Product Specification 03352 

(Revision N, 3/2017) 

CPC‐II   Oil contamination


resistant
Current‐to‐Pressure Converter 
 Precise fluid
pressure control
Applications   Stable & linear valve
control
The CPC-II (current to pressure
converter, generation II) is an  Included valve
electrohydraulic pressure-regulating linearization table
valve control designed for use in
positioning single-acting steam turbine  Redundant
valve servos. This CPC’s superb inputs/sensors for
accuracy and resolution make it ideal critical applications
for steam turbine valve control and
related turbine speed and load  Accepts signals
control. The CPC accepts a 4–20 mA from redundant
pressure demand signal and controllers
accurately controls oil pressure to
precisely position single-acting steam  Redundant (dual)
turbine governor-valves. Precise and CPCs
stable steam valve control directly
(Master/Slave)
relates to improved steam turbine
speed and load control and reduced functionality
system mechanical wear.  Standard mounting
The CPC’s redundancy features make it ideal for critical steam turbine applications, and hydraulic
where turbine up-time and availability are essential. This converter can be configured to connections
accept redundant pressure demand inputs, from one or two (redundant) controllers, and
vote the input to follow. Alternatively the CPC can be configured to accept signals from  Self cleaning valve
both its internal oil pressure sensor and an external (redundant) oil pressure sensor, and algorithm
use the voted healthy signal.
 Status & health
The CPC’s robust design (strong actuator, corrosion-resistant material, single moving
indication
rotary valve, and self-cleaning port design) makes it ideal for challenging applications
where dirty or contaminated oil may be present.  Control pressure
Optionally two controllers can be connected to a single CPC in a redundant Master/Slave readout
fashion to allow the turbine to continue to operate if either turbine control fails, or on-line
changes are desired. Designed for use in applications requiring full redundancy,  Software service
optionally two CPCs can be applied in a dual-redundant fashion, simplifying the entire tool with trending
system and control wiring.
 Certified for North
Description  American
Hazardous
The CPC is an electrohydraulic pressure-regulating valve control that utilizes a very Locations
accurate internal pressure sensor and PID controller to precisely control steam turbine  Compliant with
valves. The CPC consists of a valve-actuator assembly, pressure sensor, and electronic
driver module. The unit’s driver module accepts one (or two) 4–20 mA pressure setpoints applicable CE
and compares these setpoints to the sensed oil pressure, to accurately control turbine Directives—ATEX,
valve oil pressure. Machinery, PED,
and EMC
The CPC controls oil pressure by porting supply-oil to its control-oil output port (turbine
valve control oil) or back to the system supply tank. This converter’s special PID  Certified for use in
architecture allows it to perform very stable pressure control during normal conditions, explosive
and respond in milliseconds to desired valve step changes during system or plant
transients. As a means of protecting the turbine, an internal valve-return-spring forces the atmospheres within
CPC to a failsafe position (port oil to drain) and safely close turbine control valves upon the Russian
any internal unit failure (electrical input power failure, pressure sensor failure, processor Federation
failure, etc.).
Woodward 03352 p.2
The CPC is factory and/or field configurable via a computer- Electrical
based service tool. The CPC’s PCI Service Tool uses a simple Input Supply: (18 to 32) V (dc) @ 1.5 A steady state, 8 A
user-friendly format to allow users to easily configure, peak (100 ms)
calibrate, and adjust all internal functions and PID control Analog Input Signals: Isolated (4 to 20) mA (250 Ω input
settings. The CPC includes a 4–20 mA output channel to impedance)
indicate control oil pressure level, and unit alarm and shutdown Analog Output Signal: (4 to 20) mA; maximum external load:
relay outputs for use as unit health and status indications into 300 Ω, Accuracy = ±1 % of full scale
the system controller or plant DCS. Discrete Inputs: Optically Isolated (requires 24 V (dc) wetting
voltage)
Features  Discrete Output Rating: 1 A @ 30 V (dc)
Service Tool Port: RS-232 communications via straight-
through serial cable
A Manual Stroke function allows users to manually stroke the
CPC output pressure (turbine valve position) locally at the Hydraulic
unit, via an internal Manual Stroke Screw. This local manual Fluid Types: Mineral or synthetic based oils may be used.
stroke function is designed with built in security logic to Contact Woodward for specific oil recommendations.
protect the users from un-intentional use of this function Maximum Input Supply Pressure: 25 bar / 363 psi
during normal operation. Manual Stroke capability is also Maximum Output Location
CPC-II Model
available via remotely or locally via the CPC’s computer Pressure Range* Rating
based PCI Tool. (0 to 25) bar /
9907-1197 Zone 1 & 2
(0 to 363) psi
Since flow through single and staged inlet steam valves tend (0 to 25) bar /
to be non-linear throughout their flow range, turbine controls 9907-1198 Zone 2
(0 to 363) psi
are typically de-tuned to compensate for instability or (0 to 10) bar /
9907-1199 Zone 1 & 2
sluggish control points throughout this range. As a way of (0 to 145) psi
allowing turbine control optimization, the CPC includes an (0 to 10) bar /
9907-1200 Zone 2
eleven-point linearization table to allow turbine OEMs or (0 to 145) psi
users to compensate for poor valve linearization by digitally (0 to 10) bar /
9907-1228 Zone 2
(0 to 145) psi
linearizing the control to valve flow relationship.
(0 to 10) bar /
9907-1349 Zone 1 & 2
Because many turbine users utilize redundant pressure (0 to 145) psi
converters to increase system reliability, and because these * Note: The recommended maximum output pressure is less than
type of applications are prone to silting build-up problems in 70 % of the supply for the best dynamic performance.
the slave unit, a special “Silt Buster” (patent pending) routine Recommended Filtration: (24 to 40) μm nominal, 75 or ISO
is also configurable to routinely remove internal silt build-up. 20/16 Class
Recommended Viscosity 20 to 100 cSt
Accessories  Specific Gravity: 0.6 to 1.0
Flow Capacity: Depends on viscosity and pressure difference
A standard steel adapter plate is available to allow the CPC (see Figure 3)
to easily interface with systems designed for Voith I/H Return/Drain Pressure: Maximum 2 bar (29 psi)
converters. Regulatory Compliance
European Compliance for CE Marking:
Specifications  EMC Directive: 2014/35/EU
ATEX Directive: 2014/34/EU-Zone2, Category 3, Group II G
Performance Ex nA IIC T4 Gc Ip66; - SIRA 11 ATEZ 1310X (Ex d) for
Accuracy: < ±0.2 % of full range Zone 1, Category 2 Group II G, Ex d IIB T4 Gb, and Zone 2
Repeatability: 0.1 % of full range Category 3 Group II G, Ex nA IIC T4 Gc IP66
Temperature Drift: < ±0.01 % of full range /°C Other European/International Compliance:
Pressure stability: < ±2 % of setpoint (Compliance with the following European Directives or
Failsafe Operation: Internal return spring forces Control Port standards does not qualify this product for application of the
oil to drain port on loss of power or detected failures CE Marking.)
Configuration: Computer based Service Tool (RS-232 EAC (Marked): Certified to Technical Regulation CU
communications port) 012/2011 for use in potentially explosive atmospheres per
Certificate RU C-US.MШ06.B.00064 as 1Ex d IIB T4 Gb X or
Physical 2Ex nA IIC T4 Gc X
Dimensions: See outline drawings EAC: Declared to Technical Regulation CU 020/2011 On
Height x Width x Depth: Approx. (290 x 270 x 270) mm Electromagnetic Compatibility of Technical Equipment
Weight: Approximately 25 kg (55 lb) without oil Declaration of Conformity Registration No: RU Д-
Fluid Ports: See outline drawings US.АЛ32.В.05498
Mounting: Any attitude, Four M10 threaded holes, IECEx: CSA 11.0017X (Ex d) for Zone 1, Category 2, Group
23 mm deep, on the face with the hydraulic ports. II G, Ex d IIB T4 Gb, and CSA 11.0017X (Ex nA) for Zone 2,
Adequate support must be provided for the unit. Category 3, Group II G, Ex nA IIC T4 Gc IP66
Environmental Machinery Directive: Compliant as a component with
Operating Temperature Range: (–40 to +85) °C 2006/42/EC
Hydraulic Supply Temperature: (15 to 70) °C Pressure Equipment Directive: Compliant as “SEP” per
Immunity: EN61000-6-2 (2005) Article 4.3 to 2014/68/EU
Emissions: EN61000-6-4 (2007) INMETRO: Declared to rule 179: 2010, NCC Certificate
Shock: US MIL-STD-810C method 516.2, procedure 1 (10 G 12.1025X, Ex d IIB T4 Gb and Ex ic nA IIC T4 Gc IP66
Peak, 11 ms duration, saw tooth waveform) North American Compliance:
Vibration: US MIL-STD 810F, M514.5A, Cat. 4 (0.015 G²/Hz, CSA: CSA Certified for Class I, Division 1, Groups C and D
(10 to 500) Hz, 1.04 Grms) and Class I, Division 2, Groups A, B, C, and D, T3 at 85 °C
Ingress Protection: IP66 per EN 60529 Ambient for use in Canada and the United States.
Woodward 03352 p.3

Figure 1. CPC-II Outline Drawing

Figure 2. Typical Redundant Control System using a CPC


Woodward 03352 p.4

90
80
70
60

Flow Rate (lpm)


50 New CPC
Capacity
40
Old CPC
30 Capacity
20
10
0
0 10 20
VIS-158
Differential Pressure - Bar 07-11-12
(P1 to Pc or Pc to Drain)

Figure 3. CPC-II Flow Capacity

SERVICE TOOL PORT MANUAL STROKE SCREW

24VDC INPUT POWER

CONTROL DEMAND SIGNAL (4-20 mA)


OPTIONAL REDUNDANT DEMAND SIGNAL (4-20 mA)
ACTUATOR
ELECTRICAL DRIVER SELECT MASTER UNIT
MODULE REDUNDANT UNIT IN-CONTROL STATUS
CONTROL PRESSURE READOUT
SHUTDOWN STATUS
ALARM/IN-CONTROL STATUS
REDUNDANT IN-CONTROL STATUS

CPC-II (ANALOG)
(DISCRETE IN)
(DISCRETE OUT)

OPTIONAL
REDUNDANT
PRESSURE PRESSURE
SENSOR SENSOR

EXTERNAL
OIL FILTER

SUPPLY TO TANK/
OIL DRAIN VIS-157 CUSTOMER SERVO
VIS-157
07-10-30 VALVE 07-11-12

Figure 4. CPC-II Interface Schematic

Technical Manual: 26615

For more information contact:


PO Box 1519, Fort Collins CO, USA 80522-1519
1041 Woodward Way, Fort Collins CO 80524
Tel.: +1 (970) 482-5811
www.woodward.com

Distributors & Service


Woodward has an international network of distributors and service facilities.
For your nearest representative, call the Fort Collins plant or see the
Worldwide Directory on our website.

This document is distributed for informational purposes only. It is not to be construed as


creating or becoming part of any Woodward contractual or warranty obligation unless
expressly stated in a written sales contract.
Copyright © Woodward 2008–2015, All Rights Reserved