Technical

Information STARDOM
Network Configuration Guide
TI 34P02K25-01E

TI 34P02K25-01E
16th Edition Jun..6 .2018 (YK)
Blank Page
i

Introduction
About This Document
STARDOM system consists of autonomous controller FCNs/FCJs, field devices, VDS,
HMI clients, and network devices, from which a user can select the optimum
configuration.
Components of STARDOM (FCN/FCJ, VDS, and HMI clients), with highly independent
functions, are acquired through open technologies, allowing flexible configurations of
devices.
This document explains basic information needed for constructing networks of
STARDOM system and detailed setting procedures along with specific cases.

IMPORTANT
In this manual, the term “FCN/FCJ” refers to FCN-500, FCN-100, FCN-RTU, and FCJ
autonomous controllers.
- The term “FCN-500” refers to the autonomous controllers with NFCP501/NFCP502
CPU module.
- The term “FCN-100” refers to the autonomous controllers with NFCP100 CPU
module.
- The term “FCN-RTU” refers to the low power autonomous controllers with NFCP050
CPU module.
- The term “FCJ” refers to the all-in-one type autonomous controllers.

Organization of This Document


Devices Overview
This chapter explains the devices that configure STARDOM system.

STARDOM Network Functions


This chapter explains basic network functions of STARDOM system.

Examples of Network Configurations


This chapter explains setting procedures of the system through specific cases of
network configurations.

All Rights Reserved. Copyright © 2002, Yokogawa Electric Corporation TI 34P02K25-01E May 31, 2017-00
Blank Page
iii

STARDOM
Network Configuration Guide
TI 34P02K25-01E 16th Edition

CONTENTS
Introduction ................................................................................................i
CONTENTS ...............................................................................................iii
1. Devices Overview .............................................................................1
1.1 STARDOM Network Overview ................................................................... 1
1.2 Autonomous Controller FCN/ FCJ ............................................................ 4
1.3 VDS ............................................................................................................ 10
1.4 Network Devices ....................................................................................... 12
1.5 Communication Protocols ....................................................................... 18
2. Network Features of STARDOM ....................................................19
2.1 Varieties of Basic Configurations ........................................................... 19
2.2 Network Basic Definitions (IP Address Settings) .................................. 23
2.3 Communication Performances ............................................................... 37
2.4 Security ..................................................................................................... 47
2.5 Network Functions of FCN/FCJ .............................................................. 50
2.6 Duplexing Control Network ..................................................................... 55
2.6.1 The Duplexed Network Function Provided on STARDOM ........... 59
2.6.2 Duplexing Communications Using an Application ........................ 73
2.7 Cautions for Network Configuration ...................................................... 76
2.8 The communication port number to use of FCN/FCJ ........................... 77
3. Examples of Network Configurations...........................................79
3.1 Small Two-layered System (Standard) ................................................... 79
3.2 Small One-layered System ...................................................................... 81
3.3 Medium Scale Two-layered System ........................................................ 82
3.4 Installing Controllers in a Field as Standalone ..................................... 84
3.5 Connecting Simple HMI to Standalone Controller in a Field ............... 86
3.6 Connecting Routers to Control Networks ............................................. 89
3.7 Connecting Several Control Networks to VDS ...................................... 91
3.8 Duplexing Networks ................................................................................. 92
3.9 Connecting Devices (e.g.PLCs) Other than FCN/FCJ to VDS ............. 95
3.10 Connecting PLC to FCN/FCJ ................................................................... 97
3.11 Duplexing Communications between FCN/FCJ and FCN/FCJ
in Different Segments ............................................................................ 103
3.12 Operation with Remote HMI .................................................................. 105

TI 34P02K25-01E Jun. 6, 2018-00


iv
3.13 Send Mails to/Receive Mails from VDS and FCN/FCJ ....................... 107
3.14 Monitoring and Maintaining FCN/FCJ Remotely ................................. 109
3.15 Setting FCN/FCJ and VDS Remotely ..................................................... 112
3.16 Connecting FCN/FCJ and VDS via WAN ............................................... 113
3.17 Connecting Remote Devices to Duplexed Control Network .............. 115
3.18 Synchronizing Times among Nodes ..................................................... 117
3.19 Using Hand-held Devices in a Field ...................................................... 123
3.20 Connecting Remote Sites Using Wireless Devices ............................ 125
3.21 Connecting to Existing ASTMAC .......................................................... 127
Revision Information .................................................................................i

TI 34P02K25-01E Jun. 6, 2018-00


<1. Devices Overview> 1

1. Devices Overview
This chapter explains the devices you need to take into consideration when
constructing STARDOM system networks.

1.1 STARDOM Network Overview


This section explains an example of basic network configuration of STARDOM
system.

STARDOM system consists of the following hardware:


Table Devices of STARDOM
Devices Contents
Controller FCN/FCN-RTU,FCJ, PLC, etc.
Data server VDS
HMI VDS Viewer
Network device Hub, router, etc.
Field device Sensor, valve, contact I/O device, etc.

HMI

Information
Network

VDS Wide Area


HMI HMI Server HMI Firewall Router Network

Control System Information Network

VDS Firewall Router


Data Server

Control Network
HMI

FCN / Configuration
FCJ PLC
FCN-RTU PC

Field Network

Field Field
Device Device

Figure Basic Network Configuration

TI 34P02K25-01E Jun. 6, 2018-00


<1. Devices Overview> 2
Control Network
A control network is a Local Area Network (LAN) that connects controller devices such
as autonomous controller FCNs/FCJs or PLCs, and VDS data servers. The reliability
and real-time operation are required by this type of network that performs critical
communications continuously over the network.

Field Network
A field network is a small and slow network connecting FCNs/FCJs and intelligent filed
devices or remote I/O devices. Typical examples are FF-H1, PROFIBUS, DEVICENET
and Ethernet.
FCNs/FCJs support FF-H1 and Ethernet in R1.11 and later.

Control System Information Network


A control system information network is a LAN that connects VDS data servers, VDS
HMI servers (commonly exist on the same PC with VDS data server) and HMI clients.
On a small system, the level of control system information network can be submitted by
connecting VDS HMI servers and HMI clients to control networks.

Information Network (Intranet)


An information network is a backbone of intra-company information system LAN.

Wide Area Network (WAN, Internet)


A WAN is a network that spans geographically dispersed area, such as public line or
internet; a variety of network are available through public switched phone networks,
leased lines, satellites, IP networks, etc.

FCN-500, FCN-100
An FCN-500 and an FCN-100 are a controller of the module mount type that is
connected to control networks, with highly reliable features, allowing to duplex the
control network, CPU, power supply and internal bus for connecting I/O module.

FCN-RTU
An FCN-RTU (Low power Autonomous controller) is a compact controller assembled
with a CPU module with built-in analog, digital I/O, communication ports, and a base
module. Eight arbitrary I/O modules can be installed.

FCJ
An FCJ is an all-in-one type controller that is connected to control networks, and can be
installed in devices at sites. It is possible to duplex control networks. FCJ cannot be
enhanced with I/O modules since it has a built-in I/O interface. In addition, it cannot
duplex the CPU, power supply and internal bus for connecting I/O module. Other
functions are same with FCN.

Field Devices (supporting field networks)


These are intelligent field devices supporting field networks. These devices support FF-
H1 and Ethernet.

PLC
Other suppliers' PLCs supporting Ethernet communication can be connected to control
networks.

VDS Data Server


A VDS data server acquires control data from controllers on control networks, providing
upper computer such as VDS HMI servers with abstracted data.

TI 34P02K25-01E Jun. 6, 2018-00


<1. Devices Overview> 3
VDS HMI Server
A PC equipped with Web-based HMI server functions. Normally, HMI servers and data
servers run on the same PC. On some large scale systems, they can run on separate
PCs.

HMI (VDS Viewer)


An HMI is a Web-based VDS HMI client device that provides operation and monitoring
windows. A PC equipped with Java VM (Virtual Machine) is used.

Configuration PC
A configuration PC is a PC that creates and downloads control logics of FCN/FCN-
RTU/FCJ or field devices, and configures devices. You use this PC with installing
configuration tools, to connect to control networks when starting up the system. You can
install configuration tools on a PC on which VDS runs, to reduce the number of PCs.
The configurations other than the basic network settings (IP addresses) of FCN/FCN-
RTU/FCJ can be made from remote PCs connected via routers.
Table Main Configuration Tools
Tools Contents
Resource Configurator Configurations of FCN/FCN-RTU/FCJ
Logic Designer FCN/FCJ control logic design and download
Web browser Advanced configurations of FCN/FCN-RTU/FCJ
Graphic Designer Design of HMI operation and monitoring windows

Network Devices (Hub, Router, etc.)


Components are connected to a hub, composing a star topology. When configuring
separate network domains or connecting remote sites, you should construct networks
via routers or firewalls. You need to choose the optimum devices according to the
conditions of infrastructures in your area.

TI 34P02K25-01E Jun. 6, 2018-00


<1. Devices Overview> 4

1.2 Autonomous Controller FCN/ FCJ


This chapter explains network interfaces of the autonomous controller FCN/FCJ.

FCN-500, FCN-100 and FCJ have two or four (FCN-500 with NFCP502 only) Ethernet
network interfaces. If you do not duplex the control network, use only network interface1.
Alternatively, they can be used as two or four separated networks.
Each port is 10/100 Mbps and 1 Gbps (FCN-500 only), supporting full-duplex and auto
negotiation functions.
FCN-RTU has one Ethernet network interface. Except for the duplex function, the
function of the FCN-RTU is the same as the FCN.
Table Ethernet Interface
CPU Model Network Interface Baud Rate
NFCP501 2 ports
10/100 Mbps, 1Gbps
NFCP502 4 ports

NFCP100 2 ports

NFCP050 1 port 10/100 Mbps


NFJT100 2 ports

FCN-500/FCN-100
The following figure shows an outside drawing of FCN with maximum configuration. The
E2 bus can be used only with FCN-500.

Figure Outside Drawing of FCN

TI 34P02K25-01E Jun. 6, 2018-00


<1. Devices Overview> 5
The network interface of FCN is installed on the front of the CPU module.

NFCP501

NFCP502

Figure CPU Module of FCN-500

Two or four network interfaces are installed; the above is 4 or 2. Each MAC address is
written on the side of the CPU module.

TI 34P02K25-01E Jun. 6, 2018-00


<1. Devices Overview> 6

Reset Switch

Shutdown Switch
DisplayLED from left
HRDY : Hardware
RDY : Control program
CTRL : Control Right
System Card Eject Button

System Card
Serial Port

Communication Status LED from top


 LINK : Normal HUB connection status MAC Address
 ACT: Send/Receivestatus
Network Interface 1
Network Interface 2

Figure CPU Module of FCN-100

Two network interfaces are installed; the above is 2 and the below is 1. Each MAC
address is written on the side of the CPU module. The upper line indicates the MAC
address of network interface1; the lower line is the MAC address of interface2.

TI 34P02K25-01E Jun. 6, 2018-00


<1. Devices Overview> 7

FCN-RTU
The following figure shows an outside drawing of FCN-RTU.

The network interface of FCN-RTU is installed on the front of the CPU module.

One network interface is installed; MAC address is written on the side of the CPU
module.

TIP
Network port can be disabled with network power switch to save power since FCN-RTU is the low
power consumption controller.
Refer to IM34P02Q01 "STARDOM FCN/FCJ Guide" for the details of FCN-RTU features.

TI 34P02K25-01E Jun. 6, 2018-00


<1. Devices Overview> 8

FCJ

Operating Status Display LED


HRDY : Normal hardware status
RDY : Normal system status
CTL : Normal control operation status

Pressure Clamp Terminal Pressure Clamp Terminal


for Analog Input for Analog Output

FOUNDATION
**** Fieldbus (H1)
****
*** Signal Connection

Pressure Clamp Terminal Pressure Clamp Terminal


for Digital Input for Digital Output

Figure Front Elevation of FCJ

Reset
System Card
Switch

Shutdown Switch
Serial Port 2
COM2

Network Interface
(upper:2, lower:1)
Serial Port 1 RJ45 Modular Connector
COM1 Communication Status LED
LINK : Normal HUB connection status
ACT : Send/Receive status

Pressure Clamp
Terminal
for Power Supply

Figure Side View of FCJ from the Right

Two network interfaces are installed; the above is 2 and the below is 1. Each MAC
address is written on the side of the CPU module. The upper line indicates the MAC
address of network interface1; the lower line is the MAC address of interface2.

TI 34P02K25-01E Jun. 6, 2018-00


<1. Devices Overview> 9

Devices that can be connected to FCN/FCJ


The following devices can be connected. For communications on control applications,
communication application portfolios corresponding to each device are required.
Table Devices that can be connected to FCN/FCJ
Communication Portfolio or
Types Devices Interfaces
Option Packages
Autonomous Yokogawa Electric FCN/FCJ Ethernet Standard
Controller
SCADA Yokogawa Electric VDS/ASTMAC Ethernet Standard
FAST/TOOLS Ethernet Standard
OPC support device Ethernet FCN/FCJ OPC Server for Windows
PLC Yokogawa Electric FA-M3 Ethernet, RS-232-C, FA-M3 Communication Portfolio
RS-422/RS-485
Mitsubishi Electric MELSEC series Ethernet MELESEC-A Communication Portfolio
Omron SYSMAC series RS-232-C,RS-422/RS-485 SYSMAC Communication Portfolio
(*1)
Power Yokogawa Electric RS-232-C, Power Monitor Communication
monitor UPM100, UPM101, RS-422/RS-485 Portfolio (*1)(*2)
UZ005 (S3 or later),
PR201 (S2 or later),PR300
UPM01, UPM02, UPM03
Yokogawa Electric Green series RS-422/RS-485 Temperature Controller
Temperature Communication Portfolio(*1)(*2)
Controller Yokogawa Electric Ethernet, Modbus Communication Portfolio
UTAdvanced series RS-422/RS-485
Field Device FOUNDATION Fieldbus H1 Device FOUNDATION fieldbus H1 PAS Portfolio
HART Communication Protocol Support HART PAS Portfolio
Device
CANopen Communication Protocol CANopen PAS Portfolio
Support Device
PROFIBUS-DP Communication Protocol PROFIBUS-DP PAS Portfolio
Support Device
Yokogawa Electric Modbus(RS-232-C, Modbus Communication Portfolio
TOP2501, TOP2301 RS-422/RS-485, Ethernet)
TOP3600T, TOP3301S
Digital Co. Modbus(RS-232-C, Modbus Communication Portfolio
・SimpleTouch RS-422/RS-485, Ethernet)
Programmabl ST400-AG41-24V, ST401-AG41-24V
e Display ・GP series
GP377 series, GP77R series,
GP2000/3000/4000 series
・GLC series , GLC2000 series
・Factory Gateway
Programmable Display corresponding to
Modbus Communication Protocol
DCS Yokogawa Electric Ethernet Standard
CENTUM VP (via UGS)
Yokogawa Electric Ethernet FCN/FCJ OPC Server for Windows
CENTUM CS3000 (via SIOS)
CENTUM VP (via SIOS)
Yokogawa Electric Modbus(RS-232-C, Modbus Communication Portfolio
CENTUM CS3000 (via FCS) RS-422/RS-485, Ethernet)
CENTUM VP (via FCS)
Others Modbus Communication Protocol Support Modbus(RS-232-C, Modbus Communication Portfolio
Device RS-422/RS-485, Ethernet)
DNP3 Communication Protocol Support DNP3(RS-232-C, DNP3 Communication Portfolio
Device RS-422/RS-485, Ethernet)
For the detailed information on connecting devices, refer to general specifications, instruction manuals or technical
information published separately.
*1: It can’t be used in FCN-RTU.
*2: It can’t be used in FCN-500.

TI 34P02K25-01E Jun. 6, 2018-00


<1. Devices Overview> 10

1.3 VDS
This section explains the network interfaces of VDS.

The network interface cards used on a PC on which VDS is implemented, can be


general-purpose ones supporting Fast Ethernet.
STARDOM realizes duplexed control networks by software; therefore, it is not required
that you use the same suppliers' network cards for both of them.

TIP
Some suppliers' network adapters provide duplexed networks by themselves with two identical network
adapters mounted. However, you cannot use the supplier-provided duplex function for STARDOM
control network.

TI 34P02K25-01E Jun. 6, 2018-00


<1. Devices Overview> 11

Devices that can be Connected to VDS Data Server


The following devices can be connected to VDS Data server.
Table Devices that can be connected to Data Server
Types Devices Interfaces Remarks
Autonomous Yokogawa Electric FCN-500, FCN-100, Ethernet (duplexed configuration
Standard
Controller FCJ possible)
Yokogawa Electric FCN-RTU Ethernet Standard
Yokogawa Electric FA-M3 series Ethernet, RS-232-C Standard
Mitsubishi Electric MELSEC series Ethernet, Serial, MELSECNET II/,
MELSEC Driver
10/H, CC-Link, etc.
Ethernet, Serial, ControllerLink,
Omron SYSMAC series SYSMAC Driver
SYSMACLINK, etc.
FL-NET Support Device FL-NET OPC server connection(*1)
PLC Fuji Electric MICREX-F RS-232-C OPC server connection(*1)
Hitachi HIDEC-S10/2 α Ethernet OPC server connection(*1)
Sharp JW series Ethernet, RS-232-C OPC server connection(*1)
Matsushita Electric Works MEWNET-FP Ethernet, RS-232-C OPC server connection(*1)
KEYENCE KZ-A300/KZ-A500 RS-232-C OPC server connection(*1)
Allen-Bradley Logix5550 Ethernet OPC server connection(*1)
Digital
OPC server connection(*1)
Programmable GP-77 series TypeR,
Ethernet (Digital middleware, "Pro
Display GP2000 series,
Server" is required)
GP3000 series
Yokogawa Electric power monitor
Power monitor RS-485 Standard
PC-Link applicable model
Yokogawa Electric
Thermometer Green series, RS-422/RS-485 Standard
UTAdvanced series
Data
Yokogawa Electric DARWIN series Ethernet DARWIN Driver
acquisition
Yokogawa Electric
Recorder Ethernet DARWIN Driver
DAQSTATION/SMARTDAC+ series
Others Options Options Created using VB

*1: It can be connected using an OPC server communication package.

TI 34P02K25-01E Jun. 6, 2018-00


<1. Devices Overview> 12

1.4 Network Devices


Use hubs or routers to connect controllers and VDSs. Generally, there are two
types of hubs: repeater hub and switching hub. Choose the optimum according to
the feature of network, with consideration especially given to the performance
and the wiring distance.

Important
Do not use 10 Mbps hubs or repeater hubs with the STARDOM system.

Hubs and Routers


Repeater Hub
The hub has the repeater function to connect two or more cables such as 10BASE-T,
100BASE-TX or 1000BASE-T. The repeater function is to relay transmission signals; it
performs waveform shaping to the signal received from one segment, amplifying it to the
given level to send to all other segments. This type of hub is used for connecting
different media segments each other, lengthening the distance of the same segments or
supporting the increase of the connecting nodes.
Do not use repeater hubs with the STARDOM system, because trouble with
performance may occur. Many repeater hubs do not support auto negotiation, and
problems frequently occur when connecting to other devices.

Switching Hub
A switching hub has bridging features, enabling to store a received packet in the buffer,
analyzing the destination address, and then forwarding it to the necessary port. Unlike
repeater hubs, switching hubs do not relay frames to all segments, which enables to
distribute loads of the network. In addition, some switching hubs have other varieties of
features including the auto-negotiation, optical interface, 1 Gbps Ethernet interface,
VALN, SNMP, STP, port mirroring, and Layer 3 switch.

Router
A router is a network device to transmit packets over networks based on the information
of network layers. Routers have a function to route communication frames. Routers are
used for connections between network domains or connections to WAN or other media.
Recently, the routers with multi-functions such as security functions, firewall, and
redundant network functions are generally used.

Main Functions of Network Devices


This subsection explains the main functions and features of network devices for
reference purposes to choose the optimum network device.

Full-Duplex
Full-duplex enables the transmission of data in two directions simultaneously (send and
receive), avoiding the collision of the two. With Fast Ethernet, 200 Mbps bandwidth is
enabled.

TI 34P02K25-01E Jun. 6, 2018-00


<1. Devices Overview> 13
Auto Negotiation
The auto negotiation is a function to confirm the communication method to be employed
between two ports connected to cables, through FLB Bursts signals. The selection
between interfaces with different speeds (10 Mbps, 100 Mbps or 1 Gbps: FCN-500 only)
or between different communication modes (half-duplex or full-duplex) is automatically
performed. The communications between two devices should be one of the following
combinations of communication speeds and communication modes.
Table Combinations of Communication Speeds and Communication Modes
10M Half 10M Full 100M Half 100M Full 1G Full Auto
10M Half X - - - - X
10M Full - X - - - -
100M Half - - X - - X
100M Full - - - X - -
1G Half - - - - - X
Auto X - X - - X

X: Possible
-: Impossible

FCN/FCJ supports the auto negotiation features only.


Therefore, specify auto negotiation (recommended) or 100 Mbps Half Duplex for a target
connecting device of FCN/FCJ.

Supporting 1 Gbps
A switching hub with a port which supports data transfer rates of 1 gigabit per second. It
is effective to use this hub for high-speed link between switches or between a switch
and a server or to a backbone. 1000BASE-X, standardized in IEEE802.3z and
1000BASE-T, standardized in IEEE802.3ab are provided. For detailed specification,
refer to the corresponding standards.

VLAN
VLAN is a function to divide a LAN logically within a switch. It imposes restrictions on the
scope of forwarding broadcast packets, and divides logical groups, in which
communications are established, enabling to construct a network so that each group
may be connected to the separate switches. VLAN also realizes highly efficient network
through the function to forward broadcast packets only within the same VLAN.

SNMP
SNTP is a switching hub with SNMP features to mange a network. SNMP is effective for
monitoring networks or tracking down the source of failures remotely.

Layer3 Switch
Layer3 switch is a switching hub with routing functions implemented in the hardware.
Faster routing operations and relatively reasonable prices than usual routers are
attained in this switching hub.

TI 34P02K25-01E Jun. 6, 2018-00


<1. Devices Overview> 14

Track Usage Record of Network Devices


Track Usage Record of Hubs
The following products were used for labo test of STARDOM.
Table Track Usage Record of Hubs
Manufacturers Product names/type names Remarks
Cisco Catalyst2912/24 XL-EN Switching hub with management features
Cisco Catalyst2950-24 Switching hub with management features
3Com SuperStack 3 Switch 3300SM 3C16985 Switching hub with management features
Allied Telesis CentreCOM FS708XL Switching hub
Allied Telesis CentreCOM FS708EXL Switching hub
Allied Telesis CentreCOM FS808TPV1 Switching hub
HP ProCurve Switch 2512/2524 Switching hub,0-55 °C

TIP
• It takes several tens of seconds for switching hubs with management features to start a packet
relay operation, because the initialization processing is generally carried out after they are turned
on. Therefore, if an FCN with duplexed CPUs is connected to such a switching hub and if the FCN
and the switching hub are turned on simultaneously, the APC (All Program Copy) processing may
fail when the FCN is turned on. In this case, turn on the switching hub first. After the initialization
processing of the switching hub is finished, turn on the FCN.
• By default, the spanning tree protocol (a function to automatically set usual routes or routes when
making detours in networks with multiple routes) is configured to Cisco’s switching hubs. In this
case, hubs do not forward data to relevant ports for about 30 seconds after devices connected to
the hubs were turned on. In order to avoid this problem, cancel the configuration for using the
spanning tree protocol.

Track Usage Record of Routers


The following products were used for labo test of STARDOM.
Table Track Usage Record of Routers
Manufacturers Product names/type names Remarks
YAMAHA RT140f VPN, firewall features
Allied Telesis CentreCOM AR320 Firewall features

Hubs for Industrial Environments


For reference purposes, hubs used for industrial environments on the market are listed
below; however, they are not used for labo test of STARDOM.
Table Hubs used for Industrial Environments
Manufacturers Product names/type names Remarks
Hirchmann RS2-TX 8 Port, 10/100Base-Tx, 24 VDC, 0-60 °C
CONTEC SH-8008L 8 Port, 10/100Base-Tx, 100Vac, 0-55 °C

TI 34P02K25-01E Jun. 6, 2018-00


<1. Devices Overview> 15

Cables
Please avoid unplugging cables attached to a device by fixing it to a rack or other
furniture, or taking other measures. Generally used LAN cables are listed as follows.

UTP Cables
A UTP cable is the most commonly used unshielded twisted pair cable. Use category 5
or higher UTP cables. There are 4-conductor cables and 8-conductor cables; the both
type can be used. Make a choice between a cross cable and straight cable according to
the intended purpose. Generally, a straight cable is used when the connection is made
between a node and a hub; a cross cable is used when the connections are made
between only hubs or only nodes. Refer to the manual of each network device because
the specification may differ by the device. Select generally used RJ-45 type plugs for the
connectors of both ends.

STP Cables
In environments with much noise, use shielded twisted pair (STP) to reduce the effects
of noise. However, conditions of usage may differ by the network device; use the cable
on your own authority referring to the manual of the network device in use.

Optical Fiber Cables


It is recommended to use this type of cable when you lengthen distances, wire between
separate buildings or use the device in the environment with much noise. The following
LAN standards are provided for the use of optical fiber cables: 10BASE-FL, 100BASE-
FX, 1000BASE-SX and 1000BASE-LX. Each standard defines the type of optical fiber
and maximum distances. For the detailed specification, refer to manuals of the network
device in use or manuals of IEEE802 or the standard itself. Media converters having
optical interfaces or switching hubs supporting optical interfaces are needed because
optical interfaces have not been mounted on FCNs/FCJs.

Specifications of Major Cables


Specifications of major network cables are shown below.
Table Specifications of Major Network Cables
Standard Bandwidth Cable Maximum Distance Remarks
Copper cable of
10BASE-T 10 Mbps UTP (Category 3) 100 m
10 Mbps
UTP (Category 5) Copper cable of
100BASE-TX 100 Mbps 100 m
STP (Type 1, 2) 100 Mbps
Optical fiber
GI/MMF wavelength 1300 nm 412 m (half duplex)
100BASE-FX 100 Mbps cables of 100
62.5/125 µm 2000 m (full duplex)
Mbps
Copper cable of
1000BASE-T 1 Gbps UTP (Category 5) 100 m
1 Gbps

TI 34P02K25-01E Jun. 6, 2018-00


<1. Devices Overview> 16

Installing Network Devices


Power Dispatching
When the power of one of network devices such as a hub is shut down, the entire
communications of all devices attached to the network device stop. You should
determine the power routing considering the scope of effects as described above. In the
case where the reliability is severely required, it is recommended to prepare backup
powers, or duplex network devices, each of which be powered via separate routing.

Selecting Devices
As far as possible, install network devices including a hub for each area, with minimum
number of wirings among the area. Choose network devices according to the purpose,
among several types e.g., devices for mounting to a 19-inch rack, to a desktop or to a
wall. For the number of ports, it is recommended to choose a hub with more ports than
you actually use at present, in consideration of the future expansion or the use as a port
for monitoring when failures will occur. According to the environment (temperature,
moisture, dust, noise, etc.) where the network device is installed, select the optimum
one.

Checking LED Display


LEDs for checking statuses are implemented on each network interface of FCN/FCJ.
Generally, LEDs are also implemented on ports of network adapters and network
devices. When finished connecting the cable, you need to check if the Link light flashes,
and Act, Send, Rcv and other lights flash while communication is performed.
Table Network Interface LEDs of FCN/FCJ
Colors Names Contents
Yellow LINK Connection is normal
Orange ACT Send/receive

For the LED displays of hubs or network adapters, refer to the manual of each device
since the number and role of each LED differ by the device.

Communication Test
When you finished setting the device and connections, check if the communication is
normally established by executing Ping command or other methods.

Replacing Network Devices


You can replace network devices such as hubs, cables or routers on-line. The
communication stops while the device is replaced; however, it starts again when you
connect the cable after the replacement. If the control network is duplexed, the network
has the feature to switch communication paths automatically, enabling to change the
device maintaining the communication. Please follow the right steps to change the
device checking the messages notifying the failure or the recovery of the network.

TI 34P02K25-01E Jun. 6, 2018-00


<1. Devices Overview> 17

Restrictions on total distances of networks


According to the 1000BASE-T/100BASE-TX/10BASE-T standards, cables of up to 100
meters can be used. It is possible to extend the total distance via hubs on many levels
with cascade connections. However, if a repeater hub is used, the following restrictions
are applied to total distances:
• If a repeater hub is used with 100BASE-TX cables
The total distance is up to 205 meters, with up to 2 levels in cascade connections,
within 100 meters for cable lengths between devices and within 5 meters for cable
length between hubs (IEEE802.3u Standard).
• If a repeater hub is used with 10BASE-T cables:
The total distance is up to 500 meters, with up to 4 levels in cascade connections
and within 100 meters for cable lengths between devices.
If the 1000BASE-T is used, or a network requires a total distance exceeding these
restrictions, use switching hubs or routers to configure such a network.

TI 34P02K25-01E Jun. 6, 2018-00


<1. Devices Overview> 18

1.5 Communication Protocols


This chapter explains the communication protocols used in the devices that
configure STARDOM system.

STARDOM system uses Ethernet for control networks and the upper control system
information network. For network layers and transport layers, the industry-standard
TCP/IP is employed.

Communications between VDS Data Server and FCN/ FCN-RTU/FCJ


For communications between VDS data server and FCN/FCJ, a communication protocol
based on Fast Ethernet and TCP/IP is employed.

Time Synchronization
FCN/FCJ has SNTP client functions and time adjusting functions as standard features,
enabling to synchronize times among nodes.
In the FCN-500, it is possible to execute the SNTP function as a standard feature. In the
FCN-100 and FCJ, it is possible to execute the SNTP function by installing a time
synchronization server portfolio.

Utility Communications
Configuration tools for defining FCN/FCJ or field network devices and designing control
logics, establish communications with FCN/FCJ using dedicated protocols. More
specifically, the tools download definitions of devices defined on Resource Configurator
or other configuration tools, download control logics created on Logic Designer, and
execute maintenance communications of control logics using Logic Designer.

Communications between VDS Data Server and VDS HMI Server


OPC-DA is employed for communications between VDS data server and VDS HMI
server, or VDS data server and other computers.

Communications between VDS HMI Server and HMI Client


HMI client does not require any software other than Java Runtime Environment. For
communications between HMI client and VDS HMI server, HTTP uses only.

Network Features of FCN/ FCN-RTU/FCJ


FCN/FCJ normally supports the protocols needed to communicate with open network
devices: receiving and sending mails, HTTP, FTP, TELNET, and other protocols.

TI 34P02K25-01E Jun. 6, 2018-00


<2. Network Features of STARDOM> 19

2. Network Features of STARDOM


This chapter explains basic network features of STARDOM system.

2.1 Varieties of Basic Configurations


Several examples of basic network configurations are shown in this section.

Small Two-layered System (Standard)


In this type of network, the control system information network connecting HMI clients
and the broadcast domain of the control network connecting controllers are separately
configured. This is one of the standard system configurations of STARDOM. Generally,
two network adapters are mounted on a VDS data server; one is used for control
network, and the other is used for control system information network.
Upper
Computer HMI HMI

Control System Information Network

VDS
Data Server (Up to 4 VDSs)
HMI Server

Control Network (Up to 126 controllers)

FCN FCN FCJ PLC (Up to 32 controllers per VDS)

Figure Small Two-layered System

Restrictions on Implementation
• The maximum node number connected to a control network: 126
• The maximum number of controllers including FCN/FCJ and PLC connected to a
single data server: 32
• The maximum number of VDS data servers connected to a control network: 4
• The maximum HMI clients (sessions) connected to a single VDS HMI server: 50
• There are no restrictions on total distances of the network.
• Routing of communication frames is needed if a control system information network
directly communicate to devices on a control network. For routing, use VDS as a
router or set a local router between the control system information network and the
control network. In consideration of the features of a control network, performing
real-time and reliable communications, you should not include frames unnecessary
for the network by routing.
SEE ALSO
• For the maximum number of data objects and data points upon per VDS data server, see "2.3
Communication Performances".
• For IP address settings on a small two-layered system, see "3.1 Small Two-layered System
(Standard)".
• For examples of configuration with routing, see "3.6 Connecting Routers to Control Networks".

TI 34P02K25-01E Jun. 6, 2018-00


<2. Network Features of STARDOM> 20

Small One-layered System


On a small system, HMI clients can be connected to a control network when there is no
need to configure a control network and a control information network separately. In this
case, one network adapter mounted on a VDS is sufficient.
VDS
Data Server
HMI Server (Up to 4 VDSs)
HMI HMI
HMI Client

Control Network (up to 126 devices)

FCN FCN FCJ PLC (Up to 32 controllers upon a VDS)

Figure Small One-layered System

SEE ALSO
• For restrictions on implementation, see "Small Two-layered System (Standard)" in this section.
• For IP address settings on a small one-layered system, see "3.2 Small One-layered System".

TI 34P02K25-01E Jun. 6, 2018-00


<2. Network Features of STARDOM> 21

Medium Scale Two-layered System


This medium scale system consists of several VDSs. A VDS HMI server collects and
consolidates data from VDS data servers, giving these data to HMI clients. You can
implement VDS HMI data server functions on one of VDS data servers.

In the following cases, it is recommended to connect several VDS data servers.


• Many controllers to be connected
• Many data points
• Controllers are distributed in remote areas

VDS Upper
HMI Server Computer HMI HMI

Control System Information Network

VDS VDS
Data Server Data Server (Up to 4 VDS data servers)

Control Network1 Control Network2

... ...
FCN FCN FCJ FCN FCN FCJ

Figure Medium Scale Two-layered System

Restrictions on Implementation
• The maximum number of VDS data servers connected to a single VDS HMI data
server: 4

SEE ALSO
• For other restrictions on the implementation, see "Small Two-layered System (Standard)".
• For the number of maximum data objects and data points upon a single VDS HMI data server, see
"2.3 Communication Performances".
• For IP address settings on a medium scale two-layered system, see "3.3 Medium Scale Two-
layered System".

TI 34P02K25-01E Jun. 6, 2018-00


<2. Network Features of STARDOM> 22

Three-layered System (Remote Operations)


For example, this network configuration may contain remotely installed HMI clients (e.g.
in offices) monitored via intra-company information network (e.g. intranet). For the
purpose of improving securities, routers or other devices are connected between the
information network and the control system information network.

HMI HMI

Information
Network Router

Remote Area

VDS
HMI Server
Router

Control System Information Network

VDS VDS
Data ... Data
Server Server

Control Network

... ...
FCN FCN FCJ PLC

Figure Three-layered System

SEE ALSO
For restrictions on implementation, see "Small Two-layered System (Standard)" and "Medium Scale
Two-layered System".

TI 34P02K25-01E Jun. 6, 2018-00


<2. Network Features of STARDOM> 23

2.2 Network Basic Definitions (IP Address


Settings)
This section explains IP address settings of FCN/FCJ and VDS connected to
control networks of STARDOM.

Rules for IP Address Allocation


STARDOM’s control networks can take two types of configurations: single and duplex.
Moreover, CPUs can be duplexed in the FCN500 and FCN-100, where an IP address is
allocated to each of the duplexed CPUs. The rules for IP address allocation in each
configuration are described below:

TIP
Not add 0 to the top of the IP address. When you add 0, it is treated as octal. It becomes the error or
the wrong address. It is checked closely with Windows 10 and Windows 7.
Example, "192.168.01.08" is an error. "192.168.01.011" is recognized as "192.168.1.9".

Single Network Configuration


[If the FCN-500 and FCN-100 does not use a configuration of duplexed CPUs, and
FCN-RTU]
There are no restrictions on the IP addresses that can be used.

[If the FCN-500 and FCN-100 uses a configuration of duplexed CPUs]


Arbitrary IP addresses can be set to both the control side CPU and the standby side
CPU of the FCN-500 and FCN-100. Use the Resource Configurator and specify an IP
address for the control side CPU. Then, select the “Detail…” button of the “General” tab
under “CPU Module”, remove the tick for “Auto” in the IP address checkbox for the
standby side CPU, and explicitly specify an IP address for the standby-side CPU.

TIP
• If there are multiple control system network domains, change the respective network addresses.
e.g.
Domain 1: 192.168.0.0
Domain 2: 192.168.1.0
• When the FCN has duplexed CPUs, the IP address of the standby side CPU is, by default,
automatically allocated on the basis of the IP address of the control side CPU according to certain
rules as explained in the “IP Address Decision Rules” section in “2.6 Duplexing Control Network”
Therefore, if the default IP address of the standby side CPU is used as it is, specify a value for the
IP address of the control side CPU in such a way that the value will not contradict the IP address of
the standby side CPU.
In a single network configuration, the default value for the IP address of the standby side CPU can
be changed by the Resource Configurator. Therefore, if you wish to designate an arbitrary IP
address for the control side CPU, change the default value for the IP address of the standby side
CPU, too.

TI 34P02K25-01E Jun. 6, 2018-00


<2. Network Features of STARDOM> 24

Duplexed Network Configuration


[If the FCN-500 and FCN-100 don’t use a configuration of duplexed CPUs]
Use class C private addresses of IPv4.
The setting procedures of IP addresses are explained as follows:

• Set an address in the range of 192.168.x.1-192.168.x.254, in which “x” is should be


at three intervals in the range of 0-252.
• Set a subnet mask to 255.255.255.0.
• Specify the address of a default router connected to the control network for the
default gateway. If you do not connect a router to the control network, it is not
needed to specify the address.
• Example of IP address settings
VIP address: 192.168.3.1
Subnet mask: 255.255.255.0
Default gateway: none
This setting reserves 192.168.4.1 and 192.168.5.1 for physical IP addresses.

[If the FCN-500 and FCN-100 use a configuration of duplexed CPUs]


Use IP addresses according to the same rule as in the case of not using a configuration
of duplexed CPUs.
However, IP addresses must be within the range of 192.168.x.1 – 192.168.x.126. An IP
address for the standby side CPU will be automatically allocated within the range of
192.168.x.129 – 192.168.x.254.

TIP
• When several network domains exist, different addresses should be set to each of them.
e.g.
Domain 1: 192.168.0.0
Domain 2: 192.168.3.0
• It is recommended to define each IP address allocation depending on the device; for example, the
controller's IP addresses begin from 192.168.x.1 and the VDS's IP addresses begin from
192.168.x.101, etc.
• In a duplexed network, IP addresses for PIP-A, PIP-B and the standby side CPU cannot be
changed because they are automatically allocated.
• The FCN/FCJ allows a configuration of separated networks (in which two network interfaces are
used as separate networks). However, in this separated network configuration, use the same
concept as in the case of a single network configuration to decide IP addresses.
• VIP means a virtual IP address. For details, see “Various IP Addresses” in “2.6 Duplexing Control
Network.”

TI 34P02K25-01E Jun. 6, 2018-00


<2. Network Features of STARDOM> 25

Network Configuration of the FCN/ FCN-RTU/FCJ


The FCN-500 (with NFCP501 CPU module), FCN-100 and FCJ have two network
interfaces on each CPU. These network interfaces can take the following three network
configurations:
• Single network configuration (in which network interface 2 is not used)
• Duplexed network configuration
• Separated network configuration (connected to two separated networks)

The FCN-500 (with NFCP502 CPU module) has four network interfaces on each CPU.
These network interfaces can take the following four network configurations:
• Single network configuration (in which network interface 2/3/4 are not used)
• Duplexed network configuration (network interface 1 and 2)
• Separated network configuration (connected to four separated networks)
• Duplexed network (network interface 1 and 2) and Separated network (network
interface 3 and 4) configuration

The FCN-RTU has one network interface on the CPU, It’s a single network
configuration. And a single CPU use only.

Each configuration is set in the “Network Group” combo box of the “Basic Configuration”
tab in the CPU Module Setting window of the Resource Configurator.
The overview of how each network configuration works is described below:

TI 34P02K25-01E Jun. 6, 2018-00


<2. Network Features of STARDOM> 26
Single Network Configuration
A single network is configured as follows:

VDS

192.168.0.101
Control Network
IP address for the Subnet mask 255.255.255.0
standby-side CPU
192.168.0.1 192.168.0.2 192.168.0.130 192.168.0.124
FCN/FCJ FCN FCN
Router
Single CPU duplexed CPU
192.168.20.124

Network for PLC


Subnet mask 255.255.255.0
192.168.20.1 192.168.20.2

PLC1 PLC2

Figure Example of a Single Network Configuration

In duplex CPU configuration of FCN-500 and FCN-100, IP address of the previous


control side is alternated to IP address of new control side along with control right in
case of CPU switchover.
The following figure shows the switchover operations of IP addresses when the control
right is alternated in a single network configuration when CPUs are duplexed in the
FCN.
FCN FCN
(Control) (Standby)
IP address for Without IP 2 2 Without IP IP address for
the control-side the standby-side
CPU CPU
192.168.0.2 1 1 192.168.0.130

Alternation of Control

FCN FCN
(Stop) (Control)
Without IP 2 2 Without IP IP address for
the control-side
CPU
Without IP 1 1 192.168.0.2

APC

FCN FCN
(Standby) (Control)
IP address for Without IP 2 2 Without IP IP address for
the standby-side the control-side
CPU CPU
192.168.0.130 1 1 192.168.0.2

Figure Operations when Control Right is Alternated in a Single Network Configuration

TI 34P02K25-01E Jun. 6, 2018-00


<2. Network Features of STARDOM> 27
Duplexed Network Configuration (FCN/FCJ: System R1.85 or Later)
A duplexed network is configured as follows:
PC

172.16.1.21
Control System Information Network
172.16.1.64 Subnet mask 255.255.0.0

VDS
192.168.0.101 (VIP)

192.168.1.101 192.168.2.101 PIP-A (NetAdr):


192.168.1.0
PIP-B (NetAdr): Control Network
192.168.2.0 Subnet mask 255.255.255.0
192.168.1.2 192.168.1.130 VIP (NetAdr): 192.168.0.0
192.168.1.1 192.168.2.1 192.168.2.2 192.168.2.130
FCN/FCJ FCN FCN
Single CPU duplexed CPU
192.168.0.1 (VIP) 192.168.0.2 (VIP) NetAdr: Network Address

Figure Example of a Duplexed Network Configuration (FCN/FCJ: System R1.85 or Later)

In duplex CPU configuration of FCN-500 and FCN-100, IP address of the previous


control side is alternated to IP address of new control side along with control right in
case of CPU switchover.
The following shows the switchover operations of IP addresses when the control right is
alternated in a duplexed network configuration when CPUs are duplexed in the FCN.
IP address for the FCN FCN IP address for the
control-side CPU (Control) (Standby) standby-side CPU
192.168.2.2 (PIP-B) 2 2 192.168.2.130 (PIP-B)

192.168.1.2 (PIP-A) 1 1 192.168.1.130 (PIP-A)

192.168.0.2 (VIP)

Alternation of Control

FCN FCN IP address for the


(Stop) (Control) control-side CPU
Without IP 2 2 192.168.2.2 (PIP-B)

Without IP 1 1 192.168.1.2 (PIP-A)

192.168.0.2 (VIP)
APC

IP address for the FCN FCN IP address for the


standby-side CPU (Standby) (Control) control-side CPU
192.168.2.130 (PIP-B) 2 2 192.168.2.2 (PIP-B)

192.168.1.130 (PIP-A) 1 1 192.168.1.2 (PIP-A)

192.168.0.2 (VIP)

Figure Operations when Control Right is Alternated in a Duplexed Network Configuration


(FCN/FCJ: System R1.85 or Later)

TIP
VIP means a virtual IP address. PIP-A and PIP-B mean physical IP address A and physical IP address
B respectively. For details, see “Various IP Addresses” in “2.6 Duplexing Control Network”

TI 34P02K25-01E Jun. 6, 2018-00


<2. Network Features of STARDOM> 28

Duplexed Network Configuration (FCN/FCJ: System R1.80 or Earlier)


A duplexed network is configured as follows:
PC

172.16.1.21
Control System Information Network
172.16.1.64 Subnet mask 255.255.0.0

VDS
192.168.0.101 (VIP)

192.168.1.101 192.168.2.101 PIP-A (NetAdr):


192.168.1.0
PIP-B (NetAdr): Control Network
192.168.2.0 Subnet mask 255.255.255.0
192.168.1.2 192.168.1.130 VIP (NetAdr): 192.168.0.0
192.168.1.1 192.168.2.1 192.168.2.2 192.168.2.130
FCN/FCJ FCN FCN
Single CPU duplexed CPU
192.168.0.1 (VIP) 192.168.0.2 (VIP) NetAdr: Network Address

Figure Example of a Duplexed Network Configuration (FCN/FCJ: System R1.80 or Earlier)

If control right is alternated when CPUs are duplexed in the FCN-100, IP addresses are
changed as follows:
IP address for the FCN FCN IP address for the
control-side CPU (Control) (Standby) standby-side CPU
192.168.2.2 (PIP-B) 2 2 192.168.2.130 (PIP-B)

192.168.1.2 (PIP-A) 1 1 192.168.1.130 (PIP-A)

192.168.0.2 (VIP)
PIP on the right
remains as it is.
PIP on the left remains as it is.

Alternation of Control

FCN FCN IP address for the


(Stop) (Control) control-side CPU
Without IP 2 2 192.168.2.130 (PIP-B)

Without IP 1 1 192.168.1.130 (PIP-A)

192.168.0.2 (VIP)
APC

FCN FCN IP address for the


IP address for the control-side CPU
standby-side CPU (Standby) (Control)
192.168.2.130 (PIP-B)
192.168.2.2 (PIP-B) 2 2
192.168.1.130 (PIP-A)
192.168.1.2 (PIP-A) 1 1
192.168.0.2 (VIP)

Figure Operations when Control Right is Alternated in a Duplexed Network Configuration


(FCN/FCJ: System R1.80 or Earlier)

TIP
VIP means a virtual IP address. PIP-A and PIP-B mean physical IP address A and physical IP address
B respectively. For details, see “Various IP Addresses” in “2.6 Duplexing Control Network”

TI 34P02K25-01E Jun. 6, 2018-00


<2. Network Features of STARDOM> 29

Separated Network Configuration


In a separated network configuration, network interface 1 of the FCN/FCJ is used for a
control network, while network interface 2 (network interfaces 2/3/4 in NFCP502 only) is
used for a network independent of the control network: for example, network interface 2
can be connected to a dedicated PLC network by PLC communication.
However, when connecting PLCs or PCs to the FCN/FCJ via a network, the network
must be configured to avoid having influences on FCN/FCJ control by communication
load lead from other devices.

SEE ALSO
Refer to “2.7 Cautions for Network Configuration” when connecting devices other than VDS and
FCN/FCJ devices to the network.

This network configuration has the following restrictions:


• No routing can be performed between network interface 1 and network interface 2
(network interface 1/2/3/4 in NFCP502 only).
• With respect to FCN/FCJ communications using the communication function block,
network interface 1 allows communications via routers (communications to separate
subnets), while network interface 2 does not. (FCN/FCJ: Only for System R1.80 or
Earlier)
Separated networks are configured as follows:

PC

172.16.1.21
Control system information network
172.16.1.1 Subnet mask 255.255.0.0

VDS

192.168.0.101
Control network
Subnet mask 255.255.255.0
192.168.0.1 192.168.0.2 192.168.0.130
FCN FCN IP address for
FCN/FCJ the standby- Network 2
Single CPU Duplexed CPU side CPU dedicated to PLC
Subnet mask
192.168.20.3 Network 1 192.168.40.3 192.168.40.131 255.255.255.0
dedicated to PLC
Subnet mask
192.168.20.1 192.168.20.2 255.255.255.0 192.168.40.1 192.168.40.2 192.168.40.124
PLC1 PLC2 PLC3 PLC4 Router

192.168.60.124
Network 3
dedicated to PLC
Subnet mask
255.255.255.0
192.168.60.1
PLC5

Figure Example of a Separated Network Configuration

TI 34P02K25-01E Jun. 6, 2018-00


<2. Network Features of STARDOM> 30
In duplex CPU configuration of FCN-500 and FCN-100, IP address of the previous
control side is alternated to IP address of new control side along with control right in
case of CPU switchover.
The following figure shows the switchover operations of IP addresses when the control
right is alternated in a separated network configuration when CPUs are duplexed in the
FCN.
FCN FCN
(Control) (Standby)
IP address for 192.168.40.3 2 2 192.168.40.131IP address for
the control-side the standby-side
CPU CPU
192.168.0.2 1 1 192.168.0.130

Alternation of Control

FCN FCN
(Stop) (Control)
IP address for
Without IP 2 2 192.168.40.3 the control-side
CPU
Without IP 1 1 192.168.0.2

APC

FCN FCN
(Standby) (Control)
IP address for IP address for
the standby-side192.168.40.131 2 2 192.168.40.3 the control-side
CPU CPU
192.168.0.130 1 1 192.168.0.2

Figure Operations when Control Right is Alternated in a Separated Network Configuration

TI 34P02K25-01E Jun. 6, 2018-00


<2. Network Features of STARDOM> 31
Duplexed network and Separated network
In FCN-500 (with NFCP502), a combination of duplexed network (network interface
1and 2) and separated network (network interface 3 and 4) is configured as follows:
In FCN-500 (with NFCP502), network interface 1 and 2 are used in a duplexed network.

Figure Example of a Duplexed Network and Separated Network Configuration

TI 34P02K25-01E Jun. 6, 2018-00


<2. Network Features of STARDOM> 32
In duplex CPU configuration of FCN-500 (with NFCP502), IP address of the previous
control side is alternated to IP address of new control side along with control right in
case of CPU switchover. The following shows the switchover operations of IP addresses
when the control right is alternated in a duplexed network configuration.
IP address for the FCN FCN IP address for the
control-side CPU (Control) (Standby) standby-side CPU
192.168.2.2 (PIP-B) 2 2 192.168.2.130 (PIP-B)

192.168.1.2 (PIP-A) 1 1 192.168.1.130 (PIP-A)

192.168.0.2 (VIP)

Alternation of Control

FCN FCN IP address for the


(Stop) (Control) control-side CPU
Without IP 2 2 192.168.2.2 (PIP-B)

Without IP 1 1 192.168.1.2 (PIP-A)

192.168.0.2 (VIP)
APC

IP address for the FCN FCN IP address for the


standby-side CPU (Standby) (Control) control-side CPU
192.168.2.130 (PIP-B) 2 2 192.168.2.2 (PIP-B)

192.168.1.130 (PIP-A) 1 1 192.168.1.2 (PIP-A)

192.168.0.2 (VIP)

Figure Operations when Control Right is Alternated in a Duplexed Network Configuration

TIP
VIP means a virtual IP address. PIP-A and PIP-B mean physical IP address A and physical IP address
B respectively. For details, see “Various IP Addresses” in “2.6 Duplexing Control Network”

In FCN-500 (with NFCP502), network interface 3 and 4 are used in a separated


network.
For example, network interface 3 and 4 can be connected to each different dedicated
PLC network by PLC communication. However, when connecting PLCs or PCs to the
FCN-500 via a network, the network must be configured to avoid having influences on
FCN-500 control by communication load lead from other devices.

SEE ALSO
Refer to “2.7 Cautions for Network Configuration” when connecting devices other than VDS and
FCN/FCJ devices to the network.

This network configuration has the following restrictions:


• No routing can be performed between network interface 3 and network interface 4.

TI 34P02K25-01E Jun. 6, 2018-00


<2. Network Features of STARDOM> 33
In duplex CPU configuration of FCN-500, IP address of the previous control side is
alternated to IP address of new control side along with control right in case of CPU
switchover. The following figure shows the switchover operations of IP addresses when
the control right is alternated in a separated network configuration.

Figure Operations when Control Right is Alternated in a Separated Network Configuration

TI 34P02K25-01E Jun. 6, 2018-00


<2. Network Features of STARDOM> 34

IP Address Settings to FCN/FCJ


You can configure IP addresses to an FCN/FCJ on Resource Configurator as follows:

1. Connect a PC on which Resource Configurator is installed to FCN/FCJ, and start


Resource Configurator on the PC. Resource Configurator and FCN/FCJ must be
connected on the same broadcast domain. The IP addresses cannot be set via a
router.

2. To the network interface1 of FCN/FCJ, connect an Ethernet cable. IP addresses


cannot be correctly configured if you use the interface2.

3. Start FCN/FCJ in IP addresses setting status. If the LED is flashed as in the table
below, FCN/FCJ is in that status.
Table Flashing Statuses of LED
LEDs Statuses
HRDY High speed flashing
CPURDY Low speed flashing
CTL Lighted out

TIP
In FCN-500 and FCN-RTU, IP addresses are written to an on-board flash memory on CPU module. An
CPU module, to which IP addresses has never been configured, becomes IP address setting status
automatically when powered on. If an IP address is reconfigured to an CPU module that already has IP
addresses, reboot from the maintenance window on a Web browser in IP addresses setting status, or
press a shutdown switch of FCN-500 or FCN-RTU. For the detailed sequence, see the corresponding
manuals or online-help files.
In FCN-100 and FCJ, IP addresses are written to an FCN/FCJ system card (Compact Flash). An
FCN/FCJ system card, to which IP addresses has never been configured, becomes IP address setting
status automatically when powered on. If an IP address is reconfigured to an FCN/FCJ system card
that already has IP addresses, reboot from the maintenance window on a Web browser in IP
addresses setting status, or press a shutdown switch of FCN/FCJ. For the detailed sequence, see the
corresponding manuals or online-help files.

4. Select [File] and then [Set IP Address] from the menu of Resource Configurator to
display the IP address setting dialog.

5. On the IP address setting dialog, configure IP addresses and subnet mask


corresponding to the displayed MAC address. Configure a default gateway as
necessary. When you finished all settings, click [OK].

TIP
The IP address setting window of Resource Configurator is displayed using the BOOTP protocol; if
FCN/FCJ with no IP addresses is connected, Resource Configurator displays MAC address of the
FCN/FCJ on its IP address setting window. The duplicated IP addresses due to incorrect-inputs must
be carefully avoided.

TI 34P02K25-01E Jun. 6, 2018-00


<2. Network Features of STARDOM> 35
With these settings, the IP address settings of the single control network configuration
have been completed. If you are to have the duplexed or separated control network
configuration, perform the following settings:
6. Use the Resource Configurator to connect to the FCN/FCJ and configure a control
network. For detailed operation methods, see the “Network functions” section on the
[FCN/FCJ Setting] – [CPU Module Setting] page of the Resource Configurator’s
online help and set a duplexed or separated network configuration.

IP Address Settings to VDS


You will set IP addresses to a PC onto which you will mount functions of VDS (VDS data
server, VDS HMI server, and HMI client).

Configure the same network addresses of FCN/FCJ to the network interface of VDS
data server connected to the control network. If you do not use the duplexed control
network function, configure the IP addresses according to the Windows standard
procedures.

VIP (Virtual IP Address) Settings


If you use the duplexed control network function, you need to start FCN/FCJ connection
setting tool to configure virtual IP addresses (VIP).

SEE ALSO
For settings of the duplexed control network function and VIP, see "2.6 Duplexing Control Network".

TI 34P02K25-01E Jun. 6, 2018-00


<2. Network Features of STARDOM> 36

Creating HOSTS Files


The correspondences between IP addresses connected to a control network and host
names are managed in HOSTS files. The HOSTS files are referred for host name
resolution while communicating.

TIP
HOSTS files are used for managing each node with the logical name. If you set nodes to be managed
with only IP addresses, it is possible to omit the procedure to create HOSTS files.

VDS
HOSTS files of VDS exist in the following directory.
%windir%\system32\drivers\etc
Using editors like notepad, input host names and IP addresses of all nodes connected to
the control network. If you use the duplexed control network function, describe VIPs as
IP addresses.
The following lines indicate an example of inputs to a HOST file. This example contains
comments to easily identify devices configuring the control network, however not
required.
Input example:
192.168.0.1 FCN01 #STARDOM FCN
192.168.0.2 FCN02 #STARDOM FCN
192.168.0.65 PLC01 #PLC
192.168.0.101 VDS01 #STARDOM VDS
192.168.0.102 EWS01 #Config PC

FCN/FCJ
Open the maintenance homepage on a Web browser to edit HOST files of FCN/FCJ.
Input IP addresses and host names in the system setting file window of this homepage,
and when finished typing, click the [OK] button.

SEE ALSO
For the operating sequence up to opening the system setting file window, see "2.5 FCN/FCJ Network
Features".

TI 34P02K25-01E Jun. 6, 2018-00


<2. Network Features of STARDOM> 37

2.3 Communication Performances


A STARDOM system collects and monitors data from controllers via networks.
Therefore, it is important to estimate communication performances of the
network. This chapter details the approximate scale of a standard STARDOM
system and how to estimate communication loads.

Standard System Scale


The approximate calculation of data (data object number, data point number) and
communication time (data acquisition time, starting time) are indicated in the table
below:
Table Approximate Traffic
Types Items Specifications
Amount of data per FCN/FCJ At most 3200 points/sec
At most 400 objects/sec,
Data number per VDS data server
At most 6400 points/sec
VDS data server
and FCN/FCJ Communication time per object
At most 50 ms
(accessing a single object, 100 Mbps)
Communication time per 100 objects
At most 400 ms
(accessing several objects, 100 Mbps)
At most 400 objects/sec,
Amount of data per VDS data server
At most 6400 points/sec
VDS data server
At most 1600 objects/sec,
and VDS HMI server Amount of data per VDS HMI server
At most 25600 points/sec
Communication time per object 100 ms or less

VDS HMI server HMI clients per VDS HMI server At most 50 clients
and HMI client Communication time per object 100 ms or less

Necessity of Network Load Calculation


It is necessary to calculate network load factor accurately when you construct a large-
scale system or employ low band including wide area network as the communication
infrastructure. For a small high-speed network system, the accurate calculation is not
always necessary, however, it is recommended to estimate approximate network load
factor.

TI 34P02K25-01E Jun. 6, 2018-00


<2. Network Features of STARDOM> 38

Estimating Network Load


It is possible to estimate network load by calculating the entire traffics passed through
hubs, nodes, and ports of hubs (see the figure below). It is necessary to estimate the
amount considering features of two types of hubs: switching hubs and repeater hubs. A
repeater hub forwards frames received from a port to all ports; therefore, traffics
received by and forwarded to all ports of hubs should be calculated. On a switching hub,
a unicast communication between two ports is not forwarded to other ports. As indicated
in the figure below, calculate traffics that may be passed through each port of hubs. In a
general configuration, it is presumed that communication loads center on the port
connected to VDS data server or the port connecting switching hubs.

Switching HUB Switching HUB

VDS VDS VDS FCN FCJ PLC


HMI HMI Data
Server Server

Figure Estimating Network Load

TIP
When estimating system performances, you should include CPU loads of FCN/FCJ and the one of
VDS data server, in addition to network communication loads.

TI 34P02K25-01E Jun. 6, 2018-00


<2. Network Features of STARDOM> 39

Reducing Network Load


If it becomes clear that the network is overloaded as the result of calculating network
load factor, the following methods can reduce the load.
• Leave only data needed to be referred and window needed to be displayed
• Lengthen the interval of updating data
• Employ a switching hub and configure the system so as to minimize collisions on
communications between devices
• Configure the system so as to minimize communications between switching hubs
• Employ broadband network configurations for the loaded part of the network; e.g.
supporting gigabit, or employing port aggregation (a function to use multiple ports
for the connection of two hubs and to enable high throughput using them as one
network connection).
• Divide a broadcast domain using the VLAN or Layer3 switch.
• Use a switching hub with higher data forwarding performance.
• Distribute the loads to several VDS data servers.
• Distribute the loads to several FCNs or FCJs.

TI 34P02K25-01E Jun. 6, 2018-00


<2. Network Features of STARDOM> 40

Network Load Factor Calculation (Steady State)


A network load factor can be calculated from total traffic per second.
R (%) = 100 * (VDSD + OPCD + HMID + FCXD + PLCD + ETCD) / A .......................... (1)
The steady-state network load factor (R) should fall within the following range.
R (%) < 20 ........................................................................................................................ (2)
When the value falls within the range above, the real time processing is guaranteed to a
degree even if collisions frequently occur on the communication frame.

VDSD
VDSD is the traffic (byte) per second that occurs between FCN/FCJ and VDS data
server. It can be calculated as follows:
VDSD = VDSD(DA) + VDSD(AE) + VDSD(DG) [byte] .................................................... (3)

VDSD (DA)
VDSD (DA) is the amount of data access communication (byte) per second to be
calculated from the number of data points and sampling period. If several sampling
periods exist, it should be the total amount calculated from each sampling period.
VDSD(DA) = DataNum * 50 / T(DA) [byte] ...................................................................... (4)
DataNum: number of data points
T (DA): data sampling period (sec)
To simplify, the overhead to communicate a data point is assumed to be 50byte.

VDSD (AE)
VDSD (AE) is the amount of data per second to be calculated from the amount of
message occurrences.
VDSD(AE) = MsgNum * 160 [byte].................................................................................. (5)
MsgNum: number of messages per second
To simplify, the overhead to communicate a message is assumed to be 160 byte.

VDSD (DG)
VDSD (DG) is the amount of diagnostic communication (byte) that occurs when the
duplexed network function is enabled. It is calculated from the number of nodes for
which the duplexed network function is enabled and the diagnostic transmission interval.
VDSD(DG) = NodeNum * 300 * Ntpgy / T(DG)[byte] ...................................................... (6)
NodeNum: number of nodes
Ntpgy: network topology
Ntpgy= 1: single LAN, dual LAN
T (DG): diagnostic communication interval (sec)

If a network is not duplexed, you do not consider the above. To simplify, the overhead to
communicate a message is assumed to be 300byte.

TI 34P02K25-01E Jun. 6, 2018-00


<2. Network Features of STARDOM> 41

OPCD
OPCD is the traffic per second that occurs between VDS data server and VDS HMI data
server. It can be calculated as follows:
OPCD = OPCD(DA) + OPCD (AE) + OPCD (HDA) ........................................................ (8)

OPCD (DA)
OPCD (DA) is the traffic that occurs when the data on VDS data server changes in
reference to the data that is monitored on a VDS Viewer of HMI client. OPCD (DA) per
second can be calculated as follows:
OPCD(DA) = DataNum * 100 [byte] ................................................................................ (9)
DataNum: number of data items
To simplify, the overhead to communicate a data item is assumed to be 100byte.

OPCD (AE)
OPCD (AE) is the traffic (byte) that occurs when a new message occurs on VDS data
server when the message window is displayed on a VDS Viewer of HMI client. OPCD
(AE) per second can be calculated as follows:
OPCD(AE) = MsgNum * 160 [byte] ............................................................................... (10)
MsgNum: number of messages per second
To simplify, the overhead to communicate a message is assumed to be 160byte.

OPCD (HDA)
OPCD (HDA) is the data traffic that occurs when the historical trend window is displayed
on a VDS Viewer of an HMI client. OPCD (HDA) per second can be calculated as
follows:
OPCD(HDA) = HdaDataNum * 800 [byte] ..................................................................... (11)
HdaDataNum: number of historical trend data points
To simplify, the overhead to communicate a historical trend data point is assumed to be
800 bytes.

HMID
HMID is the traffic per second (byte) between VDS HMI server and HMI client, which
can be calculated as follows.
HMID = HMID(DA) + HMID(AE) + HMID(HDA)............................................................. (12)

HMID (DA)
HMID (DA) is the traffic that occurs when the data on VDS HMI data server changes in
reference to the data that is monitored on a VDS Viewer of HMI client. HMID (DA) per
second can be calculated as follows:
HMID (DA) = 1800 + DataNum * 150 [byte] .................................................................. (13)
DataNum: number of data items

HMID (AE)
HMID (AE) is the amount of data communication that occurs when an alarm summary
window is displayed on a VDS Viewer of HMI client. HMID (AE) per second can be
calculated as follows:
HMID(AE) = AeNum * 2700[byte] .................................................................................. (14)
AeNum: number of message generation per second

TI 34P02K25-01E Jun. 6, 2018-00


<2. Network Features of STARDOM> 42
HMID (HDA)
HMID (HDA) is the data traffic that occurs when the trend window is displayed on a VDS
Viewer of HMI client. HMID (HDA) per second can be calculated as follows:
HMID(HDA) = 10000 + HdaNum * 100 [byte]................................................................ (15)
HdaNum: number of displayed trend pens per second

FCXD
FCXD is the traffic (byte) via the communication FB, which can be calculated as follows.
FCXD = DataNum * 50 [byte] ........................................................................................ (16)
DataNum: number of data items
To simplify, the overhead to communicate a data item is assumed to be 50byte.

PLCD
PLCD is the traffic (byte) between PLC and VDS data server or PLC and FCN/FCJ,
which can be determined by the communication protocol, amount of data, data updating
method, data interval, etc.
With FA-M3, PLCD can be calculated as follows.
PLCD = DataNum * 20 [byte]......................................................................................... (17)
DataNum: number of data items
To simplify, the overhead to communicate a data item is assumed to be 20byte.

ETCD
ETCD is the traffic that occurs by the factors other than the above communications.

A
A is the transmission rate on a line (byte/sec). With Fast Ethernet, it will be as follows.
A = 12500000 (byte/sec)................................................................................................ (18)

TI 34P02K25-01E Jun. 6, 2018-00


<2. Network Features of STARDOM> 43

Network Load Factor Calculation (Startup)


VDS and HMI perform communications differently at startup and at steady state. In
some cases, a startup can consume longer time; you should additionally calculate each
starting time.

Starting Time of VDS Data Server


This subsection explains the calculation of communication time, through calculating
traffic occurs when the first communication starts (a session is established) between
FCN/FCJ and VDS data server.
The communication to establish a session includes uploading time of database
(ADLST.csv) for accessing data, and reading time of messages.
The communication time can be calculated as follows:
VDSST [s] = (SesOp + DataNum * 100 + MsgNum * 160 [byte]) / A ............................ (20)
SesOp: time for establish connections
DataNum: number of data items
MsgNum: number of messages per second
A: transmission rate on a line (byte/sec)
To simplify, it is assumed that the amount of database per a point of data be 100byte
and the overhead to communicate a message be 160byte.
While starting up, VDS data server reads all messages managed by FCN/FCJ. When
calculating communication time, you need to consider that VDS data server reads off the
maximum number of messages (MaxMsgNum).

Starting Time of HMI Client


Through calculating traffic occurs during the time between starting of HMI client (by
starting of VDS Viewer) and being ready for monitoring data on HMI, the communication
time can be calculated. Actually, in addition to the communication time, the time for
authorizing each logon and displaying graphics are added. The communication time
should be considered as an approximate guide for starting time of HMI client. The
communication time can be calculated as follows:
HMIST [s] = (HMID(STT) + HMID(APP) + HMID(GRA) ) / A + HMID(INT) ................... (22)

HMID (STT)
HMID (STT) is the traffic on HMI client from invoking a server on a VDS Viewer to
logging on.
HMID (STT) = 20 [kbyte]................................................................................................ (23)

HMID (APP)
HMID (APP) is the traffic that occurs when displaying a graphic window only for the first
display of the window.
HMID (APP) = 500 [kbyte] ............................................................................................. (24)

HMID (GRA)
HMID (GRA) is the size of a graphic file (.sgr). For a typical graphic window, the
following should be assumed as an approximate value.
HMID (GRA) = 100 [kbyte]............................................................................................. (25)

TI 34P02K25-01E Jun. 6, 2018-00


<2. Network Features of STARDOM> 44

HMID (INT)
HMID (INT) is the time from the completion of downloading a graphic display program till
the completion of a display. While this time depends not on communication time but on
the PC’s CPU performance, the following should be assumed as an approximate value:
HMID (INT) = 20 [sec].................................................................................................... (26)
If displayed again using the same Viewer, the following should be assumed as an
approximate value:
HMID (INT) = 5 [sec]

TI 34P02K25-01E Jun. 6, 2018-00


<2. Network Features of STARDOM> 45

Example of Network Load Estimation


For the example of network load estimation, we assume the following small system
configuration.
VDS
Data Server
HMI Server
HMI Client HMI HMI

Control Network

FCN FCN FCJ PLC

Figure Example of System Configuration

A VDS data server and an HMI server was implemented on a single PC, with two HMIs,
a PLC (FA-M3) and two FCN and an FCJ are connected on a same network domain.
The VDS data server acquires data from two FCNs, a FCJ, and a PLC, and monitors
these data using two HMIs.

Network Wiring
As indicated in the figure below, a 100 Mbps switching hub connects all devices.
Switching HUB

VDS VDS VDS FCN 1 FCN 2 FCJ PLC


HMI 1 HMI 2 Data Server

Figure Example of Connecting Network Devices

TI 34P02K25-01E Jun. 6, 2018-00


<2. Network Features of STARDOM> 46
Data for Estimating Traffic of Data on Controllers (Example)
FCN1 FCN2 FCJ
Number of objects 5 5 3
Number of data points 80 80 48
Number of operation
80 80 48
and monitoring points
Maximum messages 1000 1000 1000
Data acquiring interval
1 1 1
(S)

Example of Calculation of Traffic on Ports


Data
HMI 1 HMI 2 FCN 1 FCN 2 FCJ PLC Remarks
Server
VDSD(DA) - - 11400 4000 4000 2800 -
Assuming 10/sec per
VDSD(AE) - - 4800 1600 1600 1600 -
FCN/FCJ
VDSD(DG) - - - - - - -
OPCD(DA) - - - - - - -
OPCD(AE) - - - - - - -
OPCD(HDA) - - - - - - -
HMID(DA) 4800 4800 9600 - - - - Assuming 10 % changes
HMID(AE) 45 45 45 - - - - Assuming 1 message/sec
HMID(HDA) 12000 12000 24000 - - - - Monitors 20 points
FCXD - - - 500 500 - - Assuming 10 points
PLCD - - 600 600 Monitors 30 points
ETCD - - - - - - -
Total 16845 16845 50490 7100 7100 4200 600
R(Communication
0.135 0.135 0.404 0.057 0.057 0.034 0.005
load)

TI 34P02K25-01E Jun. 6, 2018-00


<2. Network Features of STARDOM> 47

2.4 Security
This chapter explains the security features on STARDOM networks.

Security on Control Networks


For communications between VDS data server and controllers, the original idea is
applied to the design of session management and database, to prevent wiretapping
activities, passing-off, and tampers from outside of the networks.

Security Features between VDS Data Server and VDS HMI Server
For communications between VDS data server and VDS HMI server, DCOM is
employed ensuring security functions working with the Windows-system user
management.

SEE ALSO
For the detailed information on security functions, see "VDS/ASTMAC Security"(IM 34P02D12-01E).

Security at Wide Area Network


Considering the features of HMI client that can be set on remote offices via a LAN or
WAN, it is furthermore important to ensure security functions for this type of network.
Between VDS HMI server and HMI client, an authorization was given by user name and
password at logging on of the user. The typed password is encrypted before
transmission. If you use a WAN, the security control described above is insufficient. You
should connect routers supporting VPN, which allows communication frames to be
encrypted, preventing wiretapping activities, tampers and other accesses from outsiders.
In addition, a firewall should be implemented between external networks and internal
networks to minimize accessing from outside; basically, only HTTP communications to
HMI server are authorized.
Counter measure by VPN and/or firewall is necessary for remote direct access to
FCN/FCJ by InfoWell package and remote maintenance purpose to reduce risk.

SEE ALSO
For cases of installing firewalls and VPN routers, see "3.12 Operation with Remote HMI".

TI 34P02K25-01E Jun. 6, 2018-00


<2. Network Features of STARDOM> 48

HMI

Information
Network

VDS Wide Area


HMI HMI Server HMI Firewall Router Network

Control System Information Network

VDS Firewall Router


Data Server

Control Network
HMI

FCN / Configuration
FCJ PLC
FCN-RTU PC

Field Network

Field Field
Device Device

Figure Basic Network Configuration

When the fire wall of VDS or the engineering PC is made effective in the intranet, make
the relevant port effective refer to “The communication port to use of STARDOM.”
Firewall router is effective counter measure against security risk from wide area network.
Unexpected accesses are blocked by minimizing number of ports which is opened to
network.
Firewall router configuration must be done with good enough considering of network
security risk.

SEE ALSO
For port number to use of FCN/FCJ, see "2.8 The communication port number to use of FCN/FCJ."

TI 34P02K25-01E Jun. 6, 2018-00


<2. Network Features of STARDOM> 49

The communication port number to use of STARDOM


Information about firewall settings of STARDOM in the port number used is shown
below.
Table Port number when FCN/FCJ sends
Function Port Protocol Description When and where used
number
Basic Unknown TCP FTP In case of using maintenance Command earlier R2.01
Software version, setting is required on the PC.
(FcxBackup/FcxRestore/FcxLogSave/FcxRevup)
Passive mode from version R2.10 now. Earlier R2.01
version in Active mode, the program must be specified in
firewall.
25 TCP SMTP In case of sending e-mail by using Java applications,
setting is required on the SMTP server PC.
53 UDP DNS In case of using DNS by using Java applications, setting
is required on the DNS server PC.
110 TCP POP3 In case of receiving e-mail by using Java applications,
setting is required on the POP server PC.
123 UDP SNTP In case of using time synchronization function, setting is
required on the time synchronization server PC.
67 UDP BOOTP In case of setting the IP address by Resource
Configurator setting is required.
APPF 80 TCP HTTP In case of displaying the Web viewing by InfoEnergy,
FCN/FCJ firewall setting is required.
20/21/80 TCP FTP Log collector selects Passive mode.
34170~ TCP Webmetry In case of displaying the real time screen by Infowell. If
34172 there is a firewall in FCN/FCJ, setting is required.
OPC 135 TCP RPC FCN/FCJ OPC server and OPC client setting is required.
Unknown
(*)
Etc 1092 UDP In case of using duplexed networks, setting is required.
*: If beyond the firewall, RPC specifies a dynamic allocation, refer to the "How to configure RPC dynamic port allocation to
work with firewalls" (*1).
*1: Refer to the Microsoft Web site. http://support.microsoft.com/kb/154596/

SEE ALSO
For port number when FCN/FCJ receives, see "2.8 The communication port number to use of
FCN/FCJ."

Table Port number when VDS receives


Function Port Protocol Description When and where used
number
HMI 80 TCP HTTP VDS Client. HMI PC server or firewall router setting is
Client required.
OPC Unknown TCP RPC VDS/ASTMAC master station /ASTMAC view client
setting is required.
Note 1: The client side configuration is required, for
sending an alarm.
Note 2: ASTMAC are checking the equipment by ping,
it is not beyond the firewall.
Events 12306 UDP Asynchronou VDS/ASTMAC in the master station setting is required.
received (3012H) s Events
(*1) received
Etc 1092 UDP In case of using duplexed networks, setting is required.
*1: Can be changed in the settings (hexadecimal) of the object Builder.

TI 34P02K25-01E Jun. 6, 2018-00


<2. Network Features of STARDOM> 50

2.5 Network Functions of FCN/FCJ


FCN/FCJ supports Web server functions, forwarding files, and sending/receiving
mails that are general communication protocols on TCP/IP. FCN/FCJ also is able
to operate and acquiring data independent of VDS.

Maintenance Homepage (Web Server)


FCN/FCJ comes with Web server functions. When you access on a Web browser, the
maintenance homepage is displayed. In this homepage, you can refer to setting
information and maintenance information; configure parameters, reboot and other
operations on Web browsers.

You can change settings using the maintenance windows in the sequence below.

1. For a URL on a Web browser, type the IP address of the FCN/FCJ adding /mnt at
the end of the address; the maintenance homepage is displayed.

2. Clicking the link of "Maintenance Menu" on the homepage opens the maintenance
menu. Since the page is normally displayed in online mode, you can only refer to
parameters. If you want to configure or change the parameters, you should reboot
the FCN/FCJ in maintenance mode.

3. Clicking the link of [Reboot] displays the reboot window. On this window, select
"Reboot (Maintenance Mode)" and click [OK].

4. After rebooted, follow the sequence described in step1 to open the maintenance
homepage.

System Setting File


You can edit the system setting file on the window displayed when you click the link of
[Edit] in "System Setting Files" on the maintenance menu.

TI 34P02K25-01E Jun. 6, 2018-00


<2. Network Features of STARDOM> 51

FCN/FCJ Duolet Functions


FCN/FCJ Duolet functions allow the user to create Duolet applications, enabling to
provide Duolet applications with various services of the OS, e.g. access to hardware,
access to various data of the control function, and send/receive mails, which ensures
radical trimming of man-hours needed for programming, and strong maintainability and
reliability. FCN/FCJ Duolet functions provide multi-task environment for Duolet
applications; the application unit is referred to as Duolet. For the details, see the TI
“STARDOM FCN/FCJ Duolet Function Programmer’s Guide” and the online help of the
FCN/FCJ Duolet Application Development Kit.

Development Environment
The user can originally develop Duolet applications using the Java development
environments of Oracle, Inc., the FCN/FCJ Duolet Application Development Kit, and
Webmetry basic library portfolios.

Example of Application
You can easily create Duolet applications, e.g. monitoring a given data, detecting
original alarms, or diagnosing I/O paths. It is also possible to forward alarms or other
information to mail servers or beepers.

TI 34P02K25-01E Jun. 6, 2018-00


<2. Network Features of STARDOM> 52

JEROS Basic Configuration


On a Web browser, you can define basic operations of the system by editing JEROS
basic setting files. The following table shows the list of setting items.
Table Setting Items in JEROS Basic Configuration File
Functions Setting items Keys Default values
Host name HostName None
IP address IpAddress None
Network
Subnet mask SubnetMask Default mask
Default gateway GatewayAddress None
Serial communication Console display COM port ConsoleComPort None
System shutdown Shutdown timer ShutDownTimer 30 sec
Java start parameter JavaStart None
Java execution
Additional Java class path AdditionalClassPath None
Start FTP server FtpdStart YES
FTP server
FTP server data reception timeout FtpdDataTimeout 60 sec
Start Web server HttpdStart YES
Web server
HTTP open space HttpOpenSpace /JEROS/WWW
Maintenance Security in maintenance operations MaintenanceSecurity NO
DNS client Start DNS client DnsStart NO
SNTP client Start time synch client SntpStart NO
Time zone Set time zone TIMEZONE JST::-540

Table Setting Items in Duolet Environment Setting File


Functions Setting items Keys Default values
Log server name LogServerName None
System log Server transmission log level LogServerLevel INFO
other logs submitted
Duolet monitor Shutdown password ShutdownPassword None
Start Duolet RootDuolet None
Duolet Duolet storage address RemoteClassBase None
Duolet wait time (msec) DuoletTimedOut 10000 ms
Communication port number SystemPort 34101
Communication time out NetTimeOut 500 msec
Communication
Communication retry times NetRetryTimes 3
Communication trace output NetTrace OFF

Send and Receive Mails


You can send and receive internet mails on FCN/FCJ. On remote FCN/FCJ, it is easy to
transmit warning messages to an administrator without any intermediate manual
operations, contact to a mobile of someone by transmitting a message, etc. You can
also remotely send a mail for checking conditions of the site to be replied to FCN/FCJ.
For sending, SMTP protocol is used; for receiving, POP3 is used.

SEE ALSO
For an example of system configuration for send/receive mails, see "3.12 Send Mails to/Receive Mails
from VDS and FCN/FCJ".

TI 34P02K25-01E Jun. 6, 2018-00


<2. Network Features of STARDOM> 53

PPP (Point to Point Protocol) Connections


You can exchange data by installing a modem to a serial port of FCN/FCJ via a public
line. You can access from a PC to FCN/FCJ.

SEE ALSO
For an example of the system configuration with PPP connection, see "3.13 Monitoring and
Maintaining FCN/FCJ Remotely".

CAUTION
If you duplex a CPU of FCN, this feature is unavailable.

SLIP (Serial Line Internet Protocol) Communication


SLIP enables point-to-point IP communication by using serial line (RS-232-C). SLIP
communication is available in any of two modes, online or maintenance.

SEE ALSO
For SLIP settings, see the online help files.

CAUTION
If you duplex a CPU of FCN, this feature is unavailable.

Webmetry Functions (FCN-100 and FCJ)


Webmetry functions of FCN-100 and FCJ are class libraries to create monitoring
applications on Web browsers of PCs on networks by acquiring data on controllers. By
using data display applets (digital, bar, and trend displays) on Web browsers along with
data communication part to the applets, simple monitoring windows can be obtained
only through programming of data acquisition part.
These functions are enabled by using the Webmetry basic libraries in the FCN/FCJ
Duolet Application Development Kit.
The following table shows estimated operating performances of monitoring windows
using Webmetry.
Table Performances of Webmetry
Items Contents
Data point numbers Approximately 50 points
Interval 1-2 sec
Simultaneously connected clients 5 clients (Web browser)

TI 34P02K25-01E Jun. 6, 2018-00


<2. Network Features of STARDOM> 54

FTP Client and Server


This function is to exchange files or data between external systems and FCN/FCJ.
Through this function, it is possible to forward files from FCN/FCJ to your data server or
from external systems to FCN/FCJ.

InfoWell (FCN-100, FCN-RTU and FCJ)


InfoWell is a package running on FCN/FCJ Duolet functions in FCN-100, FCN-RTU and
FCJ. It is unprogrammed and enables you to create web pages or send e-mails.
This package allows you to use simple settings and send information from an FCN/FCJ
without Java programming knowledge.
InfoWell is comprised of the following portfolios:

Graphic Portfolio
The Graphic Portfolio is a function with which an FCN/FCJ becomes a Web server to
allow transmission of control function data to graphical Web pages.

Web Application Portfolio


The Web Application Portfolio is a function with which an FCN/FCJ becomes a Web
server to allow transmission of control function data to various Web pages.

E-mail Application Portfolio


The E-mail Application Portfolio is a function to use data messages of FCN/FCJ control
functions as triggers to send e-mails.

SEE ALSO
• For the Graphic Portfolio, see “InfoWell Graphic Portfolio” (IM 34P02Q52-01E).
• For the Web Application Portfolio or the E-mail Application Portfolio, see “InfoWell” ( IM 34P02Q51-
01E).

TI 34P02K25-01E Jun. 6, 2018-00


<2. Network Features of STARDOM> 55

2.6 Duplexing Control Network


Control networks connecting VDS and FCN/FCJ require real-time operation and
high reliability.
The duplexed network function provided on STARDOM allows you to easily build
duplexed networks connecting VDS and FCN/FCJ.
In the case where failures occur on one of the two communication paths, the
communication paths are switched quickly and automatically to ensure that
communications are maintained and applications are not adversely affected.
Furthermore, in the case where failures occur on the control side CPU of FCN and
the control right moves to the standby side CPU when the CPU is duplexed in the
FCN-500 and FCN-100, it is possible to maintain communications with the VDS
and FCN/FCJ that communicate with this FCN.
VDS

It is possible to easily duplex


communications between
VDS and FCN/FCJ

Network Interface1(Network-A)

Network Interface2(Network-B)

FCJ FCN
It is possible to easily duplex communications
between FCN/FCJ and FCN/FCJ

Figure The Duplexed Network Function Provided on STARDOM (Conceptual Diagram)

VDS

A B

Hub-A Hub-B

A B A B
A B
Control-side CPU Standby-side CPU

FCJ FCN
Figure Duplexed Network Function Provided on STARDOM (Example of Connection)

Important
When duplexing control networks connecting VDS and FCN/FCJ, application programs
are not required to duplex the networks.

TI 34P02K25-01E Jun. 6, 2018-00


<2. Network Features of STARDOM> 56
Duplexing Communications with other Devices such as PLCs
It is possible to duplex communications between FCN/FCJ and other devices such as
PLCs. However, an application program is required.

Control Network1 (System-A)

Control Network2 (System-B)

PLC, etc
It is possible to duplex communications
FCJ FCN between FCN/FCJ and PLC, etc.

Figure Example of Connecting PLC to FCN/FCJ in Duplexed Network Configuration

Important
It is not possible to duplex communications between VDS and other devices such as
PLCs. Communications are performed in a single connection configuration.

SEE ALSO
• For the duplexed network function provided on STARDOM, see “2.6.1 The Duplexed Network
Function Provided on STARDOM.”
• For duplexing communications with other devices such as PLCs, see “2.6.2 Duplexing
Communications Using an Application.”

TI 34P02K25-01E Jun. 6, 2018-00


<2. Network Features of STARDOM> 57

Methods of Duplexing Networks


STARDOM provides the following two methods of duplexing networks (*2).
1. Duplexing communications using the duplexed network function provided on
STARDOM
2. Duplexing communications using an application (*1)
*1: This method applies to FCN/FCJ system R1.85 or later.
*2: FCN-RTU is not corresponding to the duplexing network.

Table Duplexing Communications


Item Duplexing networks Duplexing networks using an application
provided on STARDOM
Method Using the duplexed network Implementing using an application program
function provided on
STARDOM
Devices that can • VDS ↔ • FCN-500, FCN-100, FCJ ↔ PLC
be connected for FCN-500, FCN-100, FCJ • FCN-500, FCN-100, FCJ ↔
duplexed • FCN-500, FCN-100, FCJ ↔ CENTUM CS3000 FCS, CENTUM VP FCS
communications FCN-500, FCN-100, FCJ • FCN-500, FCN-100, FCJ ↔ FCN-500, FCN-100,
• FCN/FCJ OPC Server for FCJ (In the case of communications between
Windows (*2) ↔ segments) (*1)
FCN-500, FCN-100, FCJ
Application Not required Required: The following is implemented by an
application
• Two-system network failures are detected by the
application
• Two-system networks are switched.
Scope of Only effective within the same It is possible to duplex communications between
duplexing segment other segments (*1)
Network switching High-speed switching while Time-consuming because the connection needs to
connection is maintained be disconnected and then reconnected by the
application.
FCN/FCJ network Duplexing Duplexing/separated
settings
*1: Communications between segments, for example, via routers.
*2: Duplexed Network Program for FCN/FCJ OPC Server is required.

The Duplexed Network Function Provided on STARDOM


STARDOM allows you to easily duplex communications between VDS and FCN/FCJ,
and between FCN/FCJ and FCN/FCJ.
However, this duplexed communications function cannot be applied to communications
with other devices such as PLCs or to communications between segments.
VDS

It is possible to easily duplex


communications between
VDS and FCN/FCJ.

Control Network1 (System-A)

Control Network2 (System-B)

FCJ FCN
It is possible to easily duplex communications
between FCN/FCJ and FCN/FCJ.

Figure The Duplexed Network Function Provided on STARDOM (Conceptual Diagram)

TI 34P02K25-01E Jun. 6, 2018-00


<2. Network Features of STARDOM> 58
SEE ALSO
For the duplexed network function provided on STARDOM, see “2.6.1 The Duplexed Network Function
Provided on STARDOM.”

Duplexing Communications Using an Application


It is possible to duplex communications between FCN/FCJ and other devices such as
PLCs or communications between segments via routers using an application program.
However, it is not possible to duplex communications between VDS and other devices
such as PLCs or communications between segments via routers.
FCJ PLC
Another
Segment
It is possible to duplex
communications between FCN/FCJ
in one segment and FCN/FCJ in
another segment via routers.

Router Router
Control Network1 (System-A)

Control Network2 (System-B)

PLC
It is possible to duplex communications
FCJ FCN between FCN/FCJ and PLC.

Figure Example of Connecting PLC to FCN/FCJ in Duplexed Network Configuration

SEE ALSO
For duplexing communications using an application, see “2.6.2 Duplexing Communications Using an
Application.”

TI 34P02K25-01E Jun. 6, 2018-00


<2. Network Features of STARDOM> 59

2.6.1 The Duplexed Network Function Provided on STARDOM

Scope of Duplexing Network


The duplexed network function provided on STARDOM is implemented in control
network layer and effective in the scope of broadcast domain of the control network. The
following figure shows the scope of a network duplexing.
HMI

Router

Information System Network

HMI HMI Router

Control System Information Network

VDS VDS VDS VDS


HMI Server Data Server Data Server Data Server

Control Network
PLC PLC FCJ FCN FCN FCJ FCN FCJ

Scope of Duplexing Scope of Duplexing Scope of Duplexing


Network Network Network

Figure Scope of Duplexing Network

TI 34P02K25-01E Jun. 6, 2018-00


<2. Network Features of STARDOM> 60

Features
Duplexing of STARDOM control network is attained by general-purpose network
adapters, device drivers, network devices (switch, cable, etc.) based on TCP/IP
protocol. Each node has several network interfaces and controls communication paths
between them by routing table. For applications, the duplexed network is invisible
because they communicate using each node name or IP address. It is outstanding for
short switching time between network paths and seamless switching for applications. In
addition, you can connect devices that do not have the duplexed network function like
PLCs to the duplexed control network.

Related Terms
The following subsections explain an example of dual network and related terms.
HUB-A HUB-B

HMI PLC A B A B A B A B

FCN/FCJ Control Standby


VDS -side -side
Data Server
FCN/FCJ
Single Interface
Device Dual Interface Device

Figure Basic Configuration of Duplexed Network

Network-A
The network indicated in solid lines is referred to as Network-A, which is used normally.
If Network-B is used and an abnormal situation is detected in Network-B, Network-A is
used as a substitute for Network-B.

Network-B
The network indicated in dotted lines is referred to as Network-B. If an abnormal
situation is detected in Network-A, Network-B is used as a substitute for Network-A.

HUB-A
A hub used for Network-A is referred to as HUB-A.

HUB-B
A hub used for Network-B is referred to as HUB-B.

TI 34P02K25-01E Jun. 6, 2018-00


<2. Network Features of STARDOM> 61

Two Networks
In duplexed STARDOM network, there are two routes for nodes engaged in
communications: the above-mentioned Network-A and Network-B. Two respective
networks are on an equal basis. Which network is used for data communications is
determined in each node (peer-to-peer) engaged in communications.
Therefore, if we focus on a certain VDS, there can be a situation in which Network-A is
used between the VDS and a controller, while Network-B is used between the VDS and
another controller.
However, if a node is activated in a situation where both network cables of the node are
properly connected to networks, Network-A is generally used.

Single Interface Device


A single interface device is the node that has only a single network interface for control
networks or does not have STARDOM duplexed network function.

Dual Interface Devices


Dual interface device is the node that has dual network interfaces for control networks
and STARDOM duplexed network function. It refers to FCN/FCJ and VDS which has
configured duplexed network function.

Interface A
The first network interface on each node is referred to as interface A. Network interface
of a single interface device is interface A. On VDS, the network interface to which VIP
and PIP-A are configured is interface A. On FCN/FCJ, network interface1 is interface A.

Interface B
The second network interface on each node is referred to as interface B. Network
interface of a single interface device does not have interface B. On VDS, the network
interface to which PIP-B is configured is interface B. On FCN/FCJ, network interface2 is
interface B.

TI 34P02K25-01E Jun. 6, 2018-00


<2. Network Features of STARDOM> 62

Various IP Addresses
For realizing the duplexed network, it is necessary to configure virtual IP addresses and
physical IP addresses for nodes. An application simply recognizes virtual IP addresses.
Physical IP addresses are used for maintenances of communication paths through the
duplexed network function. If you do not use the duplexed network function, the
distinction between virtual and physical IP addresses is not needed; replace virtual IP
addresses to IP addresses for understanding this manual.

Virtual IP Address (VIP)


VIP is the typical IP address defined by a node. Resource Configurator defines this IP
address. General applications communicate using node names and VIP. A VIP is
configured for a network interface for which PIP-A is configured.

TIP
If the control right is alternated when CPUs are duplexed in the FCN, VIPs move from the original
control side to the new control side in conjunction with the control right.
Accordingly, general applications are not required to duplex the CPU of FCN.

Physical IP Address (PIP)


PIP is the IP address configured in network interfaces and created automatically based
on rules defined in advance.

Physical IP Addresses A (PIP-A)


PIP-A is the IP address configured to interfaces on interfaces A sides. PIP-A of each
node is set so as to be identical network address. General applications do not realize
this address.

Physical IP Addresses B (PIP-B)


PIP-B is the IP address configured to interfaces on interfaces B side. PIP-B of each
node is set so as to be identical network address and different from the one of PIP-A.
General applications do not realize this address.

IP Address Decision Rules


Physical IP addresses (PIP-A, PIP-B) when FCN/FCJ networks are duplexed or the IP
address of the standby side CPU when CPUs are duplexed in the FCN are decided
according to certain rules, depending on the virtual IP address (VIP) to be set by a user
to the FCN/FCJ.
The IP calculation rules are described below.

Necessary Information Prior to Deciding IP Addresses


Although IP addresses are usually expressed as four decimal numbers such as
192.168.1.1, they are internally treated as 32-bit binary numbers. For the notation of
192.168.1.1, a 32-bit number is divided into four 8-bit numbers from the top, each of
these being converted into decimal numbers and connected with a dot (.). This address
becomes C0A80101 if expressed in hexadecimal notation.
An IP address is divided into a network address and a host address according to its
subnet mask.

TI 34P02K25-01E Jun. 6, 2018-00


<2. Network Features of STARDOM> 63
A subnet mask is set as 255.255.255.0. A network address is decided by an IP address
and a subnet mask are respectively converted into binary numbers and a “logical AND”
of each bit is performed. If an IP address is 192.168.1.1 and a subnet mask is
255.255.255.0, they are converted into hexadecimal numbers of C0A80101 and
FFFFFF00 respectively. Thus, the network address is C0A80100 = 192.168.1.0.
A host address is an address after a network address. If an IP address is 192.168.1.1
and a subnet mask is 255.255.255.0, it is 01 as a hexadecimal number and 1 as a
decimal number.
Physical IP addresses (PIP-A, PIP-B), when FCN/FCJ networks are duplexed, or IP
addresses of two CPUs, when CPUs are duplexed, are decided by using network
addresses and host addresses of the virtual IP address (VIP).

Rules for Deciding the PIP of a Single CPU and the Duplexed Network
Configuration of an FCN/FCJ
In a single CPU and duplexed network configuration of an FCN/FCJ, physical IP
addresses (PIP-A, PIP-B) of FCN/FCJ are decided on the basis of the virtual IP address
(VIP) according to the following rules:
[PIP-A]
• Network address: a value obtained by adding 1 to the VIP’s network address
• Host address: the same value as the VIP’s host address
[PIP-B]
• Network address: a value obtained by adding 2 to the VIP’s network address
• Host address: the same value as the VIP’s host address
If these rules are applied to a VIP of 192.168.0.1 and a subnet mask of 255.255.255.0,
hexadecimal network addresses are C0A80100 and C0A80200 for PIP-A and PIP-B
respectively, while hexadecimal host addresses are 01 for both PIP-A and PIP-B. Their
IP addresses are shown in the table below:
Table IP Addresses when an FCN/FCJ Network is Duplexed
IP Address (Hexadecimal)
VIP 192.168.0.1 (C0A80001)
PIP-A 192.168.1.1 (C0A80101)
PIP-B 192.168.2.1 (C0A80201)

TIP
• In a duplexed network configuration, use class C private addresses of IPv4 and set a subnet mask
to 255.255.255.0.
• In a duplexed network configuration, PIP-A/B cannot be changed via the Resource Configurator.
Therefore, set the values to a VIP so that no contradictions will occur to PIP-A/B in the above rules.

TI 34P02K25-01E Jun. 6, 2018-00


<2. Network Features of STARDOM> 64

Rules for Deciding the IP Address of a Duplexed CPU and a Single Network
Configuration of FCN-500 and FCN-100
In a duplexed CPU of FCN-500 and FCN-100 and single network configuration or a
separated network configuration of an FCN, the IP address of the standby side CPU is
decided on the basis of the IP address of the control side CPU according to the following
rules:
• Network address: the same value as the network address of the control side CPU
• Host address: a value obtained by setting the most significant bit of the host
address of the control side CPU as 1
If these rules are applied to an IP address of 192.168.1.1 with a subnet mask of
255.255.255.0 for the control side CPU in a single network configuration, the network
address remains C0A80100 and the host address is 81 (10000001 in the binary
notation) in the hexadecimal notation with respect to the IP address of the standby side
CPU.
Thus, the IP address of the standby side CPU is C0A80181 = 192.168.1.129.
IP addresses of control side/standby side CPUs are shown in the table below:
Table IP Addresses of Control Side/Standby Side CPUs
IP Address of Control Side CPU (Hexadecimal) IP Address of Standby Side CPU (Hexadecimal)
192.168.1.1 (C0A80101) 192.168.1.129 (C0A80181)

In this configuration, the IP addresses of two duplexed CPUs are alternated every
time they switch from the control side to the standby side and vice versa.

TIP
• In a single network configuration or in a separated configuration, there is no distinction between the
virtual IP address (VIP) and the physical IP address (PIP). IP addresses are simply treated as those
of the control side/standby side.
• The IP address of the standby side CPU when CPUs are duplexed in the FCN-500 and FCN-100 is,
as mentioned above, the value obtained by setting the most significant bit of the host address of the
control side IP address as 1. For the IP address of the control side CPU, therefore, use a host
address whose most significant bit is 0. For example, if a subnet mask is 255.255.255.0 and 1 to
126 (01 to 7E in the hexadecimal notation) is used for the host address of the control side CPU, the
host address of the standby side CPU becomes 129 to 254 (81 to FE in the hexadecimal notation).
• In a single network configuration or in a separated configuration, the standby side CPU’s IP
address decided according to the above rules can be changed via the Resource Configurator.

TI 34P02K25-01E Jun. 6, 2018-00


<2. Network Features of STARDOM> 65

Rules for Deciding the IP Address of a Duplexed CPU and a Duplexed


Network Configuration of FCN-500 and FCN-100 (FCN/FCJ: System
R1.85 or Later)
In a duplexed CPU and a duplexed network configuration of FCN-500 and FCN-100, the
PIP-A/B of control side/standby side CPUs are determined on the basis of the FCN’s
VIP according to the following rules:
[PIP-A of the control side CPU]
• Network address: a value obtained by adding 1 to the VIP’s network address
• Host address: the same value as the VIP’s host address
[PIP-B of the control side CPU]
• Network address: a value obtained by adding 2 to the VIP’s network address
• Host address: the same value as the VIP’s host address
[PIP-A of the standby side CPU]
• Network address: a value obtained by adding 1 to the VIP’s network address
• Host address: a value obtained by setting the most significant bit of the VIP’s host
address as 1
[PIP-B of the standby side CPU]
• Network address: a value obtained by adding 2 to the VIP’s network address
• Host address: a value obtained by setting the most significant bit of the VIP’s host
address as 1
As described above, host addresses of the PIP-A/B of the standby side CPU are the
values obtained by setting the most significant bit of the VIP’s host address as 1. If this
is applied to a VIP of 192.168.1.1 with a subnet mask of 255.255.255.0 (the host
address is 01 in the hexadecimal notation), the PIP-A/B host addresses of the standby
side CPU become 81 in the hexadecimal notation (10000001 in the binary notation) or
129 in the decimal notation.
If these rules are applied to a VIP of 192.168.0.1 with a subnet mask of 255.255.255.0,
PIP/A and PIP-B are decided as in the table below:
Table IP Addresses of Control/Standby side CPUs
IP Address of the Control side CPU IP Address of the Standby side CPU
(Hexadecimal) (Hexadecimal)
VIP 192.168.0.1 (C0A80001) < to be allocated to the control side CPU >
PIP-A 192.168.1.1 (C0A80101) 192.168.1.129 (C0A80181)
PIP-B 192.168.2.1 (C0A80201) 192.168.2.129 (C0A80281)

In this configuration, VIP, PIP-A and PIP-B allocations of two duplexed CPUs are
changed every time CPUs switch from the control side to the standby side.

TI 34P02K25-01E Jun. 6, 2018-00


<2. Network Features of STARDOM> 66

TIP
• In a duplexed network configuration, use class C private addresses of IPv4 and set a subnet mask
to 255.255.255.0.
• The IP address of the standby side CPU when CPUs are duplexed in FCN-500 and FCN-100 is, as
mentioned above, the value obtained by setting the most significant bit of the VIP’s host address as
1. For the VIP, therefore, use a host address whose most significant bit is 0. A VIP's host address
uses the value from 1 to 126 (01 to 7E in the hexadecimal notation), and a PIP-A/B's host address
of the standby side CPU becomes 129 to 254 (81 to FE in the hexadecimal notation).
• In a duplexed network configuration, PIP-A/B cannot be changed via the Resource Configurator.
Therefore, set the values to a VIP so that no contradictions will occur with PIP-A/B in the above-
mentioned rules.
• FCN/FCJ: For system R1.85 or later, PIP is calculated automatically by the control side
CPU/standby side CPU.
FCN/FCJ: For system R1.80 or earlier, PIP is calculated automatically by the position of the
implemented CPU (left side/right side).

Important
Rules for IP address allocation differ between the FCN/FCJ system R1.80 or earlier and
the system R1.85 or later. Accordingly, there is no communication compatibility between
the FCN/FCJ system R1.80 or earlier and the system R1.85 or later.
Therefore, if you use a FCN/FCJ system R1.85 or later, use the following versions.
• VDS/ASTMAC: R5.40.10 or later
• FCN/FCJ: R1.85.01 or later
• Duplexed network program for FCN/FCJ OPC server: R1.85.01 or later

SEE ALSO
For an example of IP address value, see "3.8 Duplexing Networks".

TI 34P02K25-01E Jun. 6, 2018-00


<2. Network Features of STARDOM> 67

Rules for Deciding the IP Address of a Duplexed CPU and a Duplexed


Network Configuration of an FCN-100 (FCN/FCJ: System R1.80 or
Earlier)
In a duplexed CPU and a duplexed network configuration of an FCN-100, the PIP-A/B of
left/right CPUs are determined on the basis of the FCN’s VIP regardless of the control
side/standby side according to the following rules:
[PIP-A of the left CPU]
• Network address: a value obtained by adding 1 to the VIP’s network address
• Host address: the same value as the VIP’s host address
[PIP-B of the left CPU]
• Network address: a value obtained by adding 2 to the VIP’s network address
• Host address: the same value as the VIP’s host address
[PIP-A of the right CPU]
• Network address: a value obtained by adding 1 to the VIP’s network address
• Host address: a value obtained by setting the most significant bit of the VIP’s host
address as 1
[PIP-B of the right CPU]
• Network address: a value obtained by adding 2 to the VIP’s network address
• Host address: a value obtained by setting the most significant bit of the VIP’s host
address as 1
As described above, host addresses of the PIP-A/B of the right CPU are the values
obtained by setting the most significant bit of the VIP’s host address as 1. If this is
applied to a VIP of 192.168.1.1 with a subnet mask of 255.255.255.0 (the host address
is 01 in the hexadecimal notation), the PIP-A/B host addresses of the right CPU become
81 in the hexadecimal notation (10000001 in the binary notation) or 129 in the decimal
notation.
If these rules are applied to a VIP of 192.168.0.1 with a subnet mask of 255.255.255.0,
PIP/A and PIP-B are decided as in the table below:
Table IP Addresses of Right/Left CPUs
IP Address of the Left CPU (Hexadecimal) IP Address of the Right CPU (Hexadecimal)
VIP 192.168.0.1 (C0A80001) < to be allocated to the control side CPU >
PIP-A 192.168.1.1 (C0A80101) 192.168.1.129 (C0A80281)
PIP-B 192.168.2.1 (C0A80201) 192.168.2.129 (C0A80381)

In this configuration, VIP allocations of two duplexed CPUs are changed every time
CPUs switch from the control side to the standby side and vice versa. However, PIP-A
and PIP-B are fixed for use without being changed.

TI 34P02K25-01E Jun. 6, 2018-00


<2. Network Features of STARDOM> 68

TIP
• In a duplexed network configuration, use class C private addresses of IPv4 and set a subnet mask
to 255.255.255.0.
• The IP address of the right CPU when CPUs are duplexed in an FCN-100 is, as mentioned above,
the value obtained by setting the most significant bit of the VIP’s host address as 1. For the VIP,
therefore, use a host address whose most significant bit is 0. A VIP's host address uses the value
from 1 to 126 (01 to 7E in the hexadecimal notation), and a PIP-A/B's host address of the right CPU
becomes 129 to 254 (81 to FE in the hexadecimal notation).
• In a duplexed network configuration, PIP-A/B cannot be changed via the Resource Configurator.
Therefore, set the values to a VIP so that no contradictions will occur with PIP-A/B in the above-
mentioned rules.
• FCN/FCJ: For system R1.85 or later, PIP is calculated automatically by the control side
CPU/standby side CPU.
FCN/FCJ: For system R1.80 or earlier, PIP is calculated automatically by the position of the
implemented CPU (left side/right side).

SEE ALSO
For an example of IP address value, see "3.8 Duplexing Networks".

TI 34P02K25-01E Jun. 6, 2018-00


<2. Network Features of STARDOM> 69

Various Topologies
For duplexed control networks, various network topologies can be employed. The
following subsections explain each topology briefly, and which to be employed through
comparing each feature.

Single LAN
HUB

HMI PLC A B A A B A B

FCN/FCJ Control Standby


VDS -side -side
Data Server
FCN/FCJ
Single Interface
Device Dual Interface Device

Figure Single LAN Configuration

In this configuration, the network path is not duplexed, which does not provide
alternative path on the occasion of network failure.

Dual LAN
HUB-A HUB-B

HMI PLC A B A B A B A B

FCN/FCJ Control Standby


VDS -side -side
Data Server
FCN/FCJ
Single Interface
Device Dual Interface Device

Figure Dual LAN Configuration

This is a network topology where network interfaces of nodes are duplexed and cables
and hubs connecting them each other are duplexed, as well as physically independent.
The highest fault tolerance is assured.
Connect single interface devices to HUB-A. The network is not duplexed on a single
interface device and used only with Network-A.

TI 34P02K25-01E Jun. 6, 2018-00


<2. Network Features of STARDOM> 70

Guide for Selecting an Optimum Network Topology


The following table lists features of network topologies, which may be helpful as a
measure for selecting the optimum topology.
Table Comparing Network Topologies
Single LAN Dual LAN
Reliability Low High (No common part )
Network load Low Low
Cost (Network devices) Low High
Wiring Simple Relatively complicated

Choose the optimum network topology according to the features of your application
(intended purpose, connecting devices, location, etc.).
For a standard network configuration that consists of FCN/FCJ and VDS, it is
recommended to employ dual LAN in the light of reliability and easy maintenance.

Internal Operations in the Duplexed Network Function


This section explains the internal operations in the duplexed network function of
STARDOM.

Network Status Table (NSTBL)


Network functions of FCN/FCJ or VDS connected to a control network manage statuses
of network interfaces (network statuses) of each node as a network interface status
table (NSTBL). For nodes with the duplexed network function, information of standby
side network interface is also managed. All VDSs and FCNs/FCJs have NSTBLs used
for algorisms of network failure, switching between network paths, network recovery, etc.
NSTBL contains the following information:
Table Example of Network Status Table
Device Network Path Information
VIP PIP-A PIP-B
Index Network-A Network-B
1 192.168.0.1 192.168.1.1 192.168.2.1 OK OK
2 192.168.0.2 192.168.1.2 192.168.2.2 OK OK
3 192.168.1.130 192.168.2.130 OK OK

TI 34P02K25-01E Jun. 6, 2018-00


<2. Network Features of STARDOM> 71

Diagnostic Communication Frame


Duplexed network function of FCN/FCJ or VDS connected to a control network performs
periodically multicast transport of network interface statuses as diagnostic
communication frames, for updating NSTBL. The diagnostic communication frames
store NSTBL managed by the node. A node that received diagnostic communication
frames of other node updates its NSTBL based on the information stored in that frame.
Diagnostic communication frames are transmitted by each dual interface individually.

The default diagnostic communication interval is 500ms. The two consecutive failures of
diagnostic communications are recognized as a failure, making switching time 1000 to
1500 ms when diagnostic communication interval is 500ms.
Diagnostic communication frames are sent in conjunction with the number of duplexed
devices (such as FCNs or VDSs) to a network and are received by the devices. These
devices process frames every time they are received: the greater the number of
duplexed devices, the greater the reception processing of diagnostic communication
frames, thereby increasing the load on CPUs. Therefore, if the number of duplexed
devices is substantial, the transmission cycle of diagnostic communication frames
should be extended.
The table below provides a guide for the number of devices and diagnostic cycles.
Table Guide for the Number of CPUs and the Diagnostic Cycles
Number of CPUs Diagnostic Cycle (msec) Remarks
Up to 12 500 Default value for diagnostic cycles
13 to 25 1,000
26 to 37 1,500
38 to 50 2,000
51 to 62 2,500
63 to 75 3,000
76 to 87 3,500
88 to 100 4,000
101 to 112 4,500
113 to 125 5,000
126 to 137 5,500
138 to 150 6,000
151 to 162 6,500
163 to 175 7,000
176 to 187 7,500
188 to 200 8,000
201 to 212 8,500
213 to 225 9,000
226 to 237 9,500
238 to 248 10,000

Note: The number of CPUs is the total number of FCNs/FCJs/VDSs in a network which uses the network duplex function (if
CPUs of an FCN are duplexed, the number of CPUs is 2).

TI 34P02K25-01E Jun. 6, 2018-00


<2. Network Features of STARDOM> 72

SEE ALSO
For the communication load of diagnostic communication frames, see "2.3 Communication
Performances".

Network Failure
A network failure is the status where one of dual network paths is unavailable. The
network failure is managed per node. If diagnostic communication frames cannot be
received from a node, the network path to the node is recognized to be failed, which is
notified to the operator as a message. The cause of failures can be as follows: failure of
network interface of own node, failure of network interface of the destination node,
failure of network devices (hubs and cables) on the network path between the two
nodes, communication jamming due to the temporary noises, etc.

Switching between Network Paths


If a network failure to a node is detected, Routing Table is automatically changed,
switching immediately over another of dual network paths.

Network Recovery
The node that detects a network failure continues to monitor the failed network. If the
recovery is detected, the message notifying the network recovery is sent to the operator.

Supporting Duplexed CPU of FCN-500 and FCN-100


When a control side CPU (controlling the system) of FCN-500 and FCN-100 fails, the
control right is moved to a standby side CPU (: this side always equalizes with the
control side and in waiting status to receive the control right in the case that the control
side fails). The equalization between the control side and standby side is performed via
the control network. The CPU that newly acquires the control right continues to
communicate, by succeeding the network information (virtual IP addresses, host names,
etc.) of the CPU that previously had the control.
Other nodes that had been communicated with FCN-500 and FCN-100 whose CPU was
switched, detect the switching between network paths, switching over another path
automatically. Communication of the control network will stop for 1 to 3 seconds. This
function ensures operations for applications of the nodes that had been communicated
with the FCN-500 and FCN-100.

Host Name and IP Address


A host name and IP address (VIP) with duplexed CPU is consistent and can be
recognized as a single device for applications of a client (e.g. VDS). When the switching
takes place between CPUs in FCN-500 and FCN-100, the VIP is also moved to the CPU
that takes control immediately.

Standby Side CPU Network Interface Status


The network interface statuses of the standby side CPU are always checked and the
results are reflected to NSTBL.

TI 34P02K25-01E Jun. 6, 2018-00


<2. Network Features of STARDOM> 73

2.6.2 Duplexing Communications Using an Application


It is possible to duplex communications between FCN/FCJ and other devices such as
PLCs using an application program.
However, it is not possible to duplex communications between VDS and other devices.

The following devices can be connected by duplexing communications using an


application.
• PLC (FA-M3R, MELSEC)
• M-system remote I/O
• FCN/FCJ in another segment, etc.

VDS

Control Network1 (System-A)

Control Network2 (System-B)

It is possible to duplex
FCJ FCN communications between
FCN/FCJ and PLC.

Figure Example of Connecting PLC to FCN/FCJ in Duplexed Network Configuration

VDS

Control Network1 (System-A)

Control Network2 (System-B) M-System Remote I/O


(Modbus/TCP
Connection)
Connection)

FCJ FCN
It is possible to duplex communications
between FCN/FCJ and remote I/O.

Figure Example of Connecting Remote I/O to FCN/FCJ in Duplexed Network Configuration

TI 34P02K25-01E Jun. 6, 2018-00


<2. Network Features of STARDOM> 74

VDS
FCJ

Control Network1 (System-A) Router


Wide Router
area
Router network Router
Control Network2 (System-B)

FCJ FCN It is possible to duplex communications FCN


between FCN/FCJ and FCN/FCJ.

Figure Example of Connecting FCN/FCJ and FCN/FCJ Remotely via Routers

Application Program
To duplex communications with other devices such as PLCs or to duplex
communications between segments via routers, a communications application is
required.
When using an application, implement the following logics on each communication port
in the communication FB.

Logics embedded in application


1. Detection of communication failure
2. Switch of communication paths

1. Failure detection

2. Switch of communication paths

FCN/FCJ
FA-M3
System-A communications
(PORT1:192.168.0.1)
192.168.0.50 FA-M3 comm. FB A:192.168.0.50

System-B communications
(PORT2:192.168.2.1)
192.168.2.50 FA-M3 comm. FB B:192.168.2.50

Figure Logics Embedded in Application (Example of Communications with FA-M3)

TI 34P02K25-01E Jun. 6, 2018-00


<2. Network Features of STARDOM> 75

“Duplexing” Setting and “Separated” Setting


When duplexing communications of FCN/FCJ using an application, the network can be
configured in the following two ways.

• Duplexed network configuration


• Separated network configuration

For STARDOM, it is recommended to use the “duplexed network function provided on


STARDOM” and “duplexed network configuration” that allows for “duplexing
communications using an application.”

SEE ALSO
For the “duplexed network configuration” and “separated network configuration,” see “Duplexed
Network Configuration” and “Separated Network Configuration” sections in “2.2 Network Basic
Definitions (IP Address Settings).”

TI 34P02K25-01E Jun. 6, 2018-00


<2. Network Features of STARDOM> 76

2.7 Cautions for Network Configuration


Connecting other devices on to network
The communication loads between FCN/FCJ and other devices such as PLC, field
devices, PC may influence the control function shown in the following table.
Table Influences on FCN/FCJ Communication Protocol
Protocol Method Effects on FCN/FCJ
Unicast Communications to one Communications to any devices other than FCN/FCJ never
specific node adversely affect FCN/FCJ.
Multicast Communications to one
specific group of nodes
Broadcast Communications to all As communication processing has high priority, all types of
nodes in the network communication frames, including irrelevant ones, are received by
the FCN/FCJ. When broadcast communication loads are too high,
the control processing of the FCN/FCJ is influenced (for example,
processing delay can occur).

The broadcast communications increase the communication loads, so that connecting


FCN/FCJ to the network with broadcast communications should be avoided.
If the connections are required, separate broadcast domain via router or VLAN shown in
the following documentation.

SEE ALSO
For the use of routers, refer to the following:
1. “Figure Example of a Single Network Configuration” and “Figure Example of a Separated Network
Configuration” in “2.2 Network Basic Definitions (IP Address Settings)”
2. “3.6 Connecting Routers to Control Networks”

CAUTION
1. The broadcast communications are also used as ARP (Address Resolution
Protocol). If a number of devices using ARP are connected to the network, the
massive broadcast communications may occur.
2. Even if under not frequent broadcast communication environment, the massive
broadcast communication might occur due to the abnormal condition of devices.
Therefore the switching HUBs with the broadband suppression function are
recommended to be installed.

TI 34P02K25-01E Jun. 6, 2018-00


<2. Network Features of STARDOM> 77

2.8 The communication port number to use of


FCN/FCJ
Information about the communication port number to use of FCN/FCJ is shown below. If
you want to connect of network FCN/FCJ and other equipment, please do not use the
port number duplication.
Table The communication port number to use of FCN/FCJ recieves
port number Protocol Remarks
20~21 TCP FTP
23 TCP Telnet
80 TCP HTTP
123 UDP SNTP
502 TCP Modbus/TCP server
1024~1089 TCP Reserved by the system
1024~1089 UDP Reserved by the system
1090 TCP HSE Communication
1090 UDP HSE Communication
1091 TCP Reserved by the system
1091 UDP Reserved by the system
1092 TCP Reserved by the system
1092 UDP Duplexed networks
1093~5000 TCP Reserved by the system
1093~5000 UDP Reserved by the system
10037 TCP Resource Configurator
19999 TCP DNP3 secure communication
20000 TCP DNP3 TCP server
20001~20015 TCP Communication between the FCN/FCJ controllers
When generating input variables of “CONNECT POU” by use the
SD_CFCX_CONNECT_EX POU in sample library (SD_CFCX_PF).
20050 TCP DNP3 TCP server
20547 TCP Logic Designer
34101 TCP JEROS
34170~34172 TCP Webmetry
34308 TCP Duplexed networks

TI 34P02K25-01E Jun. 6, 2018-00


Blank Page
<3. Examples of Network Configurations> 79

3. Examples of Network Configurations


Devices and functions provided by STARDOM are highly independent, enabling to
construct various systems in combination with other open devices. This chapter
explains needed information for constructing a system and examples of network
configuration.

3.1 Small Two-layered System (Standard)


HUB

Control System Information Network

HMI 1 HMI
1 2
VDS
Data Server

HUB

Control Network

1 2 1 2

FCN FCJ

I/O I/O I/O I/O

Figure Example of Small Two-layered System

TI 34P02K25-01E May 31, 2017-00


<3. Examples of Network Configurations> 80
Connection
Implement a network adapter on VDS, connect FCN/FCJ and HMI on the same control
network. Use port 1 for network interface of FCN/FCJ.
Table Example of IP Address Setting in Small Two-layered System
Network
Nodes IP Addresses Settings Remarks
interfaces
Control network
FCN 1 192.168.0.1 Resource Configurator
Single network setting

Control network
FCJ 1 192.168.0.2 Resource Configurator
Single network setting

1 172.16.1.1 Windows setting Control system information network


VDS data server
2 192.168.0.101 Windows setting Control network
HMI1 172.16.1.21 Windows setting Control system information network
HMI2 172.16.1.22 Windows setting Control system information network

SEE ALSO
For the restrictions on connecting devices, see "2.1 Varieties of Basic Configurations".

TI 34P02K25-01E May 31, 2017-00


<3. Examples of Network Configurations> 81

3.2 Small One-layered System


HUB

Control Network

HMI HMI 1 1 2 1 2
1 2
VDS FCN FCJ
Data Server

I/O I/O I/O I/O

Figure Example of small One-layered System

Connection
Implement a network adapter on VDS, connect FCN/FCJ and HMI on the same control
network. Use port 1 for network interface of FCN/FCJ.
Table Example of IP Address Configuration in Small One-layered System
Network
Nodes IP Addresses Settings Remarks
interfaces
FCN 1 192.168.0.1 Resource Configurator Single network setting
FCJ 1 192.168.0.2 Resource Configurator Single network setting
VDS data server 1 192.168.0.101 Windows setting
HMI1 192.168.0.121 Windows setting
HMI2 192.168.0.122 Windows setting

SEE ALSO
For the restrictions on connecting devices, see "2.1 Varieties of Basic Configurations".

TI 34P02K25-01E May 31, 2017-00


<3. Examples of Network Configurations> 82

3.3 Medium Scale Two-layered System


HUB

Control System Information Network

HMI HMI 1 1
1 2
VDS VDS
Data Server 1 Data Server 2

2 2

HUB HUB

Control Network

1 2 1 2 1 2 1 2

FCN 1 FCJ 1 FCN 2 FCJ 2

I/O I/O I/O I/O I/O I/O I/O I/O

Figure Example of Medium Scale Two-layered System

TI 34P02K25-01E May 31, 2017-00


<3. Examples of Network Configurations> 83
Connection
Implement two network adapters per VDS, one for control network connecting FCN/FCJ,
the other for control system information network connecting HMI or upper computers.
One of VDSs is used as an HMI server. Use port 1 for network interface of FCN/FCJ.
Table Example of IP Address Setting in Medium Scale Two-layered System
Network
Nodes IP Addresses Settings Remarks
interfaces
Control network
FCN1 1 192.168.0.1 Resource Configurator
Single network setting

Control network
FCJ1 1 192.168.0.2 Resource Configurator
Single network setting

VDS data 1 172.16.1.1 Windows setting Control system information network


server1 2 192.168.0.101 Windows setting Control network
Control network
FCN2 1 192.168.20.1 Resource Configurator
Single network setting
Control network
FCJ2 1 192.168.20.2 Resource Configurator
Single network setting

VDS data 1 172.16.1.2 Windows setting Control system information network


server2 2 192.168.20.101 Windows setting Control network
HMI1 172.16.1.21 Windows setting Control system information network
HMI2 172.16.1.22 Windows setting Control system information network

SEE ALSO
For the restrictions on connecting devices, see "2.1 Varieties of Basic Configurations".

TI 34P02K25-01E May 31, 2017-00


<3. Examples of Network Configurations> 84

3.4 Installing Controllers in a Field as


Standalone
An autonomous controller FCN/FCJ can be installed on the devices of the field as
a standalone controller. VDS is not needed for this type of configuration.
Resource Configurator
Web Browser

Modem Ethernet
Cross Cable
RS232C
Cable

WAN Serial Port 1 2

FCN/FCJ

I/O I/O

Figure Example of Standalone Installation

Configuration and Maintenance


When you perform configurations, maintenances or checks of devices, connect a PC on
which Resource Configurator and Web browser are implemented, to the interface1 of
FCN/FCJ (see the figure above).
Using Ethernet cross cable, the wiring without network devices (e.g. hubs) are obtained.
However, you can use hubs and straight cables as usual.

Remote Connection
Connecting a modem to a serial port of FCN/FCJ enables connections to a WAN. You
can create an application for accessing and monitoring information acquired by
FCN/FCJ once a day.

SEE ALSO
For remote connections, see "3.13 Monitoring and Maintaining FCN/FCJ Remotely".

TI 34P02K25-01E May 31, 2017-00


<3. Examples of Network Configurations> 85

When Duplexing CPU


When CPU is duplexed on FCN, the equalization from the control side to the standby
side is performed via the control network. Therefore, even when the FCN is installed as
a standalone controller, it is necessary to connect the control side and the standby side
over the network in the case that the CPU is duplexed. Use a cross cable to connect
network interface2 or use a straight cable and a hub to connect network interface1.
Resource Configurator
Resource Configurator
Web Browser
Web Browser
Ethernet
Cross Cable Ethernet
Ethernet Straight Cable
Cross Cable HUB

1 2 1 2 1 2 1 2
Control Standby Control Standby
-side -side -side -side

FCN FCN

Figure Standalone Installation with duplexed CPU

TI 34P02K25-01E May 31, 2017-00


<3. Examples of Network Configurations> 86

3.5 Connecting Simple HMI to Standalone


Controller in a Field
This section explains the configuration for monitoring control operations by
connecting simple HMI with FCN/FCJ installed in the field.

Using VDS as HMI

HMI (VDS Viewer) Ethernet


Resource Configurator Straight Cable

Hub Connecting to
Ethernet Upper Device
Cross Cable

1 2

FCN/FCJ

I/O I/O

Figure Connecting VDS as HMI to an FCN/FCJ

As HMI, use a PC on which VDS Data/HMI Server functions, VDS Viewer, Resource
Configurator and Logic Designer are installed. For wiring, use Ethernet cross cables to
connect to the network interface1 of FCN/FCJ. There is no problem if you use hubs and
straight cables.
If you connect the network to upper devices, connect from HMI to upper computers.
Configure router functions to HMI if you want to communicate from the upper devices to
FCN/FCJ directly.

TI 34P02K25-01E May 31, 2017-00


<3. Examples of Network Configurations> 87

Using Webmetry Functions of FCN/FCJ


HMI (Web browser)
Resource Configurator

Ethernet
Cross Cable

1 2

FCN/FCJ

I/O I/O

Figure Connecting a Web Browser Implemented PC to a single FCN/FCJ as HMI

By using the InfoWell’s Web application portfolios or Webmetry functions of FCN/FCJ,


you can easily construct an operation and monitoring applications with only Web
browsers. In the figure above, a Windows PC on which a Web browser is implemented
is also used as FCN/FCJ configuration PC. For wiring, use Ethernet cross cables to
connect to the network interface1 of FCN/FCJ. There is no problem if you use hubs and
straight cables.

SEE ALSO
For the InfoWell and Webmetry functions, see "2.5 Network Functions of FCN/FCJ".

TI 34P02K25-01E May 31, 2017-00


<3. Examples of Network Configurations> 88

Connecting Programmable Displays to Serial Port


Programmable Web Browser
Displays Resource Configurator

RS232C Ethernet
Cable Cross Cable

Serial Port 1 2

FCN/FCJ

I/O I/O

Figure Connecting Programmable Displays to FCN/FCJ

Using FA-M3 emulation features of FCN/FCJ, you can connect GP series programmable
displays of Digital Electronics Co. via RS-232C port.

For wiring to programmable displays, use serial communication cables connecting to


COM port of FCN/FCJ.
For configurations of FCN/FCJ, connect a PC on which Web browsers and Resource
Configurator are installed, to the network interface1 of FCN/FCJ via Ethernet cross
cables. There is no problem if you use hubs and straight cables.

TI 34P02K25-01E May 31, 2017-00


<3. Examples of Network Configurations> 89

3.6 Connecting Routers to Control Networks


To connect control network devices directly to upper devices like the ones on
control system information network, you need to install routers between the
networks for routing of communication frames.
There are two ways for routing: routing communication frames using a PC on
which VDS data server is mounted, and installing exclusive router devices.
HUB

Control Network

HMI Router 1 2 1 1 2

FCJ VDS FCN


Data Server

2
HUB

HUB
HMI
Control System Information Network

HMI HMI

Figure Connecting Routers to Control Network

Security
The control network is highly secure network requiring real-time operations and
reliability; you need to be careful when you perform routing functions between the
control network and other networks. Take count of securities or loads of control
networks, introducing filtering of unneeded accesses or firewalls.

TI 34P02K25-01E May 31, 2017-00


<3. Examples of Network Configurations> 90

Configuration of Routing Information


You need to perform default gateway settings to the devices connected to control
networks that communicate to upper networks.

SEE ALSO
For the configuration of default gateway, see "2.2 Network Basic Definitions (IP Address Settings)".

You need to add routing information besides default gateway settings when connecting
two or more routers to a control network and configuring routers to switch according to
the target device. In this case, don't change the routing information dynamically from
external equipment and specify routing information statically as in the example of this
chapter.

How to Configure FCN/FCJ


1. Click the link of [Edit] in "System File Setting" from the maintenance menu. Select
"IP Routing File" on the system configuration file window and click [OK].

2. On the IP routing file edit window, add the routing information in the following
format.
net <destination> :Subnet mask gateway <gateway>
host <destination> gateway <gateway>
"net" is the keyword that indicates the <destination> is a network; "host" is the
keyword that indicates the <destination> is a host. Specify names or IP addresses
for <destination> and <gateway>. If a subnet mask is omitted, the subnet mask for
the destination IP address class is used.
e.g.
net 172.20.3.0 :ffff0000 gateway vds01
net 192.168.9.0 gateway 192.168.0.252
host hmi10 gateway 192.168.0.252

How to Configure VDS


Add routing information using the ROUTE command on the DOS command window.
e.g.
ROUTE -P ADD 192.168.99.0 MASK 255.255.255.0.192.168.6.10

TI 34P02K25-01E May 31, 2017-00


<3. Examples of Network Configurations> 91

3.7 Connecting Several Control Networks to VDS


When connecting devices other than FCN/FCJ (e.g. PLC), you may well connect to
another network, separating physically from the network connecting to FCN/FCJ.
Thereby communications with devices other than FCN/FCJ using exclusive
protocols (e.g. MELSEC-NET, FL-NET) can be guarded from external perturbations
arise from the communications to FCN/FCJ.
HUB HUB

Control Network2
Control Network1

PLC PLC 3 2 1 2 1 2
1 2
VDS FCN FCJ
Data Server

HUB

Control System Information Network

HMI HMI
1 2

Figure Connecting Several Control Network to VDS

In the example above, three network adapters are installed on a VDS; connecting
network interface1 to control network1; interface2 to control network2; interface3 to
control network3.
Table Example of IP Address Setting when Connecting Several Control Networks to VDS
Network
Nodes IP Addresses Settings Remarks
interfaces
Control network1
FCN 1 192.168.0.1 Resource Configurator
Single network setting
Control network1
FCJ 1 192.168.0.2 Resource Configurator
Single network setting

1 172.16.1.1 Windows setting Control system information network


VDS data server 2 192.168.0.101 Windows setting Control network1
3 192.168.20.101 Windows setting Control network2
Setting Defined by the
PLC1 192.168.20.1 Control network2
PLC
Setting Defined by the
PLC2 192.168.20.2 Control network2
PLC
HMI1 172.16.1.21 Windows setting Control system information network
HMI2 172.16.1.22 Windows setting Control system information network

TI 34P02K25-01E May 31, 2017-00


<3. Examples of Network Configurations> 92

3.8 Duplexing Networks


For control networks, it is possible to duplex network interfaces, cables and hubs
using the duplexed network function of STARDOM. This section explains a typical
example of duplexed network system attained through the duplexed network
function of STARDOM.
HUB-A

HUB-A HUB-A

1 1 1 1 1 FCN 1 Configu- HMI


PLC
FCJ FCN VDS FCJ Control Standby ration Client
2 2 2 2 2 -side -side 2 PC

HUB-B HUB-B

HUB-B

Figure Example of Duplexed Network Configuration

Installation of Devices and Wirings


Install hubs for Networks-A and Networks-B separately. Connect a single interface
device to HUBs-A.

SEE ALSO
For the features of network topologies, see "2.6 Duplexing Control Network".

Connecting FCN/FCJ
Connect interface1 to HUB-A, interface2 to HUB-B. For the FCN with a duplexed CPU,
install wirings for both control side CPU and standby side CPU.

TI 34P02K25-01E May 31, 2017-00


<3. Examples of Network Configurations> 93

IP Address Setting to FCN/FCJ


Configure VIP to IP addresses using Resource Configurator.

SEE ALSO
For IP address settings to FCN/FCJ, see "2.2 Network Basic Definitions (IP Address Settings)".

For your reference, the examples of IP addresses configured to each network interface
of the FCN with duplexed CPU are indicated as follows:

[Control side] Interface A:


IP address = 192.168.0.1, Subnet mask = 255.255.255.0 (VIP)
IP address = 192.168.1.1, Subnet mask = 255.255.255.0 (PIP-A)
Interface B:
IP address = 192.168.2.1, Subnet mask = 255.255.255.0 (PIP-B)

[Standby side] Interface A:


IP address = 192.168.1.129, Subnet mask = 255.255.255.0 (PIP-A)
Interface B:
IP address = 192.168.2.129, Subnet mask = 255.255.255.0 (PIP-B)

Parameter Settings of FCN/FCJ


Set the “Network” of “CPU Module” – “General” of the Resource Configurator to
“Duplex.”

TI 34P02K25-01E May 31, 2017-00


<3. Examples of Network Configurations> 94

Connecting VDS
Install two network interface cards, each of which connects to HUB-A and HUB-B.

IP Address Configuration to VDS


Configure VIP, PIP-A and PIP-B on Windows network configurations. Configure VIP and
PIP-A to the network interface card connecting to HUB-A; configure PIP-B to the
network interface card connecting to HUB-B.

SEE ALSO
For IP address settings to VDS, see "D2.3 IP Address Setting Procedure to VDS" in "FCN/FCJ Guide"
(IM 34P02Q01-01E).

Parameter Settings of VDS


Configure VIP using "FCN/FCJ Connection Setting Tool" of VDS. Start the tool and type
VIP to "Virtual IP Address" in the "General" tab.

Connection and Configuration of Single Interface Device


Be sure to connect a single interface device to HUB-A. If Network-A fails, the
communication also fails because the communications are performed via Networks-A.
Configure VIP for an IP address. For the sequence of configuration, see the manual of
each device.

TI 34P02K25-01E May 31, 2017-00


<3. Examples of Network Configurations> 95

3.9 Connecting Devices (e.g.PLCs) Other than


FCN/FCJ to VDS
You can connect devices (e.g.PLCs) other than FCN/FCJ to VDS data server.

Basic (Single) Configuration


You can connect devices other than FCN/FCJ including PLCs on the same network to
which FCN/FCJ is connected. The following example shows a typical configuration and
IP address settings.
HUB

Control Network

HMI PLC 1 2 1 1 2 1 2

FCJ VDS Control Standby


Data Server -side -side
FCN
2

HUB

Control System Information Network

HMI HMI HMI

Figure Connecting Devices Other than FCN/FCJ to Control Network

Use port 1 as network interface of FCN/FCJ.


Table Example of IP Address Setting when Connecting VDS and PLC (Single Configuration)
Network
Nodes IP Addresses Settings Remarks
interfaces
FCN 1 192.168.0.1 Resource Configurator Single network setting
FCJ 1 192.168.0.2 Resource Configurator Single network setting
Setting Defined by the
PLC 192.168.0.3
PLC
Control system information network
VDS data server 1 192.168.0.101 Windows setting
(port2) requires individual setting
HMI 192.168.0.121 Windows setting

SEE ALSO
For the restrictions on the number of connecting devices, see "2.1 Varieties of Basic Configurations".

TI 34P02K25-01E May 31, 2017-00


<3. Examples of Network Configurations> 96

When Control Network is Duplexed


You can connect devices other than FCN/FCJ to a duplexed control network connecting
FCN/FCJ. The following figure shows a typical example of configuration and IP address
settings.
HUB-A HUB-B

Control Network

HMI PLC 1 2 1 2 1 2 1 2

FCJ VDS Control Standby


Data Server -side -side
FCN
3

HUB

Control System Information Network

HMI HMI HMI

Figure Connecting Devices Other than FCN/FCJ to Duplexed Control Network

Connect PLCs to Network-A of the control network.


Table Example of IP Address Setting When Connecting VDS and PLC (Duplexed Configuration)
Network
Nodes IP Addresses Settings Remarks
interfaces
Configure only VIP. PIP is automatically set.
FCN 1/2 192.168.0.1 Resource Configurator
Duplexed network setting
Configure only VIP. PIP is automatically set.
FCJ 1/2 192.168.0.2 Resource Configurator
Duplexed network setting

Setting Defined by the Configure the same network address as VIP


PLC 192.168.0.3
PLC set to FCN/FCJ or VDS.
192.168.0.101(VIP) Configure VIP and PIP-A to network interface1;
1 Windows setting
192.168.1.101(PIP-A) PIP-B to network interface2. Control system
VDS data server
information network side (port3) requires
2 192.168.2.101(PIP-B) Windows setting exclusive IP address.

Configure the same network address as VIP


HMI 192.168.0.121 Windows setting
set to FCN/FCJ or VDS.

TI 34P02K25-01E May 31, 2017-00


<3. Examples of Network Configurations> 97

3.10 Connecting PLC to FCN/FCJ


FCN/FCJ can communicate to devices like PLCs, other than FCN/FCJ or VDS, via
control networks. However, the network must be configured to avoid having
influences on FCN/FCJ control by communication load lead from other devices.

SEE ALSO
Refer to “2.7 Cautions for Network Configuration” when connecting devices other than VDS and
FCN/FCJ devices to the network.

Network Connection between FCN/FCJ and Other Devices Such as PLCs


The following table shows the network connection configurations of FCN/FCJ and
devices such as PLCs.
The following pages explain each of the connection configurations.
Table Connection Configurations between FCN/FCJ and Other Devices Such as PLCs
Connection Configurations with Devices
other than FCN/FCJ (e.g. PLC)
FCN/FCJ Single configuration Single connection
network Duplexed control network Single connection or duplexing using AP (*1)
connection configuration
configuration
Separated network Single connection or duplexing using AP (*1)
configuration

*1 Duplexing using AP allows for duplexing network communications using an application program.

SEE ALSO
For duplexing using an AP, see “2.6.2 Duplexing Communications Using an Application.”

TI 34P02K25-01E May 31, 2017-00


<3. Examples of Network Configurations> 98

Basic (Single) Configuration


You can connect devices (e.g.PLCs) other than FCN/FCJ to the same control network to
which FCN/FCJ is connected. The following figure shows a typical example of
configuration and IP address settings.
HUB

Control Network

HMI PLC 1 2 1 2 1 2 1 2

FCJ VDS Control Standby


Data Server -side -side
FCN
3

HUB

Control System Information Network

HMI HMI HMI

Figure Connecting PLC to FCN/FCJ

Use port1 for the network interface of FCN/FCJ.


Use function block for PLC connections as control application of FCN/FCJ.
Table Example of IP Address when Connecting FCN/FCJ to PLC (Single Configuration)
Network
Nodes IP Addresses Settings Remarks
interfaces
FCN 1 192.168.0.1 Resource Configurator Single network setting
FCJ 1 192.168.0.2 Resource Configurator Single network setting
Setting Defined by the
PLC 192.168.0.3
PLC
Control system information
VDS data server 1 192.168.0.101 Windows setting network side (Network interfacet2)
requires exclusive IP address
HMI 192.168.0.121 Windows setting

SEE ALSO
For the restrictions on the number of connecting devices, see "2.1 Varieties of Basic Configurations".

TI 34P02K25-01E May 31, 2017-00


<3. Examples of Network Configurations> 99

When Control Network is Duplexed


When Connecting Devices Such as PLCs in a Single Connection
The following example explains the configuration when single connecting devices other
than FCN/FCJ to a duplexed control network connecting to FCN/FCJ.
HUB-A HUB-B

Control Network

HMI PLC 1 2 1 2 1 2 1 2

FCJ VDS Control Standby


Data Server -side -side
FCN
3

HUB

Control System Information Network

HMI HMI HMI

Figure Example of Connecting PLC to FCN/FCJ in a Single Connection in a Networked


Configuration

Connect PLCs to Network-A of a control network. Use function block for PLC
connections as the control application of FCN/FCJ.
Table Example of IP Address Setting When Connecting FCN/FCJ and PLC (Duplexed
Configuration)
Network
Nodes IP Addresses Settings Remarks
interfaces
Configure only VIP. PIP is automatically set.
FCN 1/2 192.168.0.1 Resource Configurator
Duplexed network setting
Configure only VIP. PIP is automatically set.
FCJ 1/2 192.168.0.2 Resource Configurator
Duplexed network setting
Setting Defined by the Configure the same network address as VIP set
PLC 192.168.0.3
PLC to FCN/FCJ or VDS.
192.168.0.101(VIP) Configure VIP and PIP-A to network interface1;
1 Windows setting
VDS data 192.168.1.101(PIP-A) PIP-B to network interface2. Control system
server information network side (port3) requires
2 192.168.2.101(PIP-B) Windows setting exclusive IP address.
Configure the same network address as VIP set
HMI 192.168.0.121 Windows setting
to FCN/FCJ or VDS.

SEE ALSO
For the restrictions on the number of connecting devices, see "2.1 Varieties of Basic Configurations".

TI 34P02K25-01E May 31, 2017-00


<3. Examples of Network Configurations> 100

When Connecting Devices Such as PLCs for Duplexed Communications


The following figure shows an example of duplexing a control network connecting
FCN/FCJ and connecting other devices to that network for duplexed communications.

VDS

A B

HUB-A HUB-B

A B A B
A B A B
Control-Side CPU Standby-Side CPU

PLC FCJ FCN


Note: It is not possible to duplex communications between VDS and PLCs.

Figure Example of Duplexing Network and Connecting PLCs to FCN/FCJ for Duplexed
Communications

Use function block for PLC connections as the control application of FCN/FCJ.
PLC's IP address of A should be set the same network address as one of the VIP. That's
because the VIP is set in the source IP address.

Table Example of IP Address Setting When Connecting FCN/FCJ and PLC (Duplexed
Configuration)
Network
Nodes IP Addresses Settings Remarks
interfaces
FCN 1/2 192.168.0.1 Resource Configure only VIP. PIP is automatically set.
Configurator Duplexed network setting
FCJ 1/2 192.168.0.2 Resource Configure only VIP. PIP is automatically set.
Configurator Duplexed network setting
PLC 1 192.168.0.3 Setting Defined by Configure the same network address as VIP set to
the PLC FCN/FCJ or VDS.
2 192.168.2.3 Configure PIP-B to network interface2.
1 192.168.0.101 (VIP) Configure VIP and PIP-A to network interface1;
VDS Windows setting
192.168.1.101 (PIP-A) PIP-B to network interface2. Control system
data
2 192.168.2.101 (PIP-B) Windows setting information network side (port3) requires exclusive
server
IP address.
HMI 192.168.0.121 Configure the same network address as VIP set to
Windows setting
FCN/FCJ or VDS.

SEE ALSO
For restrictions on the number of connecting devices, see "2.1 Varieties of Basic Configurations".

TI 34P02K25-01E May 31, 2017-00


<3. Examples of Network Configurations> 101

Separated Network Configuration


When Connecting Other Devices Such as PLCs in a Single Connection
The figure below shows a configuration example in which network interface 1 of the
FCN/FCJ is connected to a control network (for communications with the VDS), while
network interface 2 is connected to a PLC-dedicated network (for communications with
the PLCs).
VDS VDS
HMI HMI

Control System
Information Network

2
VDS Data Server
1
Control Network

1 1
FCN FCJ
2
PLC-dedicated Network

PLC1 PLC2

Figure Example of a Separated Network with PLCs Connected to the FCN/FCJ

Table Examples of IP Addresses for Connection between the FCN/FCJ and the PLCs (Separated
Network Configuration)
Network
Nodes IP Addresses Settings Remarks
interfaces
FCN 1 192.168.0.1 Resource Configurator Single network setting
Separated network setting (network interface 1
1 192.168.0.2 Resource Configurator
address)
FCJ
Separated network setting (network interface 2
2 192.168.20.3 Resource Configurator
address)
Setting Defined by the
PLC1 192.168.20.1
PLC Specify the same network address as the address
Setting Defined by the of FCJ’s network interface 2.
PLC2 192.168.20.2
PLC
1 192.168.0.101 Windows setting For control networks
VDS data server
2 172.16.1.1 Windows setting For control system information networks
Specify the same network address as the control
HMI 172.16.1.21 Windows setting system information network side (network interface
2) of the VDS.

SEE ALSO
For restrictions on the number of connecting devices, see "2.1 Varieties of Basic Configurations".

TI 34P02K25-01E May 31, 2017-00


<3. Examples of Network Configurations> 102

When Connecting Other Devices such as PLCs for Duplexed


Communications
The following figure shows a configuration example of FCN/FCJ and PLCs using the
control networks 1 and 2 for duplexed communications with the control network 1
connecting VDSs.

VDS VDS
HMI 1 HMI 2
LAN LAN

Control System
Information Network
2

VDS Data Server


1
Control Network 1

1 1 1 1 1
Control Standby
FCJ Side
CPU
FCN Side
CPU
PLC1 PLC1
2 2 2 2 2

Control Network 2
Figure Example of Connecting PLC (duplexed communications) to FCN/FCJ in a Separated
Network Configuration

Table Examples of IP Addresses when Connecting FCN/FCJ and PLC (Duplexed


Communication) in a Separated Network Configuration
Network
Nodes IP Addresses Settings Remarks
interfaces
FCJ 1 192.168.0.2 Resource Separated network setting (network interface 1 address)
2 192.168.20.2 Configurator Separated network setting (network interface 2 address)
FCN 1 192.168.0.3 Separated network setting (network interface 1 address)
(Control 2 192.168.20.3 Separated network setting (network interface 2 address)
Side CPU) Resource
FCN 1 192.168.0.131 Configurator Separated network setting (network interface 1 address)
(Standby 2 192.168.20.131 Separated network setting (network interface 2 address)
Side CPU)
PLC1 1 192.168.0.5 Setting Defined by Separated network setting (network interface 1 address)
2 192.168.20.5 the PLC Separated network setting (network interface 2 address)
PLC2 1 192.168.0.6 Setting Defined by Separated network setting (network interface 1 address)
2 192.168.20.6 the PLC Separated network setting (network interface 2 address)
VDS data 1 192.168.0.101 Windows setting For control networks
server 2 172.16.1.1 Windows setting For control system information networks
HMI 1 172.16.1.21 Specify the same network address as the control system
Windows setting
information network side (network interface 2) of the VDS.
HMI 2 172.16.1.22 Specify the same network address as the control system
Windows setting
information network side (network interface 2) of the VDS.

SEE ALSO
For restrictions on the number of connecting devices, see "2.1 Varieties of Basic Configurations".

TI 34P02K25-01E May 31, 2017-00


<3. Examples of Network Configurations> 103

3.11 Duplexing Communications between


FCN/FCJ and FCN/FCJ in Different
Segments
The following explains a typical configuration example of duplexing
communications between FCN/FCJ and FCN/FCJ located in different segments via
routers.

Important
To duplex communications between FCN/FCJ and FCN/FCJ located in different
segments, an application program is required to switch communication paths.
For the communication switching application program, place two CONNECT function
blocks that specify IP addresses for network A and B, for each connection destination. It
requires two channels with one connected device.
The maximum number of channels for FCN/FCJ communication prepared for each
FCN/FCJ is 15. When using communication switching application program, pay attention
to the number of channels.

SEE ALSO
For applications to switch communication paths, see “2.6.2 Duplexing Communication Using an
Application.”

Segment 1 Segment 2

HUB-A HUB-A

Router Router
A1 A2

1 1 1 1 1
Control WAN Control Standby
FCJ 1 Side
CPU
FCN 2 FCJ 3 Side
CPU
FCN 4 CPU
Side

2 2 2 2 2

Router Router
B1 B2

HUB-B HUB-B

Figure Example of Connecting Control Network to WAN

TI 34P02K25-01E May 31, 2017-00


<3. Examples of Network Configurations> 104
Table Examples of IP Addresses when Connecting FCN/FCJ and FCN/FCJ Located in Different
Segments in a Duplexed Network Configuration
Network IP
Nodes Settings Remarks
interfaces Addresses
FCJ 1 1/2 172.16.0.1 Resource Configure only VIP. PIP is automatically set.
Configurator Duplexed network setting
FCN 2 1/2 172.16.0.2 Resource Configure only VIP. PIP is automatically set.
Configurator Duplexed network setting
FCJ 3 1/2 192.168.0.3 Resource Configure only VIP. PIP is automatically set.
Configurator Duplexed network setting
FCN 4 1/2 192.168.0.4 Resource Configure only VIP. PIP is automatically set.
Configurator Duplexed network setting
Router 172.16.0.5 Setting Defined For Segment 1 and Network-A
A1 by the Router
Router 192.168.0.5 Setting Defined For Segment 2 and Network-A
A2 by the Router
Router 172.16.2.5 Setting Defined For Segment 1 and Network-B
B1 by the Router
Router 192.168.2.5 Setting Defined For Segment 2 and Network-B
B2 by the Router

TI 34P02K25-01E May 31, 2017-00


<3. Examples of Network Configurations> 105

3.12 Operation with Remote HMI


STARDOM realizes Web-based configuration of HMIs, allowing you to easily
construct a system for operation and monitoring remotely via WAN including
telephone lines and internet.

Example of Construction
The following figure shows an example of system configuration using a WAN.

WAN

HMI Firewall
VPN
Router Firewall
Control System VPN
Information Network Router

Information Network

VDS VDS
Data Server Data
HMI Server Server
HMI HMI
Control Network

... ... Remote Operation

FCN FCN FCJ PLC

Figure Example of Remote Operation

• As a WAN, you can use ISDN, leased line, frame relay or inexpensive internet. If
you perform operation and monitoring remotely, choose an optimum WAN after due
consideration of traffic at operation and monitoring, available network infrastructure,
etc. To realize a full-scale operation, it is recommended to employ high-speed
infrastructure, assured bandwidth, depending on the scale of operation.
• For connection part of a WAN, routers supporting protocols for connecting
telephone lines, ISDN, leased lines, etc. are needed. If necessary, consider the
installation of a firewall, VPN (Virtual Private Network) to acquire the needed
security and band. Firewalls protect against external unauthorized accesses and
tampering. VPN protects against wiretapping activities and passing off. For the
network securities, follow the network policy of your company.
• For communication band of the part of WAN, calculate the actual traffic and employ
the infrastructure with excess capacities. Consider the traffic when starting HMIs or
time when events are concentrated as well as steady communication load when
collecting data.

SEE ALSO
For the estimation of traffic, see "2.3 Communication Performances".

• For infrastructures of WAN, use services provided by manufacturers of


communication infrastructure of each area (e.g. in Japan, NTT). WAN may be
suspended due to accidents or engineering works. You can set backup WAN or
duplex routers as necessary. See manuals of the router in use for the detailed
procedures.

TI 34P02K25-01E May 31, 2017-00


<3. Examples of Network Configurations> 106

Internet Connection
If failures occur in the system at a site, you can send internet mails to remote terminals
from FCN/FCJ or VDS in the field or send mails to a cell phone via telephone lines. With
that it is possible to notify the contact person who is not in the site of important events
immediately. The same person can also simply send Internet mails to ask conditions of
the site. By these functions, a contact person who has received an urgency mail calls
Web browsers using a cell phone or a hand-held device to check conditions of the site.
You can acquire the application that enables these functions.

TI 34P02K25-01E May 31, 2017-00


<3. Examples of Network Configurations> 107

3.13 Send Mails to/Receive Mails from VDS and


FCN/FCJ
If failures occur in the system at a site, you can send Internet mails to remote
terminals from FCN-100, FCN-RTU, FCJ or VDS in the field or send mails to a cell
phone via telephone lines. With that it is possible to notify the contact person who
is not in the site of important events immediately. The same person can also
simply send Internet mails to ask conditions of the site. By these functions, a
contact person who has received an urgency mail calls Web browsers using a cell
phone or a hand-held device to check conditions of the site. You can acquire the
application that enables these functions.

Example of Construction
The following figure indicates an example of system configuration to realize the following
functions: inquire remote FCN-100, FCN-RTU, FCJ or VDS using internet mail functions
and send urgent mails from remote FCN-100, FCN-RTU, FCJ or VDS.

WAN Cell
Phones,
etc.

HMI POP Server Dial-up


SMTP Server Router

Control System Information Network

VDS VDS
HMI Server HMI
Data Server Server

Control Network

... ...
FCN FCN FCJ PLC

Figure Example of System Configuration with Mail Functions

• Connection between the devices of the field and WAN is performed using
commercially available routers with dial-up, ISDN and ADSL connection functions.
In the example above, a dial-up router for analog lines is used. See manuals of
each router for the setting procedures.
• To connect to a WAN, take due account of securities.
• For send and receive mails, a server dedicated to send/receive mails is required. In
the example above, POP server and SMTP server are installed in a company. If you
cannot install a server for sending and receiving mails, you may use a server
provided by providers or manufacturer of cell phones instead, according to your
condition.
• Between a dial-up router and a VDS, FCN-100, FCN-RTU or FCJ, install firewalls or
VPN routers as necessary.

TI 34P02K25-01E May 31, 2017-00


<3. Examples of Network Configurations> 108

Configurations of FCN-100, FCN-RTU and FCJ Mail Functions


FCN-100, FCN-RTU and FCJ support SMTP as send mail protocol; POP3 as receive
mail protocol.
Send/receive mail functions of FCN, FCN-RTU and FCJ can be defined in the
maintenance windows on a Web browser. The following table lists setting items. For
details of each, see other instruction manuals or online help files.
Table Configurations List of Mail Setting File
Functions Setting items Keys Default values
POP3 user name PopUser None
Send/receive mails Communication trace output TraceMode NO
Send/receive log output MailLog YES
POP3 password PopPassward None
POP3 server address PopServer None
Receive mail cycle RecvCycle 0 (m)
Receive mails
Maximum mail size MaxMailSize 2 (Kbyte)
Authorization phase AuthPhase None
Authorization error handling OnAuthError Send
SMTP server address SmtpServer None
Domain name Domain None
Mail sender TrueName None
Error mail send destination ErrorsTo None
Send mails Reply mail destination ReplyTo None
Send mail cycle SendCycle 0 (m)
Send mail spool size QueueSize 0 (Kbytes)
Send mail spool type QueueType Memory
Maximum send error QueueExpire 5 (times)

Configuration Procedures
1. Click the link of [Edit] in "System Setting File" of the maintenance menu. Select "E-
Mail Configuration File" on the system setting file window and click [OK].

2. On the mail function setting window, perform the needed configuration. For the
detailed explanation, see the online help files.

TIP
When using the E-mail Application Portfolio of the InfoWell, the above configuration can be set in the
portfolio’s setting window. Therefore, there is no need to be aware of the above E-mail Configuration
File when using the portfolio.

TI 34P02K25-01E May 31, 2017-00


<3. Examples of Network Configurations> 109

3.14 Monitoring and Maintaining FCN/FCJ


Remotely
FCN/FCJ is an autonomous network controller, enabling easily to realize systems
for operation and monitoring or maintaining remotely via a WAN.

The following figure shows an example of system configuration for simple operation and
monitoring and maintenances of FCN/FCJ remotely installed, via a WAN including
telephone lines or internet.

WAN

HMI Firewall
VPN
Router Firewall
Control System VPN
Inforamtion Network Router

VDS VDS
Data Server Data
HMI Server Server
Web
Browser
Control Network

... ... Remote Operation

FCN FCN FCJ PLC

Figure Example of Monitoring Operation from Remote FCN/FCJ

Routing
You need to install firewalls, authorization, and enciphere for securities of connections to
a WAN. In the figure above, routers supporting firewalls and VPN are employed.
The routing operations between a control network and a control system network are
performed on VDS data server in the example above; however, another router can be
installed.

SEE ALSO
For the installation of routers, see "3.6 Connecting Routers to Control Networks".

TI 34P02K25-01E May 31, 2017-00


<3. Examples of Network Configurations> 110

Maintenances of FCN/FCJ
By specifying URL of an FCN/FCJ on a Web browser, the maintenance homepage of the
FCN/FCJ is displayed. Using this function, you can check or change configurations of
FCN/FCJ remotely.

Operation and Monitoring on Web Browser


Using the Web Application Portfolio or Webmetry functions, you can construct simple
operation and monitoring windows.

CAUTION
Communication protocols for some Web windows of the Web Application Portfolio and
windows of the Webmetry functions do not generally pass through firewalls. If these
windows need to be displayed via a firewall, set passage to be allowed through the
firewall’s port 34170.

TI 34P02K25-01E May 31, 2017-00


<3. Examples of Network Configurations> 111

Remote Connection of FCN/FCJ via Modems

Public Circuit

Modem
Modem

Serial
Cable

FCN

PC
Remote area

Office or other sites

Figure Example of Monitoring Operations from Remote FCN/FCJ (Small System)

FCN/FCJ supports PPP connections, easily realizing connections to public line through
modems on a serial port of FCN/FCJ to acquire data via a public line. Communication
from a remote PC to an FCN/FCJ is possible via a public line.

Setting Procedures of PPP (Point to Point Protocol) Connections on


FCN/FCJ
1. Click the link of [Edit] in "System Setting File" from the maintenance menu. Select
"PPP Setting File" on the system configuration file window and click [OK].

2. On the PPP function setting file edit window, perform needed configurations
referring to examples of settings or online help files.

3. Reboot FCN/FCJ in online mode.

TIP
If you duplex a CPU on FCN, this function is not available.

TI 34P02K25-01E May 31, 2017-00


<3. Examples of Network Configurations> 112

3.15 Setting FCN/FCJ and VDS Remotely


If you install FCN/FCJ remotely from VDS data server, or in a separated building,
the configuration can be as follows:

VDS
VDS Data HMI
HMI Server Server

Control Network

Switching HUB

Area1

Optical Fiber Optical Fiber

Area2 Area3

Switching HUB Switching HUB

... ...
FCN FCN FCN FCN

Figure Example of Control Network in Remote Areas

Wiring
If you connect devices in separate buildings or remote places, use optical fiber that
enables long-distance transmissions and is fairly resistant to noise. However, the total
distance of CAT5 twisted pair cable is 100 m at most because it is exclusive of indoor
wiring; it is not appropriate for wiring between separated buildings or in long distances.
To use optical fibers, prepare a switching hub with an optical fiber interface of at least
100 Mbps.

Setting Parameters
There are no parameters to be set.

TI 34P02K25-01E May 31, 2017-00


<3. Examples of Network Configurations> 113

3.16 Connecting FCN/FCJ and VDS via WAN


You may want to install VDS and FCN/FCJ in remote places connected via a WAN
(leased line, telephone line, ISDN, etc.). It is difficult to completely ensure
communications between VDS and FCN/FCJ via WAN, because 100 Mbps Ethernet
is assumed to be used for communications between them; in addition, a general
WAN cannot guarantee band or response time and operation test with a WAN is
not performed at developing process.

Example of Construction
The following figure indicates an example of construction. Note that this example only
illustrates reference information, of which operations are not guaranteed. Draw upon
approaches to estimate communication performances in this document; construct a
system based upon understanding of the features of the WAN on your own authority as
an engineer in charge of system construction.

HUB

Router VDS VDS HMI


HMI Data
Server Server
Area1

WAN

Router Router

HUB HUB

FCN ... FCN FCN ... FCN


Area2 Area3

Figure Example of Control Network via WAN

TI 34P02K25-01E May 31, 2017-00


<3. Examples of Network Configurations> 114
Notes for Communication Performances
In the example above, VDS data server acquires data of remote FCN/FCJ. Between a
WAN and the connecting part, routers according to the infrastructure are installed. The
communications between VDS data server and FCN/FCJ include steady data
acquisitions as well as uploading of definition data at starting-up, and concentrations of
events. Therefore, you should employ the infrastructure with excess band for the WAN
to correspond to the traffic during starting-up and event concentration, in addition to the
steady state.

SEE ALSO
For the estimation of communication performances, see "2.3 Communication Performances".

Configurations
Be sure to configure the default gateway of remote FCN/FCJ and VDS correctly.

SEE ALSO
For the settings of default gateway, see "2.2 Network Basic Definitions (IP Address Settings).

TI 34P02K25-01E May 31, 2017-00


<3. Examples of Network Configurations> 115

3.17 Connecting Remote Devices to Duplexed


Control Network
This section explains the network configuration when connecting remote devices
to duplexed control networks.

Example of Construction
STARDOM duplexed network function is not available for communications to remote
devices. Therefore, the connection to a WAN is performed only in HUB-A as shown in
the figure below.
HUB-A

HUB-A

Router Router
HUB-A

1 1 Router Router
FCJ FCN WAN 1 1 FCN 1 1
2 2 FCJ Control Standby VDS
2 2 -side -side 2 2

HUB-B

HUB-B

Figure Example of Connecting Control Network to WAN

Connection
A router connecting to a WAN is connected to HUB-A as a single interface device. When
performing routing, you need to configure the related devices. For the configuration of
the router, see the instruction manual of each router.

SEE ALSO
It is possible to duplex communications between FCN/FCJ and FCN/FCJ located in different segments
via the wide area network. For details, see “3.11 Duplexing Communications between FCN/FCJ and
FCN/FCJ Located in Different Segments.”

TI 34P02K25-01E May 31, 2017-00


<3. Examples of Network Configurations> 116

Duplexing WAN Part


The part of router and WAN can be duplexed using a duplexed network function of the
router. As shown in doted lines in the figure above, connect backup routers to HUBs-A
and to the WAN for the backup side. The WAN on the primary side and on the backup
side should be physically different. With that configuration, if the WAN (or the router
supporting WAN) fails, the path is switched automatically over another one. For a
duplexed network function of a router, see the manual of each router.

TIP
Because the communication band on a WAN is not completely guaranteed, the STARDOM duplexed
control network function does not apply to the part of the WAN network.

Configurations
Be sure to configure the default gateway of the remote FCN/FCJ and VDS correctly.

SEE ALSO
For the settings of default gateway, see "2.2 Network Basic Definitions (IP Address Settings)".

TI 34P02K25-01E May 31, 2017-00


<3. Examples of Network Configurations> 117

3.18 Synchronizing Times among Nodes


To synchronize times of event occurrences, you need to synchronize times
among nodes of the control network. On STARDOM, the time between nodes can
be synchronized using SNTP (Simple Network Time Protocol; refer to RFC2030), a
general technology for the time synchronization function of Ethernet.
The accuracy of the synchronization is assumed to be 1 second or shorter, which
is because VDS uses a PC and Windows for the platform, and Ethernet and TCP/IP
for the communication protocol.

Example of Construction
The following figure indicates an example of construction when synchronizing times on
control network.
SNTP
server in a
HMI HMI
company

Control System Information Network

SNTP SNTP
Client Client
VDS VDS
Data Server Data Server

SNTP SNTP
Server Server

Control Network

FCN FCN FCJ PLC


SNTP SNTP SNTP
Client Client Client

Figure Example of Construction when Synchronizing Times on Control Network

TI 34P02K25-01E May 31, 2017-00


<3. Examples of Network Configurations> 118
How to Configure the Time Synchronization Function
SNTP has server and client functions. Server functions allow transmission of their own
times. Client functions allow reception of the time for synchronization of their own times.
It is also possible to run server and client functions simultaneously in order to send
(relay) the time received from another SNTP server to other machines.
SNTP configuration methods in different system configurations are described below:

[If a STARDOM system is connected to the intranet of a company]


As shown in the above configuration example, simultaneously run SNTP server
functions and SNTP client functions in the VDSs to receive the time from the SNTP
server in the company for delivery to the FCNs/FCJs.

TIP
In the domain environments of Windows operating systems, time in client PCs is automatically
synchronized. Therefore, if PCs operating VDSs have been used in such domains, the SNTP client
functions of these VDSs have already been running. In such cases, run SNTP server functions of the
VDSs and send the time to the FCNs/FCJs.

[If a STARDOM system is independent of the intranet of a company]


One of FCN-500, FCN-100 or FCJ will be used as an SNTP server. Other FCNs/FCJs or
VDSs receive the time from this time master machine.
If FCN-500 is used as SNTP server, enable SNTP server in maintenance page. If FCN-
100 or FCJ is used as SNTP server, install the time synchronization server portfolio
license to them.

TIP
Windows 10/Windows 7 allows the operation of SNTP client functions or the simultaneous operation of
the SNTP client and server functions, but not the operation of SNTP server functions only. Therefore, a
single Windows 10/Windows 7 machine cannot become the time master.

[When multiple FCNs/FCJs are used exclusively]


One of FCN-500, FCN-100 or FCJ will be used as an SNTP server. Other FCNs/FCJs
receive time from this time master machine.
If FCN-500 is used as SNTP server, enable SNTP server in maintenance page. If FCN-
100 or FCJ is used as SNTP server, install the time synchronization server portfolio
license to them.

Basic Operations of SNTP


Time synchronization communications are performed between SNTP client functions
implemented on each node and SNTP server connected to a network. There are two
approaches for time synchronization communications: multicasting time to network from
SNTP server functions, and inquiring time to SNTP server from SNTP client, that is a
client-server (unicast) mode.

TI 34P02K25-01E May 31, 2017-00


<3. Examples of Network Configurations> 119
Adjusting Time on FCN/FCJ
FCNs/FCJs have SNTP client functions installed as standard features. Moreover,
FCN/FCJ has a function to adjust OS time gradually (smooth adjustment) for
synchronizing with times received by SNTP clients, preventing skips or reverses of time.
By default, it performs time synchronization of unicast communication every 100
seconds; it performs smooth adjustment for the difference of 5 sec or less; and it does
not perform any adjustments for the difference of 500 ms or less. These parameters can
be configured in the maintenance homepage on a Web browser.
In addition, installation of a time synchronization server portfolio on an FCN/FCJ makes
it possible to run SNTP server functions.

Adjusting Time of VDS


VDSs use the time synchronization function of Windows operating systems.
To enable SNTP client/server functions, as following.

• To enable SNTP client functions, use the following methods:


1. Click the [Control Panel] - “Clock, Language, and Region” - “Date and Time” from the
start menu. "Date and Time” is displayed.
2. Click the [Change settings] button of “Internet Time” tab. "Internet Time Settings” is
displayed.
3. Select the [Synchronize with an Internet time server] check box and specify a server.
4. Click the [Update now] button.
5. Check the message “The clock was successfully synchronized with time, <server
name> on <Synchronize with Date and time>.”
6. Click the [OK] button to finish the setup.

TIP
A PC is synchronous once per a week by initialization of Windows. If time slips large in a day, specify
the synchronous every day.
(1) Click the [Control Panel]-[Administrative Tools]-[Task Scheduler] from the start menu.
(2) Open the [Task Scheduler Library]-[Microsoft]-[Windows]-[Time Synchronization], and right-click
the [properties].
(3) Click the [Triggers] tab.
(4) Click the [Edit] button.
(5) Select the [On a schedule] on “Begin the task”, and click the [Daily] on “settings”.
(6) Click the [OK] button, and close all the windows.

• To enable SNTP server functions, check "Time Delivery" on the "Time


Synchronization” tab in the FCN/FCJ connection setting tool. Notice that if this
function is used on Windows, SNTP client functions need to be already enabled.
After the above settings have been entered, restart the PC.

TI 34P02K25-01E May 31, 2017-00


<3. Examples of Network Configurations> 120
Connecting to External SNTP Server
As necessary, configure settings to perform the time synchronization with your standard
SNTP server or an external standard SNTP server. In the example above, the time is
synchronized between SNTP server in a company and VDS.

TIP
SNTP servers are managed in a tree structure on the Internet. They can be generally accessed.
However, in view of loads on public SNTP servers, it is not practical that all computers acquire time
from public SNTP servers.
Therefore, it is recommended that an SNTP server in your company be used for VDSs. If you wish to
use an external SNTP server, refer for example, to the information that is available at
http://www.ntp.org/.
In some connecting methods to the Internet, SNTP packets may be blocked by firewalls or other
systems.

TI 34P02K25-01E May 31, 2017-00


<3. Examples of Network Configurations> 121

Configurations on SNTP of FCN/FCJ


Configurations of SNTP client functions are performed in the maintenance homepage on
a Web browser by editing the SNTP (synch time) setting file. The following table lists
setting items.
Table SNTP Setting Items
Setting items Keys Default values
Operation mode SntpMode UNICAST
Server address1 SntpServer1
Server address2 Sntpserver2
Server address3 Sntpserver3
Server address4 Sntpserver4
Server timeout (ms) ServerResponseTime 3000
Request retransmission RequestRetry 3
Time inquiring polling interval (sec) SyncIntervalTime 100
Maximum ignore time (ms) MaxIgnoreTime 500
Maximum smooth adjusting time (sec) MaxSmoothTime 5
Maximum round trip time (ms) MaxRtt 500
Communication trace TraceMode NO

As a time server address, configure the IP address of VDS; configure the VIP with
duplexed network. In the example above, configure IP addresses of two VDS data
servers to server address1 and server address2. Other setting items operate in default
values without problems. If you want to make advanced settings, change the parameters
referring to the instruction manuals of Duonus or online-help files on maintenance
windows on a Web browser.

Initial Time Setting to FCN/FCJ


Time is not set to FCN/FCJ when shipped. The following sequence explains how to set
time initially to FCN/FCJ.

1. Access to FCN/FCJ on a Web browser and click the link of [Reboot] in the
maintenance menu of the maintenance homepage. FCN/FCJ is restarted in the
maintenance mode.

2. Click the link of [Set Data and Time] in the maintenance menu.

3. Set the present time and click [OK] in the date/time setting window.

4. Open the initial window of the maintenance homepage to check if the time is
correctly set.

TI 34P02K25-01E May 31, 2017-00


<3. Examples of Network Configurations> 122

SNTP Client Settings to FCN/FCJ


The following sequence is for the configurations of SNTP operation parameters on
FCN/FCJ. Configuration is done in the maintenance mode.

1. Access to FCN/FCJ on a Web browser and click the link of [Edit] in "System Setting
File" in the maintenance menu on the maintenance homepage.

2. Select "JEROS Basic Setting File" and click [OK].

3. Configure SNTP and time zone. Type "YES" in the part of SntpStart; input the
parameter of your area for TIMEZONE. Input the parameters, and click [OK].

4. After the same procedure as “2.”, Select "SNTP Setting File" and click [OK].

5. Configure parameters. Set the time synchronization mode to set the SNTP server
address to SntpServer. Up to 4 time servers can be configured. Default values are
set to other parameters and can be changed if necessary. When you finished
inputting the parameters, click [OK].

6. Restart FCN/FCJ in online mode.

SNTP Server Settings for the FCN/FCJ


In FCN-500, SNTP server function is set by the maintenance page.
In FCN-100 and FCJ, SNTP server function runs by installation of a time
synchronization server portfolio license.

TI 34P02K25-01E May 31, 2017-00


<3. Examples of Network Configurations> 123

3.19 Using Hand-held Devices in a Field


You can monitor operations, perform adjustment and maintenance of a device at a
site by connecting hand-held devices to control networks via a wireless LAN.

Example of Construction
The following figure indicates a system with a wireless LAN.
HUB

HUB HUB

Wireless Control
FCN
Standby Wireless
FCJ FCN Access VDS FCJ -side -side Access HMI
Point Point

Hand-held Hand-held
HMI HMI

Figure Example of Network Connecting Hand-held Devices and Wireless LAN

Wireless LAN
As a typical wireless communication, you can use the wireless LAN standardized by
IEEE802.11. In the example above, the radio wave called spread spectrum (SS) is used
as the infrastructure mode. The SS mode provides high confidentiality and is resistant
against noise. Prepare additional access points or exclusive communication cards.

How to Set Wireless Devices


Install access points for the IEEE802.11 wireless LAN for each site as in the example.
Connect the access points to hubs (with dual network, to HUBs-A). Install IEEE802.11
wireless LAN adapters on hand-held devices. If the access points and hand-held
devices are physically remote, or radio waves are not well received due to obstructions,
install several access points to use roaming functions. IEEE802.11b communications
are performed with radio waves of 2.4 GHz; be careful if the devices using the same
band exist in the same area.

Securities
Comparing to a cable LAN, a wireless LAN is more vulnerable to tapping and
unauthorized accesses; you need to install security functions including encipher or user
authorization systems. You can use build-in security functions of hand-held devices.

Band
Note that the speed of a wireless communication is slower than the one with cables. As
the maximum communication speed, 11 Mbps (a logical value) can be obtained with
802.11b devices; 54 Mbps (a logical value) can be obtained with 802.11a or 802.11g
devices.
Estimate communication loads using examples in "Communication Performances" of
chapter 2 and choose a wireless LAN device leaving some extra capacities.

TI 34P02K25-01E May 31, 2017-00


<3. Examples of Network Configurations> 124

Reliability
Duplexing can be attained by installing several access points. For the detailed
procedures of installation, see the instruction manual of each wireless device.

TIP
Duplexed network function of STARDOM on the part of wireless LAN is not guaranteed in
performances and reliabilities.

TI 34P02K25-01E May 31, 2017-00


<3. Examples of Network Configurations> 125

3.20 Connecting Remote Sites Using Wireless


Devices
You may want to connect remote sites, e.g., between buildings, factories or bases
where cable communication infrastructures are not prepared or communication
cables cannot be installed (at sea, in a desert, forest, etc.). In these conditions, it
is relatively easy and inexpensive to install networks with wireless technologies.
Typically, install antennas at two remote sites to communicate using territorial or
communication satellite.
According to your communication equipment and infrastructure of your area,
choose the optimum communication infrastructure. (This document does not
cover the specific communication infrastructures.)

Example of Construction

Wireless device

Wireless device

HUB

HUB

FCJ FCN

VDS HMI
Remote Area

Data Center

Figure Example of Remote Connection with Wireless Devices

Install wireless devices and antennas at two remote sites. Connect the wireless devices
to hubs (to HUBs-A with duplexed network) connected to STARDOM devices. For the
types and procedures of installation, see the instruction manuals of each device.

Securities
A wireless LAN is more vulnerable to tapping and unauthorized accesses; you need to
install security functions including encipher or user authorization systems. Most of hand-
held devices have built-in security functions. Read the manuals of the device in use
carefully to configure the device properly.

Communication Band
Estimate communication loads to choose a wireless LAN infrastructure leaving some
extra capacities.

SEE ALSO
For the estimations of communication load, see "2.3 Communication Performances".

TI 34P02K25-01E May 31, 2017-00


<3. Examples of Network Configurations> 126

Reliability
Duplex the system by installing several wireless devices or antennas if necessary. For
the detailed procedures of installation, see the instruction manual of each wireless
device.

TIP
Duplexed network function of STARDOM on the part of wireless LAN is not guaranteed in
performances and reliabilities. Installing wireless devices for communications between a VDS and a
controller is not guaranteed. If you actually employ these configurations, be sure to check operations in
advance and construct the system on your own authority.

TI 34P02K25-01E May 31, 2017-00


<3. Examples of Network Configurations> 127

3.21 Connecting to Existing ASTMAC


This section explains the points to keep in mind when you connect an existing
ASTMAC and the VDS or FCN/FCJ on the same network.
VDS VDS
HMI HMI

Control System Information Network

VDS
Data Server ASTMAC
HMI Server

Control Network

FCN FCN FCJ PLC PLC

Figure Example of Connecting FCN/FCJ and VDS Data Server to ASTMAC

When connecting ASTMAC and VDS on the same network, you can view various data
on ASTMAC (data, trends, reports, and messages) via VDS data server; and data on
VDS (data, trends, reports, and messages) via ASTMAC.

Notices When Setting IP Addresses


STARDOM devices have rules to decide IP addresses. Therefore, when connecting the
VDS or FCN/FCJ to the existing ASTMAC system, you should check if the scope of IP
addresses on the VDS or FCN/FCJ is not used on the ASTMAC system. If they are
duplicated, you should change the settings of the IP addresses.

SEE ALSO
For the rules of IP addresses on STARDOM, see "2.2 Network Basic Definitions (IP Address Settings)"
and "2.6 Duplexing Control Network".

TI 34P02K25-01E May 31, 2017-00


Blank Page
i

Revision Information
Title : STARDOM Network Configuration Guide
Manual No. : TI 34P02K25-01E

Sep. 2002/1st Edition


Newly published

Feb. 2004/2nd Edition


Revised
Errors correction
Addition of the new network function of STARDOM

Apr. 2006/3rd Edition


Revised
• Addition of “Cautions for Network Configuration (for devices frequently conducting broadcast communication)”
• Error correction (VDS redisplay time)

Sep. 2006/4th Edition


Revised
• Addition of enhanced duplexed network function.
• Error correction

Mar. 2007/5th Edition


Revised
• Addition of restriction on using 10 Mbps hubs or repeater hubs.

Mar. 2007/6th Edition


Revised
• Addition of the SLIP Communication function.
• Addition of the Graphic Portfolio (InfoWell) function.

Sep. 2009/7th Edition


Revised
• Error correction

Jun. 2010/8th Edition


Revised
• Update "Table Devices that can be connected to FCN/FCJ" and "Table Devices that can be connected to Data Server"
• Delete "Network Adapter Track Usage Records"

Subject to change without notice. TI 34P02K25-01E Jun. 6, 2018-00


ii
Mar. 2011/9th Edition
Revised
• Support for Windows 7.
• VDS Viewer Function was added.
• Update "Table Devices that can be connected to FCN/FCJ"

Apr. 2011/10th Edition


Revised
• Addition of the communication port number to use of STARDOM
• Error correction

Sep. 2012/11th Edition


Revised
• Addition of the FCN-RTU.
• Update "Table Devices that can be connected to FCN/FCN-RTU/FCJ"
• Error correction

Mar. 2013/12th Edition


Revised
• Addition of the communication port number to use of FCN/FCJ.

Jun. 2015/13th Edition*


Revised
• Deleted Windows XP
• Error correction

Jul. 2016/14th Edition


Revised
• Addition of the FCN-500

May 2017/15th Edition


Revised
• Support for Windows 10.

Jun 2018/16th Edition*


Revised
• Error correction

* : Denotes the release number of the software corresponding to the contents of this Technical Information.
The revised contents are valid until the next edition is issued.

Subject to change without notice. TI 34P02K25-01E Jun. 6, 2018-00


iii

■ For Questions and More Information


If you have any questions, you can send an E-mail to the following address.
E-mail:[email protected]
■ Written by Yokogawa Electric Corporation
■ Published by Yokogawa Electric Corporation
2-9-32 Nakacho, Musashino-shi, Tokyo 180-8750, Japan

Subject to change without notice. TI 34P02K25-01E Jun. 6, 2018-00