Inside Inside
Area Height in Volume
SI.NO Room Name Condition Condition Occupancy
(Sq.ft) feet (Cu.ft)
DBT F DBT C
1 Office 392 11 4312 70 21 7
2 Discussion Room 110 11 1210 70 21 4
BASIS OF DESIGN
Total Heat
Selected Lights Appliances Refrigeration
Btu/hr SHF ADP Deh.CFM
Fresh CFM (Watt/Sqft) (W) Tonnage (TR)
60 1.5 1500 20152 0.91 54 1260 2.16
26 1.5 0 7299 0.86 54 435 0.81
CFM Tonnage Selected Area / SELECTED EQUIP
TYPE
(TR) (TR) TR TR
3.1 3.1 124 1.5TR x 2Nos Cassette
1.1 1.1 101 1.5TR x 1No Cassette
Height in Volume in Air Change per
S.NO LOCATION Area in SQ.FT
Feet Cu.ft HR
1 MIXER & RM TESTING ROOM 1087 12 13044 20
BASIS OF DESIGN
OUTDOOR CONDITION INDOOR CONDITION
AIR FLOW RATE IN CFM
DB WB RH W DB WB
4400 92 82 64 146 68
INDOOR CONDITION
SENSIBLE LOAD in LATENT LOAD in
RH W TOTAL CAPACITY IN TR
BTU / HR BTU / HR
50 51 114048 285437 33
BASIS OF DESIGN
Air
Height in Volume in
S.NO Location Area in SQ.FT Change
Feet Cu.ft
per HR
1 FURNACE ROOM 353 12 4236 15
BASIS OF DESIGN
Air
Height in Volume in
S.NO LOCATION Area in SQ.FT Change
Feet Cu.ft
per HR
1 MIXER & RM TESTING ROOM 1087 12 13044 20
IGN
Exhaust Air Quantity in CFM Fresht Air Quantity in CFM
1100 1000
AIR FLOW RATE IN CFM
4400
HVAC WORKS - SUMMARY
S.No Description Amount (INR)
1 Highside BOQ - Equipment 2199960
2 Lowside BOQ - Ancillary Works 2305219
Grand Total - INR 4505179
BILL OF QUANTITIES - HVAC WORKS
S.No Description Unit Qty
TREATED FRESH AIR UNIT - LAB AREA
Supply of Treated Fresh Air unit Double Skin with Thermal Break Profile of 50 mm thick PUF
insulated Air handling Unit, comprising of the following as,8 row deep DX - cooling coil with
inlet and outlet piping connections for Once Throw AHU. Face velocity for both the chilled
1 water cooling coils should not exceed 500FPM. Draw throw DIDW backward curved Nos 1
centrifugal fan with aerofoil blade. 20 micron pre filter , 10micron fine filter, Three Circuit as
11.0TR x 3Nos. AHU will comprise of heater bank section with humidistat control to maintain
required RH
Capacity : 33 TR, Air Quantity : 4400 CFM, ESP : 500Pa
Supply of Condensing unit for Treated Fresh air Unit with single skin powder coated cabinets,
having all necessary controls for HP/LP switch, the unit should comprise of scroll/rotary
2
compressor . The outdoor unit should be powder coated , refrigerant is R-22 (MAKE :
BLUESTAR) - LAB AREA
a Capacity : 11.0 TR, Nos 3
Supply of Ceiling Suspended cassette units with single skin powder coated cabinets, having
all necessary controls for HP/LP switch, the unit should comprise of scroll/rotary compressor .
3
The outdoor unit should be powder coated , refrigerant is R-22 (Make -
BLUESTAR) - OFFICE AREA
a 1.5 TR, Four way cassette unit Nos 3
4 Supply of cabinet type ventilation fans of following capacity
Supply of Cabinet type Fresh air Fan with double skin 25mm thick PUF panel casing, 20
micron filter, DIDW Centrifugal fan - FURNACE ROOM
a Air Quantity - 1000 CFM, ESP -250Pa. No 1
Supply of Cabinet type Exhaust air Fan with double skin 25mm thick PUF panel casing,
DIDW Centrifugal fan - FURNACE ROOM
b Air Quantity - 1100 CFM, ESP -300Pa. No 1
Supply of Cabinet type Exhaust air Fan with double skin 25mm thick PUF panel casing,
DIDW Centrifugal fan, - LAB AREA
c Air Quantity - 4400 CFM, ESP -350Pa. No 1
TOTAL
GST @ 28%
GST @ 18%
GRAND TOTAL
Material Rate Material Amount
884042 884042
138100 414300
58586 175758
75400 75400
72500 72500
117450 117450
1739450
412748
47763
2199960
BILL OF QUANTITIES - HVAC WORKS
S.No Description Unit Qty
TREATED FRESH AIR UNIT:
Installation, testing and Commissioning of Treated Fresh Air unit Double Skin with Thermal Break
Profile of 50 mm thick PUF insulated Air handling Unit, comprising of the following as,8 row deep DX -
cooling coil with inlet and outlet piping connections for Once Throw AHU. Face velocity for both the
1 chilled water cooling coils should not exceed 500FPM. Draw throw DIDW backward curved centrifugal Nos 1
fan with aerofoil blade. 20 micron pre filter , 10micron fine filter, Three Circuit as 11.0TR x 3Nos. AHU
will comprise of heater bank section with humidistat control to maintain required RH
Capacity : 33 TR, Air Quantity :
4400 CFM, ESP : 500Pa
Installation, testing and Commissioning Condensing Outdoor unit for Treated Fresh air Unit single skin
powder coated cabinets, having all necessary controls for HP/LP switch, the unit should comprise of
2
scroll/rotary compressor . The outdoor unit should be powder coated , refrigerant is R-22 (Make -
BLUESTAR)
a Capacity : 11.0 TR, Nos 3
Installation of Ceiling Suspended cassette units with single skin powder coated cabinets, having all
3 necessary controls for HP/LP switch, the unit should comprise of scroll/rotary compressor . The outdoor
unit should be powder coated , refrigerant is R-22 (Make - BLUESTAR)
a 1.5 TR, Four way cassette unit Nos 3
4 Installation of cabinet type ventilation fans of following capacity & Specification.
Installation of Cabinet type Fresh air Fan with double skin 25mm thick PUF panel casing, 20
micron filter, DIDW Centrifugal fan - FURNACE ROOM
a Air Quantity - 1000 CFM, ESP -250Pa. No 1
Installation of Cabinet type Exhaust air Fan with double skin 25mm thick PUF panel casing, DIDW
Centrifugal fan - FURNACE ROOM
b Air Quantity - 1100 CFM, ESP -300Pa. No 1
Installation of Cabinet type Exhaust air Fan with double skin 25mm thick PUF panel casing, DIDW
Centrifugal fan, - LAB AREA Air
c Quantity - 4400 CFM, ESP -350Pa. No 1
Supply and Installation of 22G hard drawn copper pipe with 13mm XLPE insulation with supports for
5 Rmt 100
ductable system suction and liquid pipes together.
Supply and Installation of PVC condensate piping with 9mm thick XLPE insulation and supports of
6
following szes
a 25mm Rmt 30
Supply and Installation of communication cable between IDU and ODU for ductable unit with ISI 20MM
7 Rmt 150
PVC conduit
8 Supply and Installation of fire rated canvass connection Nos 5
9 Supply and Charging of R-22 refrigerant for ductable system Kgs 41
EMERGENCY PUSH BUTTON STATION FOR AHU :
10 Nos 3
Supply, installation of emergency push button station
11 Starter Panel for Ventilation units outdoor type floor mounted Nos 3
12 Starter Panel for TFA unit outdoor type floor mounted No 1
13 Supply and Installation of GI Made Rectangular ducting with supports of following guages
a 0.63mm - 24 G Sqmtr 120
b 0.80mm -22 G Sqmtr 60
c 1.0mm - 20 G Sqmtr 30
Supply and Installation of 10mm thick open cell XLPE accosound insulation board with adhesive and
14 Sqmtr 45
tape
Supply and Installation of 9mm thick open cell XLPE insulation without aluminum foil with adhesive
15 Sqmtr 120
and tape
Supply and Installation of extruded aluminum linear bar grille with required reflection as per architects
16 Sqmtr 6
approved color pattern, size of the grille iis 150mm height or wide
17 Supply and Installation of G.I volume control damper Sqmtr 3
18 Supply and Installation of MS Outdoor Stand for Ductable Unit Nos 3
19 Supply and Installation of MS Outdoor Stand for Cassette Unit Nos 3
20 4C x 16 Sq.mm copper armoured cable(from isolator near ODU to ODU) Rmt 30
21 4C x 10 Sq.mm copper armoured cable(from starter panel to AHU Motor) Rmt 10
22 4C x 6 Sq.mm copper armoured cable (from isolator near ventilation unit to Unit) Rmt 30
23 4C x 4 Sq.mm copper armoured cable (from isolator near ODU toODU - Casstte) Rmt 30
24 Supply and Installation of copper lugs Lot 1
25 Supply and Installation of PG Gland Lot 1
26 Supply and Installation of flexible weather proof PVC hose. Lot 1
27 Supply and Installation of GI wire earthing Lot 1
28 Supply and Installation of powder coated cable tray with cover for refrigerant pipeand electrical cables Lot 1
29 Supply and Installation of spring isolator for Indoor cassette units Nos 12
30 Supply and Installation of rubber mounts for ventilation, Cassette ODU and TFA Units Nos 60
TOTAL
GST @ 18%
GST @ 18%
GRAND TOTAL
HVAC WORKS
Material Rate Labour Rate Material Amount Labour Amount
33750 33750
27000 81000
4725 14175
6075 6075
6075 6075
20250 20250
800 50 80000 5000
325 50 9750 1500
425 25 63750 3750
6000 2000 30000 10000
700 25 28700 1025
4500 1500 13500 4500
31395 10125 94185 30375
44396 14175 44396 14175
3120 945 374400 113400
3250 945 195000 56700
3380 1013 101400 30375
950 250 42750 11250
600 250 72000 30000
6000 1500 36000 9000
7500 1500 22500 4500
5000 65 15000 195
1800 50 5400 150
965 75 28950 2250
850 75 8500 750
775 75 23250 2250
650 75 19500 2250
5600 1200 5600 1200
8521 1620 8521 1620
6874 1000 6874 1000
18475 6871 18475 6871
48713 15410 48713 15410
725 100 8700 1200
354 75 21240 4500
1427054 526521
256870
94774
2305219