Untitled - Load Flow Report

This document summarizes the results of a load flow analysis of an electrical transmission and distribution system. It shows the voltage, generation, load, and power flow between buses. Key buses include Bus 4 (500kV) which supplies power to other buses through transformers. The load flow is within acceptable limits with some transformers operating at around 80% power factor and 1539 amps of current on the highest loaded transformer.

Uploaded by

ananta iqbal
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
43 views1 page

Untitled - Load Flow Report

This document summarizes the results of a load flow analysis of an electrical transmission and distribution system. It shows the voltage, generation, load, and power flow between buses. Key buses include Bus 4 (500kV) which supplies power to other buses through transformers. The load flow is within acceptable limits with some transformers operating at around 80% power factor and 1539 amps of current on the highest loaded transformer.

Uploaded by

ananta iqbal
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

ETAP

Project: Page: 1
12.6.0H
Location: Date: 13-11-2019
Contract: SN:
Engineer: Revision: Base
Study Case: LF
Filename: transmisi & ptt Config.: Normal

LOAD FLOW REPORT

Bus Voltage Generation Load Load Flow XFMR

ID kV % Mag. Ang. MW Mvar MW Mvar ID MW Mvar Amp %PF %Tap

Bus2 150.000 98.505 -5.3 0 0 334.953 207.585 Bus13 -334.953 -207.585 1539.8 85.0

Bus3 150.000 98.547 -5.3 0 0 333.133 206.457 Bus7 -333.133 -206.457 1530.8 85.0

Bus4 500.000 100.000 0.0 160.000 120.000 0 0 Bus6 0.000 0.000 0.0 0.0

Bus12 80.000 60.000 115.5 80.0

Bus14 80.000 60.000 115.5 80.0

Bus6 500.000 100.000 0.0 0 0 0 0 Bus4 0.000 0.000 0.0 0.0

Bus7 0.000 0.000 0.0 0.0

Bus7 500.000 100.000 0.0 0 0 0 0 Bus3 334.050 252.316 483.4 79.8 -5.000

Bus6 0.000 0.000 0.0 0.0

Bus8 -334.050 -252.316 483.4 79.8

Bus8 500.000 100.000 0.0 0 0 0 0 Bus7 334.050 252.316 483.4 79.8

Bus12 -80.000 -60.000 115.5 80.0

Bus13 -254.050 -192.316 367.9 79.7

Bus12 500.000 100.000 0.0 0 0 0 0 Bus4 -80.000 -60.000 115.5 80.0

Bus8 80.000 60.000 115.5 80.0

Bus13 500.000 100.000 0.0 0 0 0 0 Bus2 335.881 253.987 486.2 79.8 -5.000

Bus8 254.050 192.316 367.9 79.7

Bus14 -589.932 -446.303 854.2 79.7

* Bus14 500.000 100.000 0.0 509.932 386.303 0 0 Bus4 -80.000 -60.000 115.5 80.0

Bus13 589.932 446.303 854.2 79.7


* Indicates a voltage regulated bus (voltage controlled or swing type machine connected to it)
# Indicates a bus with a load mismatch of more than 0.1 MVA