13401010en Voltage Regulator VC 100-BU PDF
13401010en Voltage Regulator VC 100-BU PDF
VC 100-BU
Operating Instructions
Maschinenfabrik Reinhausen GmbH
Postfach 12 03 60
D-93025 Regensburg
Phone: +49 9 41 40 90-0
BA 134/01 en - 0597/2000 Fax: +49 9 41 40 90-1 11
Printed in Germany Telex: 65881
VOLTAGE REGULATOR
TYPE VC 100-BU
Operating Instructions No. 134/01
Contents Page
1. General __________________________________________________________________ 2
3. Operation _________________________________________________________________ 8
7. Failures __________________________________________________________________ 29
Please note:
Drawings and illustrations contained herein may differ in detail from the tap changer equipment delivered.
They are for reference only and are subject to change without notice.
134/01/01/0 1
1. GENERAL
WARNING:
This information indicates particular danger
to life and health.
2 134/01/01/0
1.2 Application The parameters of the regulator can be set by means
of a PC via a serial interface (RS 232). The appropriate
The electronic voltage regulator VC 100-Bu (fig. 1, 2)
PC software can be purchased from MR.
is used for automatic control of transformers with a
motor driven on-load tap changer. The control follows A load-dependent line voltage drop, e.g. of a spur line
the step-by-step principle, i.e. a single control pulse leading from the transformer to the load, can be com-
operates the tap changer from one service position to pensated either by line simulation (Line Drop Compen-
the next. sator) or by load-current dependent increase of the
voltage level (Z-Compensation).
1.4 Designs
The standard design (version 01, fig. 1) of the
voltage regulator VC 100-BU can be used with the
CT, V T SETTING
VT kV/100 V
parallel control unit SKB 30 for the parallel operation of
100.0 V CT
CT, VT
RATING
PHASE 2 up to 6 transformers. Two pre-programmed values
REGULATION SETTING LINE-COMPENSATION INFO
for the voltage level modifications can be activated via
external relay contacts or switches.
VOLTAGE
LEVEL
BAND-
WIDTH
DELAY 1
DELAY 2
Ur
VOLTRISE
Ux
LIMIT
D1 - Dn In special design (version 02, fig. 2) the voltage
regulator VC 100-BU is equipped with a parallel control
LIMIT CONTROL
LDC Z-KOMP
AUTO
minimum circulating reactive current method or master-
follower method) of two transformers by two voltage
ALARM ACTIVE ACTIVE ACTIVE LOCAL REMOTE
regulators is possible without an additional parallel
VC 100-BU
VOLTAGE CONTROL
control unit. Please note, this version cannot be used
DATA PORT
MADE IN GERMANY
Further options:
1
int079 The voltage regulator VC 100-BU can be equipped
with a serial optical fibre interface which allows to
parameterize and operate the voltage regulator from
the remote control device VC 100-RC.
CT, V T SETTING
VT kV/100 V
NOTE ! When voltage regulation is effected by
100.0 V CT
CT, VT
RATING
PHASE tapped transformers and voltage regulators, it is
REGULATION SETTING LINE-COMPENSATION INFO assumed that a change of the tap position results
in a significant voltage change.
Ur Ux
When generators feed the voltage level to be
DELAY 1
VOLTAGE BAND-
D1 - Dn
LEVEL WIDTH
DELAY 2 VOLTRISE LIMIT
LIMIT CONTROL PARALLEL CONTROL SPECIAL MODE OF OPERATION that a correct regulation of the voltage cannot be
guaranteed. In such cases MR should be
consulted in the planning stage.
STABILITY SENSITIVITY MANUAL
U< U> I> ARS
MASTER
TAP MAX AUTO
FOLLOWER
VC 100-BU
VOLTAGE CONTROL
DATA PORT
MADE IN GERMANY
2 int080
134/01/01/0 3
1.5 Construction The operating state is indicated by an 8-character
alphanumerical LC display and several LED lamps.
The electronic voltage regulator VC100-BU is installed
The electronic voltage regulator is controlled by an 8-
in a protective housing with hinged cover and window.
bit microcontroller (see block diagram, fig. 1a and 2a).
It is suitable for flush or projected panel mounting. The
Besides a voltage transformer and a current trans-
front panel contains several function keys and slide
former it contains optocoupler inputs with potential
switches as well as a scroll wheel for parameter
separation as well as potential-free output relay
setting.
contacts.
Voltage
level
change
1a Block diagram with the connection of the measuring transformers (version 01) intVC1a
to second
VC 100-BU02
Optical-fibre cable to VC 100-RC Shielded cable, max. 25 m
Optocoupler
Relay driver
Current transformer
2a Block diagram with the connection of the measuring transformers (version 02) intVC2a
4 134/01/01/0
2. TECHNICAL DATA
Setting ranges
Voltage level change Two different values, each 0...10 % of desired voltage level, setting in steps of 0.1 %
Undervoltage blocking 70...99 % of desired voltage level, setting in steps of 1 %, delay time 10 s for signalling relay
Overcurrent blocking 50... 210 % of rated current of current transformer, setting in steps of 5 %
Function keys for parametering of current and voltage transformer measuring ranges and configuration
(CT, VT SETTING),
desired voltage level (VOLTAGE LEVEL),
bandwidth (BANDWIDTH)
delay time 1 (DELAY 1),
delay time 2 (DELAY 2),
LDC: Ur,
LDC: Ux,
Z-Compensation: voltage rise (VOLTRISE),
Z-Compensation: limitation (LIMIT),
information key D1-Dn for indication of operating data,
undervoltage (U<),
overvoltage (U>),
overcurrent (I>),
function key for customer-specific control program (ARS),
mode of operation switch (MANUAL/AUTO).
In standard design (version 01): voltage level change (1-2) (VOLTAGE LEVEL CHANGE),
individual setting up to max. ± 10 %.
In special design (version 02): parallel control,
stability (STABILITY) or max. tap position (TAP MAX),
sensitivity (SENSITIVITY) for circulating reactive current signal.
134/01/01/0 5
Output relays 1 output relay each RAISE and LOWER control pulses,
pulse duration approx. 1.5 s or continuous pulse,1 N/C and 1 N/O contact;
signalling relay for undervoltage blocking, 1 change-over contact with a delay time of approx. 10 s;
signalling relay for overvoltage, 1 change-over contact;
signalling relay for overcurrent blocking, 1 change-over contact;
signalling relay for function monitoring, 1 change-over contact with a delay time of
approx. 15 minutes (for ARS approx. 31 minutes);
signalling relay for AUTO/MANUAL mode of operation, 1 change-over contact;
signalling relay for FAIL VOLTAGE REGULATOR, 1 change-over contact.
In special design (version 02):
signalling relay for INDIV./PARALLEL mode of operation,1 change-over contact;
signalling relay for PARALLEL OPERATION DISTURBED, 1 change-over contact;
Power supply 115 V (+25 % - 35 %), 40...60 Hz, either from measuring voltage or separate supply voltage,
consumption approx. 6.5 VA (at 110 V, idle state),
supply voltage AC 230 V can be set at the factory.
Protective housing Steel plate housing with window for flush or projecting panel mounting, flint grey finish RAL 7032,
width x height x depth = 216 x 326 x 115 mm,
enclosure protection IP44 according to IEC 529,
weight approx. 5.4 kg.
6 134/01/01/0
13 12 11 10 9 8 7
CT, V T SETTING
VT kV/100 V
CT RATING
CT, VT PHASE
16
17 LDC Z-COMP.
1
VC 100-BU
VOLTAGE CONTROL
DATA PORT
22
23 24
MADE IN GERMANY
int079a
PARALLEL CONTROL
25
STABILITY SENSITIVITY
MASTER
TAP MAX
FOLLOWER
26
PARALLEL ALARM
134/01/01/0 7
3. OPERATION Manual or automatic operation is selected by actuating
the MANUAL/AUTO switch accordingly.
3.1 Input and output of data, functions
MANUAL position: The voltage regulator is in service.
When the voltage regulator is inactive, the operating However, the RAISE/LOWER output contacts are
data listed on page 14 under 3.1.12 can be displayed. inactive. The motor drive is operated by manual
When the function key is pressed, the last setting of control.
the corresponding parameter appears on the display
AUTO position: The LED lamp for AUTO lights up.
This setting can be changed by means of the scroll
The voltage regulator is in service with all its functions.
wheel as required. When the function key is released
The motor drive cannot be operated by manual
the value displayed is stored.
control.
Some keys allow to set several parameters which are
The selected mode of operation is signalled by relay
selected by pressing the key repeatedly. Exceptions
contacts (terminals 51, 52, 54).
are the function keys for LINE COMPENSATION
where the parameters are selected by means of the A supply voltage breakdown or voltage regulator
slide switch LDC/Z-COMP. failure is signalled by relay contacts (terminals 57, 58,
59).
All values entered are automatically protected when
the power supply of the voltage regulator is
interrupted, and they are immediately available when
3.1.03 Measuring transformers (CT, VT SETTING,
the voltage regulator is switched on again.
fig. 5, display see fig. 5a)
The ratios and configuration of the voltage and current
3.1.01 Indication field transformers are to be set by selecting the corres-
ponding parameters by repeatedly pressing the
The indication field consists of the 8-character LC corresponding function key and change of the selected
display and of two LED lamps each for undelayed parameter by turning the scroll wheel.
signalling of RAISE and LOWER when the deviation
exceeds the preset bandwidth limits. There are further Example:
signalling LED lamps for the following functions: U<, Voltage transformer used: 22 kV/110 V.
U>, I>, voltage level change, customer-specific control Setting on the voltage regulator:
program, mode of operation, and parallel control (in (22 kV . 100) / 110 V = 20 kV
version 02). Ratio of the voltage transformer VT (kV/100 V)
The rated primary voltage (referred to 100 V
secondary voltage) is set from 0.100 kV to 999 kV
3.1.02 Mode of operation (MODE OF OPERATION, using the scroll wheel.
fig. 4)
Ratio of the current transformer CT (In)
For parametering directly on the voltage regulator, set The rated primary current (referred to 0.2 / 1 / 5 A
the Local/Remote slide switch to Local position. In secondary current) is set from 100 A to 5000 A using
Remote position, the parameters are set via a serial the scroll wheel.
interface using a PC or optionally the remote control
device VC 100-RC.
MANUAL
AUTO
LOCAL REMOTE
4 5 from int079
from int079
8 134/01/01/0
Measuring transformer configuration CT, VT PHASE
(Phase angle of current/voltage transformer, fig. 5a)
134/01/01/0 9
3.1.04 Setting of the desired voltage level
(VOLTAGE LEVEL, fig. 6)
The desired voltage level can be set from 85 V to 140 110.0 V
V in steps of 0.5 V by pressing the function key
VOLTAGE LEVEL and turning the scroll wheel.
This setting refers to the secondary side of the voltage
REGULATION SETTING
transformer connected to the VC 100-BU.
100 USt
BW (%) = from int079
UN 6
BW = bandwidth (%)
USt = step voltage
UN = rated voltage
from int079
8
10 134/01/01/0
If a delay time with inverse response is set, the delay
time is automatically shortened inversely to the
percentage deviation down to a minimum of 1 s, i.e. DEL2 10 s
effective
set delay time (s) . BW (%)
delay time (s) =
voltage deviation dU (%)
REGULATION SETTING
where BW = bandwidth (%)
85 %
3.1.07 Setting the undervoltage blocking (U <)
The response threshold for undervoltage blocking (fig.
10) can be set from 70 % to 99 % of the voltage level
in steps of 1 % by pressing the function key and REGULATION SETTING
from int079
11
134/01/01/0 11
If the voltage regulator regulates towards a higher
voltage than the set limit U due to an unfavourable
parametering (e.g. too high LDC settings), it is pre- 180 %
vented from exceeding the limit. This condition is
signalled by the signalling relay for function moni-
toring, after 15 minutes (in case of ARS function:
after 31 minutes).
LIMIT CONTROL
13a intVC13a
12 134/01/01/0
Calculation of the required settings: Setting the voltage rise (VOLTRISE)
The calculated percentage of the voltage rise, referred
R to the voltage level, is set by pressing the function key
Ur = IN . CT . r . L (V)
RVT and turning the scroll wheel.
RCT
Ux = IN . . x . L (V)
Calculation of the required setting:
RVT
where
Ur = LDC setting for resistive line voltage drop in V UTr - ULoad IN . RCT
Voltage rise (%) = 100 . .
from int079
14
134/01/01/0 13
3.1.11 Setting the voltage level change
(VOLTAGE LEVEL CHANGE, fig. 15)
This function is included in the standard design – 9.0 %
(version 01).
The alternative design (version 02) is equipped with a
parallel control module instead of the voltage level
change function, so that the parallel control of two VOLTAGE LEVEL CHANGE
Reactive power
in VAr, kVAr, MVAr 330 kVAr
STABILITY SENSITIVITY
WARNING: VC 100-BU
Take care to properly connect the voltage
regulator and the housing to ground.
Danger to life !
134/01/01/0 15
b) Set the ratios and configuration of the voltage and shortened inversely proportional to the deviation.
current transformers according to 3.1.03.
k) Set the response threshold for undervoltage
c) Let the measured voltage (= voltage from the blocking U < to 85 % as described under 3.1.07.
voltage transformer) be indicated on the display of Set the mode of operation switch to MANUAL, and
the voltage regulator (select “Measured voltage in reduce the desired voltage level, e.g. 110 V, to
V” using the INFO key and scroll wheel according 110 V . 0.85 = 94 V so that the actual voltage now
to 3.1.12). corresponds to the set response threshold for
undervoltage blocking. The presignal LED lamp for
d) Set the desired voltage level. By manual control of
RAISE must light up. Set the mode of operation
the motor drive, bring the tap changer to the ser-
switch to AUTO. After approx. 10 s the signalling
vice position so that the desired voltage level is
relay “U <“ must be energized, the signalling con-
obtained.
tact (terminals 22, 23) must open, but the output
e) Set VOLTAGE LEVEL to this value as described relay RAISE must not issue a control command
under 3.1.04. (terminal 18). Now set the desired response
f) Let the current, power, and phase angle values be threshold for undervoltage blocking.
indicated on the display by pressing the INFO key l) Set the response threshold for overvoltage
and turning the scroll wheel. Compare these values detection U> to 115 % as described under 3.1.08.
with those from possibly existing service measuring Set the mode of operation switch to MANUAL, and
instruments. If wrong signs are indicated, reverse increase the desired voltage level, e.g. 110 V, to
the polarity of the current or voltage transformer. 110 V . 1.15 = 127 V so that the actual voltage
g) Set BANDWIDTH to 1.0 % as described under now corresponds to the set response threshold for
3.1.05. In most cases the voltage regulator is now overvoltage detection. The presignal LED lamp for
in a balanced state (no presignal LED lamp lights LOWER must light up. Set the mode of operation
up). Otherwise change the desired voltage level in switch to AUTO. The output relay LOWER must
steps of 0.5 V until a balanced state is reached. issue periodic control commands at 1.5 s intervals.
The relay contact (terminals 24, 25) must open.
h) Set BANDWIDTH according to 3.1.05 as a function Now set the desired response threshold for
of the step voltage (= service setting): overvoltage detection and set the desired voltage
i) Set the delay time 1 (DELAY 1) to 20 s lin. as level to its initial value.
desribed under 3.1.06. By manual control move the m) Set the response threshold for overcurrent blocking
tap changer towards “Raise” by one step, the pre- I > as described under 3.1.09. A function check is
signal LED lamp for LOWER must light up. Set the not necessary.
mode of operation switch to AUTO. Then 20 s after
the presignal the voltage regulator must control the n) Setting of LDC (see paragraph 3.1.10)
tap changer back to its initial position. The pre- Set the mode of operation switch to MANUAL.
signal LED lamp goes out. Set Ux and Ur to 0, no presignal LED lamp must
light up.
Set the mode of operation switch to MANUAL. Set Ur to 20 V and Ux to 0 V, the presignal LED
Repeat the procedure towards “Lower”. lamp for RAISE must light up.
Set the delay time 2 (DELAY 2) to 10 s. Set the Set Ur to -20 V and Ux to 0 V, the presignal LED
mode of operation switch to MANUAL. By manual lamp for LOWER must light up.
control move the tap changer towards “Raise” by (During this function check a load current of 5 % of
two steps, the presignal LED lamp for LOWER the rated current of the current transformer must
must light up. Set the mode of operation switch to flow.)
AUTO. Then 20 s after the presignal the voltage Carry out the required setting of the LDC as
regulator must control the tap changer by one step described under 3.1.10.
and after further 10 s by another step back to its
initial position. Set the mode of operation switch to AUTO. Check
if the setting is correct by observing the voltage at
Set the delay times DELAY 1 and DELAY 2 to the the line end during service and with different loads.
desired value. If DELAY 2 is not used, the setting When the setting is correct the voltage at the line
OFF is necessary. end will remain constant.
When putting the voltage regulator into service, it is
recommended to set DELAY 1 provisionally to 100
s. Depending on the existing operating con-ditions,
the definitive setting can only be deter-mined after
some time of observation. For this purpose it is
recommended to register the varia-tion of the
actual voltage and the number of tap change
operations per day.
If an inverse response of the voltage regulator is
desired, set DELAY 1 to a value with the addition
“inv”. In this case the delay time is automatically
16 134/01/01/0
o) Setting of Z-Compensation (see paragraph 3.1.11) 4.0 CUSTOMER-SPECIFIC CONTROL
as an alternative to LDC. PROGRAM „ARS“
Set the mode of operation switch to MANUAL and (Advanced Regulating System)
the slide switch for LDC/Z-COMP to Z-COMP.
Set VOLTRISE to 0, the voltage regulator is in a 4.01 General
balanced state, no presignal LED lamp must light
up. The voltage regulator VC 100-BU offers the choice of
Set VOLTRISE to 15 %, the presignal LED lamp for two control algorithms which are independent from
RAISE must light up. each other. Apart from the usual symmetrical control
(During this functional check a load current of 10 % algorithm there is another algorithm with the
of the rated current of the current transformer must designation ARS which is a new, adaptable and
flow.) customer-oriented voltage regulation system.
Carry out the required setting of the Z-Compen- It is possible to change over from one control
sation as described under 3.1.10. algorithm to the other without losing the set
parameters.
Set the mode of operation switch to AUTO. Check if The ARS is a control algorithm that can be defined
the setting is correct by observing the voltage at the completely by the customer. It is straight forward and
line end during service and with different loads. can be checked at any time.
When the setting is correct the voltage at the line The open structure of the ARS algorithm allows the
end will remain constant. voltage regulation to be individually and more
efficiently effected than any other control system
p) Set the VOLTAGE LEVEL CHANGES 1 and 2 to used to date.
the desired values as described under 3.1.11.
Set the mode of operation switch to MANUAL and The reaction of the voltage regulator VC 100-BU can
jumper the terminals 31, 34. Depending on the be defined individually for each direction of the
direction of the set VOLTAGE LEVEL CHANGE 1, deviation of the actual voltage from the set voltage
the presignal LED lamp for LOWER or RAISE must level by assigning different delay times and band-
light up, as well as the LED lamp for VOLTAGE widths directly on the VC 100-BU.
LEVEL CHANGE 1. It is possible, for example, to set an unsymmetrical
Set the VOLTAGE CHANGE 2 in the same way, but control response and thus define the operation of the
jumpering the terminals 31, 33. tap changer individually for the most important voltage
Set the mode of operation switch to AUTO. ranges.
By activating the function “Tendency” the quality of
the voltage supply can be increased without more
tap change operations.
The permanent monitoring of the control criteria
allows the setting of extremely long delay times even
while a switching delay is in progress which can result
in a reduction of the number of switching operations
without deteriorating the quality of the voltage supply.
Since the ARS system in the VC 100-BU is parallel to
the usual control system, it can also be activated
temporarily, for example to solve certain network
situations, and thus contribute to an optimized
voltage regulation.
All monitoring functions (U>, U<, I>) and auxiliary
functions (line compensation, voltage level change,
parallel control) of the voltage regulator VC 100-BU
remain active irrespective of the selected control
algorithm.
134/01/01/0 17
4.02 Control criteria During this delay time the VC 100-BU determines the
percentage of time during which the deviation was
The transformer voltage measured by the VC 100-BU
really present (see fig. 21) and compares it with the
is compared with the set voltage level. The actual
set „Tendency“ value. The voltage regulator only emits
deviation is determined from the difference and the set
a RAISE or LOWER control pulse when the deter-
bandwidth.
mined percentage exceeds the „Tendency“ value.
This way the negative effects of short-time voltage
Difference between actual and set voltage fluctuations which in the standard regulating system
Deviation =
set bandwidth would prevent the adaptation of the transformer
voltage is eliminated. See fig. 21.
The setting Tend = OFF corresponds to an effective
A timer is started and only stopped when the preset
delay time of 100 %, i.e. the deviation must be present
delay time + nT (+1T, +2T, ..., or -1T, -2T, ...) assigned
for the whole duration of the delay time before a tap
to the magnitude of this deviation has elapsed. See
change is initiated.
fig. 20.
n - Deviation
Individually
defininable
time intervals (nT)
18 134/01/01/0
As each case of absolute deviation is monitored possible from a PC through the parametering interface
individually by ARS and can be treated according and with the aid of the communication software
to the existing requirements, it is possible to assign supplied with the equipment.
an extremely long delay time to small deviations
without running the risk of not being able to
compensate large voltage deviations in time. Explanation of the symbols used and their represen-
In the case of the smallest deviation by one step it is tation in the set of ARS parameters:
even possible to set an infinite delay time (display text:
+1T OFF or -1T OFF) so that such a deviation will .............V: Desired voltage level
permanently be tolerated by the VC 100-BU.
In many cases it might be useful from the point of view +1T......s: Delay time in case of positive
of control engineering to treat positive and negative deviations of > 1 . (+Bw)
deviations from the set voltage level in a supply net-
work differently. As it is possible to assign different -1T.....s: Delay time in case of negative
bandwidths to the two directions of deviation, ARS deviations of > 1 . (-Bw)
allows to set an unsymmetrical control response so
that voltage ranges with different importance for the +2T......s: Delay time in case of positive
actual application can be treated differently. deviations of > 2 . (+Bw)
+ 3 T = 2 s...1800
+ 2 T = 2 s...1800 +Tend = 70...99 %, off + Bw = 0.5 ... 10 %
+ 1 T = 2 s...1800, off OFF/ON
85 ... 140 V
- 1 T = 2 s...1800, off
- 2 T = 2 s...1800 -Tend = 70...99 %, off - Bw = 0.5 ... 10 %
- 3 T = 2 s...1800
134/01/01/0 19
4.05 Universal presetting of parameters required, have been set (in the standard control
system), the universal presetting can either be used
To facilitate setting of parameters as much as possible
for a “single-knob control” with defined results after
when the voltage regulator VC 100-BU is put into ser-
the ARS function has been activated, or it can serve
vice, the unit is delivered with a universal presetting.
as a basis for a further, application-specific optimi-
After the desired voltage level, the measuring transfor-
zation of the voltage regulation.
mer ratios and configuration, the limit values to be
supervised, and values for line drop compensation, if
+3T = 5s
+ 2 T = 20 s + Tend = 97 % + Bw = 1.1 %
To be set + 1 T = 900 s OFF
by user !
- 1 T = Aus
- 2 T = 60 s -Tend = 97 % - Bw = 1.2 %
- 3 T = 10 s
– Very suitable for step voltages: – The negative effects of short-time voltage
1.2 - 1.6 % of UN. fluctuations that extend into the set bandwidth are
– Basic tolerance of the regulated voltage: eliminated due to the tendency setting (97 % of T).
+1 step voltage / – A “slighly unsymmetrical” bandwidth setting can
-2 step voltages of desired voltage level. contribute to an increase of the stability of the
– Positive deviations are corrected faster than regulating system.
negative deviations.
setting. to second
VC 100-BU02
When an inadmissibly high circulating reactive current
is found, a tap change operation by the tap changers
involved is inititated already after 10 s have elapsed,
regardless of the set delay time.
This method is suitable for transformers with similar
power and voltage and with identical or different step intVC22
voltage. No information about the tap position is 22
required.
22 134/01/01/0
5.2.1 System configuration, settings In the lowest tap position the indication should be
“TAP 1”.
The additional connections to the two voltage
When the tap position signalling is interrupted, the
regulators are carried out according to fig. 24.
indication is “TAP 0”.
The following jumpers are attached to the terminals
Master-Follower configuration (fig. 23).
90, 92, 93:
Either voltage regulator can be selected as Master or
jumper A (terminals 90, 92), it determines the parallel Follower by pressing the MASTER/FOLLOWER key
control according to the “Master-Follower” method and turning the scroll wheel. The indicator shows
(synchronism control); “MASTER” or “FOLLOWER” as long as the key is kept
jumper B (terminals 90, 93), if the increase of the tap pressed. During parallel operation the indicator of the
position number shall not result in an increasing but a voltage regulator chosen as Follower shows
decreasing transformer voltage. “FOLLOWER” constantly.
If both voltage regulators are chosen as Follower
The tap position signal from the motor drive is to be or as Master during parallel operation, the voltage
applied to the terminals 94, 95. regulators are blocked and „Alarm“ is signalled
Setting of the tap position range (TAP MAX, fig. 23) (terminals 83, 84, 85, of the signalling relay).
A value of 4 to 40 can be set by pressing the TAP Activation of the parallel control
MAX key and turning the scroll wheel. This value is Parallel control is activated when on both voltage
determined as follows: regulators the terminals 90, 91, are connected with
each other by a switch contact. The LED lamp for
TAP MAX = nmax - nmin “Parallel” lights up and the signalling contact (terminals
80, 81, 82) is activated).
nmin = lowest tap position,
nmax = highest tap position.
5.2.2 Function test, putting into service
Examples: Presettings
NOTE ! A precondition for the correct function of
Tap position range TAP MAX setting
the parallel control is that the voltage regulators
are put into service in the INDIVIDUAL mode ac-
1...19 18
cording to 3.2.3 (contact on terminals 90, 91, must
1...39 38
be open).
-9....0....+9 18
-13....0....+13 26 The voltage regulators must have the same operating
parameter settings for VOLTAGE LEVEL, BAND-
The function test of the tap position signalling is WIDTH, DELAY 1, as well as for LINE COMPEN-
carried out as follows: SATION, if any.
Operate the transformer over the complete tapping The jumpers according to 5.2.1 must have been
range and check the tap position indication by means attached and the tap position signalling must function
of the INFO key (according to 3.1.12). correctly.
VC 100-BU02
Individual / Parallel
Without jumper A: minimum circulating reactive current method. With jumper A: “Master-
Follower” method (synchronism control). Attach jumper B if the increase of the tap position
number shall result in a decreasing transformer voltage.
To the second
4 ... 20 mA Þ tap position n min ...n max VC 100-BU02
Shielded cable, max. 25 m
intVC24
24
134/01/01/0 23
The MANUAL mode must be selected on both voltage 6. REGULATOR PARAMETERING
regulators. SOFTWARE
Operate the tap changers of the two transformers in VRR-CONTROL
INDIVIDUAL mode so that their tap positions are the
same and both voltage regulators are in a balanced VRR-CONTROL offers the possibility of programming
state (no RAISE oder LOWER presignal). and interrogating the parameters of the voltage
regulator VC 100-BU from a PC via the serial
Connect the transformers in parallel and close the interface. A program disc is included in the standard
switch contacts on the terminals 90, 91, of each delivery.
voltage regulator. The voltage regulators must still be
in a balanced state. Select the AUTO mode on one of A Hardware
the two voltage regulators. The LED lamps for “Paral-
lel” on both voltage regulators must light up. The execution of the transmission program requires an
IBM-PC compatible computer with MS-DOS operating
With the second voltage regulator in MANUAL mode, system (version 3.3 or higher). The system should
move the tap changer towards RAISE by one step. include a graphics card with VGA capability. The data
The voltage regulator in AUTO mode must now transmission itself requires a bidirectional serial inter-
automatically control its tap changer to the same tap face and a shielded data transmission cable.
position.
The LED lamps for “Alarm” light up for a short time
while the tap positions are different. If the first trans-
former is not controlled to this same tap position both Pin assignment for the transmission cable:
voltage regulators are blocked and a signalling relay If the PC has a 9-pole interface connector:
(terminals 83, 84, 84) activated after 30 s.
VC 100-BU PC
5.2.3 Parallel control failure (25-pole plug) (9-pole socket)
If one or both voltage regulator are signalling “Parallel
control failure” instead of “Parallel” although the
control inputs (terminals 90, 91) on both voltage
regulators are correctly configured, the causes can be
the following:
– Interruption of the data communication between
the voltage regulators. The shielded cable must be
checked for such an interruption.
– The second voltage regulator is not operable.
– Different parallel control methods have been
selected.
The voltage regulators are blocked in such a case.
VC 100-BU PC
(25-pole plug) (25-pole socket)
24 134/01/01/0
B Description of the program 2. Sub-menu “Communication”
VRR-CONTROL is started under DOS by entering This sub-menu appears after the item “Communi-
cation” has been selected (fig. 22) in the main menu.
<A:>mrvrr RETURN It contains a dialog window where the control para-
meters of the programm can be set:
Emphasis in the development stage was on user-
friendly operation. All functions are mainly self- 1 PC-Port COM1,COM2,...:
explanatory.
selection of the serial interface on the PC.
All entries are made by a keyboard, a mouse is not
required. 2 Interrogation clock min, 5 sec, 10 sec:
The following short explanations show the possible This is the waiting time during monitor operation until
functions. the values are updated again.
After the program has been started the desired 3 Data transmission ON/OFF:
language is selected. The heading appears on the The data transmission to the voltage regulator is
display followed by the main menu after any key has switched on or off.
been pressed.
Immediately after the start of the program, the serial
interface of the PC used for the data transmission
1. Main menu
must be entered here. After the voltage regulator has
In the upper part of the display screen there is the been connected to the PC and the data transmission
menu bar. The individual menu items can be selected has been switched on, the message “Communication
here by means of the cursor keys (left/right) or initial ok” should appear in the status bar. If no message
letter and the RETURN key (fig. 25). appears the following points must be checked:
In the bottom part of the display screen there is the – Is an interface cable according to the hardware
status bar which always shows the current state of the specification (point A) used?
data transmission. Possible errors in the
– Does the serial interface comply with the program
communication with the voltage regulator can be read
specifications?
here (fig. 25).
(Sometimes the data transmission does not
Above the status bar there is a short “context help” function via certain serial interfaces
which describes how the program can be served at the on the PC. In such a case it should be tried to use
moment (fig. 25). any other serial interface.)
To establish communication with the voltage regulator – Is the voltage regulator in the correct operating
certain settings must be made first. condition?
134/01/01/0 25
3. Sub-menu “Options” Then the question is asked whether the parameter
values are to be stored.
Here it is possible to store the values of the parameter
If the answer is affirmative, the data file name and
settings in a data file (1 Secure Parameters) and to
path must be entered so that the values are stored as
reload them into the voltage regulator (2 Load Para-
text file under this name (fig. 27).
meters) (fig. 26).
26 Options 27 Open the data file (the data name shown is an example)
26 134/01/01/0
The function “Load Parameters” is accomplished The dialog window for the particular voltage regulator
analogously. Make sure that the Local/Remote switch version appears (fig. 29). The individual parameter
on the voltage regulator is set to Remote parameter- groups are selected in the left hand area. By pressing
ing so that the voltage regulator can take over the the RETURN key the parameter entry field is dis-
values. played where the individual parameters can be
selected with the cursor keys and the RETURN key.
The option “New parameter” allows to create a new
Go back by means of the escape key.
parameter data file. Values can also be taken over
from an existing file to serve as a basis. This procedure does not require a communication
with the VC 100-BU. If only this procedure is to be
With the option “New parameter” the same parame-
carried out, e.g. for pre-parametering on the PC,
ters can be set as on the VC 100-BU directly.
then the data leads and settings described under
Exception: The voltage regulator identification code
paragraph 2 can be omitted.
(a four-digit registration number 0...9999) can only be
set by means of this parametering program and not on The editor area is left by pressing the ESC key.
the VC 100-BU directly. The parameter values are stored by entering the data
file name.
First enter the version number of the voltage regulator
for which the parameters are set (i.e. 01 or 02, on the
nameplate of the VC 100-BU).
134/01/01/0 27
4. Sub-menu “Monitor”
This sub-menue indicates the present operating status The values are updated after a waiting time entered as
of the voltage regulator (fig. 30) including all “Interrogation clock”.
measured values and the info data.
30 Sub-menu “Monitor”
28 134/01/01/0
7. FAILURES
134/01/01/0 29
For flush panel
mounting remove
nipples threaded Lug for
flush panel
mounting
30 134/01/01/0
Customer Voltage regulator type:
MR order number:
Address: Serial no:
Connection diagram:
Voltage transformer rating:
Current transformer rating:
Measuring transformer config.:
Notes:
134/01/01/0 31
Voltage regulator VC 100-BU
Delay time
- Time 1 0 ... 180 s lin / inv s lin / inv
- Time 2 0 ... 10 s / off s / off
Measuring transformers
- Voltage transformer 0.1 ... 999.0 kV Referred to 100 V (secondary),
- Current transformer 100 ... 5000 A see page 8, fig. 5a
- Phase angle between current
path and voltage path 0°, 90°, 30°, –30°
LDC
- Ur 0 ... ± 25 V V Resistive,
- Ux 0 ... ± 25 V V reactive
in steps of 1 V voltage drop
Z-compensation
- Voltage raise 0 ... 15 %, %
- Limitation 0 ... 15 % of desired voltage %
level in steps of 1 %
Instructions for the setting of the regulating parameters are to be found in paragraph 3.2.3 and in paragraph 5 for
the setting of the parallel operation.
If the indicator shows the failure message “PARAM” press all function keys without turning the scroll wheel and
check the setting parameters. Correct if necessary (in case of double-function keys check both parameters,
actuate LOCAL/REMOTE and LDC/Z-Comp. switches). If the message “PARAM” continues to be displayed, refer
to paragraph 7 “operating failures”.
32 134/01/01/0
BA 134/01 en - 0597/2000
134/01/01/0
F0043500