEQ-MCBR-031~047 MV switchgear to enable operation of both 1 No No
SWGR, the other incomer can not be operated because of incomers.
non-availability of the Synchro-check function.
The max. short circuit withstand voltage rating for the Underrate equipment need to be replaced. Value
KPS1 MV equipment is not enough for parallel operation as Switchgears (MV & LV) KPS1-EEQ-MCBR-031~047 1 no no
engineering analysis is recommended.
illustrated in APPENDIX (short circuit calculations).
Wrong setting and configuration of some protection KPS1-EEQ-MCBR-031~047 Relay coordination study need to be made correctly
KPS1 functions, relay coordination is not done correctly. Switchgears (MV & LV) according to short circuit calculation. 1 No No
VT supervision function is not enabled for all voltage Enable VT supervision function for voltage
KPS1 Switchgears (MV & LV) KPS1-EEQ-MCBR-031~047 2 No No
protections. protection.
There is no duct for control wires inside 33KV KPS1-EEQ-MCBR-031~047 Wiring ducts to be provided for control wires inside
KPS1 Switchgears (MV & LV) 2 Yes No
switchgear control cubicle. cubicle.
Voltmeters are malfunctioning for both AVRs of 33 KV
KPS1 Switchgears (MV & LV) KPS1-EEQ-MCBR-031~047 Replace both defected voltmeters of AVRs 1 Yes No
Power Transformers.
Setting of the AVR relays (TAPCON) need to be
KPS1 The setting of AVR relays (TAPCON) is not correct. Switchgears (MV & LV) KPS1-EEQ-MCBR-031~047 1 No No
corrected and tested.
KPS1 AVR1 Tap indicator not working properly. Switchgears (MV & LV) KPS1-EEQ-MCBR-031~047 Tap indicator need to be replaced. 2 Yes No
MV cables are connected to the switchgear without
KPS1 Switchgears (MV & LV) KPS1-EEQ-MCBR-031~047 remake MV cables by using cable glands . 1 Yes Yes
glands.
KPS1 As-built drawings not in line with actual installation. Switchgears (MV & LV) KPS1-EEQ-MCBR-031~047 Update the as-built drawings. 1 No No
Meters including analogue meters, multifunction digital
KPS1 meters and energy counters are not calibrated. No calibration Switchgears (MV & LV) KPS1-EEQ-MCBR-031~047 All meters need to be calibrated every single year 1 Yes No
stick or report is found.
Install 2 sets of 2.5 MVAR (Five steps for each)
Load Flow analysis revealed that reactive power is high,
KPS1 Switchgears (MV & LV) KPS1-EEQ-MCBR-031~047 capacitor banks to compensate the reactive power 2 Yes Yes
approximately 5 MVAR. and to improve the station power factor
Re-commission LV switchgear and prepare as-built
KPS1 LV Switchgear is not commissioned properly. Switchgears (MV & LV) KPS1-EEQ-MCBR-031~047 1 No No
drawing accordingly.
LV Switchgear needs another incoming for DG (Please
KPS1 Switchgears (MV & LV) KPS1-EEQ-MCBR-031~047 Add additional incomer to the LV Switchgear. 1 yes yes
refer to UniTech’s Recommended SLD)
Provide reliable power supply ( from existing UPS)
Multifunction meters of incomers (KPS1-EEQ-LDV-007 & Switchgears (MV & LV)
KPS1 KPS1-EEQ-MCBR-031~047 for SWG Control system including multifunction 1 Yes Yes
KPS1-EEQ-LDV-009) is out of service. meters.
ATS is not available. ATS is required to achieve reliable Provide ATS controller and modify internal wiring
KPS1 Switchgears (MV & LV) KPS1-EEQ-MCBR-031~047 1 Yes Yes
power supply. accordingly.
Regarding to this fact that LV circuit breakers are three Install an earth fault protection relay and modify
KPS1 poles a proper earth fault protection system must be Switchgears (MV & LV) KPS1-EEQ-MCBR-031~047 1 Yes No
internal wiring accordingly.
provided.
Booster pumps are supplying from KPS1 while they are KPS1-EEQ-MCBR-031~047 Supply booster pumplocated
from the station that they are
KPS1 Switchgears (MV & LV) 1 No No
located outside (in CPS1) and controlled from there. in.
Lack of periodically inspection & preventative Provide periodic inspection and preventive
KPS1 maintenance program. Switchgears (MV & LV) KPS1-EEQ-MCBR-048~058 maintenance program. 1 No No
Power Transformer protection (mechanical & electrical) must Inter-trip setting for transformer HV & LV sides
KPS1 trip both sides (HV & LV), inter-trip setting (wiring) between Switchgears (MV & LV) KPS1-EEQ-MCBR-048~058 should be activated by completing wiring and 1 No No
transformer LV-HV feeders is missing. commissioning.
Lack of Synchro-check function (relay) which affects system Synchro-check function need to be activated for the
reliability, currently only one incomer can supply the MV
KPS1 SWGR, the other incomer can not be operated because of Switchgears (MV & LV) KPS1-EEQ-MCBR-048~058 MV switchgear to enable operation of both 1 No No
incomers.
non-availability of the Synchro-check function.
The max. short circuit withstand voltage rating for the Underrate equipment need to be replaced. Value
KPS1 MV equipment is not enough for parallel operation as Switchgears (MV & LV) KPS1-EEQ-MCBR-048~058 1 no no
engineering analysis is recommended.
illustrated in APPENDIX (short circuit calculations).
Wrong setting and configuration of some protection KPS1-EEQ-MCBR-048~058 Relay coordination study need to be made correctly
KPS1 Switchgears (MV & LV) 1 No No
functions, relay coordination is not done correctly. according to short circuit calculation.
VT supervision function is not enabled for all voltage Enable VT supervision function for voltage
KPS1 Switchgears (MV & LV) KPS1-EEQ-MCBR-048~058 2 No No
protections. protection.
There is no duct for control wires inside 33KV KPS1-EEQ-MCBR-048~058 Wiring ducts to be provided for control wires inside
KPS1 Switchgears (MV & LV) 2 Yes No
switchgear control cubicle. cubicle.
Voltmeters are malfunctioning for both AVRs of 33 KV
KPS1 Switchgears (MV & LV) KPS1-EEQ-MCBR-048~058 Replace both defected voltmeters of AVRs 1 Yes No
Power Transformers.
Setting of the AVR relays (TAPCON) need to be
KPS1 The setting of AVR relays (TAPCON) is not correct. Switchgears (MV & LV) KPS1-EEQ-MCBR-048~058 1 No No
corrected and tested.
KPS1 AVR1 Tap indicator not working properly. Switchgears (MV & LV) KPS1-EEQ-MCBR-048~058 Tap indicator need to be replaced. 2 Yes No
KPS1 As-built drawings not in line with actual installation. Switchgears (MV & LV) KPS1-EEQ-MCBR-048~058 Update the as-built drawings. 1 No No
Meters including analogue meters, multifunction digital
KPS1 meters and energy counters are not calibrated. No calibration Switchgears (MV & LV) KPS1-EEQ-MCBR-048~058 All meters need to be calibrated every single year 1 Yes No
stick or report is found.
Install 2 sets of 2.5 MVAR (Five steps for each)
Load Flow analysis revealed that reactive power is high,
KPS1 Switchgears (MV & LV) KPS1-EEQ-MCBR-048~058 capacitor banks to compensate the reactive power 2 Yes Yes
approximately 5 MVAR. and to improve the station power factor
Re-commission LV switchgear and prepare as-built
KPS1 LV Switchgear is not commissioned properly. Switchgears (MV & LV) KPS1-EEQ-MCBR-048~058 1 no no
drawing accordingly.
LV Switchgear needs another incoming for DG (Please
KPS1 Switchgears (MV & LV) KPS1-EEQ-MCBR-048~058 Add additional incomer to the LV Switchgear. 1 Yes Yes
refer to UniTech’s Recommended SLD)
Provide reliable power supply ( from existing UPS)
Multifunction meters of incomers (KPS1-EEQ-LDV-007 & Switchgears (MV & LV)
KPS1 KPS1-EEQ-MCBR-048~058 for SWG Control system including multifunction 1 Yes Yes
KPS1-EEQ-LDV-009) is out of service. meters.
ATS is not available. ATS is required to achieve reliable Provide ATS controller and modify internal wiring
KPS1 Switchgears (MV & LV) KPS1-EEQ-MCBR-048~058 1 Yes Yes
power supply. accordingly.
Regarding to this fact that LV circuit breakers are three Install an earth fault protection relay and modify
KPS1 poles a proper earth fault protection system must be Switchgears (MV & LV) KPS1-EEQ-MCBR-048~058 1 Yes No
internal wiring accordingly.
provided.
Booster pumps are supplying from KPS1 while they are KPS1-EEQ-MCBR-048~058 Supply booster pumplocated
from the station that they are
KPS1 Switchgears (MV & LV) 1 No No
located outside (in CPS1) and controlled from there. in.
Lack of periodically inspection & preventative Provide periodic inspection and preventive
KPS1 Switchgears (MV & LV) KPS1-EEQ-MCBR-059~064 1 No No
maintenance program. maintenance program.
Power Transformer protection (mechanical & electrical) must Inter-trip setting for transformer HV & LV sides
KPS1 trip both sides (HV & LV), inter-trip setting (wiring) between Switchgears (MV & LV) KPS1-EEQ-MCBR-059~064 should be activated by completing wiring and 1 No No
transformer LV-HV feeders is missing. commissioning.
Lack of Synchro-check function (relay) which affects system Synchro-check function need to be activated for the
reliability, currently only one incomer can supply the MV
KPS1 Switchgears (MV & LV) KPS1-EEQ-MCBR-059~064 MV switchgear to enable operation of both 1 No No
SWGR, the other incomer can not be operated because of incomers.
non-availability of the Synchro-check function.
The max. short circuit withstand voltage rating for the Underrate equipment need to be replaced. Value
KPS1 MV equipment is not enough for parallel operation as Switchgears (MV & LV) KPS1-EEQ-MCBR-059~064 1 no no
engineering analysis is recommended.
illustrated in APPENDIX (short circuit calculations).
Wrong setting and configuration of some protection KPS1-EEQ-MCBR-059~064 Relay coordination study need to be made correctly
KPS1 Switchgears (MV & LV) 1 No No
functions, relay coordination is not done correctly. according to short circuit calculation.
VT supervision function is not enabled for all voltage Enable VT supervision function for voltage
KPS1 Switchgears (MV & LV) KPS1-EEQ-MCBR-059~064 2 No No
protections. protection.
There is no duct for control wires inside 33KV KPS1-EEQ-MCBR-059~064 Wiring ducts to be provided for control wires inside
KPS1 Switchgears (MV & LV) 2 Yes No
switchgear control cubicle. cubicle.
Voltmeters are malfunctioning for both AVRs of 33 KV
KPS1 Switchgears (MV & LV) KPS1-EEQ-MCBR-059~064 Replace both defected voltmeters of AVRs 1 Yes No
Power Transformers.
Setting of the AVR relays (TAPCON) need to be
KPS1 The setting of AVR relays (TAPCON) is not correct. Switchgears (MV & LV) KPS1-EEQ-MCBR-059~064 1 No No
corrected and tested.
KPS1 AVR1 Tap indicator not working properly. Switchgears (MV & LV) KPS1-EEQ-MCBR-059~064 Tap indicator need to be replaced. 2 Yes No
KPS1 As-built drawings not in line with actual installation. Switchgears (MV & LV) KPS1-EEQ-MCBR-059~064 Update the as-built drawings. 1 No No
Meters including analogue meters, multifunction digital
KPS1 meters and energy counters are not calibrated. No calibration Switchgears (MV & LV) KPS1-EEQ-MCBR-059~064 All meters need to be calibrated every single year 1 Yes No
stick or report is found.
Install 2 sets of 2.5 MVAR (Five steps for each)
Load Flow analysis revealed that reactive power is high,
KPS1 Switchgears (MV & LV) KPS1-EEQ-MCBR-059~064 capacitor banks to compensate the reactive power 2 Yes Yes
approximately 5 MVAR. and to improve the station power factor
Re-commission LV switchgear and prepare as-built
KPS1 LV Switchgear is not commissioned properly. Switchgears (MV & LV) KPS1-EEQ-MCBR-059~064 1 No No
drawing accordingly.
LV Switchgear needs another incoming for DG (Please
KPS1 Switchgears (MV & LV) KPS1-EEQ-MCBR-059~064 Add additional incomer to the LV Switchgear. 1 Yes Yes
refer to UniTech’s Recommended SLD)
Provide reliable power supply ( from existing UPS)
Multifunction meters of incomers (KPS1-EEQ-LDV-007 & Switchgears (MV & LV)
KPS1 KPS1-EEQ-MCBR-059~064 for SWG Control system including multifunction 1 Yes Yes
KPS1-EEQ-LDV-009) is out of service. meters.
ATS is not available. ATS is required to achieve reliable Provide ATS controller and modify internal wiring
KPS1 Switchgears (MV & LV) KPS1-EEQ-MCBR-059~064 1 Yes Yes
power supply. accordingly.
Regarding to this fact that LV circuit breakers are three Install an earth fault protection relay and modify
KPS1 poles a proper earth fault protection system must be Switchgears (MV & LV) KPS1-EEQ-MCBR-059~064 1 Yes No
internal wiring accordingly.
provided.
Booster pumps are supplying from KPS1 while they are KPS1-EEQ-MCBR-059~064 Supply booster pumplocated
from the station that they are
KPS1 Switchgears (MV & LV) 1 No No
located outside (in CPS1) and controlled from there. in.
Transformer need to be washed and investigated for
KPS1 Transformer is dirty and oil spills in some areas Power Transformer KPS1-PWE-TRA-001 1 No No
oil leak
KPS1 Insufficient cable support at HV side of transformers Power Transformer KPS1-PWE-TRA-001 Install proper cable support for HV side Cables. 1 Yes Yes
KPS1 There is no cable support at LV side Power Transformer KPS1-PWE-TRA-001 Install proper cable support for LV side Cables. 1 Yes Yes
The signals of winding and oil temperature are swapped, The internal wiring need to be changed at related
KPS1 Power Transformer KPS1-PWE-TRA-001 1 No No
causing malfunction of protection alarms SWG cubicle/
Cables are exposed to direct sunlight due to missing
KPS1 Power Transformer KPS1-PWE-TRA-001 Provide cover for the cable tray. 3 Yes No
cover of cable tray
KPS1 Insufficient earthing (only one point provided) Power Transformer KPS1-PWE-TRA-001 Additional earthing connection must be provided. 1 No No
KPS1 Insufficient earthing (only one point provided). Power Transformer KPS1-PWE-TRA-002 Additional earthing connection must be provided. 1 no no
Cable boxes are not insulated properly due to missing Provide missing bolt and fix cable box cover
KPS1 bolts of cover plates and uncovered opening. There are lot of Power Transformer KPS1-PWE-TRA-003 1 Yes No
properly and cover opening.
dust and corrosion spot inside cable box.
KPS1 HV and LV Bushing terminals are corroded. Power Transformer KPS1-PWE-TRA-003 Bushing’s terminals must be replaced. 2 Yes Yes
KPS1 There are not any cable supports at HV and LV sides. Power Transformer KPS1-PWE-TRA-003 Install proper cable supports for HV and LV cables. 1 NO NO
Trip signal of main tank oil level (low-low) is not connected to Main tank oil level trip signal must be connected to
KPS1 Power Transformer KPS1-PWE-TRA-003 1 No No
the related SWG cubicle. the related cubicles.
KPS1 Tap changer indicator is broken. Power Transformer KPS1-PWE-TRA-003 Replace tap changer indicator. 1 Yes Yes
Regarding that the transformer is equipped with on-
Tap changer motor drive is out of service. There is no
KPS1 Power Transformer KPS1-PWE-TRA-003 load tap changer mechanism. Providing AVR relay 1 Yes No
AVR relay to control voltage. and panel is recommended.
KPS1 Some of earthing conductors are damaged. Power Transformer KPS1-PWE-TRA-003 Replace damaged conductors. 2 Yes No
KPS1 Rail-brakes are not installed Power Transformer KPS1-PWE-TRA-003 Install proper rail-brakes 1 NO NO
Transformer is dirty and there are oil spills in some Transformer need to be washed and investigated for
KPS1 Power Transformer KPS1-PWE-DTT-003 2 Yes No
areas. oil leak.
KPS1 Trip and alarm signals of Buchholz relay are swapped. Power Transformer KPS1-PWE-DTT-003 Buchholz relay wiring need to be modify. 1 No No
KPS1 Rail-brake of transformer wheels are not installed. Power Transformer KPS1-PWE-DTT-003 Install proper rail-brakes. 1 NO NO
KPS1 There is a slight oil leaks on the radiator. Power Transformer KPS1-PWE-DTT-003 Repair oil leak. 3 Yes No
Covers of cable boxes (primary and secondary) are not Provide missing bolt and fix cable box cover
KPS1 fixed properly due to missing bolts. Cable boxes are dusty Power Transformer KPS1-PWE-DTT-003 properly 1 Yes No
Transformer is dirty and there are oil spills in some Transformer need to be washed and investigated for
KPS1 Power Transformer KPS1-PWE-DTT-004 2 Yes no
areas. oil leak.
Covers of cable boxes (primary and secondary) are not Provide missing bolt and fix cable box cover
KPS1 Power Transformer KPS1-PWE-DTT-004 1 Yes No
fixed properly due to missing bolts. Cable boxes are dusty. properly.
Trip and alarm signals of Buchholz, winding temperature and The signals must be sent individually. Annunciators
KPS1 pressure relief valve are merged and sent as a trip signal to Power Transformer KPS1-PWE-DTT-004 1 No No
must be install in related cubicles.
circuit breaker.
KPS1 Rail-brake of transformer wheels are not installed. Power Transformer KPS1-PWE-DTT-004 Install proper rail-brakes. 1 NO NO
Separate earthing conductor (directly connected to
KPS1 Improper neutral to earth connection. Power Transformer KPS1-PWE-DTT-004 the main grid) must be provided. Install cable 1 Yes No
ladder’s cover
Cable are exposed to the direct sunlight, there is no
KPS1 Power Transformer KPS1-PWE-DTT-004 provide cable tray and shades. 3 Yes no
cable tray cover
Transformer is dirty and there are oil spills in some Transformer need to be washed and investigated for
KPS1 Power Transformer KPS1-PWE-DTT-005 3 Yes no
areas. oil leak.
Covers of cable boxes (primary and secondary) are not Provide missing bolt and fix cable box cover
KPS1 Power Transformer KPS1-PWE-DTT-005 1 Yes No
fixed properly due to missing bolts. Cable boxes are dusty. properly.
Trip and alarm signals for Buchholz relay and winding The signals must be sent individually. Annunciators
KPS1 temperature and main tank pressure relief valve are merged Power Transformer KPS1-PWE-DTT-005 1 No No
must be install in related cubicles.
and sent as a trip signal to circuit breaker.
KPS1 Rail-brake of transformer wheels are not installed. Power Transformer KPS1-PWE-DTT-005 Install proper rail-brakes. 1 NO NO
Separate earthing conductor (directly connected to
KPS1 Improper neutral to earth connection. Power Transformer KPS1-PWE-DTT-005 1 No No
the main grid) must be provided.
Cable are exposed to the direct sunlight (there is no
KPS1 Power Transformer KPS1-PWE-DTT-005 Install cable ladder’s cover 3 Yes no
cable tray cover)
Transformer is dirty and there are oil spills in some Transformer need to be washed and investigated for
KPS1 Power Transformer KPS1-PWE-DTT-006 3 Yes no
areas. oil leak.
Covers of cable boxes (primary and secondary) are not Provide missing bolt and fix cable box cover
KPS1 Power Transformer KPS1-PWE-DTT-006 1 Yes No
fixed properly due to missing bolts. Cable boxes are dusty. properly.
KPS1 Rail-brake of transformer wheels are not installed. Power Transformer KPS1-PWE-DTT-006 Install proper rail-brakes. 1 NO NO
Disconnect cables from transformer. It would be
Although transformer is not used the primary side is still
KPS1 Power Transformer KPS1-PWE-DTT-006 safer and faster in case of replacement with in 1 No No
connected service transformers
Transformer is dirty and there are oil spills in some Transformer need to be washed and investigated for
KPS1 Power Transformer KPS1-PWE-DTT-007 1 No No
areas. oil leak.
KPS1 There is no support for primary cables. Power Transformer KPS1-PWE-DTT-007 Install proper cables support for primary cables. 1 NO NO
KPS1 There is no support for secondary cables. Power Transformer KPS1-PWE-DTT-007 Install proper cables support for secondary cables. 1 NO NO
Control cable for the mechanical trips and signals not All of mechanical trip and alarm signals must be
KPS1 connected to the related cubicle and abandoned at the cable Power Transformer KPS1-PWE-DTT-007 1 No No
connected to the related cubicle.
gallery.
KPS1 Rail-brake of transformer wheels are not installed. Power Transformer KPS1-PWE-DTT-007 Install proper rail-brake. 1 NO NO
KPS1 Cable are exposed to direct sunlight. Power Transformer KPS1-PWE-DTT-007 Install cable ladder’s cover. 3 Yes no
KPS1 Silica gel needs to be changed Power Transformer KPS1-PWE-DTT-007 Change silica gel. 2 Yes no
KPS1 Poor cable termination. Power Transformer KPS1-PWE-DTT-007 Remake cable termination in a proper way. 1 No No
Oil drain pit size is not match with transformer oil capacity. Make a bigger oil drain pit and fill it by proper size of
KPS1 Power Transformer KPS1-PWE-DTT-007 1 NO NO
Oil drain pit need to be fill by stone stone
Although transformer is not used. The primary is still We recommend to disconnect cables from
KPS1 connected to 6.6KV SWG and secondary cables are Power Transformer KPS1-PWE-DTT-008 transformer and keep it ready as spare transformer 1 No No
abandoned in cable tray. of KPS1-PWE-DTT-00
Transformer is dirty and there are oil spills in some Transformer need to be washed and investigated for
KPS1 Power Transformer KPS1-PWE-DTT-008 3 Yes no
areas. oil leak.
KPS1 Rail-brake of transformer wheels are not installed. Power Transformer KPS1-PWE-DTT-008 Install proper rail-brakes. 1 NO NO
There are some rusts on the gland plates and cable
KPS1 Power Transformer KPS1-PWE-DTT-008 Remove rusts and paint corroded parts . 3 Yes no
boxes.
Size of oil drain pit is not match with transformer oil capacity. Make a bigger oil drain pit and fill it by proper size of
KPS1 Power Transformer KPS1-PWE-DTT-008 1 NO NO
Oil drain pit need to be fill by stone. stone
We recommend to overhaul transformer and use it
KPS1 Transformer is not in service. Power Transformer KPS1-PWE-DTT-009 1 no no
as main LV supplier to increase reliability.
There are a lot of rusts on the main tank and radiators
KPS1 Power Transformer KPS1-PWE-DTT-009 Transformer needs overall painting. 3 Yes no
and cable boxes.
KPS1 There is no support for MV cables. Power Transformer KPS1-PWE-DTT-009 Install proper support for MV cables. 1 NO NO
KPS1 There is no support for LV cables. Power Transformer KPS1-PWE-DTT-009 Install proper support for LV cables. 1 NO NO
Mechanical Trip and alarm signals are not connected to the Connect mechanical trip and alarm signals to the
KPS1 Power Transformer KPS1-PWE-DTT-009 1 No No
related cubicles. related cubicles and perform signal test .
KPS1 Rail-brake of transformer wheels are not installed. Power Transformer KPS1-PWE-DTT-009 Install proper rail-brakes. 1 No No
There are a lot of dust and rusts inside cable boxes. Cable Provide missing bolts and fix the cover of cable
KPS1 boxes is not isolated properly due to missing bolts of cover Power Transformer KPS1-PWE-DTT-009 boxes properly 3 yes No
plates.
KPS1 Permanent tags not provided (stickers installed). Electrical Motors KPS1-MPA-FAS-SSP-023 Install permanent tags of equipment 1 No No
There is no Local/Remote selector switches in local Replaced existing local control boxes with a new
KPS1 Electrical Motors KPS1-MPA-FAS-SSP-023 1 Yes no
control boxes. control boards which is equipped with
KPS1 There is no emergency stop buttons at local. Electrical Motors KPS1-MPA-FAS-SSP-023 provide emergency stop buttons at local. 1 Yes Yes
KPS1 Steel Structures are not earthed. Electrical Motors KPS1-MPA-FAS-SSP-023 Provide earth connection for steel structures 1 Yes No
Replace conventional glands with explosion proof
KPS1 Some conventional glands are used in pump shade area. Electrical Motors KPS1-MPA-FAS-SSP-023 1 Yes Yes
glands.
Some conventional junction boxes are installed in pump Replace conventional junction boxes with explosion
KPS1 Electrical Motors KPS1-MPA-FAS-SSP-023 1 Yes Yes
shade area. proof junction boxes.
Some conventional distribution boards are used in Replaced conventional distribution boards with
KPS1 Electrical Motors KPS1-MPA-FAS-SSP-023 1 Yes Yes
pump shade area. explosion proof boards.
Provide missing bolts and fix covers (doors)
KPS1 Some bolts of ex-boxes are missing. Electrical Motors KPS1-MPA-FAS-SSP-023 1 Yes No
properly.
KPS1 The distribution boards need cable arrangement. Electrical Motors KPS1-MPA-FAS-SSP-023 Re-arrange distribution boards cables. 1 No No
Insufficient earthing connection. Only one earthing
KPS1 Electrical Motors KPS1-MPA-FAS-SSP-023 Provide another earthing connection. 1 YES No
connection to the main grid is provided.
KPS1 Space heater power supply is not provided. Electrical Motors KPS1-MPA-FAS-SSP-023 Provide power supply for space heater. 1 Yes no
Electrical motor is not properly installed. There is gap
KPS1 Electrical Motors KPS1-MPA-FAS-SSP-023 Rectify Electrical motor installation 1 No No
between motor stand and body.
KPS1 Permanent tags not provided (stickers installed). Electrical Motors KPS1-MPA-FAS-SSP-030 Install permanent tags of equipment 1 No No
There is no Local/Remote selector switches in local Replaced existing local control boxes with a new
KPS1 Electrical Motors KPS1-MPA-FAS-SSP-030 1 Yes No
control boxes. control boards which is equipped with
KPS1 There is no emergency stop buttons at local. Electrical Motors KPS1-MPA-FAS-SSP-030 provide emergency stop buttons at local. 1 Yes Yes
KPS1 Steel Structures are not earthed. Electrical Motors KPS1-MPA-FAS-SSP-030 Provide earth connection for steel structures 1 No No
Replace conventional glands with explosion proof
KPS1 Some conventional glands are used in pump shade area. Electrical Motors KPS1-MPA-FAS-SSP-030 1 Yes Yes
glands.
Some conventional junction boxes are installed in pump Replace conventional junction boxes with explosion
KPS1 Electrical Motors KPS1-MPA-FAS-SSP-030 1 Yes Yes
shade area. proof junction boxes.
Some conventional distribution boards are used in Replaced conventional distribution boards with
KPS1 Electrical Motors KPS1-MPA-FAS-SSP-030 1 Yes Yes
pump shade area. explosion proof boards.
Provide missing bolts and fix covers (doors)
KPS1 Some bolts of ex-boxes are missing. Electrical Motors KPS1-MPA-FAS-SSP-030 1 Yes No
properly.
KPS1 The distribution boards need cable arrangement. Electrical Motors KPS1-MPA-FAS-SSP-030 Re-arrange distribution boards cables. 1 No No
KPS1 Motor is under maintenance for a long time: Electrical Motors KPS1-MPA-FAS-SSP-030 Finalize motor maintenance and put it in service. 2 No No
KPS1 Space heater power supply is not provided. Electrical Motors KPS1-MPA-FAS-SSP-030 Provide power supply for space heater 1 Yes No
KPS1 Permanent tags not provided (stickers installed). Electrical Motors KPS1-MPA-FAS-SSP-035 Install permanent tags of equipment 1 No No
There is no Local/Remote selector switches in local Replaced existing local control boxes with a new
KPS1 Electrical Motors KPS1-MPA-FAS-SSP-035 1 Yes No
control boxes. control boards which is equipped with
KPS1 There is no emergency stop buttons at local. Electrical Motors KPS1-MPA-FAS-SSP-035 provide emergency stop buttons at local. 1 Yes Yes
KPS1 Steel Structures are not earthed. Electrical Motors KPS1-MPA-FAS-SSP-035 Provide earth connection for steel structures 1 YES No
Replace conventional glands with explosion proof
KPS1 Some conventional glands are used in pump shade area. Electrical Motors KPS1-MPA-FAS-SSP-035 1 Yes No
glands.
Some conventional junction boxes are installed in pump Replace conventional junction boxes with explosion
KPS1 Electrical Motors KPS1-MPA-FAS-SSP-035 1 Yes Yes
shade area. proof junction boxes.
Some conventional distribution boards are used in Replaced conventional distribution boards with
KPS1 Electrical Motors KPS1-MPA-FAS-SSP-035 1 Yes No
pump shade area. explosion proof boards.
Provide missing bolts and fix covers (doors)
KPS1 Some bolts of ex-boxes are missing. Electrical Motors KPS1-MPA-FAS-SSP-035 properly. 1 Yes No
KPS1 The distribution boards need cable arrangement. Electrical Motors KPS1-MPA-FAS-SSP-035 Re-arrange distribution boards cables. 1 No No
There is no proper busbar inside motor terminal box for Install proper busbar inside the terminal box for a
KPS1 Electrical Motors KPS1-MPA-FAS-SSP-035 1 Yes No
cable connection. proper termination.
Electrical motor is not properly installed. There is gap
KPS1 Electrical Motors KPS1-MPA-FAS-SSP-035 Rectify Electrical motor installation. 1 No No
between motor stand and body.
KPS1 Permanent tags not provided (stickers installed). Electrical Motors KPS1-MPA-FAS-SSP-043 Install permanent tags of equipment 1 No No
There is no Local/Remote selector switches in local Replaced existing local control boxes with a new
KPS1 Electrical Motors KPS1-MPA-FAS-SSP-043 1 Yes No
control boxes. control boards which is equipped with
KPS1 There is no emergency stop buttons at local. Electrical Motors KPS1-MPA-FAS-SSP-043 provide emergency stop buttons at local. 1 Yes Yes
KPS1 Steel Structures are not earthed. Electrical Motors KPS1-MPA-FAS-SSP-043 Provide earth connection for steel structures 1 YES No
Replace conventional glands with explosion proof
KPS1 Some conventional glands are used in pump shade area. Electrical Motors KPS1-MPA-FAS-SSP-043 1 Yes Yes
glands.
Some conventional junction boxes are installed in pump Replace conventional junction boxes with explosion
KPS1 Electrical Motors KPS1-MPA-FAS-SSP-043 1 Yes Yes
shade area. proof junction boxes.
Some conventional distribution boards are used in Replaced conventional distribution boards with
KPS1 Electrical Motors KPS1-MPA-FAS-SSP-043 1 Yes Yes
pump shade area. explosion proof boards.
Provide missing bolts and fix covers (doors)
KPS1 Some bolts of ex-boxes are missing. Electrical Motors KPS1-MPA-FAS-SSP-043 1 Yes No
properly.
KPS1 The distribution boards need cable arrangement. Electrical Motors KPS1-MPA-FAS-SSP-043 Re-arrange distribution boards cables. 1 no no
Insufficient earthing connection. Only one earthing
KPS1 Electrical Motors KPS1-MPA-FAS-SSP-043 Provide another earthing connection. 1 YES No
connection to the main grid is provided.
KPS1 Improper cable glanding (two cables in one gland). Electrical Motors KPS1-MPA-FAS-SSP-043 Remake cable connection. 1 No No
KPS1 Cable handling is really poor. Electrical Motors KPS1-MPA-FAS-SSP-043 Rectify Electrical motor installation. 1 No No
Electrical motor is not properly installed. There is gap Provide cable tray and arrange cables properly
KPS1 Electrical Motors KPS1-MPA-FAS-SSP-043 1 Yes No
between motor stand and body. inside cable tray.
There is no proper busbar inside motor terminal box for Install proper busbar inside the terminal box for
KPS1 Electrical Motors KPS1-MPA-FAS-SSP-043 1 Yes No
cable connection. proper termination.
KPS1 Permanent tags not provided (stickers installed). Electrical Motors KPS1-MPA-FAS-SSP-060 Install permanent tags of equipment 1 No No
There is no Local/Remote selector switches in local Replaced existing local control boxes with a new
KPS1 Electrical Motors KPS1-MPA-FAS-SSP-060 1 Yes No
control boxes. control boards which is equipped with
KPS1 There is no emergency stop buttons at local. Electrical Motors KPS1-MPA-FAS-SSP-060 provide emergency stop buttons at local. 1 Yes Yes
KPS1 Steel Structures are not earthed. Electrical Motors KPS1-MPA-FAS-SSP-060 Provide earth connection for steel structures 1 No No
KPS1 Some conventional glands are used in pump shade area. Electrical Motors KPS1-MPA-FAS-SSP-060 Replace conventional glands with explosion proof 1 Yes Yes
glands.
Some conventional junction boxes are installed in pump Replace conventional junction boxes with explosion
KPS1 Electrical Motors KPS1-MPA-FAS-SSP-060 1 Yes Yes
shade area. proof junction boxes.
Some conventional distribution boards are used in Replaced conventional distribution boards with
KPS1 Electrical Motors KPS1-MPA-FAS-SSP-060 1 Yes Yes
pump shade area. explosion proof boards.
Provide missing bolts and fix covers (doors)
KPS1 Some bolts of ex-boxes are missing. Electrical Motors KPS1-MPA-FAS-SSP-060 1 Yes No
properly.
KPS1 The distribution boards need cable arrangement. Electrical Motors KPS1-MPA-FAS-SSP-060 Re-arrange distribution boards cables. 1 No No
KPS1 Bolts of motor junction box (ex-type) are missing. Electrical Motors KPS1-MPA-FAS-SSP-060 Providing missing bolts and fix the cover properly. 1 Yes No
Replace non-standard material with proper
KPS1 Improper materials are used for alignment. Electrical Motors KPS1-MPA-FAS-SSP-060 2 YES No
material.
Replace the gasket of damaged flange with new
KPS1 There is slight oil leak on the flange of lube oil pipe. Electrical Motors KPS1-MPA-FAS-SSP-060 1 Yes No
gasket.
KPS1 MV Terminal box is corroded. Electrical Motors KPS1-MPA-FAS-SSP-060 Clean rust and paint terminal box. 3 Yes No
KPS1 There is no proper cable tray/ladder for MV cable. Electrical Motors KPS1-MPA-FAS-SSP-060 Provide cable tray/ladder and modify motor 1 Yes No
platform for better cable root .
KPS1 Permanent tags not provided (stickers installed). Electrical Motors KPS1-MPA-FAS-SSP-075 Install permanent tags of equipment 1 No No
There is no Local/Remote selector switches in local Replaced existing local control boxes with a new
KPS1 Electrical Motors KPS1-MPA-FAS-SSP-075 1 Yes No
control boxes. control boards which is equipped with
KPS1 There is no emergency stop buttons at local. Electrical Motors KPS1-MPA-FAS-SSP-075 provide emergency stop buttons at local. 1 Yes Yes
KPS1 Steel Structures are not earthed. Electrical Motors KPS1-MPA-FAS-SSP-075 Provide earth connection for steel structures 1 No No
Replace conventional glands with explosion proof
KPS1 Some conventional glands are used in pump shade area. Electrical Motors KPS1-MPA-FAS-SSP-075 1 Yes Yes
glands.
Some conventional junction boxes are installed in pump Replace conventional junction boxes with explosion
KPS1 Electrical Motors KPS1-MPA-FAS-SSP-075 1 Yes Yes
shade area. proof junction boxes.
Some conventional distribution boards are used in Replaced conventional distribution boards with
KPS1 Electrical Motors KPS1-MPA-FAS-SSP-075 1 Yes Yes
pump shade area. explosion proof boards.
Provide missing bolts and fix covers (doors)
KPS1 Some bolts of ex-boxes are missing. Electrical Motors KPS1-MPA-FAS-SSP-075 1 Yes No
properly.
KPS1 The distribution boards need cable arrangement. Electrical Motors KPS1-MPA-FAS-SSP-075 Re-arrange distribution boards cables. 1 No No
KPS1 Bolts of motor junction box (ex-type) are missing. Electrical Motors KPS1-MPA-FAS-SSP-075 Providing missing bolts and fix the cover properly. 1 Yes No
KPS1 HV Terminal box is corroded. Electrical Motors KPS1-MPA-FAS-SSP-075 Clean rust and paint terminal box. 3 Yes No
Provide cable tray/ladder and modify motor
KPS1 There is no proper cable tray/ladder for MV cable. Electrical Motors KPS1-MPA-FAS-SSP-075 1 Yes No
platform for better cable root .
Replace non-standard material with proper
KPS1 Improper materials are used for alignment Electrical Motors KPS1-MPA-FAS-SSP-075 3 Yes No
material.
KPS1 Permanent tags not provided (stickers installed). Electrical Motors KPS1-MPA-FAS-SSP-085 Install permanent tags of equipment 1 No No
There is no Local/Remote selector switches in local Replaced existing local control boxes with a new
KPS1 Electrical Motors KPS1-MPA-FAS-SSP-085 1 Yes No
control boxes. control boards which is equipped with
KPS1 There is no emergency stop buttons at local. Electrical Motors KPS1-MPA-FAS-SSP-085 provide emergency stop buttons at local. 1 Yes Yes
KPS1 Steel Structures are not earthed. Electrical Motors KPS1-MPA-FAS-SSP-085 Provide earth connection for steel structures 1 YES No
Replace conventional glands with explosion proof
KPS1 Some conventional glands are used in pump shade area. Electrical Motors KPS1-MPA-FAS-SSP-085 1 Yes Yes
glands.
Some conventional junction boxes are installed in pump Replace conventional junction boxes with explosion
KPS1 Electrical Motors KPS1-MPA-FAS-SSP-085 1 Yes Yes
shade area. proof junction boxes.
Some conventional distribution boards are used in Replaced conventional distribution boards with
KPS1 Electrical Motors KPS1-MPA-FAS-SSP-085 1 Yes Yes
pump shade area. explosion proof boards.
Provide missing bolts and fix covers (doors)
KPS1 Some bolts of ex-boxes are missing. Electrical Motors KPS1-MPA-FAS-SSP-085 properly. 1 Yes No
KPS1 The distribution boards need cable arrangement. Electrical Motors KPS1-MPA-FAS-SSP-085 Re-arrange distribution boards cables. 1 No No
Insufficient earthing connection. Only one earthing
KPS1 Electrical Motors KPS1-MPA-FAS-SSP-085 Provide another earthing connection. 1 No No
connection to the main grid is provided.
There is no proper busbar inside motor terminal box for Install proper busbar inside the terminal box for
KPS1 Electrical Motors KPS1-MPA-FAS-SSP-085 1 Yes No
cable connection. proper termination.
Electrical motor is not properly installed. There is gap
KPS1 Electrical Motors KPS1-MPA-FAS-SSP-085 Rectify Electrical motor installation. 1 No No
between motor stand and body.
KPS1 There are scratches and rusts on motor body. Electrical Motors KPS1-MPA-FAS-SSP-085 Electrical Motor need to be painted. 3 YES No
KPS1 permanent tags not provided (stickers installed). Electrical Motors KPS1-MPA-FAS-SSP-085 Provide Permanent tags 1 no no
KPS1 Permanent tags not provided (stickers installed). Electrical Motors KPS1-MPA-FAS-SSP-098 Install permanent tags of equipment 1 no no
There is no Local/Remote selector switches in local Replaced existing local control boxes with a new
KPS1 Electrical Motors KPS1-MPA-FAS-SSP-098 1 Yes No
control boxes. control boards which is equipped with
KPS1 There is no emergency stop buttons at local. Electrical Motors KPS1-MPA-FAS-SSP-098 provide emergency stop buttons at local. 1 Yes Yes
KPS1 Steel Structures are not earthed. Electrical Motors KPS1-MPA-FAS-SSP-098 Provide earth connection for steel structures 1 YES No
Replace conventional glands with explosion proof
KPS1 Some conventional glands are used in pump shade area. Electrical Motors KPS1-MPA-FAS-SSP-098 1 Yes Yes
glands.
Some conventional junction boxes are installed in pump Replace conventional junction boxes with explosion
KPS1 Electrical Motors KPS1-MPA-FAS-SSP-098 1 Yes Yes
shade area. proof junction boxes.
Some conventional distribution boards are used in Replaced conventional distribution boards with
KPS1 Electrical Motors KPS1-MPA-FAS-SSP-098 1 Yes Yes
pump shade area. explosion proof boards.
Provide missing bolts and fix covers (doors)
KPS1 Some bolts of ex-boxes are missing. Electrical Motors KPS1-MPA-FAS-SSP-098 1 Yes No
properly.
KPS1 The distribution boards need cable arrangement. Electrical Motors KPS1-MPA-FAS-SSP-098 Re-arrange distribution boards cables. 1 No No
Insufficient earthing connection. Only one earthing
KPS1 Electrical Motors KPS1-MPA-FAS-SSP-098 Provide another earthing connection. 1 No No
connection to the main grid is provided.
There is no proper busbar inside motor terminal box for Install proper busbar inside the terminal box for
KPS1 Electrical Motors KPS1-MPA-FAS-SSP-098 1 Yes No
cable connection. proper termination.
Electrical motor is not properly installed. There is gap
KPS1 Electrical Motors KPS1-MPA-FAS-SSP-098 Rectify Electrical motor installation. 1 No No
between motor stand and body.
KPS1 Local Control box is installed on cable tray. Electrical Motors KPS1-MPA-FAS-SSP-098 Install local control box on proper stand 1 Yes No
KPS1 Majority of steel structures are not earthed. Earthing System N/A Provide earthing connection for steel structures. 1 YES No
KPS1 14 lighting poles are not earthed. Earthing System N/A Provide earthing connection for lighting poles. 1 Yes No
Provide earthing connection for cable ladders/trays
KPS1 Insufficient earthing connection for cable ladder/trays. Earthing System N/A 1 Yes No
every 20 meters.
KPS1 There are a lot of loose earthing connections. Earthing System N/A Repair loose connection. 2 No No
Provide proper earthing connection for distribution
KPS1 Five distributions boards are not earthed. Earthing System N/A 1 Yes No
boards.
KPS1 Earthing cables/conductors are not arranged properly. Earthing System N/A Re-arrange earthing cables/conductors. 2 No No
KPS1 Insufficient earthing connection for building. Earthing System N/A Providing more earthing connections for building. 1 YES No
KPS1 Fence and main gate are not earthed. Earthing System N/A Provide earthing connection for fence and gate. 1 Yes No
Connect abandoned conductors to the related
KPS1 There are a lot of abandoned earthing cable. Earthing System N/A 1 No No
device.
KPS1 There are corroded connection points Earthing System N/A Remake corroded connection 2 No No
10 pack of 110V batteries (20 cells) are failed in discharging Replaced spoiled (broken) battery packs and repeat
KPS1 UPS and Battery System KPS1-EEQ-UPS-002 1 Yes No
test. charging and discharging test.
KPS1 Insufficient ventilation for battery room. UPS and Battery System KPS1-EEQ-UPS-002 Provide stronger ex-type fan for battery room 1 Yes No
KPS1 There is no eye wash or shower in the battery room. UPS and Battery System KPS1-EEQ-UPS-002 Install eyewash and shower in the battery room. 1 Yes Yes
Battery room cables are not arranged properly due to Provide plastic duct for the cables and re-arranged
KPS1 UPS and Battery System KPS1-EEQ-UPS-002 2 Yes No
missing duct them.
10 pack of 110V batteries (20 cells) are failed in Replaced spoiled (broken) battery packs and repeat
KPS1 UPS and Battery System KPS1-EEQ-NICD-002 1 Yes No
discharging test. charging and discharging test.
KPS1 Insufficient ventilation for battery room. UPS and Battery System KPS1-EEQ-NICD-002 Provide stronger ex-type fan for battery room 1 Yes No
Interior design of E&I building must be revised to
The entrance of battery room must be directly from
KPS1 UPS and Battery System KPS1-EEQ-NICD-002 provide proper location and more room for battery 1 No No
outside. room.
KPS1 There is no eye wash or shower in the battery room. UPS and Battery System KPS1-EEQ-NICD-002 Install eyewash and shower in the battery room. 1 Yes Yes
KPS1 10 pack of 110V batteries (20 cells) are failed in UPS and Battery System KPS1-EEQ-REC-001 Replaced spoiled (broken) battery packs and repeat 1 Yes No
discharging test. charging and discharging test.
KPS1 Insufficient ventilation for battery room. UPS and Battery System KPS1-EEQ-REC-001 Provide stronger ex-type fan for battery room 1 Yes No
Interior design of E&I building must be revised to
The entrance of battery room must be directly from
KPS1 UPS and Battery System KPS1-EEQ-REC-001 provide proper location and more room for battery 1 No No
outside. room.
All electrical equipment installed in battery room
including lighting fixtures, ventilation fan, HVAC systems must UPS and Battery System Replaced the conventional equipment with
KPS1 KPS1-EEQ-REC-001 1 Yes Yes
be explosion proof, currently conventional equipment are explosion proof equipment.
used.
KPS1 There is no eye wash or shower in the battery room. UPS and Battery System KPS1-EEQ-REC-001 Install eyewash and shower in the battery room. 1 Yes Yes
Cable termination for generator control panel is not Cable works for generator control panel need to be
KPS2 done properly, no glands used, and some bare wires are Diesel Generator KPS2-PWE-EG-001 2 No No
done properly to meet IEC requirements.
abandoned without insulation.
Storage tank leakage not carried out properly. Need to
KPS2 Diesel Generator KPS2-PWE-EG-002 Earthing connection to be provided for fuel tank 2 No No
be investigated.
All DG indication instrumentation need to be
KPS2 The storage tank is not earthed. Diesel Generator KPS2-PWE-EG-002 2 YES No
calibrated
KPS2 No sun shade provided for DG sets. Diesel Generator KPS2-PWE-EG-002 Provide sun shade for DG sets 3 YES No
Cable trays and fuel line supply are installed very close
KPS2 to each other and no proper access provided for DG Diesel Generator KPS2-PWE-EG-002 Re-route cable tray near the DG sets 1 No No
operation and maintenance.
Cable termination for generator control panel is not Cable works for generator control panel need to be
KPS2 done properly, no glands used, and some bare wires are Diesel Generator KPS2-PWE-EG-002 2 No No
done properly to meet IEC requirements.
abandoned without insulation.
The national grid feeder to be installed to incomer #
Two incomers available, one is currently connected to
KPS2 LV Switchgear KPS2-EEQ-LVD-001 2 to provide more power supply reliability for the 1 Yes Yes
ATS panel (i.e. DG sets), the other incomer is not being used station.
Permanent tags to be provided and as-built
KPS2 Permanent tags for LV SWBD not provided. LV Switchgear KPS2-EEQ-LVD-001 drawings to be updated in accordance with new 1 No No
tagging system.
Remark
No Action Required
Test Certificate
MCC to be Provided
MCC to be Provided
MCC to be Provided
MCC to be Provided
Data sheet to be Provided
Data sheet to be Provided