DATA SHEET 260kVA

This document provides specifications for a Leroy Somer LSA 46.2 L9 / 4p generator including: 1) Main data such as generator type, power output, voltage, frequency, and ambient conditions. 2) Electrical data including efficiency levels at various power factors. 3) Reactance and time constant values. 4) Mounting details such as bearing type and orientation. 5) Cooling, protection, and ventilation details.

Uploaded by

bang nal
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
106 views5 pages

DATA SHEET 260kVA

This document provides specifications for a Leroy Somer LSA 46.2 L9 / 4p generator including: 1) Main data such as generator type, power output, voltage, frequency, and ambient conditions. 2) Electrical data including efficiency levels at various power factors. 3) Reactance and time constant values. 4) Mounting details such as bearing type and orientation. 5) Cooling, protection, and ventilation details.

Uploaded by

bang nal
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 5

Date : LS Reference : 16207 2

16-Jul-13 1
1
1
Moteurs Leroy Somer +65 6266 1726 Author : PH 1
Leroy Somer (SEA) Pte Ltd +65 6262 1953
36 Lok Yang Way, Jurong 16207 1
Singapore 628641 PH A462-09041B1RH35-xxxxxx
Subject: Site : V3.31 o - 05/2013 1
Duty: Base Rating Prime mover : Reciprocating engine 1
Industry: Industrial Applications Manufacturer : 1
Application : Type : 1
Constraint: 1

Main data: Quantity


Generator type: LSA 46.2 L9 / 4p 1 1
Power: 260 kVA 208 kWe 223 kWm 1
Voltage: 380V Star serial ± 5% Nominal current: 395 A 1
Power factor: 0,8 nominal 1
Frequency: 50 Hz Speed: 1500 rpm 1
Winding type : n° 6 (p2/3) Ambient: 40 °C 1
Insulation / Temperature rise : H/H Altitude: 1000 m 1

Electrical data: C
Efficiency: 110% 100% 75% 50% 25%
Power factor 0,8: 92,9 % 93,2 % 93,6 % 93,4 % 90,8 % 1
Power factor 1,0: 95,3 % 95,4 % 95,4 % 94,7 % 91,7 % 1

Reactances Unsaturated, (rated KVA): (%) time constants:


SCR: Xd Xq X'd X'q X"d X"q X2 Xo T'do T'd T''d Ta
0,47 304 155 1,7 2,170 0,099 0,010 0,015 1
Saturated, (rated KVA): (%) Seconds
Ra (%) Xds Xqs X'ds X'qs X"ds X"qs X2s Xo T''do T'q T"q T''qo
2,0 13,9 109 8,4 10,3 9,3 1,7 0,017 NA 0,009 0,135 1

Mounting : IM1201 1
Mounting : Single bearing Axis : horizontal 1
Rotation : Clockwise (seen when facing the D-end) 1
Bearing type: anti friction bearing - Sealed for life 2
Bearing insulation : Not insulated 1
Flector type : cylindrical with keyway 1
Balancing : Half key / balancing class : G2,5 (std) 1
Flange : To defined later 1
Shaft height : 280 mm / Width : 457 mm 1
Axial clearance : Standard 1

Comments: 1
-
Cooling : IC01 1
Protection : IP23 1
Cooler : Coolant : Air / Temperature : 40 °C 1
Air quality : Clean 1
1
Ventilation (internal) : Self vent. 1
Filter : without filter 1
Ducting (I / O) : No 1

Comments: 1

16207 rev. 2 Page 1


Date : LS Reference : 16207 2
16-Jul-13 1
1
1
-
Connection & regulation: Radio int. suppression: Class N 1
Parallel operation : Island mode ( 0F ) 1
Type of excitation: AREP 1
Sustained three phase short circuit : > 3 x FLC for 10s. 1
AVR type: R450 (In terminal box) 1
Voltage sensing : In terminal box / Not supplied 1

Comments: 1
-
Protection and measurement accessories 1
Without guide bearing sensor : 1
Without Winding sensors : 1
Without Anti-condensation heater : 1

Comments:
1
-
Terminal box :
Power connection : 3 connectors (internal neutral) 1
Line side outlet : Left hand side (viewed from drive end) 1
Gland plate : Non magnetic 1

Comments: 1
-
Various items :
Overspeed : 1800 rpm / Duration (min.) : 2 1
Requested noise level : 1
Vibration level : 1

Comments: 1
specific text to mention in drawings : 0 1
Paint : C3L - Primary - RAL 7032 1
Documentation : PDF manual Language : 0 1

Comments: 1
-
Controls :
Rules : CEI 1
QUAL/INES/006 001 Measurement of winding resistance 1
QUAL/INES/006 021 Insulation check on sensors (when fitted) 1
QUAL/INES/006 002 Voltage balance and phase order check 1
QUAL/INES/006 007 Overspeed test 1
QUAL/INES/006 009 High potential test 1
QUAL/INES/006 010 Insulation resistance measurement 1
1
-

16207 rev. 2 Page 2


Date : LS Reference : 16207 2
16-Jul-13

Author : PH V3.31 o - 05/2013


Main curves

ALTERNATOR 16207
LSA 46.2 L9 / 4p - 260kVA - 380V - 1500 rpm - 50 Hz
Capability Curve Un max
Un
Un min

kWe / rated kVA


PF -0,8 PF -0,9 PF 0,9 PF 0,8
PF -0,7 1 0,8 PF 0,7

0,8
PF -0,6 PF 0,6

PF -0,5
0,6 PF 0,5

PF -0,4 PF 0,4
0,4
PF -0,3 PF 0,3

PF -0,2 0,2 PF 0,2

PF -0,1 PF 0,1

0
-1 -0,8 -0,6 -0,4 -0,2 0 0,2 0,4 0,6 0,8 1
kVAr / rated kVA

Stator Current decrement curves


Isc (Per rated current - rms) Symetrical phase to neutral short circuit

Symetrical two phase short circuit

16 Symetrical three phase short circuit

Heat damage curve limit


14
short circuit at generator terminals

12

10

0
0,001 0,01 0,1 1 10 100
Time (second.)

16207 rev. 2 Page 1


Date : LS Reference : 16207 2
16-Jul-13

Author : PH V3.31 o - 05/2013


Main curves

ALTERNATOR 16207
LSA 46.2 L9 / 4p - 260kVA - 380V - 1500 rpm - 50 Hz
Efficiency Curves
PF 1 PF 0,8
96

95
Efficiency - Rendement en %

94

93

92

91

90

89

88
25% 50% 75% 100%
Load - Charge - % of rated electrical kWe

Transient Voltage Variation


Transient voltage dip curve Transient voltage rise curve
versus load impact versus load rejection
30% 25%
Voltage dip - (% of rated voltage)

Voltage rise - (% of rated voltage)

25%
20%

20%
15%
15%

10%
10%

5% 5%

0% 0%
PF = 0,6 PF = 0,8
0,0 0,4 0,8 1,2 1,6 2,0 0,00 0,25 0,50 0,75 1,00 1,25 1,50

Load inrush - Appel de charge - % of rated kVA kVA shedding at P.F. Delestage de charge - % of ratedPF =kVA
0,8

16207 rev. 2 Page 2


Date : LS Reference : 16207 2
16-Jul-13

Author : PH V3.31 o - 05/2013


Main curves

ALTERNATOR 16207
LSA 46.2 L9 / 4p - 260kVA - 380V - 1500 rpm - 50 Hz

Thermal Damage Curve

Stator current
3 (per rated current)

2,5

1,5

1
10 100 1000 10000
Maximum duration (second.)

Unbalance Load Curve Stator Earth Fault Current

Negative phase sequence Current Fault Current (A)


C : Extensive damage
(per rated current) 75 B : Considerable damage
3
A : Acceptable damage

2 50 C

B
1 25

A
0 0
1 10 100 1000 10000 0 1 2 3 4 5 6 7 8 9 10 11 12

Maximum duration of fault (second.) Maximum duration of fault (second.)

16207 rev. 2 Page 3