ETAP
Project: Page: 1
12.6.0H
Location: Date: 13-11-2019
Contract: SN:
Engineer: Revision: Base
Study Case: LF
Filename: transmisi & ptt Config.: Normal
LOAD FLOW REPORT
Bus Voltage Generation Load Load Flow XFMR
ID kV % Mag. Ang. MW Mvar MW Mvar ID MW Mvar Amp %PF %Tap
Bus2 150.000 98.505 -5.3 0 0 334.953 207.585 Bus13 -334.953 -207.585 1539.8 85.0
Bus3 150.000 98.547 -5.3 0 0 333.133 206.457 Bus7 -333.133 -206.457 1530.8 85.0
Bus4 500.000 100.000 0.0 160.000 120.000 0 0 Bus6 0.000 0.000 0.0 0.0
Bus12 80.000 60.000 115.5 80.0
Bus14 80.000 60.000 115.5 80.0
Bus6 500.000 100.000 0.0 0 0 0 0 Bus4 0.000 0.000 0.0 0.0
Bus7 0.000 0.000 0.0 0.0
Bus7 500.000 100.000 0.0 0 0 0 0 Bus3 334.050 252.316 483.4 79.8 -5.000
Bus6 0.000 0.000 0.0 0.0
Bus8 -334.050 -252.316 483.4 79.8
Bus8 500.000 100.000 0.0 0 0 0 0 Bus7 334.050 252.316 483.4 79.8
Bus12 -80.000 -60.000 115.5 80.0
Bus13 -254.050 -192.316 367.9 79.7
Bus12 500.000 100.000 0.0 0 0 0 0 Bus4 -80.000 -60.000 115.5 80.0
Bus8 80.000 60.000 115.5 80.0
Bus13 500.000 100.000 0.0 0 0 0 0 Bus2 335.881 253.987 486.2 79.8 -5.000
Bus8 254.050 192.316 367.9 79.7
Bus14 -589.932 -446.303 854.2 79.7
* Bus14 500.000 100.000 0.0 509.932 386.303 0 0 Bus4 -80.000 -60.000 115.5 80.0
Bus13 589.932 446.303 854.2 79.7
* Indicates a voltage regulated bus (voltage controlled or swing type machine connected to it)
# Indicates a bus with a load mismatch of more than 0.1 MVA