Ag Ss Kx6 Fdc400kxe6

This document is a submittal sheet for an MHI R410a inverter heat pump unit with a cooling capacity of 40 kW and heating capacity of 45 kW. It is model FDC400KXE6, which is a 136,500 Btu/h VRF condenser unit. The unit has dimensions of 1690 x 1350 x 720 mm and a net weight of 317 kg. It can connect to between 1-36 indoor units and has a power source of 380V, 3 Phase, 60 Hz.

Uploaded by

Shafik Atwi
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
519 views3 pages

Ag Ss Kx6 Fdc400kxe6

This document is a submittal sheet for an MHI R410a inverter heat pump unit with a cooling capacity of 40 kW and heating capacity of 45 kW. It is model FDC400KXE6, which is a 136,500 Btu/h VRF condenser unit. The unit has dimensions of 1690 x 1350 x 720 mm and a net weight of 317 kg. It can connect to between 1-36 indoor units and has a power source of 380V, 3 Phase, 60 Hz.

Uploaded by

Shafik Atwi
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

Submittal Sheet for KX6 Series

Model: FDC400KXE6

Submittal Sheet for KX6 Series


Model FDC400KXE6: MHI R410a Inverter 136,500 Btu/h (12.5Tons) VRF Condenser Unit
Job Name: Date:

Contractor
: Location:

Engineer: Tag:

Submitted For:  Approval  Record

FDC400KXE6

Nominal Cooling Capacity (Min~Max) 40.0 kW Unit Dimensions


Nominal Heating Capacity (Min~Max) 45.0 kW HxWxD 1690 x 1350 x 720 [mm]
Power Source 380V, 3 Phase, 60 Hz Net Weight 317 kg
Power Consumption 11.27/11.73 kW
Refrigerant: R410a
(Cooling/Heating)
Running Current (Cooling/Heating) 18.4/19.6 A Liquid Piping 1/2”
Breaker Capacity / Max Current 30A / 19.91A Gas Piping 1”
Control Capacity 15%-114% Pre-Charge 11.5 kg
Connection Capacity 50% - 200% Safety Features
Number of connectable indoor units 1 - 36  Compressor overheat protection
Sound Level (Cooling/Heating) 59.5/60 dB(A)  Over current protection
Standard Pressure 50/50 Pa (max)  Blue Fin Anti-Corrosive Treatment
Air Flow 250/220 CMM  Abnormal high pressure protection

AG-SS-KX6-FDC400KXE6 Page 1 of 3
Submittal Sheet for KX6 Series
Model: FDC400KXE6

Model FDC400KXE6: MHI R410a Inverter 136,500 Btu/h (12.5Tons) VRF Condenser Unit

AG-SS-KX6-FDC400KXE6 Page 2 of 3
Submittal Sheet for KX6 Series
Model: FDC400KXE6

Model FDC400KXE6: MHI R410a Inverter 136,500 Btu/h (12.5T) VRF Condenser Unit

Sound Performance for FDC400KXE6 Cooling Sound Performance for FDC400KXE6 Heating

Notes

Other Notes
 The data are measured under the following conditions (ISO-T1).
 Cooling: Indoor temp. of 27°CDB, 19°CWB, and outdoor temp. of 35°CDB. Heating: Indoor temp. of 20°CDB, and outdoor temp. of 7°CDB, 6°CWB. Piping
length is 7.5m.
 Sound values taken in an anechoic chamber. During operation these values may differ to ambient conditions.

Because of our policy of continuous improvement, we reserve right to make changes in all specifications without notice.

AG-SS-KX6-FDC400KXE6 Page 3 of 3