RAMSET Chemset Fire Resistance Test

This document provides an advisory opinion on testing done to evaluate the fire resistance of the bonded anchor system RAMSET Chemset 801 Xtrem / RAMSET Chemset 800 Xtrem. Testing was conducted to determine characteristic parameters for load under tensile stress when exposed to fire on one side and anchored in reinforced concrete. The testing showed that the anchor system can resist characteristic tensile stresses between 0.26 kN and 20.62 kN depending on the anchor size and fire exposure time. The opinion only applies to the tested anchor system installed according to manufacturer specifications in uncracked or cracked reinforced concrete.

Uploaded by

hung
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
115 views5 pages

RAMSET Chemset Fire Resistance Test

This document provides an advisory opinion on testing done to evaluate the fire resistance of the bonded anchor system RAMSET Chemset 801 Xtrem / RAMSET Chemset 800 Xtrem. Testing was conducted to determine characteristic parameters for load under tensile stress when exposed to fire on one side and anchored in reinforced concrete. The testing showed that the anchor system can resist characteristic tensile stresses between 0.26 kN and 20.62 kN depending on the anchor size and fire exposure time. The opinion only applies to the tested anchor system installed according to manufacturer specifications in uncracked or cracked reinforced concrete.

Uploaded by

hung
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 5

MFPA Leipzig GmbH

Testing, inspection and certification body for


building materials, building products and building systems
Division III - Structural Fire Protection
Dipl.-Ing. Sebastian Hauswaldt
Team 3.2 - Fire Behaviour of Building Types and
Special Structures
Dipl.-Ing. S. Bauer
Phone +49 (0) 341-6582-194
[email protected]

Advisory opinion no. GS 3.2/17-410-3

21st March 2018


1st copy

Subject matter: RAMSET Chemset 801 Xtrem / RAMSET Chemset 800 Xtrem
Summarising evaluation of the test results for the bonded anchor.
Client: ITW Australia (Ramset)
1 Ramset Drive
Chirnside Park
VIC 3116
Australia
Date of order: 10th January 2018
Person in charge: Dipl.-Ing. S. Bauer
Validity: 6th March 2023

This document consists of 3 text pages and 2 enclosures.

This document may only be copied in an unabridged form. Any publication – including extracts – requires the prior written approval
of MFPA Leipzig GmbH. The German document with original signatures and the original seal of the authorised signatory is the
legally binding version. The terms and conditions (T&C) of MFPA Leipzig GmbH apply.

Gesellschaft für Materialforschung und Prüfungsanstalt für das Bau-


wesen Leipzig mbH (MFPA Leipzig GmbH)

Registered office: Hans-Weigel-Str. 2b – 04319 Leipzig/Germany


Managing Director: Dr.-Ing. habil. Jörg Schmidt
Company Register: District Court Leipzig HRB 17719
VAT ID No.: DE 813200649
Phone: +49 (0) 341-6582-0
Fax: +49 (0) 341-6582-135
MFPA Leipzig GmbH GS 3.2/17-410-3
Structural Fire Protection 21st March 2018 Page 2 of 3

1 Objective and request


On 10th January 2018, MFPA Leipzig GmbH was commissioned by SPIT with the assessment of the re-
sistance to fire of the bonded anchor RAMSET Chemset 801 Xtrem / RAMSET Chemset 800 Xtrem with
fire exposure from one side and anchored to a reinforced concrete base in order to determine the charac-
teristic parameters for a load under tensile stress.

2 Description of the tested structure


The Injection system RAMSET Chemset 801 Xtrem / RAMSET Chemset 800 Xtrem is a bonded anchor
consisting of a cartridge with injection mortar RAMSET Chemset 801 Xtrem / RAMSET Chemset 800 Xtrem
and a steel element. The steel element consist of a threaded rod CHEMSET ANCHOR STUD with washer
and a hexagon nut or a CHEMSET ANCHOR STUD XTREM stud or a reinforcing bar. The steel element
is placed into a drilled hole filled with injection mortar and is anchored via the bond between metal part,
injection mortar and concrete and can be used in cracked and uncracked reinforced concrete. The bonded
anchor may be anchored under static and quasi-static load in reinforced and unreinforced normal concrete
with a stability class between C 20/25 and C 50/60 in accordance with DIN EN 206:2014-07 [1]. No further
description of the product will be provided here and reference is made to the European Technical Assess-
ment ETA-18/0045 [2] dated 22. February 2018.
Threaded rods with washer and hexagon nut made of galvanized steel (property class ≥ 8.8) in sizes M8
and M12 each with one anchorage depth were tested. The test set-up and the results are shown in test
report PB 3.2/17-410-1 [3].

3 Test analysis and evaluation


The test evaluation for steel failure was conducted in accordance with TR 020:2004-05 [4]. A graphical
analysis of the test results can be found in enclosure 2. In order to determine the characteristic tensile
stresses, the values were evaluated on the basis of the test results.
For size M12, one result is odd. For the test result which is marked in orange in enclosure 2, diagram 2.2,
the failure occurred so early due to slipping of the hexagonal nut that it is to be traced back to the very low
or non-existent protrusion of the threaded rod (compared to the other test specimens) when the nut was
tightened. This result is therefore not included in the evaluation.
The following characteristic parameters for the load under central tension can be quoted for the Injection
system RAMSET Chemset 801 Xtrem / RAMSET Chemset 800 Xtrem on this basis (table 1). The charac-
teristic steel stress at normal temperature also has to be taken into account for the assessment; the smaller
stress value is decisive in each case.
The determination of the characteristic parameters for other failure types (e.g. “pulling out”, or “concrete
break-out” was not the subject of the tests; they can be determined according to the simplified verification
procedure described in TR 020:2004-05 [4], or experimentally according to the method described in
TR 048:2016-08 [5].

Table 1 Characteristic tension resistance for the Injection system RAMSET Chemset 801 Xtrem / RAMSET
Chemset 800 Xtrem with threaded rod made of galvanized steel (property class ≥ 8.8)

Size of threaded rod M8 M10 M12 M16 M20 M24 M30


Minimal embedment depth 10d 10d 10d 10d 10d 10d 10d
30 min NRk,s,fi(30) [kN] 1.60 2.33 3.10 5.77 9.01 12.98 20.62
60 min NRk,s,fi(60) [kN] 1.06 1.68 2.44 4.54 7.09 10.21 16.23
90 min NRk,s,fi(90) [kN] 0.53 1.04 1.79 3.33 5.20 7.49 11.91
120 min NRk,s,fi(120) [kN] 0.26 0.71 1.46 2.72 4.24 6.11 9.71
MFPA Leipzig GmbH GS 3.2/17-410-3
Structural Fire Protection 21st March 2018 Page 3 of 3

4 Special notes
The evaluation above only applies to the Injection system RAMSET Chemset 801 Xtrem / RAMSET Chem-
set 800 Xtrem which is installed in compliance with the installation regulations of ITW and the European
Technical Assessment ETA-18/0045 [2] dated 22. February 2018.
The evaluation still only applies in uncracked and cracked reinforced concrete.
The results of the tests for threaded rods made of galvanized steel may also be transferred to threaded
rods made of stainless steel A4 and high corrosion resistant steel (HCR).
The assessment applies in general to a one-sided fire exposure of the structural elements. In the event of
a fire load on several sides, the verification procedure can only be applied if the distance to the outer edge
of the nail anchor is c ≥ 300 mm and ≥ 2 hef.
Based on this, the specified loads also apply to lateral tension and/or diagonal tension.
The assessment only applies in conjunction with reinforced concrete ceilings of strength class ≥ C 20/25
and ≤ C 50/60 acc. to DIN EN 206:2014-07 [1] that have at least the same fire resistance rating as the fire-
resistance period of the anchors. In addition, the notes contained in DIN EN 1992-1-2:2010-12 [6] (see
section 4.5) on the avoidance of concrete spalling apply. This means that the moisture content must be
less than three % by weight (or four according to the National Annex).

This document does not replace any certificate of conformity or usability as defined by the building regula-
tions (national/European).

Leipzig, 21st March 2018

Dipl.-Ing. S. Hauswaldt Dipl.-Ing. M. Juknat Dipl.-Ing. S. Bauer


Head of Division Head of Work Group Test Engineer

List of enclosures
Annex 1 Installation parameters of the Injection system RAMSET Chemset 801 Xtrem / RAMSET
Chemset 800 Xtrem in conjunction with threaded rod
Annex 2 Graphical evaluation of the test results according to TR 020: 2004-05 [4]

Corresponding documents
[1] DIN EN 206:2014-07 Concrete - Specification, performance, production and conformity
[2] European Technical Assessment ETA-18/0045 dated 22. February 2018 and issued by DIBt,
Trade name: RAMSET Chemset 801 Xtrem / RAMSET Chemset 800 Xtrem, Product family:
Bonded anchor for use in concrete
[3] Test report PB 3.2/17-410-1 SPIT VIPER XTREM - Testing according to Technical Report TR
020 “Evaluation of Anchorages in Concrete concerning Resistance to Fire” (May 2004) to deter-
mine the characteristic steel stresses under tensile stress, MFPA Leipzig GmbH of 07/03/2018)
[4] TR 020:2004-05 Evaluation of Anchorages in Concrete concerning Resistance to Fire
[5] TR 048:2016-08 Details of tests for post-installed fasteners in concrete
[6] DIN EN 1992-1-2:2010-12 Design of concrete structures - Part 1-2: General rules - Structural fire
design
MFPA Leipzig GmbH GS 3.2/17-410-3 Enclosure 1
Structural Fire Protection 21st March 2018 Page 1 of 1

Annex 1 Installation parameters of the Injection system RAMSET Chemset 801 Xtrem / RAMSET
Chemset 800 Xtrem in conjunction with threaded rod

Picture A1.1 Figure in installation condition

Table A1.2 Material parameters for threaded rods

Provided by the client.


MFPA Leipzig GmbH GS 3.2/17-410-3 Enclosure 2
Structural Fire Protection 21st March 2018 Page 1 of 1

Annex 2 Graphical evaluation of the test results according to TR 020: 2004-05 [4]

Diagram A2.1 Graphical evaluation of the Injection system RAMSET Chemset 801 Xtrem / RAMSET
Chemset 800 Xtrem in size 8 with threaded rod made of galvanized steel (≥ 8.8)
4,5

measured values M8
4,0 regression curve
extrapolation line
3,5 F,fi(30)

3,0
load in kN

2,5

2,0

1,5
1,60

1,0
1,06

0,5
0,53

0,0
0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160

fire resistance in minutes

Diagram A2.2 Graphical evaluation of the Injection system RAMSET Chemset 801 Xtrem / RAMSET
Chemset 800 Xtrem in size 12 with threaded rod made of galvanized steel (≥ 8.8)
7,0

measured values M12


runaway value
6,0
regression curve
extrapolation line
F,fi(30)
5,0

4,0
load in kN

3,0
3,10

2,44
2,0

1,79

1,0

0,0
0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160

fire resistance in minutes