Low Voltage Power Control Cables PDF
Low Voltage Power Control Cables PDF
1 OCI/PBPC/Rev-001/010909
INDEX
Introduction ……………………... 4
Cable Construction and Manufacturing Process …………………….. 5
Notes on FRLS and FR Sheathed Cables …………………….. 6
Quality …………………….. 8
XLPE Insulated Power Cables – (Dimensions & Weights) …………………….. 9
Single Core (CU/XLPE/AWA/PVC) …………………….. 10
Single Core (CU/XLPE/PVC) …………………….. 10
2 Core (CU/XLPE/SWA/PVC) …………………….. 11
2 Core (CU/XLPE/PVC) …………………….. 11
3 Core (CU/XLPE/SWA/PVC) …………………….. 12
3 Core (CU/XLPE/PVC) …………………….. 12
4 Core (CU/XLPE/SWA/PVC) …………………….. 13
4 Core (CU/XLPE/PVC) …………………….. 13
3 1/2 Core (CU/XLPE/PVC) …………………….. 14
5 Core (CU/XLPE/SWA/PVC) …………………….. 14
5 Core (CU/XLPE/PVC) …………………….. 15
Single Core (CU/XLPE/AWA/PVC) 1900/3300 V …………………….. 15
3 Core (CU/XLPE/SWA/PVC) 1900/3300 V …………………….. 16
Single Core (AL/XLPE/AWA/PVC) …………………….. 16
Single Core (AL/XLPE/PVC) …………………….. 17
2 Core (AL/XLPE/SWA/PVC) …………………….. 17
2 Core (AL/XLPE/PVC) …………………….. 17
3 Core (AL/XLPE/SWA/PVC) …………………….. 18
3 Core (AL/XLPE/PVC) …………………….. 19
4 Core (AL/XLPE/SWA/PVC) …………………….. 19
4 Core (AL/XLPE/PVC) …………………….. 20
3 1/2 Core (AL/XLPE/PVC) …………………….. 20
5 Core (AL/XLPE/SWA/PVC) …………………….. 21
5 Core (AL/XLPE/PVC) …………………….. 21
2 OCI/PBPC/Rev-001/010909
Dimensions & Weights (Cont.)
PVC Insulated PVC Sheathed Armoured Control Cables – (Dimensions & Weights) …………………….. 35
Control/Auxiliary Cables (CU/PVC/SWA/PVC) …………………….. 36
3 OCI/PBPC/Rev-001/010909
INTRODUCTION
All cable designs covered in this publication generally conform to BS 5467 or IEC 60502 Part-1 for XLPE and BS 6346 or IEC 60502
Part-1 for PVC insulated cables suitable for working voltages 600/1000 Volts and 3300 volts. The general types of cables are:
OCI also manufactures cables conforming to other National or International standards with specific customer requirements. This
includes cables with MDPE Sheath, Fire Retardant Cables (FR), Fire Retardant and Low Smoke PVC Sheathed Cables (FRLS), Fire
Retardant and Reduced Toxic emission PVC sheathed cables (FRRT), Low Smoke Halogen Free Sheathed Cables (LSF). Also, cables
with special PVC compound with anti-termite and anti-rodent properties can also be supplied upon request.
Medium Density Polyethylene (MDPE) Sheathing compound shall meet the requirements of Type ST7 to IEC 60502-1 and Type TS2
as per BS 7655-10.1. All dimensional details of such cables shall be same as cables as per IEC 60502-1 and BS 5467.
LSF Sheathed Cables shall comply with the requirements of BS 6724 and LSF material shall comply with the requirements of Type
ST8 compound to IEC 60502-1 and Type LTS1 compound as per BS 7655.
Based on specific requirement, OCI can also provide copper wire armoured cables or additional tinned copper wires in the armour,
swellable tapes under and over armour, steel tape armoured cables etc.
The above cables are supplied in Wooden/Steel drums covered with Lamiflex lagging as a standard practice.
4 OCI/PBPC/Rev-001/010909
CABLE CONSTRUCTION
&
MANUFACTURING PROCESS
Conductor : Copper or Aluminium used for the Conductors obtained in the form of 8.0 mm Copper rods or
9.5 mm Aluminium rods. After testing, rods are drawn into wires of required sizes. These wires are formed
into final Conductor in the stranding machines under strict Quality surveillance..
Insulation : Cross linked polyethylene compound or PVC is insulated over the conductors by extrusion process.
The raw materials and thicknesses of Insulation are maintained as per standards and conform to
B.S. 5467 / IEC 60502 Part-1 or B.S. 6346 / IEC 60502 Part-1 Standards as the case may be.
Laying up : The insulated cores are laid up with a right hand, or alternating left & right hand, direction of lay in the sequence
of the core numbers or colours. Where necessary non-hygroscopic fillers and binder tape is used to form a
compact and reasonably circular cable.
Bedding : All armoured cables have extruded PVC bedding. PVC used for bedding is compatible with the temperature of
Insulation material.
Armour : When armouring is required, the armour consists of single layer of galvanised steel wires/galvanized steel tapes.
The armour is applied helically as per standards.
Single core cables are armoured with Aluminium Wires or Copper wires based on requirement.
Outersheath : Standard cables are manufactured with Extruded black PVC Type-9 or ST-2. Outersheath is embossed or printed
with the information required by relevant standards.
Special FR, FRLS, FRRT, LSF, MDPE compounds are used for outersheathing of cables, to suit customer’s
specific requirements.
5 OCI/PBPC/Rev-001/010909
NOTES ON FRLS AND FR SHEATHED CABLES
The test requirement is that after all burning has ceased the charred or affected portion shall not have reached within 50mm from
the top clamp.
Special PVC Compounds with Additional Requirements which OCI can provide:
Property Material
FR FRLS FRRT
* Based on specific request, we can provide compounds which can meet flammability requirements of IEC 60332-3-23 and IEC
60332-3-22
6 OCI/PBPC/Rev-001/010909
Q.A. LABORATORY
7 OCI/PBPC/Rev-001/010909
QUALITY:
OCI maintains very high standards of product quality through strict and efficient system. OCI’s Quality department is fully equipped
with modern testing equipment and instruments duly calibrated and are from internationally reputed manufacturers. Quality methods
have been standardized and procedures are established to ensure that every length of cable going out of OCI’s premises is of
consistent quality as per stipulated standards.
OCI has always recognized the importance of quality and its commitment is reflected in each and every product. Quality is an integral
part of production and supply process and is maintained at all stages starting from raw material testing, in-process testing, finished
goods testing, packaging and shipping.
8 OCI/PBPC/Rev-001/010909
XLPE INSULATED POWER CABLES
CONFORMING TO IEC 60502-1 AND BS5467
600/1000 VOLTS
1900/3300 VOLTS
9 OCI/PBPC/Rev-001/010909
SINGLE CORE CABLES - 600/1000V
DIMENSIONS & WEIGHTS
TABLE - 1
CU/XLPE/AWA/PVC - BS 5467
COPPER CONDUCTOR, XLPE INSULATED, AL-WIRE ARMOURED, PVC SHEATHED
TABLE - 2
10 OCI/PBPC/Rev-001/010909
2 CORE CABLES - 600/1000 V
DIMENSIONS & WEIGHTS
TABLE - 3
CU/XLPE/SWA/PVC - BS 5467
COPPER CONDUCTOR, XLPE INSULATED, STEEL WIRE ARMOURED, PVC SHEATHED
Nominal Nominal Nominal Nominal
Nominal Thickness Thickness Diameter Thickness Approx. Approx. Packing
Area of of of of Overall Cable Length
of Insulation Extruded Armour Outer Diameter Weight (Standard)
Conductor Bedding Wire Sheath
mm2 mm mm mm mm mm kg/km mtrs
1.5 # 0.6 0.8 0.9 1.3 13 315 1000
2.5 # 0.7 0.8 0.9 1.4 14 380 1000
4# 0.7 0.8 0.9 1.4 15 460 1000
6# 0.7 0.8 0.9 1.4 16 550 1000
10 # 0.7 0.8 0.9 1.5 18 700 1000
16 # 0.7 0.8 1.25 1.5 20 825 1000
25 0.9 0.8 1.25 1.6 20 975 1000
35 0.9 1.0 1.6 1.7 23 1375 1000
50 1.0 1.0 1.6 1.8 26 1700 1000
70 1.1 1.0 1.6 1.9 28 2200 1000
95 1.1 1.2 2.0 2.0 32 3025 1000
120 1.2 1.2 2.0 2.1 35 3625 500
150 1.4 1.2 2.0 2.2 38 4325 500
185 1.6 1.4 2.5 2.4 42 5550 500
240 1.7 1.4 2.5 2.5 49 7025 500
300 1.8 1.6 2.5 2.6 53 8450 500
400 2.0 1.6 2.5 2.8 58 10350 500
# Circular conductor.
TABLE - 4
11 OCI/PBPC/Rev-001/010909
3 CORE CABLES - 600/1000 V
DIMENSIONS & WEIGHTS
TABLE - 5
CU/XLPE/SWA/PVC - BS 5467
COPPER CONDUCTOR, XLPE INSULATED, STEEL WIRE ARMOURED, PVC SHEATHED
Nominal Nominal ThicknessNominal ThicknessNominal DiameterNominal ThicknessApprox.Approx. Packing
Area of of of of Overall Cable Length
of Insulation Extruded Armour Outer Diameter Weight (Standard)
Conductor Bedding Wire Sheath
mm2 mm mm mm mm mm kg/km mtrs
1.5 # 0.6 0.8 0.9 1.3 14 350 1000
2.5 # 0.7 0.8 0.9 1.4 15 425 1000
4# 0.7 0.8 0.9 1.4 17 500 1000
6# 0.7 0.8 0.9 1.4 18 625 1000
10 # 0.7 0.8 1.25 1.5 20 825 1000
16 # 0.7 0.8 1.25 1.6 22 1000 1000
25 0.9 1.0 1.6 1.7 24 1450 1000
35 0.9 1.0 1.6 1.8 26 1800 1000
50 1.0 1.0 1.6 1.8 29 2250 1000
70 1.1 1.0 1.6 1.9 33 3000 1000
95 1.1 1.2 2.0 2.1 37 4150 500
120 1.2 1.2 2.0 2.2 41 5025 500
150 1.4 1.4 2.5 2.3 46 6450 500
185 1.6 1.4 2.5 2.4 49 7650 500
240 1.7 1.4 2.5 2.6 55 9600 500
300 1.8 1.6 2.5 2.7 61 11725 500
400 2.0 1.6 2.5 2.9 66 14300 250
# Circular conductor
TABLE - 6
12 OCI/PBPC/Rev-001/010909
4 CORE CABLES - 600/1000 V
DIMENSIONS & WEIGHTS
TABLE - 7
CU/XLPE/SWA/PVC - BS 5467
COPPER CONDUCTOR, XLPE INSULATED, STEEL WIRE ARMOURED, PVC SHEATHED
Nominal Nominal Thickness Nominal Thickness Nominal DiameterNominal Thickness Approx. Approx. Packing
Area of of of of Overall Cable Length
of Insulation Extruded Armour Outer Diameter Weight (Standard)
Conductor Bedding Wire Sheath
mm2 mm mm mm mm mm kg/km mtrs
1.5 # 0.6 0.8 0.9 1.3 14 375 1000
2.5 # 0.7 0.8 0.9 1.4 16 475 1000
4# 0.7 0.8 0.9 1.4 17 600 1000
6# 0.7 0.8 1.25 1.5 19 725 1000
10 # 0.7 0.8 1.25 1.5 21 950 1000
16 # 0.7 0.8 1.25 1.6 22 1225 1000
25 0.9 1.0 1.6 1.7 26 1850 1000
35 0.9 1.0 1.6 1.8 29 2300 1000
50 1.0 1.0 1.6 1.9 31 2850 1000
70 1.1 1.2 2.0 2.1 37 4100 500
95 1.1 1.2 2.0 2.2 40 5250 500
120 1.2 1.4 2.5 2.3 47 6875 500
150 1.4 1.4 2.5 2.4 51 8175 500
185 1.6 1.4 2.5 2.6 57 9900 500
240 1.7 1.6 2.5 2.7 62 12400 500
300 1.8 1.6 2.5 2.9 68 15000 250
400 2.0 1.8 3.15 3.2 78 19600 250
# Circular conductor
TABLE - 8
13 OCI/PBPC/Rev-001/010909
31/2 CORE (4 CORE WITH REDUCED NEUTRAL) CABLES- 600/1000 V
DIMENSIONS & WEIGHTS
TABLE - 9
CU/XLPE/SWA/PVC - BS 5467
COPPER CONDUCTOR, XLPE INSULATED, STEEL WIRE ARMOURED, PVC SHEATHED
Nominal
Nominal Area Nominal Thickness of Nominal Nominal Approx. Packing
of the Thickness of Extruded Diameter of Thickness of Overall Approx. Length
Conductor Insulation Bedding armour wire Outer sheath Diameter Cable weight (Standard)
mm2 mm mm mm mm mm kg/km mtrs
1.5 0.6 0.8 0.9 1.4 15 430 1000
2.5 0.7 0.8 0.9 1.4 17 550 1000
4 0.7 0.8 0.9 1.5 18 675 1000
6 0.7 0.8 1.25 1.5 20 825 1000
10 0.7 0.8 1.25 1.6 23 1100 1000
16 0.7 1.0 1.6 1.7 26 1625 1000
25 0.9 1.0 1.6 1.8 30 2275 1000
35 0.9 1.0 1.6 1.9 33 2850 1000
50 1.0 1.2 2.0 2.0 38 3950 500
70 1.1 1.2 2.0 2.2 43 5200 500
14 OCI/PBPC/Rev-001/010909
5 CORE CABLES - 600/1000 V
DIMENSIONS & WEIGHTS
TABLE - 11
CU/XLPE/AWA/PVC - BS 5467
COPPER CONDUCTOR, XLPE INSULATED, ALUMINIUM WIRE ARMOURED, PVC SHEATHED
Nominal Nominal Thickness Nominal Thickness Nominal Nominal Thickness Approx. Approx. Packing
Area of of Armour of Overall Cable Length
of Insulation Extruded Wire Oversheath Diameter Weight (Standard)
Conductor Bedding Diameter
mm2 mm mm mm mm mm kg/km mtrs
50 2.0 0.8 1.25 1.6 21 780 1000
70 2.0 0.8 1.25 1.6 23 1000 1000
95 2.0 0.8 1.25 1.6 25 1270 1000
120 2.0 1.0 1.6 1.7 27 1560 1000
150 2.0 1.0 1.6 1.7 28 1825 1000
185 2.0 1.0 1.6 1.8 30 2200 1000
240 2.0 1.0 1.6 1.8 32 2750 1000
300 2.0 1.0 1.6 1.9 35 3350 1000
400 2.0 1.2 2.0 2.0 37 4150 1000
500 2.2 1.2 2.0 2.1 40 5175 500
630 2.4 1.2 2.0 2.2 44 6550 500
800 2.6 1.4 2.5 2.4 48 8200 500
1000 2.8 1.4 2.5 2.5 52 10125 500
15 OCI/PBPC/Rev-001/010909
3 CORE CABLES - 1900/3300 V
DIMENSIONS & WEIGHTS
TABLE - 13
CU/XLPE/SWA/PVC - IEC: 60502-1
COPPER CONDUCTOR, XLPE INSULATED, STEEL WIRE ARMOURED
Nominal
Nominal Nominal thickness Nominal Nominal Approx. Approx. Packing
Area Thickness of Armour thickness Overall Cable Length
of of Extruded Wire of Diamter Weight (Standard)
Conductor Insulation Bedding Diamter Oversheath
mm2 mm mm mm mm mm kg/km mtrs
16 # 2.0 1.0 1.6 1.8 29 1500 1000
25 2.0 1.0 1.6 1.8 32 1900 1000
35 2.0 1.0 1.6 1.9 31 2125 1000
50 2.0 1.2 2.0 2.0 35 2825 1000
70 2.0 1.2 2.0 2.1 38 3575 1000
95 2.0 1.2 2.0 2.2 41 4475 1000
120 2.0 1.4 2.5 2.3 46 5775 500
150 2.0 1.4 2.5 2.4 49 6725 500
185 2.0 1.4 2.5 2.5 51 7850 500
240 2.0 1.6 2.5 2.6 57 9825 300
300 2.0 1.6 2.5 2.7 62 11825 300
400 2.0 1.6 2.5 2.9 66 14300 300
# Circular conductors
Nominal Nominal Nominal Thickness Nomial Diameter Nominal Thickness Approx. Approx. Packing
Area Thickness of of of Overall Cable Length
of of Extruded Armour Outer Diameter Weight (Standard)
Conductor Insulation Bedding Wire Sheath
mm2 mm mm mm mm mm kg/km mtrs
50 1.0 0.8 0.9 1.5 19 400 1000
70 1.1 0.8 1.25 1.5 21 500 1000
95 1.1 0.8 1.25 1.6 23 625 1000
120 1.2 0.8 1.25 1.6 25 750 1000
150 1.4 1.0 1.6 1.7 27 900 1000
185 1.6 1.0 1.6 1.8 29.0 1050 1000
240 1.7 1.0 1.6 1.8 32 1300 1000
300 1.8 1.0 1.6 1.9 34 1525 1000
400 2.0 1.2 2.0 2.0 39 2000 500
500 2.2 1.2 2.0 2.1 42 2425 500
630 2.4 1.2 2.0 2.2 47 3025 500
800 2.6 1.4 2.5 2.4 53 3925 500
1000 2.8 1.4 2.5 2.5 58 4725 500
16 OCI/PBPC/Rev-001/010909
SINGLE CORE CABLES - 600/1000 V
DIMENSIONS & WEIGHTS
TABLE - 15
AL/XLPE/PVC - BS 7889
ALUMINIUM CONDUCTOR, XLPE INSULATED, PVC SHEATHED (UNARMOURED)
Nominal Nominal Nominal Thickness Nominal Diameter Nominal Thickness Approx. Approx. Packing
Area Thickness of of of Overall Cable Length
of of Extruded Armour Outer Diameter Weight (Standard)
Conductor Insulation Bedding Wire Sheath
mm2 mm mm mm mm mm kg/km mtrs
16# 0.7 0.8 1.25 1.5 20 625 1000
25 0.9 0.8 1.25 1.6 20 675 1000
35 0.9 1.0 1.6 1.7 23 950 1000
50 1.0 1.0 1.6 1.8 26 1125 1000
70 1.1 1.0 1.6 1.9 28 1400 1000
95 1.1 1.2 2.0 2.0 32 1900 1000
120 1.2 1.2 2.0 2.1 35 2200 500
150 1.4 1.2 2.0 2.2 38 2550 500
185 1.6 1.4 2.5 2.4 42 3350 500
240 1.7 1.4 2.5 2.5 49 4125 500
300 1.8 1.6 2.5 2.6 53 4825 500
400 2.0 1.6 2.5 2.8 58 5700 500
# Circular conductors
17 OCI/PBPC/Rev-001/010909
2 CORE CABLES - 600/1000 V
DIMENSIONS & WEIGHTS
TABLE - 17
AL/XLPE/PVC To IEC 60502 Part 1
ALUMINIUM CONDUCTOR, XLPE INSULATED, PVC SHEATHED (UNARMOURED)
# Circular conductor
18 OCI/PBPC/Rev-001/010909
3 CORE CABLES - 600/1000V
DIMENSIONS & WEIGHTS
TABLE - 19
AL/XLPE/PVC To IEC 60502 Part 1
ALUMINIUM CONDUCTOR, XLPE INSULATED, PVC SHEATHED (UNARMOURED)
19 OCI/PBPC/Rev-001/010909
4 CORE CABLES - 600/1000V
DIMENSIONS & WEIGHTS
TABLE - 21
AL/XLPE /PVC To IEC 60502 Part 1
ALUMINIUM CONDUCTOR, XLPE INSULATED, PVC SHEATHED (UNARMOURED)
20 OCI/PBPC/Rev-001/010909
FIVE CORE CABLES - 600/1000 V
DIMENSIONS & WEIGHTS
TABLE - 23
AL/XLPE/SWA/PVC - BS 5467
ALUMINIUM CONDUCTOR, XLPE INSULATED, STEEL WIRE ARMOURED, PVC SHEATHED
Nominal Nominal Nominal Thickness Nominal Diameter Nominal Thickness Approx. Approx. Packing
Area Thickness of of of Overall Cable Length
of of Extruded Armour Outer Diameter Weight (Standard)
Conductor Insulation Bedding Wire Sheath
mm2 mm mm mm mm mm kg/km mtrs
10 0.7 0.8 1.25 1.6 23 800 1000
16 0.7 1.0 1.6 1.7 26 1150 1000
25 0.9 1.0 1.6 1.8 30 1500 1000
35 0.9 1.0 1.6 1.9 33 1750 1000
50 1.0 1.2 2.0 2.0 38 2500 500
70 1.1 1.2 2.0 2.2 43 3125 500
21 OCI/PBPC/Rev-001/010909
PVC INSULATED POWER CABLES
CONFORMING TO IEC 60502-1 AND BS 6346
600/1000 VOLTS
1900/3300 VOLTS
22 OCI/PBPC/Rev-001/010909
SINGLE CORE CABLES -600/1000V
DIMENSIONS & WEIGHTS
TABLE - 25
CU/PVC/AWA/PVC B.S. 6346
COPPER CONDUCTOR, PVC INSULATED, AL-WIRE ARMOURED, PVC SHEATHED
23 OCI/PBPC/Rev-001/010909
2 CORE CABLES - 600/1000V
DIMENSIONS & WEIGHTS
TABLE - 27
CU/PVC/SWA/PVC To BS 6346
COPPER CONDUCTOR, PVC INSULATED, STEEL - WIRE ARMOURED, PVC SHEATHED
Nominal Nominal Nominal Thickness Nominal Diameter Nominal Thickness Approx. Approx. Packing
Area Thickness of of of Overall Cable Length
of of Extruded Armour Outer Diameter Weight (Standard)
Conductor Insulation Bedding Wire Sheath
mm2 mm mm mm mm mm kg/km mtrs
1.5 # 0.6 0.8 0.9 1.4 14 350 1000
2.5 # 0.7 0.8 0.9 1.4 15 400 1000
4# 0.8 0.8 0.9 1.4 17 525 1000
6# 0.8 0.8 0.9 1.5 18 625 1000
10 # 1.0 0.8 1.25 1.6 21 800 1000
16 # 1.0 0.8 1.25 1.6 22 900 1000
25 1.2 1.0 1.6 1.7 23 1200 1000
35 1.2 1.0 1.6 1.8 25 1475 1000
50 1.4 1.0 1.6 1.9 28 1850 1000
70 1.4 1.0 1.6 1.9 30 2350 1000
95 1.6 1.2 2.0 2.1 35 3275 1000
120 1.6 1.2 2.0 2.2 37 3850 1000
150 1.8 1.2 2.0 2.3 40 4575 500
185 2.0 1.4 2.5 2.4 44 5850 500
240 2.2 1.4 2.5 2.5 51 7425 500
300 2.4 1.6 2.5 2.7 56 8950 300
400 2.6 1.6 2.5 2.9 62 10875 250
# Circular conductors
24 OCI/PBPC/Rev-001/010909
3 CORE CABLES - 600/1000 V
DIMENSIONS & WEIGHTS
TABLE - 29
CU/PVC/SWA/PVC BS 6346
COPPER CONDUCTOR, PVC INSULATED, STEEL-WIRE ARMOURED, PVC SHEATHED
Nominal Nominal Nominal Thickness Nominal Diameter Nominal Thickness Approx. Approx. Packing
Area Thickness of of of Overall Cable Length
of of Extruded Armour Outer Diameter Weight (Standard)
Conductor Insulation Bedding Wire Sheath
mm2 mm mm mm mm mm kg/km mtrs
1.5 # 0.6 0.8 0.9 1.4 15 400 1000
2.5 # 0.7 0.8 0.9 1.4 16 450 1000
4# 0.8 0.8 0.9 1.4 18 575 1000
6# 0.8 0.8 1.25 1.5 19 700 1000
10 # 1.0 0.8 1.25 1.6 21 925 1000
16 # 1.0 0.8 1.25 1.6 23 1100 1000
25 1.2 1.0 1.6 1.7 25 1575 1000
35 1.2 1.0 1.6 1.8 28 1950 1000
50 1.4 1.0 1.6 1.9 31 2475 1000
70 1.4 1.2 2.0 2.0 35 3450 1000
95 1.6 1.2 2.0 2.1 39 4425 500
120 1.6 1.2 2.0 2.2 42 5300 500
150 1.8 1.4 2.5 2.4 48 6800 500
185 2.0 1.4 2.5 2.5 51 8050 500
240 2.2 1.6 2.5 2.6 57 10175 300
300 2.4 1.6 2.5 2.8 64 12350 300
400 2.6 1.6 2.5 3.0 69 15400 250
# Circular conductors
25 OCI/PBPC/Rev-001/010909
4 CORE CABLES - 600/1000 V
DIMENSIONS & WEIGHTS
TABLE - 31
CU/PVC/SWA/PVC BS 6346
COPPER CONDUCTOR, PVC INSULATED, STEEL-WIRE ARMOURED, PVC SHEATHED
Nominal Nominal Nominal Thickness Nominal Diameter Nominal Thickness Approx. Approx. Packing
Area Thickness of of of Overall Cable Length
of of Extruded Armour Outer Diameter Weight (Standard)
Conductor Insulation Bedding Wire Sheath
mm2 mm mm mm mm mm kg/km mtrs
1.5 # 0.6 0.8 0.9 1.4 15 400 1000
2.5 # 0.7 0.8 0.9 1.4 16 500 1000
4# 0.8 0.8 1.25 1.5 18 650 1000
6# 0.8 0.8 1.25 1.5 19 775 1000
10 # 1.0 0.8 1.25 1.6 22 1050 1000
16 1.0 1.0 1.6 1.7 26 1500 1000
25 1.2 1.0 1.6 1.8 28 2000 1000
35 1.2 1.0 1.6 1.9 30 2450 1000
50 1.4 1.2 2.0 2.0 34 3350 1000
70 1.4 1.2 2.0 2.1 38 4325 500
95 1.6 1.2 2.0 2.2 43 5600 500
120 1.6 1.4 2.5 2.4 49 7275 500
150 1.8 1.4 2.5 2.5 53 8600 500
185 2.0 1.6 2.5 2.6 59 10450 500
240 2.2 1.6 2.5 2.8 65 13075 500
300 2.4 1.6 2.5 3.0 68 15275 250
400 2.6 1.8 3.15 3.3 78 19525 250
# Circular conductors
26 OCI/PBPC/Rev-001/010909
31/2 CORE (4 CORE WITH REDUCED NEUTRAL) CABLES- 600/1000 V
DIMENSIONS & WEIGHTS
TABLE - 33
CU/PVC/PVC To IEC 60502 Part 1
COPPER CONDUCTOR, PVC INSULATED, PVC SHEATHED (UNARMOURED)
Nominal Nominal Nominal Thickness Nominal Diameter Nominal Thickness Approx. Approx. Packing
Area Thickness of of of Overall Cable Length
of of Extruded Armour Outer Diameter Weight (Standard)
Conductor Insulation Bedding Wire Sheath
mm2 mm mm mm mm mm kg/km mtrs
10 1.0 1.0 1.6 1.7 25 1150 1000
16 1.0 1.0 1.6 1.7 27 1600 1000
25 1.2 1.0 1.6 1.9 32 1900 1000
35 1.2 1.0 1.6 1.9 34 3000 1000
50 1.4 1.2 2.0 2.1 40 4200 500
70 1.4 1.2 2.0 2.2 45 5400 500
27 OCI/PBPC/Rev-001/010909
FIVE CORE CABLES - 600/1000 V
DIMENSIONS & WEIGHTS
TABLE - 35
CU/PVC/PVC - IEC: 60502
COPPER CONDUCTOR, PVC INSULATED, PVC SHEATHED (UNARMOURED)
Nominal Nominal Nominal Thickness Nominal Diameter Nominal Thickness Approx. Approx. Packing
Area Thickness of of of Overall Cable Length
of of Extruded Armour Over Diameter Weight (Standard)
Conductor Insulation Bedding Wire Sheath
mm2 mm mm mm mm mm kg/km m
50 2.2 0.8 1.25 1.6 20 750 1000
70 2.2 0.8 1.25 1.6 22 975 1000
95 2.2 1.0 1.6 1.7 24 1275 1000
120 2.2 1.0 1.6 1.7 26 1575 1000
150 2.2 1.0 1.6 1.8 28 1875 1000
185 2.2 1.0 1.6 1.8 30 2250 1000
240 2.2 1.0 1.6 1.9 33 2875 1000
300 2.4 1.0 1.6 1.9 35 3500 500
400 2.6 1.2 2.0 2.1 40 4500 500
500 2.8 1.2 2.0 2.1 43 5625 500
630 2.8 1.2 2.0 2.2 47 7050 500
800 2.8 1.4 2.5 2.4 53 9050 500
1000 3.0 1.4 2.5 2.5 58 11100 500
28 OCI/PBPC/Rev-001/010909
3 CORE CABLES - 1900/3300 V
DIMENSIONS & WEIGHTS
TABLE - 37
CU/PVC/SWA/PVC BS 6346
COPPER CONDUCTOR, PVC INSULATED, STEEL WIRE ARMOURED, PVC SHEATHED
Nominal Nominal Nominal Thickness Nominal Diameter Nominal Thickness Approx. Approx. Packing
Area Thickness of of of Overall Cable Length
of of Extruded Armour Over Diameter Weight (Standard)
Conductor Insulation Bedding Wire Sheath
mm2 mm mm mm mm mm kg/km m
16 # 2.2 1.0 1.6 1.8 29 1575 1000
25 # 2.2 1.0 1.6 1.8 32 1975 1000
35 2.2 1.0 1.6 1.9 32 2175 1000
50 2.2 1.2 2.0 2.0 36 2925 500
70 2.2 1.2 2.0 2.1 39 3625 500
95 2.2 1.2 2.0 2.2 42 4550 500
120 2.2 1.4 2.5 2.3 47 5875 500
150 2.2 1.4 2.5 2.4 50 6825 500
185 2.2 1.4 2.5 2.5 51 7925 500
240 2.2 1.6 2.5 2.6 57 9925 500
300 2.4 1.6 2.5 2.8 64 12050 500
400 2.6 1.6 2.5 3.0 69 14650 250
# Circular conductors
Nominal Nominal Nominal Thickness Nominal Diameter Nominal Thickness Approx. Approx. Packing
Area Thickness of of of Overall Cable Length
of of Extruded Armour Over Diameter Weight (Standard)
Conductor Insulation Bedding Wire Sheath
mm2 mm mm mm mm mm kg/km mtrs
50 1.4 0.8 1.25 1.5 20 475 1000
70 1.4 0.8 1.25 1.6 22 575 1000
95 1.6 0.8 1.25 1.6 24 700 1000
120 1.6 1.0 1.6 1.7 26 850 1000
150 1.8 1.0 1.6 1.7 28 1000 1000
185 2.0 1.0 1.6 1.8 30 1175 1000
240 2.2 1.0 1.6 1.9 33 1450 1000
300 2.4 1.0 1.6 1.9 36 1700 1000
400 2.6 1.2 2.0 2.1 40 2200 1000
500 2.8 1.2 2.0 2.1 43 2650 1000
630 2.8 1.2 2.0 2.2 47 3225 1000
800 2.8 1.4 2.5 2.4 53 4150 1000
1000 3.0 1.4 2.5 2.5 58 4975 300
29 OCI/PBPC/Rev-001/010909
SINGLE CORE CABLES - 600/1000 V
DIMENSIONS & WEIGHTS
TABLE - 39
AL/PVC/PVC To IEC 60502 Part 1
ALUMINIUM CONDUCTOR, PVC INSULATED, PVC SHEATHED (UNARMOURED)
Nominal Nominal Nominal Thickness Nominal Diameter Nominal Thickness Approx. Approx. Packing
Area Thickness of of of Overall Cable Length
of of Extruded Armour Over Diameter Weight (Standard)
Conductor Insulation Bedding Wire Sheath
mm 2
mm mm mm mm mm kg/km mtrs
16 # 1.0 0.8 1.25 1.6 22 700 1000
25 1.2 1.0 1.6 1.7 23 900 1000
35 1.2 1.0 1.6 1.8 25 1050 1000
50 1.4 1.0 1.6 1.9 28 1300 1000
70 1.4 1.0 1.6 1.9 30 1525 1000
95 1.6 1.2 2.0 2.1 35 2150 1000
120 1.6 1.2 2.0 2.2 37 2425 1000
150 1.8 1.2 2.0 2.3 40 2800 1000
185 2.0 1.4 2.5 2.4 44 3650 1000
240 2.2 1.4 2.5 2.5 51 4550 1000
300 2.4 1.6 2.5 2.7 56 5350 500
400 2.6 1.6 2.5 2.9 62 6250 500
# Circular conductors
30 OCI/PBPC/Rev-001/010909
2 CORE CABLES - 600/1000 V
DIMENSIONS & WEIGHTS
TABLE - 41
AL/PVC/PVC To IEC 60502 Part 1
ALUMINIUM CONDUCTOR, PVC INSULATED, PVC SHEATHED (UNARMOURED)
Nominal Nominal Nominal Thickness Nominal Diameter Nominal Thickness Approx. Approx. Packing
Area Thickness of of of Overall Cable Length
of of Extruded Armour Over Diameter Weight (Standard)
Conductor Insulation Bedding Wire Sheath
mm2 mm mm mm mm mm kg/km mtrs
16 # 1.0 0.8 1.25 1.6 23 825 1000
25 1.2 1.0 1.6 1.7 25 1100 1000
35 1.2 1.0 1.6 1.8 28 1325 1000
50 1.4 1.0 1.6 1.9 31 1600 1000
70 1.4 1.2 2.0 2.0 35 2225 500
95 1.6 1.2 2.0 2.1 39 2725 500
120 1.6 1.2 2.0 2.2 42 3175 500
150 1.8 1.4 2.5 2.4 48 4150 500
185 2.0 1.4 2.5 2.5 51 4775 500
240 2.2 1.6 2.5 2.6 57 5850 500
300 2.4 1.6 2.5 2.8 64 6900 500
400 2.6 1.6 2.5 3.0 69 8075 250
# Circular conductors
31 OCI/PBPC/Rev-001/010909
3 CORE CABLES - 600/1000 V
DIMENSIONS & WEIGHTS
TABLE - 43
AL/PVC/PVC to IEC 60502 Part 1
ALUMINIUM CONDUCTOR, PVC INSULATED, PVC SHEATHED (UNARMOURED)
Nominal Nominal Nominal Thickness Nominal Diameter Nominal Thickness Approx. Approx. Packing
Area Thickness of of of Overall Cable Length
of of Extruded Armour Over Diameter Weight (Standard)
Conductor Insulation Bedding Wire Sheath
mm 2
mm mm mm mm mm kg/km mtrs
25 1.2 1.0 1.6 1.8 28 1375 1000
35 1.2 1.0 1.6 1.9 30 1600 1000
50 1.4 1.2 2.0 2.0 34 2225 1000
70 1.4 1.2 2.0 2.1 38 2700 1000
95 1.6 1.2 2.0 2.2 43 3350 1000
120 1.6 1.4 2.5 2.4 49 4400 1000
150 1.8 1.4 2.5 2.5 53 5075 500
185 2.0 1.6 2.5 2.6 59 6075 500
240 2.2 1.6 2.5 2.8 65 7300 500
300 2.4 1.6 2.5 3.0 68 8550 250
400 2.6 1.8 3.15 3.3 78 11350 250
32 OCI/PBPC/Rev-001/010909
4 CORE CABLES - 600/1000 V
DIMENSIONS & WEIGHTS
TABLE - 45
AL/PVC/PVC to IEC 60502 Part 1
ALUMINIUM CONDUCTOR, PVC INSULATED, PVC SHEATHED (UNARMOURED)
33 OCI/PBPC/Rev-001/010909
FIVE CORE CABLES - 600/1000 V
DIMENSIONS & WEIGHTS
TABLE - 47
AL/PVC/SWA/PVC to IEC 60502 Part 1
ALUMINIUM CONDUCTOR, PVC INSULATED, STEEL WIRE ARMOURED PVC SHEATHED
Nominal Nominal Nominal Thickness Nominal Diameter Nominal Thickness Approx. Approx. Packing
Area Thickness of of of Overall Cable Length
of of Extruded Armour Over Diameter Weight (Standard)
Conductor Insulation Bedding Wire Sheath
mm2 mm mm mm mm mm kg/km mtrs
10 1.0 1.0 1.6 1.7 25 650 1000
16 1.0 1.0 1.6 1.7 27 900 1000
25 1.2 1.0 1.6 1.9 32 1400 1000
35 1.2 1.0 1.6 1.9 34 1500 1000
50 1.4 1.2 2.0 2.1 40 2100 500
70 1.4 1.2 2.0 2.2 45 2650 500
34 OCI/PBPC/Rev-001/010909
PVC INSULATED PVC SHEATED
ARMOURED CONTROL CABLES
35 OCI/PBPC/Rev-001/010909
CONTROL/AUXILIARY CABLES
DIMENSIONS & WEIGHTS - 1.5mm2 (stranded)
TABLE - 49
No. Nominal Nominal Thickness Nominal Diameter Nominal Thickness Approx. Approx. Packing
of Thickness of of of Overall Cable Length
Cores of Extruded Armour Over Diameter Weight (Standard)
Insulation Bedding Wire Sheath
mm mm mm mm mm kg/km mtrs
5 0.6 0.8 0.9 1.4 14 375 1000
6 0.6 0.8 0.9 1.4 15 400 1000
7 0.6 0.8 0.9 1.4 16 500 1000
9 0.6 0.8 0.9 1.5 18 625 1000
12 0.6 0.8 1.25 1.5 19 725 1000
19 0.6 0.8 1.25 1.6 22 975 1000
27 0.6 1.0 1.6 1.7 26 1450 1000
37 0.6 1.0 1.6 1.8 29 1750 1000
48 0.6 1.0 1.6 1.9 32 2100 1000
61 0.6 1.2 2.0 2.1 35 2500 500
No. Nominal Nominal Thickness Nominal Diameter Nominal Thickness Approx. Approx. Packing
of Thickness of of of Overall Cable Length
Cores of Extruded Armour Over Diameter Weight (Standard)
Insulation Bedding Wire Sheath
mm mm mm mm mm kg/km mtrs
2 0.6 0.8 0.9 1.3 12 250 1000
3 0.6 0.8 0.9 1.3 13 275 1000
4 0.6 0.8 0.9 1.3 14 325 1000
5 0.6 0.8 0.9 1.4 14 375 1000
7 0.6 0.8 0.9 1.4 16 500 1000
12 0.6 0.8 1.25 1.5 19 725 1000
19 0.6 0.8 1.25 1.6 22 975 1000
27 0.6 1.0 1.6 1.7 26 1450 1000
37 0.6 1.0 1.6 1.8 29 1750 1000
48 0.6 1.0 1.6 1.9 32 2100 1000
36 OCI/PBPC/Rev-001/010909
DIMENSIONS & WEIGHTS - SIZE 1.5 mm2 (stranded)
TABLE - 51
No. Nominal Nominal Thickness Nominal Diameter Nominal Thickness Approx. Approx. Packing
of Thickness of of of Overall Cable Length
Cores of Extruded Armour Over Diameter Weight (Standard)
Insulation Bedding Wire Sheath
Nos. mm mm mm mm mm kg/km mtrs
5 0.7 0.8 0.9 1.4 17 575 1000
6 0.7 0.8 1.25 1.5 18 625 1000
7 0.7 0.8 1.25 1.5 18 650 1000
9 0.7 0.8 1.25 1.6 21 825 1000
12 0.7 0.8 1.25 1.6 22 975 1000
19 0.7 1.0 1.6 1.7 26 1500 1000
27 0.7 1.0 1.6 1.8 30 1925 1000
37 0.7 1.0 1.6 1.9 33 2375 1000
48 0.7 1.2 2.0 2.1 36 2625 1000
61 0.7 1.2 2.0 2.2 39 3150 500
37 OCI/PBPC/Rev-001/010909
38 OCI/PBPC/Rev-001/010909
39 OCI/PBPC/Rev-001/010909
DIMENSIONS & WEIGHTS - SIZE 2.5 mm2 (solid)
TABLE - 53
SOLID COPPER CONDUCTOR, PVC INSULATED, STEEL WIRE ARMOURED, PVC SHEATHED
No. Nominal Nominal Thickness Nominal Diameter Nominal Thickness Approx. Approx. Packing
of Thickness of of of Overall Cable Length
Cores of Extruded Armour Outer Diameter Weight (Standard)
Insulation Bedding Wire Sheath
mm mm mm mm mm kg/km m
2 0.7 0.8 0.9 1.4 17 575 1000
3 0.7 0.8 0.9 1.4 18 625 1000
4 0.7 0.8 0.9 1.4 18 650 1000
5 0.7 0.8 0.9 1.4 21 825 1000
7 0.7 0.8 1.25 1.5 22 975 1000
12 0.7 0.8 1.25 1.6 26 1450 1000
19 0.7 0.8 1.6 1.7 30 1925 1000
27 0.7 1.0 1.6 1.8 33 2375 1000
37 0.7 1.0 1.6 1.9 36 2625 1000
48 0.7 1.0 2.0 2.1 39 3150 1000
40 OCI/PBPC/Rev-001/010909
Current rating of Cables:
Current rating of Cables given below are based on the ERA (Electrical Research Association) report.
ERA’s report is accepted world wide and hence this report of current carrying capacity is referred by
TABLE - 55
Operating Conditions
Ambient air temp. 50˚C
Ground temp. 35˚C
Depth of Laying 0.50 m
Thermal resistivity of Soil 1.2 K.m/W
41 OCI/PBPC/Rev-001/010909
TABLE - 55A
Operating Conditions
Ambient air temp. 50˚C
Ground temp. 35˚C
Depth of Laying 0.50 m
Thermal resistivity of Soil 1.2 K.m/W
42 OCI/PBPC/Rev-001/010909
TABLE - 56
4 30 30 39 37 16.5
6 39 39 49 45 10.24
10 53 53 65 62 6.84
16 72 72 84 79 4.2
25 94 94 109 103 2.7
35 118 118 127 123 1.93
50 129 135 152 153 1.44
70 165 172 187 186 1.0
95 204 211 224 219 0.73
120 237 245 255 248 0.59
150 274 282 285 271 0.49
185 319 325 322 301 0.40
240 381 385 372 341 0.32
300 442 441 418 377 0.27
400 487 487 473 426 0.25
500 538 538 536 483 0.21
630 610 610 609 549 0.19
800 690 690 689 622 0.18
1000 775 775 772 697 0.17
Operating Conditions
Ambient air temp. 50˚C
Ground temp. 35˚C
Depth of Laying 0.50 m
Thermal resistivity of Soil 1.2 K.m/W
43 OCI/PBPC/Rev-001/010909
TABLE - 56A
Operating Conditions
Ambient air temp. 50 'C
Ground temp. 35 'C
Depth of Laying 0.50 m
Thermal resistivity of Soil 1.2 K.m/W
44 OCI/PBPC/Rev-001/010909
TABLE - 57
Operating Conditions
Ambient air temp. 50˚C
Ground temp. 35˚C
Depth of Laying 0.50 m
Thermal resistivity of Soil 1.2 K.m/W
45 OCI/PBPC/Rev-001/010909
TABLE - 57A
Operating Conditions
Ambient air temp. 50˚C
Ground temp. 35˚C
Depth of Laying 0.50 m
Thermal resistivity of Soil 1.2 K.m/W
46 OCI/PBPC/Rev-001/010909
TABLE - 58
Operating Conditions
Ambient air temp. 50˚C
Ground temp. 35˚C
Depth of Laying 0.50 m
Thermal resistivity of Soil 1.2 K.m/W
47 OCI/PBPC/Rev-001/010909
TABLE - 58A
Operating Conditions
Ambient air temp. 50˚C
Ground temp. 35˚C
Depth of Laying 0.50 m
Thermal resistivity of Soil 1.2 K.m/W
48 OCI/PBPC/Rev-001/010909
TABLE - 59
16 52 52 69 65 3.97
25 69 69 90 85 2.50
Operating Conditions
Ambient air temp. 50 'C
Ground temp. 35 'C
Depth of Laying 0.50 m
Thermal resistivity of Soil 1.2 K.m/W
49 OCI/PBPC/Rev-001/010909
TABLE - 59A
16 50 52 73 60 4.6
25 64 66 94 77 2.89
35 78 80 114 92 2.09
Operating Conditions
Ambient air temp. 50˚C
Ground temp. 35˚C
Depth of Laying 0.50 m
Thermal resistivity of Soil 1.2 K.m/W
50 OCI/PBPC/Rev-001/010909
TABLE - 60
Operating Conditions
Ambient air temp. 50˚C
Ground temp. 35˚C
Depth of Laying 0.50 m
Thermal resistivity of Soil 1.2 K.m/W
51 OCI/PBPC/Rev-001/010909
TABLE - 60A
Operating Conditions
Ambient air temp. 50˚C
Ground temp. 35˚C
Depth of Laying 0.50 m
Thermal resistivity of Soil 1.2 K.m/W
52 OCI/PBPC/Rev-001/010909
TABLE - 61
Correction factor 0.8 0.7 0.65 0.6 0.57 0.52 0.48 0.45 0.43 0.41 0.39 0.38
Where spacing between adjacent cables is more than twice their overall diameters, no correction factor need to be applied
TABLE - 62
GROUP RATING FACTORS FOR MORE THAN THREE SINGLE CORE CABLES LAID IN
CONDUITS BURIED IN CONCRETE, ON SURFACE OF WALL, IN TRUNKING, RACKS ETC.
(COMMON FOR INSTALLATION IN AIR, GROUND,DUCT, TRENCH ETC)
Correction factor 0.8 0.69 0.62 0.59 0.55 0.51 0.48 0.43 0.41 0.39 0.38 0.36
TABLE - 63
Ambient temperature ˚C 25 30 35 40 45 50 55
PVC insulated cables 1.49 1.40 1.31 1.22 1.11 1.0 0.86
XLPE insulated cables 1.27 1.22 1.17 1.12 1.06 1.0 0.94
TABLE - 64
Ground temperature ˚C 15 20 25 30 35 40 45
PVC insulated cables 1.25 1.19 1.12 1.06 1.0 0.92 0.85
XLPE insulated cables 1.16 1.13 1.08 1.03 1.0 0.95 0.90
53 OCI/PBPC/Rev-001/010909
TABLE - 65
Depth of
Laying Cables Laid Direct in Ground Cables Laid in Ducts
TABLE - 66
No. of cables 2 3 4 5 6 7 8 9 10 11 12
Cables laid touching 0.81 0.7 0.63 0.59 0.55 0.52 0.50 0.48 0.47 0.45 0.44
Cables laid 15 cm apart 0.87 0.78 0.74 0.70 0.68 0.66 0.64 0.63 0.62 0.61 0.60
Cables laid 30 cm apart 0.91 0.84 0.81 0.78 0.77 0.75 0.75 0.74 0.73 0.73 0.72
Cables laid 45 cm apart 0.93 0.88 0.86 0.84 0.83 0.82 0.81 0.81 0.80 0.80 0.80
Cables laid 60 cm apart 0.95 0.90 0.89 0.87 0.87 0.86 0.86 0.85 0.85 0.85 0.84
54 OCI/PBPC/Rev-001/010909
TABLE - 67
Nominal
Area of
Thermal Resistivity of Soil in K.m/W
Conductor
mm2 0.7 0.8 0.9 1.0 1.2 1.5 2.0 2.5 3.0 3.5 4.0
50 1.21 1.16 1.11 1.07 1.0 0.91 0.81 0.73 0.68 0.63 0.59
70 1.22 1.16 1.12 1.07 1.0 0.91 0.81 0.73 0.68 0.63 0.59
95 1.22 1.16 1.12 1.07 1.0 0.91 0.81 0.73 0.68 0.63 0.59
120 1.22 1.16 1.12 1.07 1.0 0.91 0.81 0.73 0.68 0.63 0.59
150 1.22 1.16 1.12 1.07 1.0 0.91 0.81 0.73 0.68 0.63 0.59
185 1.22 1.17 1.12 1.07 1.0 0.91 0.81 0.73 0.68 0.62 0.59
240 1.23 1.17 1.12 1.07 1.0 0.91 0.80 0.73 0.68 0.62 0.59
300 1.23 1.17 1.12 1.07 1.0 0.91 0.80 0.73 0.68 0.62 0.59
400 1.23 1.17 1.12 1.07 1.0 0.91 0.80 0.73 0.67 0.62 0.58
500 1.23 1.17 1.12 1.07 1.0 0.91 0.80 0.73 0.67 0.62 0.58
630 1.23 1.17 1.12 1.07 1.0 0.91 0.80 0.73 0.67 0.61 0.58
800 1.23 1.17 1.12 1.07 1.0 0.91 0.80 0.72 0.66 0.61 0.58
1000 1.25 1.18 1.12 1.07 1.0 0.91 0.80 0.72 0.66 0.61 0.58
TABLE - 68
Nominal
Area of
Thermal Resistivity of Soil in K.m/W
Conductor
mm2 0.7 0.8 0.9 1.0 1.2 1.5 2.0 2.5 3.0 3.5 4.0
1.5/2.5 1.12 1.09 1.07 1.04 1.0 0.94 0.86 0.80 0.75 0.70 0.66
4 1.13 1.10 1.07 1.05 1.0 0.94 0.85 0.79 0.74 0.69 0.65
6 1.14 1.10 1.07 1.05 1.0 0.93 0.85 0.79 0.74 0.68 0.64
10 1.15 1.11 1.08 1.05 1.0 0.93 0.85 0.78 0.73 0.67 0.63
16 1.16 1.12 1.08 1.05 1.0 0.93 0.84 0.77 0.72 0.66 0.62
25 1.17 1.13 1.09 1.05 1.0 0.93 0.83 0.77 0.71 0.65 0.61
35 1.17 1.13 1.09 1.06 1.0 0.92 0.83 0.76 0.71 0.65 0.61
50 1.17 1.13 1.09 1.06 1.0 0.92 0.83 0.76 0.71 0.65 0.61
70 1.18 1.14 1.09 1.06 1.0 0.92 0.83 0.75 0.70 0.64 0.60
95 1.18 1.14 1.09 1.06 1.0 0.92 0.83 0.75 0.70 0.64 0.60
120 1.19 1.14 1.10 1.06 1.0 0.92 0.82 0.75 0.69 0.63 0.59
150 1.19 1.14 1.10 1.06 1.0 0.92 0.82 0.75 0.69 0.63 0.59
185 1.19 1.14 1.10 1.06 1.0 0.92 0.82 0.74 0.69 0.63 0.59
240 1.20 1.15 1.10 1.07 1.0 0.92 0.81 0.74 0.69 0.63 0.59
300 1.20 1.15 1.10 1.07 1.0 0.92 0.81 0.74 0.69 0.63 0.59
400 1.20 1.15 1.10 1.07 1.0 0.92 0.81 0.74 0.69 0.63 0.59
55 OCI/PBPC/Rev-001/010909
TABLE - 69
Nominal
Area of
Thermal Resistivity of Soil in K.m/W
Conductor
mm2 0.7 0.8 0.9 1.0 1.2 1.5 2.0 2.5 3.0 3.5 4.0
50 1.08 1.06 1.04 1.03 1.0 0.96 0.90 0.85 0.81 0.77 0.74
70 1.08 1.06 1.05 1.03 1.0 0.96 0.90 0.84 0.80 0.76 0.73
95 1.08 1.07 1.05 1.03 1.0 0.95 0.89 0.84 0.80 0.75 0.72
120 1.09 1.07 1.05 1.03 1.0 0.95 0.89 0.83 0.79 0.75 0.71
150 1.09 1.07 1.05 1.03 1.0 0.95 0.88 0.83 0.79 0.74 0.71
185 1.09 1.07 1.05 1.03 1.0 0.95 0.88 0.83 0.78 0.74 0.70
240 1.10 1.08 1.05 1.04 1.0 0.95 0.88 0.82 0.78 0.73 0.70
300 1.10 1.08 1.06 1.04 1.0 0.95 0.87 0.82 0.77 0.72 0.69
400 1.11 1.08 1.06 1.04 1.0 0.94 0.87 0.82 0.77 0.72 0.68
500 1.12 1.08 1.06 1.04 1.0 0.94 0.87 0.81 0.76 0.71 0.68
630 1.12 1.09 1.06 1.04 1.0 0.94 0.87 0.81 0.76 0.71 0.67
800 1.13 1.10 1.07 1.04 1.0 0.94 0.86 0.80 0.75 0.71 0.67
1000 1.13 1.10 1.07 1.04 1.0 0.94 0.86 0.80 0.75 0.70 0.66
TABLE - 70
Nominal
Area of
Thermal Resistivity of Soil in K.m/W
Conductor
Sq mm 0.7 0.8 0.9 1 1.2 1.5 2 2.5 3 3.5 4
50 1.11 1.08 1.06 1.04 1.0 0.94 0.87 0.82 0.77 0.73 0.69
70 1.12 1.09 1.06 1.04 1.0 0.94 0.87 0.81 0.76 0.72 0.68
95 1.12 1.09 1.06 1.04 1.0 0.94 0.87 0.81 0.76 0.72 0.68
120 1.13 1.10 1.07 1.04 1.0 0.94 0.86 0.80 0.75 0.72 0.67
150 1.13 1.10 1.07 1.04 1.0 0.94 0.86 0.80 0.75 0.71 0.67
185 1.13 1.10 1.07 1.04 1.0 0.93 0.86 0.79 0.75 0.70 0.67
240 1.14 1.11 1.07 1.04 1.0 0.93 0.86 0.79 0.74 0.70 0.66
300 1.14 1.11 1.08 1.05 1.0 0.93 0.85 0.79 0.74 0.69 0.65
400 1.14 1.11 1.08 1.05 1.0 0.93 0.85 0.78 0.73 0.68 0.65
500 1.15 1.11 1.08 1.05 1.0 0.93 0.85 0.78 0.73 0.68 0.64
630 1.15 1.12 1.09 1.05 1.0 0.93 0.84 0.78 0.72 0.68 0.64
800 1.16 1.12 1.09 1.05 1.0 0.93 0.84 0.77 0.72 0.67 0.64
1000 1.16 1.13 1.09 1.05 1.0 0.92 0.84 0.77 0.71 0.67 0.63
56 OCI/PBPC/Rev-001/010909
TABLE - 71
Nominal
Area of
Thermal Resistivity of Soil in K.m/W
Conductor
Sq mm 0.7 0.8 0.9 1 1.2 1.5 2 2.5 3 3.5 4
1.5/2.5 1.04 1.03 1.02 1.02 1.00 0.98 0.94 0.91 0.88 0.86 0.83
4 1.04 1.04 1.03 1.02 1.00 0.97 0.94 0.90 0.87 0.85 0.82
6 1.05 1.04 1.03 1.02 1.00 0.97 0.93 0.90 0.86 0.84 0.81
10 1.05 1.04 1.03 1.02 1.00 0.97 0.93 0.89 0.86 0.83 0.80
16 1.06 1.04 1.03 1.02 1.00 0.97 0.92 0.88 0.85 0.82 0.79
25 1.06 1.05 1.03 1.02 1.00 0.96 0.92 0.88 0.84 0.82 0.78
35 1.06 1.05 1.03 1.02 1.00 0.96 0.92 0.87 0.83 0.81 0.77
50 1.07 1.05 1.03 1.02 1.00 0.96 0.91 0.87 0.83 0.80 0.77
70 1.07 1.05 1.04 1.02 1.00 0.96 0.91 0.86 0.82 0.79 0.76
95 1.07 1.05 1.04 1.02 1.00 0.96 0.91 0.86 0.82 0.79 0.76
120 1.08 1.06 1.04 1.03 1.00 0.95 0.90 0.85 0.81 0.78 0.74
150 1.09 1.06 1.04 1.03 1.00 0.95 0.90 0.85 0.80 0.77 0.73
185 1.09 1.07 1.05 1.03 1.00 0.95 0.89 0.84 0.80 0.76 0.72
240 1.09 1.07 1.05 1.03 1.00 0.95 0.88 0.83 0.79 0.85 0.71
300 1.10 1.07 1.05 1.03 1.00 0.95 0.88 0.83 0.78 0.75 0.71
400 1.10 1.07 1.05 1.03 1.00 0.95 0.88 0.83 0.78 0.75 0.71
TABLE - 72
mm2 ohm ohm ohm ohm ohm ohm ohm ohm ohm
1.5 12.1 — — — 10.2 9.5 — 8.8 8.2
2.5 7.41 — — — 8.8 8.2 — 7.7 6.8
4 4.61 7.41 — — 7.5 7 — 4.6 4.1
6 3.08 4.61 — — 6.8 4.6 — 4.1 3.8
10 1.83 3.08 — — 3.9 3.7 — 3.4 2.3
16 1.15 1.91 — — 3.4 3.1 1.9 2.2 2
25 0.727 1.2 — — 2.6 2.4 1.7 2.1 1.7
35 0.524 0.868 — — 2.4 2.1 1.7 1.9 1.5
50 0.387 0.641 0.82 0.73 2.1 1.9 1.3 1.3 1.1
70 0.268 0.443 0.73 0.65 1.9 1.4 1.2 1.2 0.89
95 0.193 0.32 0.64 0.45 1.3 1.2 1.1 0.98 —
120 0.153 0.253 0.45 0.42 1.2 1.1 0.74 0.71 —
150 0.124 0.206 0.4 0.39 1.1 0.74 0.69 0.65 —
185 0.0991 0.164 0.37 0.36 0.78 0.68 0.64 0.59 —
240 0.0754 0.125 0.33 0.33 0.69 0.6 0.58 0.52 —
300 0.0601 0.1 0.3 0.3 0.63 0.54 0.53 0.47 —
400 0.047 0.0778 0.21 0.21 0.56 0.49 0.48 0.34 —
500 0.0366 0.0605 0.19 0.19 — — — — —
630 0.0283 0.0469 0.18 0.18 — — — — —
800 0.0221 0.0367 0.13 0.13 — — — — —
1000 0.0176 0.0291 0.12 0.12 — — — — —
57 OCI/PBPC/Rev-001/010909
TABLE - 72A
mm2 ohm ohm ohm ohm ohm ohm ohm ohm ohm
58 OCI/PBPC/Rev-001/010909
TABLE - 73
Copper Aluminium Copper Aluminium Copper Aluminium Trefoil Flat Copper Aluminiu Copper Aluminiu Trefoil Flat
m m
mm2 Ohm/km Ohm/km Ohm/km Ohm/km Ohm/km Ohm/km Ohm/km Ohm/km Ohm/km
16 1.15 1.91 1.38 2.29 1.38 2.29 0.121 0.210 0.086 1.47 2.42 1.47 2.42 0.114 0.172 0.081
59
25 0.727 1.2 0.870 1.44 0.87 1.44 0.116 0.202 0.085 0.927 1.54 0.927 1.54 0.113 0.172 0.081
35 0.524 0.868 0.627 1.04 0.627 1.04 0.115 0.201 0.083 0.668 1.11 0.668 1.11 0.110 0.167 0.079
50 0.387 0.641 0.464 0.771 0.464 0.77 0.112 0.195 0.080 0. 494 0.822 0.494 0.822 0.106 0.161 0.075
70 0.268 0.443 0.321 0.533 0.321 0.533 0.107 0.188 0.077 0.342 0.568 0.342 0.568 0.103 0.160 0.074
95 0.193 0.32 0.232 0.385 0.232 0.385 0.103 0.186 0.077 0.247 0.411 0.247 0.411 0.098 0.155 0.073
120 0.153 0.253 0.184 0.305 0.184 0.305 0.103 0.185 0.075 0.197 0.325 0.197 0.325 0.097 0.153 0.072
150 0.124 0.206 0.150 0.248 0.150 0.248 0.101 0.185 0.075 0.160 0.265 0.160 0.265 0.097 0.153 0.072
185 0.0991 0.164 0.120 0.198 0.121 0.198 0.099 0.184 0.074 0.128 0.211 0.128 0.211 0.096 0.153 0.072
240 0.0754 0.125 0.0926 0.152 0.0929 0.152 0.096 0.181 0.074 0.0986 0.162 0.0989 0.162 0.092 0.147 0.071
300 0.0601 0.1 0.0750 0.122 0.0752 0.122 0.094 0.180 0.073 0.0800 0.130 0.0802 0.130 0.090 0.147 0.070
400 0.047 0.0778 0.0600 0.096 0.0604 0.096 0.091 0.178 0.073 0.0640 0.102 0.0645 0.102 0.090 0.146 0.070
500 0.0366 0.0605 0.0484 0.0757 0.0491 0.0757 0.089 0.176 0.072 0.0525 0.0810 0.0530 0.081 0.089 0.146 0.070
630 0.0283 0.0469 0.0398 0.0605 - - 0.086 0.173 - 0.0428 0.0658 - - 0.086 0.144 -
800 0.0221 0.0367 0.0334 0.0500 - - 0.086 0.171 - 0.0380 0.0541 - - 0.084 0.143 -
1000 0.0176 0.0291 0.0290 0.0415 - - 0.084 0.168 - 0.0334 0.0457 - - 0.081 0.140 -
OCI/PBPC/Rev-001/010909
SHORT CIRCUIT CURRENT CURVES FOR
COPPER CONDUCTOR XLPE INSULATED CABLES
60 OCI/PBPC/Rev-001/010909
SHORT CIRCUIT CURRENT CURVES FOR
COPPER CONDUCTOR PVC INSULATED CABLES
61 OCI/PBPC/Rev-001/010909
SHORT CIRCUIT CURRENT CURVES FOR
ALUMINIUM CONDUCTOR XLPE INSULATED CABLES
62 OCI/PBPC/Rev-001/010909
SHORT CIRCUIT CURRENT CURVES FOR
ALUMINIUM CONDUCTOR PVC INSULATED CABLES
63 OCI/PBPC/Rev-001/010909
NOTES:
64 OCI/PBPC/Rev-001/010909