This document provides specifications for HVAC equipment for various rooms including an office, discussion room, mixer and testing room, and furnace room. It includes details like room areas and dimensions, basis of design including airflow rates and heat loads, selected equipment with capacities, and bill of quantities for the HVAC works. The total estimated cost is INR 4,505,179 which includes the highside equipment cost of INR 21,99,960 and lowside ancillary works cost of INR 23,05,219.

Uploaded by

Ganesh Ram
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
225 views16 pages

VS Lab & Office - Hvac Boq 29032016

This document provides specifications for HVAC equipment for various rooms including an office, discussion room, mixer and testing room, and furnace room. It includes details like room areas and dimensions, basis of design including airflow rates and heat loads, selected equipment with capacities, and bill of quantities for the HVAC works. The total estimated cost is INR 4,505,179 which includes the highside equipment cost of INR 21,99,960 and lowside ancillary works cost of INR 23,05,219.

Uploaded by

Ganesh Ram
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 16

Inside Inside

Area Height in Volume


SI.NO Room Name Condition Condition Occupancy
(Sq.ft) feet (Cu.ft)
DBT F DBT C

1 Office 392 11 4312 70 21 7

2 Discussion Room 110 11 1210 70 21 4


BASIS OF DESIGN

Total Heat
Selected Lights Appliances Refrigeration
Btu/hr SHF ADP Deh.CFM
Fresh CFM (Watt/Sqft) (W) Tonnage (TR)

60 1.5 1500 20152 0.91 54 1260 2.16

26 1.5 0 7299 0.86 54 435 0.81


CFM Tonnage Selected Area / SELECTED EQUIP
TYPE
(TR) (TR) TR TR

3.1 3.1 124 1.5TR x 2Nos Cassette

1.1 1.1 101 1.5TR x 1No Cassette


Height in Volume in Air Change per
S.NO LOCATION Area in SQ.FT
Feet Cu.ft HR

1 MIXER & RM TESTING ROOM 1087 12 13044 20


BASIS OF DESIGN
OUTDOOR CONDITION INDOOR CONDITION
AIR FLOW RATE IN CFM
DB WB RH W DB WB

4400 92 82 64 146 68
INDOOR CONDITION

SENSIBLE LOAD in LATENT LOAD in


RH W TOTAL CAPACITY IN TR
BTU / HR BTU / HR

50 51 114048 285437 33
BASIS OF DESIGN

Air
Height in Volume in
S.NO Location Area in SQ.FT Change
Feet Cu.ft
per HR

1 FURNACE ROOM 353 12 4236 15

BASIS OF DESIGN
Air
Height in Volume in
S.NO LOCATION Area in SQ.FT Change
Feet Cu.ft
per HR

1 MIXER & RM TESTING ROOM 1087 12 13044 20


IGN

Exhaust Air Quantity in CFM Fresht Air Quantity in CFM

1100 1000

AIR FLOW RATE IN CFM

4400
HVAC WORKS - SUMMARY
S.No Description Amount (INR)
1 Highside BOQ - Equipment 2199960
2 Lowside BOQ - Ancillary Works 2305219
Grand Total - INR 4505179
BILL OF QUANTITIES - HVAC WORKS
S.No Description Unit Qty

TREATED FRESH AIR UNIT - LAB AREA


Supply of Treated Fresh Air unit Double Skin with Thermal Break Profile of 50 mm thick PUF
insulated Air handling Unit, comprising of the following as,8 row deep DX - cooling coil with
inlet and outlet piping connections for Once Throw AHU. Face velocity for both the chilled
1 water cooling coils should not exceed 500FPM. Draw throw DIDW backward curved Nos 1
centrifugal fan with aerofoil blade. 20 micron pre filter , 10micron fine filter, Three Circuit as
11.0TR x 3Nos. AHU will comprise of heater bank section with humidistat control to maintain
required RH
Capacity : 33 TR, Air Quantity : 4400 CFM, ESP : 500Pa

Supply of Condensing unit for Treated Fresh air Unit with single skin powder coated cabinets,
having all necessary controls for HP/LP switch, the unit should comprise of scroll/rotary
2
compressor . The outdoor unit should be powder coated , refrigerant is R-22 (MAKE :
BLUESTAR) - LAB AREA
a Capacity : 11.0 TR, Nos 3

Supply of Ceiling Suspended cassette units with single skin powder coated cabinets, having
all necessary controls for HP/LP switch, the unit should comprise of scroll/rotary compressor .
3
The outdoor unit should be powder coated , refrigerant is R-22 (Make -
BLUESTAR) - OFFICE AREA

a 1.5 TR, Four way cassette unit Nos 3


4 Supply of cabinet type ventilation fans of following capacity
Supply of Cabinet type Fresh air Fan with double skin 25mm thick PUF panel casing, 20
micron filter, DIDW Centrifugal fan - FURNACE ROOM
a Air Quantity - 1000 CFM, ESP -250Pa. No 1

Supply of Cabinet type Exhaust air Fan with double skin 25mm thick PUF panel casing,
DIDW Centrifugal fan - FURNACE ROOM
b Air Quantity - 1100 CFM, ESP -300Pa. No 1

Supply of Cabinet type Exhaust air Fan with double skin 25mm thick PUF panel casing,
DIDW Centrifugal fan, - LAB AREA
c Air Quantity - 4400 CFM, ESP -350Pa. No 1

TOTAL
GST @ 28%
GST @ 18%
GRAND TOTAL
Material Rate Material Amount

884042 884042

138100 414300

58586 175758

75400 75400

72500 72500

117450 117450

1739450
412748
47763
2199960
BILL OF QUANTITIES - HVAC WORKS
S.No Description Unit Qty

TREATED FRESH AIR UNIT:


Installation, testing and Commissioning of Treated Fresh Air unit Double Skin with Thermal Break
Profile of 50 mm thick PUF insulated Air handling Unit, comprising of the following as,8 row deep DX -
cooling coil with inlet and outlet piping connections for Once Throw AHU. Face velocity for both the
1 chilled water cooling coils should not exceed 500FPM. Draw throw DIDW backward curved centrifugal Nos 1
fan with aerofoil blade. 20 micron pre filter , 10micron fine filter, Three Circuit as 11.0TR x 3Nos. AHU
will comprise of heater bank section with humidistat control to maintain required RH
Capacity : 33 TR, Air Quantity :
4400 CFM, ESP : 500Pa

Installation, testing and Commissioning Condensing Outdoor unit for Treated Fresh air Unit single skin
powder coated cabinets, having all necessary controls for HP/LP switch, the unit should comprise of
2
scroll/rotary compressor . The outdoor unit should be powder coated , refrigerant is R-22 (Make -
BLUESTAR)

a Capacity : 11.0 TR, Nos 3

Installation of Ceiling Suspended cassette units with single skin powder coated cabinets, having all
3 necessary controls for HP/LP switch, the unit should comprise of scroll/rotary compressor . The outdoor
unit should be powder coated , refrigerant is R-22 (Make - BLUESTAR)

a 1.5 TR, Four way cassette unit Nos 3


4 Installation of cabinet type ventilation fans of following capacity & Specification.
Installation of Cabinet type Fresh air Fan with double skin 25mm thick PUF panel casing, 20
micron filter, DIDW Centrifugal fan - FURNACE ROOM
a Air Quantity - 1000 CFM, ESP -250Pa. No 1

Installation of Cabinet type Exhaust air Fan with double skin 25mm thick PUF panel casing, DIDW
Centrifugal fan - FURNACE ROOM
b Air Quantity - 1100 CFM, ESP -300Pa. No 1

Installation of Cabinet type Exhaust air Fan with double skin 25mm thick PUF panel casing, DIDW
Centrifugal fan, - LAB AREA Air
c Quantity - 4400 CFM, ESP -350Pa. No 1

Supply and Installation of 22G hard drawn copper pipe with 13mm XLPE insulation with supports for
5 Rmt 100
ductable system suction and liquid pipes together.

Supply and Installation of PVC condensate piping with 9mm thick XLPE insulation and supports of
6
following szes
a 25mm Rmt 30

Supply and Installation of communication cable between IDU and ODU for ductable unit with ISI 20MM
7 Rmt 150
PVC conduit

8 Supply and Installation of fire rated canvass connection Nos 5


9 Supply and Charging of R-22 refrigerant for ductable system Kgs 41

EMERGENCY PUSH BUTTON STATION FOR AHU :


10 Nos 3
Supply, installation of emergency push button station
11 Starter Panel for Ventilation units outdoor type floor mounted Nos 3
12 Starter Panel for TFA unit outdoor type floor mounted No 1

13 Supply and Installation of GI Made Rectangular ducting with supports of following guages

a 0.63mm - 24 G Sqmtr 120


b 0.80mm -22 G Sqmtr 60
c 1.0mm - 20 G Sqmtr 30
Supply and Installation of 10mm thick open cell XLPE accosound insulation board with adhesive and
14 Sqmtr 45
tape
Supply and Installation of 9mm thick open cell XLPE insulation without aluminum foil with adhesive
15 Sqmtr 120
and tape

Supply and Installation of extruded aluminum linear bar grille with required reflection as per architects
16 Sqmtr 6
approved color pattern, size of the grille iis 150mm height or wide

17 Supply and Installation of G.I volume control damper Sqmtr 3


18 Supply and Installation of MS Outdoor Stand for Ductable Unit Nos 3
19 Supply and Installation of MS Outdoor Stand for Cassette Unit Nos 3
20 4C x 16 Sq.mm copper armoured cable(from isolator near ODU to ODU) Rmt 30
21 4C x 10 Sq.mm copper armoured cable(from starter panel to AHU Motor) Rmt 10
22 4C x 6 Sq.mm copper armoured cable (from isolator near ventilation unit to Unit) Rmt 30
23 4C x 4 Sq.mm copper armoured cable (from isolator near ODU toODU - Casstte) Rmt 30
24 Supply and Installation of copper lugs Lot 1
25 Supply and Installation of PG Gland Lot 1
26 Supply and Installation of flexible weather proof PVC hose. Lot 1
27 Supply and Installation of GI wire earthing Lot 1

28 Supply and Installation of powder coated cable tray with cover for refrigerant pipeand electrical cables Lot 1

29 Supply and Installation of spring isolator for Indoor cassette units Nos 12
30 Supply and Installation of rubber mounts for ventilation, Cassette ODU and TFA Units Nos 60
TOTAL
GST @ 18%
GST @ 18%
GRAND TOTAL
HVAC WORKS
Material Rate Labour Rate Material Amount Labour Amount

33750 33750

27000 81000

4725 14175

6075 6075

6075 6075

20250 20250

800 50 80000 5000

325 50 9750 1500

425 25 63750 3750

6000 2000 30000 10000


700 25 28700 1025

4500 1500 13500 4500

31395 10125 94185 30375


44396 14175 44396 14175

3120 945 374400 113400


3250 945 195000 56700
3380 1013 101400 30375

950 250 42750 11250


600 250 72000 30000

6000 1500 36000 9000

7500 1500 22500 4500


5000 65 15000 195
1800 50 5400 150
965 75 28950 2250
850 75 8500 750
775 75 23250 2250
650 75 19500 2250
5600 1200 5600 1200
8521 1620 8521 1620
6874 1000 6874 1000
18475 6871 18475 6871

48713 15410 48713 15410

725 100 8700 1200


354 75 21240 4500
1427054 526521
256870
94774
2305219