Paradox Esprit-728 en PDF
Paradox Esprit-728 en PDF
Software Versions 3.1 (728+, 738EX+ and 738+), 3.2 (728EX4+, 728DZ8+ and 748+) and 3.3 (728EX+)
INSTALLER CODE
Full access to programming, except user access codes (PINs). No access to arming/disarming. Use only numeric keys from [1] to [10] (key
[10] = 0). For default installer codes, refer to Table 1 below.
Table 1: Default Installer Codes by Control Panel
728EX+ = 727272 728EX4+ = 727272 738EX+ = 737373 748+ = 484848
728+ = 282828 728DZ8+ = 282828 738+ = 383838
HEXA PROGRAMMING
Addresses 000 to 043 and 300 to 527 are programmed using the Hexa Programming method. In this mode, you can enter any hexadecimal
digit from 0 - F where keys [1] to [9] represent digits 1 to 9 respectively; the other keys represent hexadecimal digits A to F as shown in
Figure 1 on page 1. To program using the Hexa Programming method:
1) Press [ENTER] + [INSTALLER CODE] (default: see Table 1 on page 1)
2) The [ENTER] key will flash indicating you are in programming mode
3) Enter the desired 3-digit [ADDRESS]
4) The keypad will display the 2-digit data currently saved at this address as described in Figure 1 on page 1
5) Enter 2-digit [DATA] and do not press [ENTER], the software automatically saves the data
6) Return to step 2 or press [CLEAR] to exit programming mode
Each key in the first 2 rows of the keypad represents a specific value when the key is lit, as shown above. If the key
isn’t lit, the key represents 0. The sum of the values of the lit keys in the first row correspond to the second hexa
digit. The sum of the values of the lit keys in the second row correspond to the first hexa digit as shown in the
example below.
= Second digit = 8 + 2 = 10
= First digit = 4 + 2 + 1 = 7
Note: Values 10 to 15 represent hexa digits A to F respectively. See keypad to the left.
Note, the keypad will not display the current data in the Hexa Streamlined Programming method.
ZONE RECOGNITION
Device 728+ 728+ 738EX+ 738+ 738+ 748+ 748+
connected to 728EX+ 728DZ8+**
which input? 728EX4+**
728DZ8+**
No ATZ With ATZ No ATZ No ATZ With ATZ No ATZ With ATZ
Control Panel
Input 1 = Zone 1 Zones 1 & 2 Zone 1 Zone 1 Zones 1 & 7 Zone 1 Zones 1 & 13*
Input 2 = Zone 2 Zones 3 & 4 Zone 2 Zone 2 Zones 2 & 8 Zone 2 Zones 2 & 14*
Input 3 = Zone 3 Zones 5 & 6 Zone 3 Zone 3 Zones 3 & 9 Zone 3 Zones 3 & 15
Input 4 = Zone 4 Zones 7 & 8 Zone 4 Zone 4 Zones 4 & 10 Zone 4 Zones 4 & 16
Input 5 = N/A N/A Zone 5 Zone 5 Zones 5 & 11 Zone 5 Zones 5 & 17
Input 6 = N/A N/A Zone 6 Zone 6 Zones 6 & 12 Zone 6 Zones 6 & 18
Input 7 = N/A N/A Zone 7 N/A N/A Zone 7 Zones 7 & 19
Input 8 = N/A N/A N/A N/A N/A Zone 8 Zones 8 & 20
Input 9 = N/A N/A N/A N/A N/A Zone 9 Zones 9 & 21
Input 10 = N/A N/A N/A N/A N/A Zone 10 Zones 10 & 22
Input 11 = N/A N/A N/A N/A N/A Zone 11 Zones 11 & 23
Input 12 = N/A N/A N/A N/A N/A Zone 12 Zones 12 & 24
Keypad
Zone 1 = Zone 5** Zone 9** Zone 9 Zone 7 Zone 13 Zone 13 Zone 13*
Zone 2 = Zone 6** Zone 10** Zone 8 Zone 8 Zone 14 Zone 14 Zone 14*
* Control panel does not distinguish between zones 13 and 14 and keypad zones 1 (zone 13) and 2 (zone 14).
** The 728EX4+ and 728DZ8+ control panels do not support any keypad zones.
WARNING: This equipment must be installed and maintained by qualified service personnel only.
Number of rings (Max. 15) First digit disables “Answering Machine Override”
(key [2ND] or key [1]), or determines period of time
between first and second call (see above). Second
digit determines number of rings required before
panel will answer. If [2ND][2ND] is entered, panel will
not answer (default value is [2ND] [8]).
A B
Communicator Formats
Key Key * = 4-digit account codes only
[2ND] = ADEMCO slow (1400Hz, 1900Hz, 10bps) [6] = RADIONICS with PARITY (1400Hz, 40bps)
[1] = (1400Hz, 1800Hz, 10bps) [7] = RADIONICS with PARITY (2300Hz, 40bps)
[2] = SILENT KNIGHT fast (1400Hz, 1900Hz, 20bps) [8] = * ADEMCO express
[3] = SESCOA (2300Hz, 1800Hz, 20bps) [9] = * ADEMCO contact ID (programmable codes)
[4] = RADIONICS (40bps with 1400Hz handshake) [10] = * ADEMCO contact ID (all codes)
[5] = RADIONICS (40bps with 2300Hz handshake) [TRBL] = * DTMF - no handshake (personal dialing)
___ / ___ User Code 3 304 ___ / ___ User Code 27 328
___ / ___ User Code 4 305 ___ / ___ User Code 28 329
12 ___ / ___ User Code 5 306 18 ___ / ___ User Code 29 330
___ / ___ User Code 6 307 ___ / ___ User Code 30 331
___ / ___ User Code 7 308 ___ / ___ User Code 31 332
___ / ___ User Code 8 309 ___ / ___ User Code 32 333
13 ___ / ___ User Code 9 310 19 ___ / ___ User Code 33 334
___ / ___ User Code 10 311 ___ / ___ User Code 34 335
___ / ___ User Code 11 312 ___ / ___ User Code 35 336
___ / ___ User Code 12 313 ___ / ___ User Code 36 337
14 ___ / ___ User Code 13 314 20 ___ / ___ User Code 37 338
___ / ___ User Code 14 315 ___ / ___ User Code 38 339
___ / ___ User Code 15 316 ___ / ___ User Code 39 340
___ / ___ User Code 16 317 ___ / ___ User Code 40 341
15 ___ / ___ User Code 17 318 21 ___ / ___ User Code 41 342
___ / ___ User Code 18 319 ___ / ___ User Code 42 343
___ / ___ User Code 19 320 ___ / ___ User Code 43 344
___ / ___ User Code 20 321 ___ / ___ User Code 44 345
16 ___ / ___ User Code 21 322 22 ___ / ___ User Code 45 346
___ / ___ User Code 22 323 ___ / ___ User Code 46 347
___ / ___ User Code 5 356 ___ / ___ User Code 29 380
___ / ___ User Code 6 357 ___ / ___ User Code 30 381
25 ___ / ___ User Code 7 358 31 ___ / ___ User Code 31 382
___ / ___ User Code 8 359 ___ / ___ User Code 32 383
___ / ___ User Code 9 360 ___ / ___ User Code 33 384
___ / ___ User Code 10 361 ___ / ___ User Code 34 385
26 ___ / ___ User Code 11 362 32 ___ / ___ User Code 35 386
___ / ___ User Code 12 363 ___ / ___ User Code 36 387
___ / ___ User Code 13 364 ___ / ___ User Code 37 388
___ / ___ User Code 14 365 ___ / ___ User Code 38 389
27 ___ / ___ User Code 15 366 33 ___ / ___ User Code 39 390
___ / ___ User Code 16 367 ___ / ___ User Code 40 391
___ / ___ User Code 17 368 ___ / ___ User Code 41 392
___ / ___ User Code 18 369 ___ / ___ User Code 42 393
28 ___ / ___ User Code 19 370 34 ___ / ___ User Code 43 394
___ / ___ User Code 20 371 ___ / ___ User Code 44 395
___ / ___ User Code 21 372 ___ / ___ User Code 45 396
___ / ___ User Code 22 373 ___ / ___ User Code 46 397
29 ___ / ___ User Code 23 374 35 ___ / ___ User Code 47 398
___ / ___ User Code 24 ___ / ___ User Code 48 /
375 399
(Duress)
___ / ___ Power failure 507 ___ / ___ TLM restore 511
Streamline
Data Description Address
Section
___ / ___ Late to close 516 ___ / ___ Login (Espload) 524
___ / ___ No movement 517 ___ / ___ Program Change 525
65 ___ / ___ Partial Arming 518 67 [2ND]/[2ND] Future Use 526
___ / ___ Recent Close 519 [2ND]/[2ND] Future Use 527
N N
See “TLM” table at right OFF OFF - TLM disabled
[1]
N N
OFF ON - TLM generates trouble only
Keyswitch = regular arm [2] Stay arm / System A ON OFF - generates an alarm if armed
Keyswitch arming N [3] N Enabled ON ON - silent alarm becomes audible
Call back N [4] N Enabled (address 086, key [9] has to be OFF)
N N
OFF ON - Regular reporting
(1:2) Pulse Europe [10] (1:1.5) Pulse USA
N N
ON OFF - Split* reporting (Alarms & System)
[11] ON ON - Double reporting
N N
See “Reporting Options” table at right
[12] Report Dialing Sequence (tel. no.)
N N
N/A N/A Regular: 1,2,1,2,1,2,1,2, fail to comm.
[BYP]
N N
Split*: Alarms - 1,1,1,1,1,1,1,1, fail to comm
Bell squawk on arm/disarm [MEM] Enabled System - 2,2,2,2,2,2,2,2, fail to comm
Auto zone shutdown N [TRBL] N Enabled Double: 1,1,1,1,1,1,1,1, fail to comm
2,2,2,2,2,2,2,2, fail to comm
* On alarm, all reports are made to Tel. #1 until system is
KEY disarmed. Once disarmed, system reports are made to
Tel. #2.
088: OFF / ON
Automatic event buffer transmission N [2ND] N Enabled
Panic 1 (keys [1] and [3]) N [1] N Enabled
Panic 2 (keys [4] and [6]) N [2] N Enabled Tamper / Wire Fault Definitions
Panic 3 (keys [7] and [9]) N [3] N Enabled
N N
KEY
Panic 1 silent [4] Audible System Armed [10] [11] System Disarmed*
Panic 2 silent N [5] N Audible Alarm as per OFF OFF - Tamper supervision
N N
individual zone disabled
Panic 3 silent [6] Fire definitions
Key [10] - regular arming N [7] N Enabled OFF ON - No alarm, trouble
N N
Always generate code reported
Key [11] - stay or system A arm [8] Enabled
N N
trouble and ON OFF - Silent alarm.
6 digit access codes [9] 4 digit access code alarm, audible or Trouble & alarm
N N
silent as per codes reported
[10] individual zone ON ON - Audible alarm.
N N
Tamper Recognition definitions Trouble & alarm
[11] codes reported**
Beep on exit delay N [12] N Enabled
N N
* Exception: for 24 hour zones, the tamper definition
Report zone restore on bell cut-off [BYP] On zone closure will follow the audible/silent alarm definition of the 24
N N
hour zone.
Zones with EOL (1k9) [MEM] No EOL
N N
** Silent zones will generate a silent alarm.
Always report disarm [TRBL] Only after alarm
KEY
090: OFF / ON
Exclude power failure from trouble display N [2ND] N Enabled
Zone (4, 9 or 15) enabled*** N [1] N Disabled*** *** NOTE 1: This feature applies to the 728+, 728DZ8+, 738+
N N
and 748+ only. When ATZ is enabled (address 090 key [8]
Auto arm = regular arm [2] Stay / System A
N N
ON) and zone 3 is defined as a fire zone, this zone must be
N/A [3] N/A disabled. If using a 728+ or 728DZ8+, zone 4 will be
N N
disabled. If using a 738+, zone 9 will be disabled. If using a
N/A [4] N/A 748+, zone 15 will be disabled.
N/A N [5] N N/A
No tamper bypass N [6] N Tamper follows zone bypass definition
N/A N [7] N N/A
Zone doubling (ATZ)**** N [8] N Enabled****
N N
**** NOTE 2: This feature applies to the 728+, 728DZ8+,
Audible trouble warning [9] Enabled 738+ and 748+ only.
Duress N [10] N Enabled
Keypad zone 1 supervision N [11] N Enabled
Keypad zone 2 supervision N [12] N Enabled
N/A N [BYP] N N/A
N/A N [MEM] N N/A
N/A N [TRBL] N N/A
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Instant = ON 104: N N N N N N N N N N N N 106: N N N N N N N N N N N N
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Follow = ON 108: N N N N N N N N N N N N 110: N N N N N N N N N N N N
1 2 3* 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Delay 2 = ON 112: N N N N N N N N N N N N 114: N N N N N N N N N N N N
SYSTEM A / STAY SYSTEM A / STAY
If ON, zone is armed on 1 2 3* 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
116: N N N N N N N N N N N N 118: N N N N N N N N N N N N
Stay or “System A”
arming
SYSTEM B SYSTEM B
If ON, zone is armed in 1 2 3* 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
120: N N N N N N N N N N N N 122: N N N N N N N N N N N N
“System B” arming
1 2 3* 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Bypass enable = ON 124: N N N N N N N N N N N N 126: N N N N N N N N N N N N
Note: Do not use the Intellizone feature and an entry delay for the same zone, otherwise an alarm may occur as a user tries
to disarm the system.
Zones that are not selected at addresses 100 to 114 become “Delay 1” zones.
[9] “Auto Arming” Time Program Installer Code, Master Code or User Code 1
Key [9] flashes. Enter 2-digit hour (00 to 23) and 2-digit minutes (00 to 59).
[MEM] Panel Time Programming Installer Code, Master Code or User Code 1
[MEM] key flashes. Enter 2-digit hour (00 to 23) and 2-digit minutes (00 to 59).
[TRBL] Call Espload Via Telephone Installer Code, Master Code or User Code 1
Panel identifier and PC password (addresses 004 to 007 on page 3) and
computer telephone number (addresses 008 to 015 on page 3) must be
programmed.
[STAY] Cancel Communication Attempts Master Code/User Code 1 only cancel calls to Espload
Until next reportable event. The Installer Code can cancel all communications
Figure 3: N.C. Contacts, without EOL Resistor Figure 4: N.C. Contacts, with EOL Resistor (UL/ULC)
Figure 5: N.O. Contacts, with EOL Resistor (UL/ULC) Figure 6: N.C. Contacts, without EOL Resistor, with Tamper
Recognition
Figure 7: N.C. Contacts, with EOL resistor, with Tamper and Wire
Fault Recognition (UL/ULC)
Figure 8: N.C. Contacts, without EOL Resistor Figure 9: N.C. Contacts, without EOL Resistor, with Tamper
Recognition
Address 088, [MEM] = “ON” (EOL resistor disabled) Address 088,[MEM] = “ON” (EOL resistor disabled)
[10] = “OFF” Tamper/Wire Fault disabled. [10] = (See Tamper/Wire Fault defintions on
[11] = “OFF” [11] = page 11.)
Address 090, [8] = “ON” (ATZ enabled) Address 090,[8] = “ON” (ATZ enabled)
Figure 10: N.O. Contacts, with EOL Resistor, with Tamper and
Wire Fault Recognition (UL/ULC)
Figure 11: Connecting One Keypad Zone Figure 12: Connecting Two Keypad Zones (639 only)
:
Figure 14: Keypad Tamper Switch Connection Figure 15: PGM Output Relay Figure 16: Ground Start Circuit
Figure 17: Fire Alarm Zone Connections Figure 18: Fire Reset
It is recommended that all 4-wire smoke detectors be connected using a daisy chain configuration
Keypads
- LED Keypads 636, and 646
- LCD Keypad 642
The maximium number of keypads per installation is
dependent on the auxiliary output, which is not to exceed
400mA. Refer to the Reference & Installation Manual for the
current consumption table. Refer to Figure 11, Figure 12
and Figure 13 on pages 14 and 15 for information keypad
zone connections*.
Keypads
- LED Keypads 636, and 646
- LCD Keypad 642
The maximium number of keypads per installation is
dependent on the auxiliary output, which is not to exceed
400mA. Refer to the Reference & Installation Manual for the
current consumption table. Refer to Figure 11, Figure 12
and Figure 13 on pages 14 and 15 for information keypad
zone connections.
Keypads
- LED Keypads 636, and 646
- LCD Keypad 642
The maximium number of keypads per installation is
dependent on the auxiliary output, which is not to exceed
400mA. Refer to the Reference & Installation Manual for the
current consumption table. Refer to Figure 11, Figure 12
and Figure 13 on pages 14 and 15 for information keypad
zone connections.