DESIGN OF FOOTING: F3
PARAMETERS:
Lx (m) Lz (m)
SIZE OF FOOTINGS = 2 2
Lx1 (m) Lz1 (m)
SIZE OF PEDESTALS = 0.3 0.7
COVER TO BOTTOM RAFT = 75 mm
THICKNESS OF RAFT = D = 0.3 m
DEPTH OF FOOTING = H = 1 m
NGL TO FFL = 0 m
UNIT WT. OF CONC = 2.5 T/m2
UNIT WT. OF SOIL = 1.8 T/m2
WEIGHT OF FOUNDATION RAFT = 3 T
WEIGHT OF SOIL= 4.7754 T
TOTAL = 7.7754 T
LOADS:
LOAD Horizontal Vertical Gross Fy Horizontal Moment from str. Moment from str. Total Moment Total Moment
Node COMBINATION Fx Mton Fy Mton Mton Fz Mton Mx MTon-m Mz MTon-m Mx MTon-m Mz MTon-m
(Hx) (V) (Vg) (Hz) (Mx) (Mz)
29 100 DL+LL 0.518 0.657 8.4324 0.012 0 0 0 0
101 DL+WL1 -0.092 0.235 8.0104 -0.003 0 0 0 0
102 DL+WL2 0.609 0.432 8.2074 0.015 0 0 0 0
103 DL+WL3 0.113 0.291 8.0664 0.005 0 0 0 0
105 DL+LL+WL1 0.251 0.585 8.3604 0.005 0 0 0 0
106 DL+LL+WL2 0.952 0.782 8.5574 0.024 0 0 0 0
107 DL+WL3 0.456 0.641 8.4164 0.014 0 0 0 0
109 DL+SLX -1.061 -0.023 7.7524 -0.026 0 0 0 0
110 DL-SLX 1.41 0.638 8.4134 0.034 0 0 0 0
111 DL+SLZ 0.149 0.299 8.0744 0.002 0 0 0 0
112 DL-SLZ 0.2 0.316 8.0914 0.006 0 0 0 0
113 DL+LL+SLX -0.718 0.327 8.1024 -0.017 0 0 0 0
114 DL+LL-SLX 1.754 0.988 8.7634 0.042 0 0 0 0
115 DL+LL+SLZ 0.493 0.649 8.4244 0.01 0 0 0 0
116 DL+LL-SLZ 0.543 0.666 8.4414 0.015 0 0 0 0
NETT ALLOWABLE BEARING PRESSURE = 15 T/Sqm
PRESSURE OF SOIL BELOW NGL = 1.8 T/Sqm
GROSS ALLOWABLE BEARING PRESSURE = 16.8 T/Sqm (For DL, LL and ELL)
AND = 20.55 T/Sqm (For WL, SL)
CALCULATION OF BASE PRESSURE:
LOAD Vg 6Mx 6Mz PRESSURE BELLOW FOUNDATION (T/m2)
COMBINATION Lx*Lz Lx * Lz2 Lx2 * Lz p1 STATUS p2 STATUS p3 STATUS p4 STATUS
13 DL+LL 2.108 0 0 2.108 O.K 2.108 O.K 2.108 O.K 2.108 O.K
14 DL+WL1 2.003 0 0 2.003 O.K 2.003 O.K 2.003 O.K 2.003 O.K
15 DL+WL2 2.052 0 0 2.052 O.K 2.052 O.K 2.052 O.K 2.052 O.K
16 DL+WL3 2.017 0 0 2.017 O.K 2.017 O.K 2.017 O.K 2.017 O.K
17 DL+WL4 2.09 0 0 2.09 O.K 2.09 O.K 2.09 O.K 2.09 O.K
18 DL+WL5 2.139 0 0 2.139 O.K 2.139 O.K 2.139 O.K 2.139 O.K
19 DL+WL6 2.104 0 0 2.104 O.K 2.104 O.K 2.104 O.K 2.104 O.K
20 DL+WL7 1.938 0 0 1.938 O.K 1.938 O.K 1.938 O.K 1.938 O.K
21 DL+WL8 2.103 0 0 2.103 O.K 2.103 O.K 2.103 O.K 2.103 O.K
22 DL+0.8LL+ 0.8WL1 2.019 0 0 2.019 O.K 2.019 O.K 2.019 O.K 2.019 O.K
23 DL+0.8LL+ 0.8WL2 2.023 0 0 2.023 O.K 2.023 O.K 2.023 O.K 2.023 O.K
24 DL+0.8LL+ 0.8WL3 2.026 0 0 2.026 O.K 2.026 O.K 2.026 O.K 2.026 O.K
25 DL+0.8LL+ 0.8WL4 2.191 0 0 2.191 O.K 2.191 O.K 2.191 O.K 2.191 O.K
26 DL+0.8LL+ 0.8WL5 2.106 0 0 2.106 O.K 2.106 O.K 2.106 O.K 2.106 O.K
27 DL+0.8LL+ 0.8WL6 2.11 0 0 2.11 O.K 2.11 O.K 2.11 O.K 2.11 O.K
2.191 2.191 2.191 2.191 2.191
LOAD % OF GROSS Gross Fy Moment Moment F.S (z) = F.S (x) =
COMBINATION WEIGHT Mton MTon-m MTon-m Vg*Lz / 2Mx STATUS Vg*Lz / 2Mz STATUS
(Vg) (Mx) (Mz)
13 DL+LL 100% 8.4324 0 0 #DIV/0! #DIV/0! #DIV/0! #DIV/0!
14 DL+WL1 90% 8.0104 0 0 #DIV/0! #DIV/0! #DIV/0! #DIV/0!
15 DL+WL2 90% 8.2074 0 0 #DIV/0! #DIV/0! #DIV/0! #DIV/0!
16 DL+WL3 90% 8.0664 0 0 #DIV/0! #DIV/0! #DIV/0! #DIV/0!
17 DL+WL4 90% 8.3604 0 0 #DIV/0! #DIV/0! #DIV/0! #DIV/0!
18 DL+WL5 90% 8.5574 0 0 #DIV/0! #DIV/0! #DIV/0! #DIV/0!
19 DL+WL6 90% 8.4164 0 0 #DIV/0! #DIV/0! #DIV/0! #DIV/0!
20 DL+WL7 90% 7.7524 0 0 #DIV/0! #DIV/0! #DIV/0! #DIV/0!
21 DL+WL8 90% 8.4134 0 0 #DIV/0! #DIV/0! #DIV/0! #DIV/0!
22 DL+0.8LL+ 0.8WL1 90% 8.0744 0 0 #DIV/0! #DIV/0! #DIV/0! #DIV/0!
23 DL+0.8LL+ 0.8WL2 90% 8.0914 0 0 #DIV/0! #DIV/0! #DIV/0! #DIV/0!
24 DL+0.8LL+ 0.8WL3 90% 8.1024 0 0 #DIV/0! #DIV/0! #DIV/0! #DIV/0!
25 DL+0.8LL+ 0.8WL4 90% 8.7634 0 0 #DIV/0! #DIV/0! #DIV/0! #DIV/0!
26 DL+0.8LL+ 0.8WL5 90% 8.4244 0 0 #DIV/0! #DIV/0! #DIV/0! #DIV/0!
27 DL+0.8LL+ 0.8WL6 90% 8.4414 0 0 #DIV/0! #DIV/0! #DIV/0! #DIV/0!
#DIV/0! #DIV/0! #DIV/0! #DIV/0!
CHECK AGAINST SLIDING:
LOAD % OF GROSS Gross Fy Horizontal Horizontal F.S (x) = F.S (z) =
COMBINATION WEIGHT Mton Mton Fz Mton Vg*0.4/ Hx STATUS Vg*0.4 / Hz STATUS
(Vg) (Hx) (hz)
13 DL+LL 100% 8.4324 0.518 0.012 6.512 > 1.4 281.08 >1.4 0.486
14 DL+WL1 90% 7.20936 0.092 0.003 31.345 > 1.4 961.248 >1.4
15 DL+WL2 90% 7.38666 0.609 0.015 4.852 > 1.4 196.978 >1.4
16 DL+WL3 90% 7.25976 0.113 0.005 25.698 > 1.4 580.781 >1.4
17 DL+WL4 90% 7.52436 0.251 0.005 11.991 > 1.4 601.949 >1.4
18 DL+WL5 90% 7.70166 0.952 0.024 3.236 > 1.4 128.361 >1.4
19 DL+WL6 90% 7.57476 0.456 0.014 6.645 > 1.4 216.422 >1.4
20 DL+WL7 90% 6.97716 1.061 0.026 2.63 > 1.4 107.341 >1.4
21 DL+WL8 90% 7.57206 1.41 0.034 2.148 > 1.4 89.083 >1.4
22 DL+0.8LL+ 0.8WL1 90% 7.26696 0.149 0.002 19.509 > 1.4 1453.392 >1.4
23 DL+0.8LL+ 0.8WL2 90% 7.28226 0.2 0.006 14.565 > 1.4 485.484 >1.4
24 DL+0.8LL+ 0.8WL3 90% 7.29216 0.718 0.017 4.062 > 1.4 171.58 >1.4
25 DL+0.8LL+ 0.8WL4 90% 7.88706 1.754 0.042 1.799 > 1.4 75.115 >1.4
26 DL+0.8LL+ 0.8WL5 90% 7.58196 0.493 0.01 6.152 > 1.4 303.278 >1.4
27 DL+0.8LL+ 0.8WL6 90% 7.59726 0.543 0.015 5.597 > 1.4 202.594 >1.4
1.799 > 1.4 75.115 > 1.4
DESIGN OF FOOTING RAFT
AS THE FOOTING SIZE IS OPTIMIZED, FOR SIMPLICTY WE SHALL CONSIDER UNIFORM SOIL PRESSURE EQUAL TO THE MAXIMUM ENCOUNTERED NETT PRESSURE
fck = 30 Mpa D= 300 mm
fy = 500 Mpa d= 225 mm
Maximum nett pressure encountered = 0.4 t/m2
Check against Moment at column face:
Reinforcement along 'X' : (bottom)
Maximum cantilever = 0.85 m
Maximum moment at pedestal face = 0.145 t-m
Mu (max) = 0.2175 t-m /m
Mu/ bd2 = 0.043
pt = 0.07 % From SP-16
Ast = 1.575 cm2 / m
Provide 12 Φ @ 200 c/c at bottom
and 10 Φ @ 200 c/c at top
Provided steel area at bottom = 5.65 cm2 / m O.K
& Provided steel area at top = 3.93 cm2 / m
Provided percentage at bottom = 0.251 % O.K
Provided percentage at top = 0.175 % Total % of steel = 0.426 >0.12% O.K
Allowable shear stress = 0.33 Mpa From SP-16
Reinforcement along 'Z' : (bottom)
Maximum cantilever = 0.85 m
Maximum moment at pedestal face = 0.145 t-m
Mu (max) = 0.2175 T-m /m
Mu/ bd2 = 0.043
pt = 0.07 % From SP-16
Ast (reqd) = 1.575 cm2 / m
Provide 12 Φ @ 200 c/c at bottom
and 10 Φ @ 200 c/c at top
Provided steel area at bottom = 5.65 cm2 / m O.K
& Provided steel area at top = 3.93 cm2 / m
Provided percentage at bottom = 0.251 % O.K
Provided percentage at top = 0.175 % Total % of steel = 0.426 >0.12% O.K
Allowable shear stress = 0.33 Mpa From SP-16
Check against one way shear:
Critical section occurs at "d" distance from the face of the pedestal
One way shear in 'X' direction:
Distance of critical section = 0.625 m from edge o.k
Total Shear = V = 0.25 T
Shear stress = 0.017 Mpa o.k
One way shear in 'z' direction:
Distance of critical section = 0.425 m from edge o.k
Total Shear = V = 0.17 T
Shear stress = 0.0112 Mpa o.k
Check against punching shear:
0.1125 m from the face of pedestal
Location of critical section for punching shear =
Punching shear = 1.40575 T
punching stress = 0.032 Mpa
Alowable punching stress = 1.3693064 Mpa O.K
CONCLUSION :
SIZE OF FOOTING = 2 m X 2 m
THICKNESS = 300 mm
BOTTOM REINFORCEMENT IN 'X' DIRECTION = 12 Φ @ 200 c/c at bottom
BOTTOM REINFORCEMENT IN 'Z' DIRECTION = 12 Φ @ 200 c/c at bottom
TOP REINFORCEMENT IN 'X' DIRECTION = 10 Φ @ 200 c/c at bottom
TOP REINFORCEMENT IN 'Z' DIRECTION = 10 Φ @ 200 c/c at bottom
Footing Size = X Z
DESIGN OF RAFT FOUNDATION-RF3 20.94 9.41
Adopt Size= 20.94 9.41 62.867625
0.925
Horizontal Vertical Horizontal Moment 0
Z- Co-
Node X Co-Ordinate L/C Fx Mton Fy Mton Fz Mton Mx Tm Mz Tm Fy*fx Fy*fz
Ordinate
353 1.6 6.71 100 D+L+CR1 -0.133 25.283 -0.213 -0.725 0.061 40.45 169.65
355 4.866 6.71 100 D+L+CR1 0.246 24.499 -0.332 -1 -0.247 119.21 164.39 STRIP
357 9.136 6.71 100 D+L+CR1 -0.019 25.939 -0.357 -1.095 -0.033 236.98 174.05 WEIGHT OF FDN
359 12.616 6.71 100 D+L+CR1 0.13 24.048 -0.361 -1.084 -0.155 303.39 161.36 WEIGHT OF SOIL
361 16.336 6.71 100 D+L+CR1 0.005 23.699 -0.183 -0.73 -0.054 387.15 159.02
363 19.336 6.71 100 D+L+CR1 0.34 32.438 -1.542 -1.135 -0.326 627.22 217.66 2.7
485 1.6 2.7 100 D+L+CR1 0.734 64.135 0.019 -1.366 -0.487 102.62 173.16
486 4.866 2.7 100 D+L+CR1 -0.296 67.965 0.031 -1.539 -0.059 330.72 183.51
487 9.136 2.7 100 D+L+CR1 -0.027 69.972 -0.027 -1.891 -0.111 639.26 188.92 7.9167666459
488 12.616 2.7 100 D+L+CR1 1.023 66.734 -0.08 -2.041 -0.665 841.92 180.18
489 16.336 2.7 100 D+L+CR1 -0.709 63.349 -0.222 -2.194 0.103 1034.87 171.04
490 19.336 2.7 100 D+L+CR1 0.535 65.653 0.329 -2.323 -0.669 1269.47 177.26
SUMMATION 1.83 553.71 -2.94 -17.12 -2.64 5933.26 2120.2
10.72 3.83
Moment due to eccentricity = ex ez Mxe Mze Mx(total) Mz(total) ex,ez = Eccentricity in x and z
0.252 0.875 484.50 139.54 467.38 136.89 Mex, Mez = Moment due to ex,z
Depth of foundation = 2 m
Distance between NGL and FFL = 0.6 m
DEPTH OF RAFT = 750 mm d= 675 Cover 75 mm
AREA OF RAFT (A)= 197.01 m2
SELF WT. OF FOUNDATION= 369.39 Mton Zxx = 308.97 m3
WT. OF SOIL = 656.04 Mton Zzz = 687.43 m3
Total 1025.43 Mton
GROSS TOTAL WEIGHT = 1579.14 Mton
Pressure under footing (p1) 9.727 OK (Fy/A+Mx/Zxx+Mz/Zzz)
Net bearing capacity of soil = 6.5 Mton/m2 Pressure under footing (p2) 6.702 OK (Fy/A-Mx/Zxx+Mz/Zzz)
Gross allowable bearing capacity (DL,LL,CR)= 10.10 Mton/m2 Pressure under footing (p3) 9.329 OK (Fy/A+Mx/Zxx-Mz/Zzz)
Gross allowable bearing capacity (WL,SQL)= 11.73 Mton/m2 Pressure under footing (p4) 6.304 OK (Fy/A-Mx/Zxx-Mz/Zzz)
Check for overturning F.O.S L.O.C % 0
Gross weight = 1579.14 T
Moment in x (Mx) = 467.37675 T-m 14.3 OK
Moment in z (Mz) = 136.89 T-m 108.68 OK
Moment in Central portion (Shorter Direction) Net pressure under foundation= 6.13 Mton/m2
Distance between columns= 4.01 m D = 750 mm
d = 675 mm
Maximum moment at Column face (Wl /10)= 2
9.86 Mton-m/m
Mu (max) = 14.79 Mton-m/m
Mu/ bd2 = 0.319 Mpa
pt = 0.084 % From SP-16, Table-4
Ast = 5.67 cm2 / m
Provide 16 Φ@ 150 c/c at top
Provided steel area at top = 13.4 cm2 / m O.K
Moment in Cantilever portion(Shorter Direction)
Cantilever = 2.70 m
Maximum moment at Column face (Wl /2)= 2
22.34 Mton-m/m
Mu (max) = 33.51 Mton-m/m
Mu/ bd2 = 0.722 Mpa
pt = 0.191 % From SP-16, Table-4
Ast (reqd) = 12.89 cm2 / m
Provide 16 Φ@ 135 c/c at bottom
Provided steel area at bottom = 14.89 cm2 / m O.K
pt provided = 0.22 %
Total pt (Top+Bottom) 0.22 %
Allowable shear stress = 0.33 Mpa From SP-16, Table-61
Check for Shear in Shorter Direction
d= 0.675 m
Critical section for shear development= 2.025 m
Shear force at that section= 12.41 Mton/m length
Shear stress = 0.271 Mpa OK
Moment in Central portion (Longer Direction)
Distance between columns= 4.2 m
Maximum moment at Column face (Wl2/10) = 10.81 Mton-m/m
Mu (max) = 16.22 Mton-m/m
Mu/ bd2 = 0.35 Mpa
pt = 0.084 % From SP-16, Table-4
Ast = 5.67 cm2 / m
Provide 16 Φ@ 150 c/c at top
Provided steel area at top= 13.4 cm2 / m O.K
pt provided = 0.2 %
Moment in Cantilever portion (Longer Direction)
Cantilever = 1.6 m
Maximum moment at Column face (Wl2/2) = 7.85 Mton-m/m
Mu (max) = 11.78 Mton-m/m
Mu/ bd2 = 0.254 Mpa
pt = 0.07 % From SP-16, Table-4
Ast (reqd) = 4.73 cm2 / m
Provide 16 Φ@ 135 c/c at bottom
Provided steel area at bottom = 14.89 cm2 / m O.K
pt provided = 0.22 %
Total pt (Top+Bottom) 0.42 %
Allowable shear stress = 0.33 Mpa From SP-16, Table-61
Check for Shear in Longer Direction
d= 0.675 m
Critical section for shear development= 0.925 m
Shear force at that section= 5.67 Mton/m length
Shear stress = 0.124 Mpa OK
Footing Size = X Z
DESIGN OF RAFT FOUNDATION-RF3 20.94 9.41
Adopt Size= 20.94 9.41
Horizontal Vertical Horizontal Moment
Z- Co-
Node X Co-Ordinate L/C Fx Mton Fy Mton Fz Mton Mx Tm Mz Tm Fy*fx Fy*fz
Ordinate
353 1.6 6.71 122 D+L+CR1+EQZ -0.022 29.021 0.55 2.055 0.202 46.43 194.73
355 4.866 6.71 122 D+L+CR1+EQZ 0.343 27.406 0.785 2.413 -0.116 133.36 183.89
357 9.136 6.71 122 D+L+CR1+EQZ 0.081 28.942 0.736 2.299 0.101 264.41 194.2
359 12.616 6.71 122 D+L+CR1+EQZ 0.238 26.904 0.733 2.263 -0.013 339.42 180.53
361 16.336 6.71 122 D+L+CR1+EQZ 0.092 26.998 0.525 1.92 0.071 441.04 181.16
363 19.336 6.71 122 D+L+CR1+EQZ 0.47 42.985 1.715 1.988 -0.168 831.16 288.43
485 1.6 2.7 122 D+L+CR1+EQZ 0.941 65.733 2.318 11.231 -0.196 105.17 177.48
486 4.866 2.7 122 D+L+CR1+EQZ -0.068 69.763 2.768 11.864 0.235 339.47 188.36
487 9.136 2.7 122 D+L+CR1+EQZ 0.123 71.851 2.716 11.549 0.152 656.43 194
488 12.616 2.7 122 D+L+CR1+EQZ 1.222 68.501 2.614 11.209 -0.393 864.21 184.95
489 16.336 2.7 122 D+L+CR1+EQZ -0.492 65.828 2.433 10.898 0.382 1075.37 177.74
490 19.336 2.7 122 D+L+CR1+EQZ 0.695 73.581 4.561 9.98 -0.408 1422.76 198.67
SUMMATION 3.62 597.51 22.45 79.67 -0.15 6519.23 2344.14
10.91 3.92
Moment due to eccentricity = ex ez Mxe Mze Mx(total) Mz(total) ex,ez = Eccentricity in x and z
0.442 0.785 469.05 264.10 548.72 263.95 Mex, Mez = Moment due to ex,z
Depth of foundation = 2 m
Distance between NGL and FFL = 0.6 m
DEPTH OF RAFT = 750 mm d= 675 Cover 75 mm
AREA OF RAFT (A)= 197.01 m2
SELF WT. OF FOUNDATION= 369.39 Mton Zxx = 308.97 m3
WT. OF SOIL = 656.04 Mton Zzz = 687.43 m3
Total 1025.43 Mton
GROSS TOTAL WEIGHT = 1622.94 Mton
Pressure under footing (p1) 10.398 OK (Fy/A+Mx/Zxx+Mz/Zzz)
Net bearing capacity of soil = 6.5 Mton/m2 Pressure under footing (p2) 6.846 OK (Fy/A-Mx/Zxx+Mz/Zzz)
Gross allowable bearing capacity (DL,LL,CR)= 10.10 Mton/m2 Pressure under footing (p3) 9.63 OK (Fy/A+Mx/Zxx-Mz/Zzz)
Gross allowable bearing capacity (WL,SQL)= 11.73 Mton/m2 Pressure under footing (p4) 6.078 OK (Fy/A-Mx/Zxx-Mz/Zzz)
Check for overturning F.O.S L.O.C % 0
Gross weight = 1622.94 T
Moment in x (Mx) = 548.716705 T-m 12.5 OK
Moment in z (Mz) = 263.95 T-m 57.93 OK
Moment in Central portion (Shorter Direction) Net pressure under foundation= 6.8 Mton/m2
Distance between columns= 4.01 m D = 750 mm
d = 675 mm
Maximum moment at Column face (Wl2/10)= 10.93 Mton-m/m
Mu (max) = 16.4 Mton-m/m
Mu/ bd2 = 0.354 Mpa
pt = 0.084 % From SP-16, Table-4
Ast = 5.67 cm2 / m
Provide 16 Φ@ 150 c/c at top
Provided steel area at top = 13.4 cm2 / m O.K
Moment in Cantilever portion(Shorter Direction)
Cantilever = 2.70 m
Maximum moment at Column face (Wl2/2)= 24.79 Mton-m/m
Mu (max) = 37.19 Mton-m/m
Mu/ bd2 = 0.801 Mpa
pt = 0.204 % From SP-16, Table-4
Ast (reqd) = 13.77 cm2 / m
Provide 16 Φ@ 135 c/c at bottom
Provided steel area at bottom = 14.89 cm2 / m O.K
pt provided = 0.22 %
Total pt (Top+Bottom) 0.22 %
Allowable shear stress = 0.33 Mpa From SP-16, Table-61
Check for Shear in Shorter Direction
d= 0.675 m
Critical section for shear development= 2.025 m
Shear force at that section= 13.77 Mton/m length
Shear stress = 0.3 Mpa OK
Moment in Central portion (Longer Direction)
Distance between columns= 4.2 m
Maximum moment at Column face (Wl2/10) = 12 Mton-m/m
Mu (max) = 18 Mton-m/m
Mu/ bd2 = 0.388 Mpa
pt = 0.106 % From SP-16, Table-4
Ast = 7.16 cm2 / m
Provide 16 Φ@ 150 c/c at top
Provided steel area at top= 13.4 cm2 / m O.K
pt provided = 0.2 %
Moment in Cantilever portion (Longer Direction)
Cantilever = 1.6 m
Maximum moment at Column face (Wl2/2) = 8.7 Mton-m/m
Mu (max) = 13.05 Mton-m/m
Mu/ bd2 = 0.281 Mpa
pt = 0.07 % From SP-16, Table-4
Ast (reqd) = 4.73 cm2 / m
Provide 16 Φ@ 135 c/c at bottom
Provided steel area at bottom = 14.89 cm2 / m O.K
pt provided = 0.22 %
Total pt (Top+Bottom) 0.42 %
Allowable shear stress = 0.33 Mpa From SP-16, Table-61
Check for Shear in Longer Direction
d= 0.675 m
Critical section for shear development= 0.925 m
Shear force at that section= 6.29 Mton/m length
Shear stress = 0.137 Mpa OK
Footing Size = X Z
DESIGN OF RAFT FOUNDATION-RF2 3.80 11.01
Adopt Size= 3.80 11.01
Horizontal Vertical Horizontal Moment
Z- Co-
Node X Co-Ordinate L/C Fx Mton Fy Mton Fz Mton Mx Tm Mz Tm Fy*fx Fy*fz
Ordinate
48 1.9 1.9 100 D+L+CR1 -0.017 48.381 0.392 0.215 0.492 91.92 91.92
491 1.9 5.1 100 D+L+CR1 -0.683 53.968 1.341 0.415 0.1 102.54 275.24
365 1.9 9.11 100 D+L+CR1 -0.636 25.442 -0.485 -0.517 0.424 48.34 231.78
SUMMATION -1.34 127.79 1.25 0.11 1.02 242.8 598.94
1.9 4.69
Moment due to eccentricity = ex ez Mxe Mze Mx(total) Mz(total) ex,ez = Eccentricity in x and z
0 0.815 104.15 0.00 104.26 1.02 Mex, Mez = Moment due to ex,z
Depth of foundation = 2 m
Distance between NGL and FFL = 0.6 m
DEPTH OF RAFT = 600 mm d= 525 Cover 75 mm
AREA OF RAFT (A)= 41.84 m2
SELF WT. OF FOUNDATION= 62.76 Mton Zxx = 76.77 m3
WT. OF SOIL = 150.62 Mton Zzz = 26.5 m3
Total 213.38 Mton
GROSS TOTAL WEIGHT = 341.17 Mton
Pressure under footing (p1) 9.551 OK (Fy/A+Mx/Zxx+Mz/Zzz)
Net bearing capacity of soil = 6.5 Mton/m2 Pressure under footing (p2) 6.834 OK (Fy/A-Mx/Zxx+Mz/Zzz)
Gross allowable bearing capacity (DL,LL,CR)= 10.10 Mton/m2 Pressure under footing (p3) 9.474 OK (Fy/A+Mx/Zxx-Mz/Zzz)
Gross allowable bearing capacity (WL,SQL)= 11.73 Mton/m2 Pressure under footing (p4) 6.758 OK (Fy/A-Mx/Zxx-Mz/Zzz)
Check for overturning F.O.S L.O.C % 0
Gross weight = 341.17 T
Moment in x (Mx) = 104.262665 T-m 16.2 OK
Moment in z (Mz) = 1.02 T-m 574.21 OK
Moment in Central portion (Shorter Direction) Net pressure under foundation= 5.95 Mton/m2
Distance between columns= 0 m D = 600 mm
d = 525 mm
Maximum moment at Column face (Wl2/10)= 0 Mton-m/m
Mu (max) = 0 Mton-m/m
Mu/ bd2 = 0 Mpa
pt = 0.07 % From SP-16, Table-4
Ast = 3.68 cm2 / m
Provide 16 Φ@ 150 c/c at top
Provided steel area at top = 13.4 cm2 / m O.K
Moment in Cantilever portion(Shorter Direction)
Cantilever = 1.90 m
Maximum moment at Column face (Wl2/2)= 10.74 Mton-m/m
Mu (max) = 16.11 Mton-m/m
Mu/ bd2 = 0.574 Mpa
pt = 0.142 % From SP-16, Table-4
Ast (reqd) = 7.46 cm2 / m
Provide 16 Φ@ 150 c/c at bottom
Provided steel area at bottom = 13.4 cm2 / m O.K
pt provided = 0.26 %
Total pt (Top+Bottom) 0.26 %
Allowable shear stress = 0.33 Mpa From SP-16, Table-61
Check for Shear in Shorter Direction
d= 0.525 m
Critical section for shear development= 1.375 m
Shear force at that section= 8.18 Mton/m length
Shear stress = 0.229 Mpa OK
Moment in Central portion (Longer Direction)
Distance between columns= 4.01 m
Maximum moment at Column face (Wl2/10) = 9.57 Mton-m/m
Mu (max) = 14.36 Mton-m/m
Mu/ bd2 = 0.512 Mpa
pt = 0.13 % From SP-16, Table-4
Ast = 6.83 cm2 / m
Provide 16 Φ@ 150 c/c at top
Provided steel area at top= 13.4 cm2 / m O.K
pt provided = 0.26 %
Moment in Cantilever portion (Longer Direction)
Cantilever = 1.9 m
Maximum moment at Column face (Wl2/2) = 10.74 Mton-m/m
Mu (max) = 16.11 Mton-m/m
Mu/ bd2 = 0.574 Mpa
pt = 0.142 % From SP-16, Table-4
Ast (reqd) = 7.46 cm2 / m
Provide 16 Φ@ 150 c/c at bottom
Provided steel area at bottom = 13.4 cm2 / m O.K
pt provided = 0.26 %
Total pt (Top+Bottom) 0.52 %
Allowable shear stress = 0.33 Mpa From SP-16, Table-61
Check for Shear in Longer Direction
d= 0.525 m
Critical section for shear development= 1.375 m
Shear force at that section= 8.18 Mton/m length
Shear stress = 0.229 Mpa OK
Footing Size = X Z
DESIGN OF RAFT FOUNDATION-RF2 3.80 11.01
Adopt Size= 3.80 11.01
Horizontal Vertical Horizontal Moment
Z- Co-
Node X Co-Ordinate L/C Fx Mton Fy Mton Fz Mton Mx Tm Mz Tm Fy*fx Fy*fz
Ordinate
48 1.9 1.9 122 D+L+CR1+EQZ 0.03 65.148 0.644 1.143 0.666 123.78 123.78
491 1.9 5.1 122 D+L+CR1+EQZ -0.578 63.678 5.302 0.885 0.419 120.99 324.76
365 1.9 9.11 122 D+L+CR1+EQZ -0.519 36.638 -0.372 0.299 0.615 69.61 333.77
SUMMATION -1.07 165.46 5.57 2.33 1.70 314.38 782.31
1.9 4.73
Moment due to eccentricity = ex ez Mxe Mze Mx(total) Mz(total) ex,ez = Eccentricity in x and z
0 0.775 128.23 0.00 130.56 1.70 Mex, Mez = Moment due to ex,z
Depth of foundation = 2 m
Distance between NGL and FFL = 0.6 m
DEPTH OF RAFT = 600 mm d= 525 Cover 75 mm
AREA OF RAFT (A)= 41.84 m2
SELF WT. OF FOUNDATION= 62.76 Mton Zxx = 76.77 m3
WT. OF SOIL = 150.62 Mton Zzz = 26.5 m3
Total 213.38 Mton
GROSS TOTAL WEIGHT = 378.84 Mton
Pressure under footing (p1) 10.819 OK (Fy/A+Mx/Zxx+Mz/Zzz)
Net bearing capacity of soil = 6.5 Mton/m2 Pressure under footing (p2) 7.418 OK (Fy/A-Mx/Zxx+Mz/Zzz)
Gross allowable bearing capacity (DL,LL,CR)= 10.10 Mton/m2 Pressure under footing (p3) 10.691 OK (Fy/A+Mx/Zxx-Mz/Zzz)
Gross allowable bearing capacity (WL,SQL)= 11.73 Mton/m2 Pressure under footing (p4) 7.29 OK (Fy/A-Mx/Zxx-Mz/Zzz)
Check for overturning F.O.S L.O.C % 0
Gross weight = 378.84 T
Moment in x (Mx) = 130.5616 T-m 14.4 OK
Moment in z (Mz) = 1.70 T-m 381.07 OK
Moment in Central portion (Shorter Direction) Net pressure under foundation= 7.22 Mton/m2
Distance between columns= 0 m D = 600 mm
d = 525 mm
Maximum moment at Column face (Wl2/10)= 0 Mton-m/m
Mu (max) = 0 Mton-m/m
Mu/ bd2 = 0 Mpa
pt = 0.07 % From SP-16, Table-4
Ast = 3.68 cm2 / m
Provide 12 Φ@ 200 c/c at top
Provided steel area at top = 5.65 cm2 / m O.K
Moment in Cantilever portion(Shorter Direction)
Cantilever = 1.90 m
Maximum moment at Column face (Wl2/2)= 13.03 Mton-m/m
Mu (max) = 19.55 Mton-m/m
Mu/ bd2 = 0.696 Mpa
pt = 0.191 % From SP-16, Table-4
Ast (reqd) = 10.03 cm2 / m
Provide 16 Φ@ 150 c/c at bottom
Provided steel area at bottom = 13.4 cm2 / m O.K
pt provided = 0.26 %
Total pt (Top+Bottom) 0.26 %
Allowable shear stress = 0.33 Mpa From SP-16, Table-61
Check for Shear in Shorter Direction
d= 0.525 m
Critical section for shear development= 1.375 m
Shear force at that section= 9.93 Mton/m length
Shear stress = 0.278 Mpa OK
Moment in Central portion (Longer Direction)
Distance between columns= 4.01 m
Maximum moment at Column face (Wl2/10) = 11.61 Mton-m/m
Mu (max) = 17.42 Mton-m/m
Mu/ bd2 = 0.621 Mpa
pt = 0.167 % From SP-16, Table-4
Ast = 8.77 cm2 / m
Provide 16 Φ@ 150 c/c at top
Provided steel area at top= 13.4 cm2 / m O.K
pt provided = 0.26 %
Moment in Cantilever portion (Longer Direction)
Cantilever = 1.9 m
Maximum moment at Column face (Wl2/2) = 13.03 Mton-m/m
Mu (max) = 19.55 Mton-m/m
Mu/ bd2 = 0.696 Mpa
pt = 0.191 % From SP-16, Table-4
Ast (reqd) = 10.03 cm2 / m
Provide 16 Φ@ 150 c/c at bottom
Provided steel area at bottom = 13.4 cm2 / m O.K
pt provided = 0.26 %
Total pt (Top+Bottom) 0.52 %
Allowable shear stress = 0.33 Mpa From SP-16, Table-61
Check for Shear in Longer Direction
d= 0.525 m
Critical section for shear development= 1.375 m
Shear force at that section= 9.93 Mton/m length
Shear stress = 0.278 Mpa OK
Footing Size = X Z
DESIGN OF RAFT FOUNDATION-RF2 3.80 11.01
Adopt Size= 3.80 11.01
Horizontal Vertical Horizontal Moment
Z- Co-
Node X Co-Ordinate L/C Fx Mton Fy Mton Fz Mton Mx Tm Mz Tm Fy*fx Fy*fz
Ordinate
48 1.9 1.9 119 D+L+CR2+EQX 0.481 57.242 0.504 0.616 5.737 108.76 108.76
491 1.9 5.1 119 D+L+CR2+EQX 2.397 71.48 3.071 0.514 10.078 135.81 364.55
365 1.9 9.11 119 D+L+CR2+EQX 1.335 31.996 -0.439 -0.146 3.785 60.79 291.48
SUMMATION 4.21 160.72 3.14 0.98 19.60 305.36 764.79
1.9 4.76
Moment due to eccentricity = ex ez Mxe Mze Mx(total) Mz(total) ex,ez = Eccentricity in x and z
0 0.745 119.73 0.00 120.72 19.60 Mex, Mez = Moment due to ex,z
Depth of foundation = 2 m
Distance between NGL and FFL = 0.6 m
DEPTH OF RAFT = 600 mm d= 525 Cover 75 mm
AREA OF RAFT (A)= 41.84 m2
SELF WT. OF FOUNDATION= 62.76 Mton Zxx = 76.77 m3
WT. OF SOIL = 150.62 Mton Zzz = 26.5 m3
Total 213.38 Mton
GROSS TOTAL WEIGHT = 374.10 Mton
Pressure under footing (p1) 11.253 OK (Fy/A+Mx/Zxx+Mz/Zzz)
Net bearing capacity of soil = 6.5 Mton/m2 Pressure under footing (p2) 8.108 OK (Fy/A-Mx/Zxx+Mz/Zzz)
Gross allowable bearing capacity (DL,LL,CR)= 10.10 Mton/m2 Pressure under footing (p3) 9.774 OK (Fy/A+Mx/Zxx-Mz/Zzz)
Gross allowable bearing capacity (WL,SQL)= 11.73 Mton/m2 Pressure under footing (p4) 6.629 OK (Fy/A-Mx/Zxx-Mz/Zzz)
Check for overturning F.O.S L.O.C % 0
Gross weight = 374.10 T
Moment in x (Mx) = 120.71891 T-m 15.4 OK
Moment in z (Mz) = 19.60 T-m 32.64 OK
Moment in Central portion (Shorter Direction) Net pressure under foundation= 7.65 Mton/m2
Distance between columns= 0 m D = 600 mm
d = 525 mm
Maximum moment at Column face (Wl2/10)= 0 Mton-m/m
Mu (max) = 0 Mton-m/m
Mu/ bd2 = 0 Mpa
pt = 0.07 % From SP-16, Table-4
Ast = 3.68 cm2 / m
Provide 16 Φ@ 150 c/c at top
Provided steel area at top = 13.4 cm2 / m O.K
Moment in Cantilever portion(Shorter Direction)
Cantilever = 1.90 m
Maximum moment at Column face (Wl2/2)= 13.81 Mton-m/m
Mu (max) = 20.72 Mton-m/m
Mu/ bd2 = 0.738 Mpa
pt = 0.191 % From SP-16, Table-4
Ast (reqd) = 10.03 cm2 / m
Provide 16 Φ@ 150 c/c at bottom
Provided steel area at bottom = 13.4 cm2 / m O.K
pt provided = 0.26 %
Total pt (Top+Bottom) 0.26 %
Allowable shear stress = 0.33 Mpa From SP-16, Table-61
Check for Shear in Shorter Direction
d= 0.525 m
Critical section for shear development= 1.375 m
Shear force at that section= 10.52 Mton/m length
Shear stress = 0.295 Mpa OK
Moment in Central portion (Longer Direction)
Distance between columns= 4.01 m
Maximum moment at Column face (Wl2/10) = 12.3 Mton-m/m
Mu (max) = 18.45 Mton-m/m
Mu/ bd2 = 0.657 Mpa
pt = 0.154 % From SP-16, Table-4
Ast = 8.09 cm2 / m
Provide 16 Φ@ 150 c/c at top
Provided steel area at top= 13.4 cm2 / m O.K
pt provided = 0.26 %
Moment in Cantilever portion (Longer Direction)
Cantilever = 1.9 m
Maximum moment at Column face (Wl2/2) = 13.81 Mton-m/m
Mu (max) = 20.72 Mton-m/m
Mu/ bd2 = 0.738 Mpa
pt = 0.191 % From SP-16, Table-4
Ast (reqd) = 10.03 cm2 / m
Provide 16 Φ@ 150 c/c at bottom
Provided steel area at bottom = 13.4 cm2 / m O.K
pt provided = 0.26 %
Total pt (Top+Bottom) 0.52 %
Allowable shear stress = 0.33 Mpa From SP-16, Table-61
Check for Shear in Longer Direction
d= 0.525 m
Critical section for shear development= 1.375 m
Shear force at that section= 10.52 Mton/m length
Shear stress = 0.295 Mpa OK
Footing Size = X Z
DESIGN OF RAFT FOUNDATION-RF1 29.23 8.22
Adopt Size= 29.23 8.22
Horizontal Vertical Horizontal Moment
Node X Co-Ordinate Z- Co- L/C Fx Mton Fy Mton Fz Mton Mx Tm Mz Tm Fy*fx Fy*fz
Ordinate
45 1.2 4.4 122 D+L+CR1+EQZ -14.624 59.785 -2.626 27.844 12.329 71.74 263.05
46 4.2 4.4 122 D+L+CR1+EQZ 14.686 55.918 -5.902 26.613 -11.727 234.86 246.04
425 1.2 1.2 122 D+L+CR1+EQZ -0.811 109.425 22 -4.284 1.249 131.31 131.31
427 5.734 1.2 122 D+L+CR1+EQZ 1.524 75.891 -23.103 -13.253 0.116 435.16 91.07
429 8.994 1.2 122 D+L+CR1+EQZ 1.094 84.145 -24.747 -10.077 -0.233 756.8 100.97
431 13.264 1.2 122 D+L+CR1+EQZ 0.109 86.698 -24.475 -8.379 0.233 1149.96 104.04
433 16.744 1.2 122 D+L+CR1+EQZ 0.329 84.082 -24.412 -8.816 0.152 1407.87 100.9
435 20.464 1.2 122 D+L+CR1+EQZ -0.038 79.853 -24.491 -10.587 0.278 1634.11 95.82
437 23.464 1.2 122 D+L+CR1+EQZ 0.481 73.286 -22.971 -13.346 0.198 1719.58 87.94
439 28.034 1.2 122 D+L+CR1+EQZ 2.591 104.997 20.148 -4.522 -1.151 2943.49 126
543 1.2 7.02 122 D+L+CR1+EQZ -6.268 68.136 10.123 7.297 16.456 81.76 478.31
547 5.734 7.02 122 D+L+CR1+EQZ -0.947 28.83 24.263 29.391 -1.696 165.31 202.39
549 8.994 7.02 122 D+L+CR1+EQZ 1.778 23.38 28.195 38.999 1.643 210.28 164.13
551 13.264 7.02 122 D+L+CR1+EQZ 0.237 23.511 28.187 41.252 -1.034 311.85 165.05
553 16.744 7.02 122 D+L+CR1+EQZ 0.822 22.13 27.887 39.654 0.424 370.54 155.35
555 20.464 7.02 122 D+L+CR1+EQZ 1.875 21.075 27.652 36.472 -0.914 431.28 147.95
557 23.464 7.02 122 D+L+CR1+EQZ 6.134 26.256 23.759 27.867 9.073 616.07 184.32
SOIL LEFT 0.6 4.11 SELFWEIGHT 0 67.46976 0 0 0 40.48 277.3
SOIL RIGHT 28.634 4.11 SELFWEIGHT 0 67.46976 0 0 0 1931.93 277.3
SOIL UP 13.415 0.6 SELFWEIGHT 0 220.22064 0 0 0 2954.26 132.13
SOIL DOWN 13.415 7.62 SELFWEIGHT 0 220.22064 0 0 0 2954.26 1678.08
545 28.034 7.02 122 D+L+CR1+EQZ 7.524 58.91 10.586 7.835 -5.043 1651.48 413.55
SUMMATION 16.50 1661.69 70.07 209.96 20.35 22204.38 5623
13.36 3.38
Moment due to eccentricity = ex ez Mxe Mze Mx(total) Mz(total) ex,ez = Eccentricity in x and z
1.257 0.73 1213.03 2088.74 1422.99 2109.10 Mex, Mez = Moment due to ex,z
Depth of foundation = 3.8 m
Distance between NGL and FFL = 0.6 m
DEPTH OF RAFT = 600 mm d= 500 Cover 75 mm
AREA OF RAFT (A)= 240.3 m2
SELF WT. OF FOUNDATION= 360.45 Mton Zxx = 329.22 m3
WT. OF SOIL = 0 Mton Zzz = 1170.84 m3
Total 360.45 Mton
GROSS TOTAL WEIGHT = 2022.14 Mton
Pressure under footing (p1) 14.539 OK (Fy/A+Mx/Zxx+Mz/Zzz)
Net bearing capacity of soil = 6.5 Mton/m2 Pressure under footing (p2) 5.894 OK (Fy/A-Mx/Zxx+Mz/Zzz)
Gross allowable bearing capacity (DL,LL,CR)= 13.34 Mton/m2 Pressure under footing (p3) 10.936 OK (Fy/A+Mx/Zxx-Mz/Zzz)
Gross allowable bearing capacity (WL,SQL)= 14.97 Mton/m2 Pressure under footing (p4) 2.291 OK (Fy/A-Mx/Zxx-Mz/Zzz)
Check for overturning F.O.S L.O.C % 0
Gross weight = 2022.14 T
Moment in x (Mx) = 1422.992824 T-m 5.3 OK
Moment in z (Mz) = 2109.10 T-m 12.61 OK
Moment in Central portion (Shorter Direction) Net pressure under foundation= 7.7 Mton/m2
Distance between columns= 5.82 m D = 600 mm
d = 500 mm
Maximum moment at Column face (Wl2/10)= 26.08 Mton-m/m
Mu (max) = 39.12 Mton-m/m
Mu/ bd2 = 1.536 Mpa
pt = 0.4 % From SP-16, Table-4
Ast = 20 cm2 / m
Provide 20 Φ@ 150 c/c at top
Provided steel area at top = 20.94 cm2 / m O.K
Moment in Cantilever portion(Shorter Direction)
Cantilever = 1.20 m
Maximum moment at Column face (Wl2/2)= 5.54 Mton-m/m
Mu (max) = 8.31 Mton-m/m
Mu/ bd2 = 0.327 Mpa
pt = 0.094 % From SP-16, Table-4
Ast (reqd) = 4.7 cm2 / m
Provide 16 Φ@ 150 c/c at bottom
Provided steel area at bottom = 13.4 cm2 / m O.K
pt provided = 0.27 %
Total pt (Top+Bottom) 0.27 %
Allowable shear stress = 0.33 Mpa From SP-16, Table-61
Check for Shear in Shorter Direction
d= 0.5 m
Critical section for shear development= 0.7 m
Shear force at that section= 5.39 Mton/m length
Shear stress = 0.159 Mpa OK
Moment in Central portion (Longer Direction)
Distance between columns= 4.57 m
Maximum moment at Column face (Wl2/10) = 16.08 Mton-m/m
Mu (max) = 24.12 Mton-m/m
Mu/ bd2 = 0.947 Mpa
pt = 0.242 % From SP-16, Table-4
Ast = 12.1 cm2 / m
Provide 20 Φ@ 150 c/c at top
Provided steel area at top= 20.94 cm2 / m O.K
pt provided = 0.42 %
Moment in Cantilever portion (Longer Direction)
Cantilever = 1.2 m
Maximum moment at Column face (Wl2/2) = 5.54 Mton-m/m
Mu (max) = 8.31 Mton-m/m
Mu/ bd2 = 0.327 Mpa
pt = 0.084 % From SP-16, Table-4
Ast (reqd) = 4.2 cm2 / m
Provide 16 Φ@ 150 c/c at bottom
Provided steel area at bottom = 13.4 cm2 / m O.K
pt provided = 0.27 %
Total pt (Top+Bottom) 0.69 %
Allowable shear stress = 0.33 Mpa From SP-16, Table-61
Check for Shear in Longer Direction
d= 0.5 m
Critical section for shear development= 0.7 m
Shear force at that section= 5.39 Mton/m length
Shear stress = 0.159 Mpa OK
Footing Size = X Z
DESIGN OF RAFT FOUNDATION-RF1 29.23 8.22
Adopt Size= 29.23 8.22
Horizontal Vertical Horizontal Moment
Node X Co-Ordinate Z- Co- L/C Fx Mton Fy Mton Fz Mton Mx Tm Mz Tm Fy*fx Fy*fz
Ordinate
45 1.2 4.4 119 D+L+CR2+EQX -13.241 64.061 -3.479 12.125 14.822 76.87 281.87
46 4.2 4.4 119 D+L+CR2+EQX 15.918 59.46 -5.379 14.761 -9.336 249.73 261.62
425 1.2 1.2 119 D+L+CR2+EQX 4.451 78.576 7.125 -7.94 8.981 94.29 94.29
427 5.734 1.2 119 D+L+CR2+EQX 5.366 68.775 -24.37 -15.83 4.855 394.36 82.53
429 8.994 1.2 119 D+L+CR2+EQX 5.58 78.642 -25.654 -15.842 4.892 707.31 94.37
431 13.264 1.2 119 D+L+CR2+EQX 4.756 82.005 -25.642 -15.736 5.379 1087.71 98.41
433 16.744 1.2 119 D+L+CR2+EQX 4.855 78.478 -25.5 -15.493 5.221 1314.04 94.17
435 20.464 1.2 119 D+L+CR2+EQX 4.566 73.963 -25.284 -15.654 5.334 1513.58 88.76
437 23.464 1.2 119 D+L+CR2+EQX 4.886 65.754 -24.039 -15.65 5.222 1542.85 78.9
439 28.034 1.2 119 D+L+CR2+EQX 8.355 77.886 8.593 -5.892 6.293 2183.46 93.46
543 1.2 7.02 119 D+L+CR2+EQX -6.549 45.112 4.025 7.868 13.059 54.13 316.69
547 5.734 7.02 119 D+L+CR2+EQX -2.571 26.045 23.128 22.568 -4.117 149.34 182.84
549 8.994 7.02 119 D+L+CR2+EQX 1.364 22.77 25.314 26.967 1.632 204.79 159.85
551 13.264 7.02 119 D+L+CR2+EQX 0.667 22.836 24.893 26.291 -1.077 302.9 160.31
553 16.744 7.02 119 D+L+CR2+EQX 1.278 21.609 24.893 26.418 0.468 361.82 151.7
555 20.464 7.02 119 D+L+CR2+EQX 1.696 20.701 25.24 26.56 -0.904 423.63 145.32
557 23.464 7.02 119 D+L+CR2+EQX 4.674 23.875 22.896 22.054 7.315 560.2 167.6
SOIL LEFT 0.6 4.11 SELFWEIGHT 0 67.46976 0 0 0 40.48 277.3
SOIL RIGHT 28.634 4.11 SELFWEIGHT 0 67.46976 0 0 0 1931.93 277.3
SOIL UP 13.415 0.6 SELFWEIGHT 0 220.22064 0 0 0 2954.26 132.13
SOIL DOWN 13.415 7.62 SELFWEIGHT 0 220.22064 0 0 0 2954.26 1678.08
545 28.034 7.02 119 D+L+CR2+EQX 7.243 40.792 5.41 8.46 -7.711 1143.56 286.36
SUMMATION 53.29 1526.72 12.17 86.04 60.33 20245.5 5203.86
13.26 3.41
Moment due to eccentricity = ex ez Mxe Mze Mx(total) Mz(total) ex,ez = Eccentricity in x and z
1.357 0.7 1068.70 2071.76 1154.74 2132.09 Mex, Mez = Moment due to ex,z
Depth of foundation = 3.8 m
Distance between NGL and FFL = 0.6 m
DEPTH OF RAFT = 600 mm d= 525 Cover 75 mm
AREA OF RAFT (A)= 240.3 m2
SELF WT. OF FOUNDATION= 360.45 Mton Zxx = 329.22 m3
WT. OF SOIL = 0 Mton Zzz = 1170.84 m3
Total 360.45 Mton
GROSS TOTAL WEIGHT = 1887.17 Mton
Pressure under footing (p1) 13.182 OK (Fy/A+Mx/Zxx+Mz/Zzz)
Net bearing capacity of soil = 6.5 Mton/m2 Pressure under footing (p2) 6.167 OK (Fy/A-Mx/Zxx+Mz/Zzz)
Gross allowable bearing capacity (DL,LL,CR)= 13.34 Mton/m2 Pressure under footing (p3) 9.54 OK (Fy/A+Mx/Zxx-Mz/Zzz)
Gross allowable bearing capacity (WL,SQL)= 14.97 Mton/m2 Pressure under footing (p4) 2.525 OK (Fy/A-Mx/Zxx-Mz/Zzz)
Check for overturning F.O.S L.O.C % 0
Gross weight = 1887.17 T
Moment in x (Mx) = 1154.73956 T-m 6 OK
Moment in z (Mz) = 2132.09 T-m 11.64 OK
Moment in Central portion (Shorter Direction) Net pressure under foundation= 6.34 Mton/m2
Distance between columns= 5.82 m D = 600 mm
d = 525 mm
Maximum moment at Column face (Wl2/10)= 21.48 Mton-m/m
Mu (max) = 32.22 Mton-m/m
Mu/ bd2 = 1.147 Mpa
pt = 0.293 % From SP-16, Table-4
Ast = 15.38 cm2 / m
Provide 20 Φ@ 150 c/c at top
Provided steel area at top = 20.94 cm2 / m O.K
Moment in Cantilever portion(Shorter Direction)
Cantilever = 1.20 m
Maximum moment at Column face (Wl2/2)= 4.56 Mton-m/m
Mu (max) = 6.84 Mton-m/m
Mu/ bd2 = 0.244 Mpa
pt = 0.07 % From SP-16, Table-4
Ast (reqd) = 3.68 cm2 / m
Provide 16 Φ@ 150 c/c at bottom
Provided steel area at bottom = 13.4 cm2 / m O.K
pt provided = 0.26 %
Total pt (Top+Bottom) 0.26 %
Allowable shear stress = 0.33 Mpa From SP-16, Table-61
Check for Shear in Shorter Direction
d= 0.525 m
Critical section for shear development= 0.675 m
Shear force at that section= 4.28 Mton/m length
Shear stress = 0.12 Mpa OK
Moment in Central portion (Longer Direction)
Distance between columns= 4.57 m
Maximum moment at Column face (Wl2/10) = 13.24 Mton-m/m
Mu (max) = 19.86 Mton-m/m
Mu/ bd2 = 0.707 Mpa
pt = 0.191 % From SP-16, Table-4
Ast = 10.03 cm2 / m
Provide 20 Φ@ 150 c/c at top
Provided steel area at top= 20.94 cm2 / m O.K
pt provided = 0.4 %
Moment in Cantilever portion (Longer Direction)
Cantilever = 1.2 m
Maximum moment at Column face (Wl2/2) = 4.56 Mton-m/m
Mu (max) = 6.84 Mton-m/m
Mu/ bd2 = 0.244 Mpa
pt = 0.07 % From SP-16, Table-4
Ast (reqd) = 3.68 cm2 / m
Provide 16 Φ@ 150 c/c at bottom
Provided steel area at bottom = 13.4 cm2 / m O.K
pt provided = 0.26 %
Total pt (Top+Bottom) 0.66 %
Allowable shear stress = 0.33 Mpa From SP-16, Table-61
Check for Shear in Longer Direction
d= 0.525 m
Critical section for shear development= 0.675 m
Shear force at that section= 4.28 Mton/m length
Shear stress = 0.12 Mpa OK