Clean Agent Fire Suppression System
25 and 42 Bar,
FK 1230 (FK-5-1-12)
Clean Agent System
25 and 42 bar fire suppression
system to protect high-value
assets, using an agent safe for
humans and the environment
42 Bar FK-5-1-12 Clean Agent Fire Suppression System
Typical FK1230 (FK-5-1-12) Clean Agent System Layout
The fire extinguishing system uses FK1230 as fire suppression agent, which is an next-generation
alternative for Halon replacement. FK1230 is used to protect an area that contains valuable equipment or
materials, including but not limited to Museums, Banks, Clean Rooms, Data Centers, and Libraries. Fk1230
leaves no residue behind, has zero ozone depletion and has the lowest atmospheric lifetime among
halocarbon alternatives. FK1230 extinguishes the fire by heat absorption, which results in less downtime,
less cleanup, limited business interruption, and is environment friendly.
Smoke Detector
Discharge Nozzle
MS Piping
Fire Alarm Panel
Audio Alarm
Discharge Hose Warning Sign Board
Discharge Valve Manual Release
& Abort Switch
Clean Agent Cylinder
What is FK1230 (FK-5-1-12) ?
Fk1230 (FK-5-1-12) is a second generation fire suppressant
listed in NFPA 2001 and EPA's Significant New Alternatives
Program (SNAP).
How Does it Work ?
Fk1230 is a synthetic / chemical fire suppression gas and
extinguishes fire by removing the fire's heat elements. It does not
work by oxygen starvation. The concentration of FK-5-1-12 is
typically between 4.5 % to 5.9 % of the room volume.
Fire Suppression Time
The clean agent fire suppression system achieves discharge in 10
seconds. The fire will be extinguished within 30 seconds.
Safe for Humans and the Environment
Fk1230 Clean Agent fire suppression system that offers a wide
margin of safety. It has non ozone depleting potential, and has an
atmospheric lifetime of only 5 days. Person present during the
discharge of FK-5-1-12, are not adversely affected by it.
Why 42 Bar System ?
While a 25 bar system is suitable for the majority of hazards. A 42
bar offers additional flexibility in the design of systems to protect
larger or more complex hazards. These include those
incorporating directional valves for multi-zone protection and
where system cylinders are to be located further from the
protected area.
2 25 and 42 Bar, FK-5-1-12 Clean Agent System
Typical Applications
DATA PROCESSING
Innovation in the speed and capacity of data processing
hardware has exponentially increased the ability to store
critical data. This has led to widespread use of electronic
data storage and the expansion of data centers. Due to
which the data centers have to run 24 by 7 which leads to
an increase in overheating and fire scenarios.
Area of Applications :
• Data Center.
• UPS Rooms.
• Electrical Rooms.
• Sub-Floors Area.
COMMUNICATIONS
Electronic communication are so portable, reliable
and instantaneous that they are taken for granted.
The equipment that provides such communication is
heavily used and could overheat. Data management
and communication hubs could be prone to fire.
Area of Applications :
• Switching Equipment.
• Power & Battery Area.
• Cell Sites.
• Standby Engine Area.
OIL & GAS
Oil refinery operators perform a range of tasks from
the control room. They monitor the processes remotely
through electronic representations shown on monitors.
Operators make sure that processes keep running
as per SOP. They are responsible to take appropriate
actions in case of irregularities or emergencies.
Therefore control room and control system equipment
are vital to safe operations in a facility that handles
processes within refinery. Clean agent suppression
system extinguishes fire without causing harm to the
control room equipment.
Area of Applications :
• Control Room.
• Metering Stations.
3
System Components
NFPA 2001, Requirements For Minimum Fk1230 (FK-5-1-12) Fire Suppression Agent
Values
Fk1230 (FK-5-1-12) agent compiles with NFPA Standard 2001
Class A Class A Class C Class B
Agent
MEC Design Design Design
standard on “Clean Agent Fire Extinguishing Systems.” EPA SNAP
Program (Significant New Alternate Policy)
FK-5-1-12 3.5 4.5 4.5 5.9
The Fk1230 is classified as suitable for use in occupied areas and
has no ozone depleting potential (ODP)
Environmentally Friendly
Description
FK-5-1-12
Description Fk1230 systems reach extinguishing levels in 40 seconds or less,
( FK1230 )
stopping ordinary combustible, electrical, and flammable liquid fires
Ozone Depletion Potential (ODP) 0.0 before they can cause significant damage. That’s the fastest fire
Global Warming Potential (GWP) 1 protection available, When a fire is extinguished this quickly, it means
less damage, lower repair costs, and an extra margin of safety for
Atmospheric Lifetime (Years) 5 DAYS people. It also means less downtime and disruption of business.
SNAP (Yes / No) YES Physical & Chemical Properties
Empirical formulae.................................................CF3CF2C(O)CF3)2
IUPAC Designation...................Dodecafiuoro-2-methylpentan-3one
ASHRAE Designation.............................................FK-5-1-12
Molecular Weight....................................................316.04
Boiling Point at 1 Atm............................................49.2 °C (120.6 °F )
Freezing Point..........................................................-108.0⁰C ( -162.4°F )
No Observed Adverse Effect Level.....................10 %
Lowest Observed Adverse....................................>10%
Fk1230 (FK-5-1-12) Cylinder
The cylinders are manufactured and marked in accordance with IS
7285 Standard and approved by PESO for their use. The cylinders
are available in following sizes. 34ltr., 80ltr, 120ltr and 140ltr.
And welded cylinder are are complying to DOT specification. The
cylinders are available in following sizes. 15ltr, 29ltr, 49ltr, 80ltr,
104ltr, 148ltr, 227ltr and 369ltr,
The cylinders are charged with Fk1230 and super pressurized with
dry nitrogen at a total pressure of 360 psig (25 bars) or 610 psig (42
bars) at 70°F (21°C) to assure rapid discharge at temperatures as
low as 32°F (0°C) storage temperature.
These cylinders have the optional facility of Switch-in-Gauge unit,
designed to monitor the pressure of the cylinder. The 2 in 1 unit
offers the facility to monitor cylinder pressure locally and remotely
via using Fire Alarm Panel interface unit or any other control panel.
4 25 and 42 Bar, FK-5-1-12 Clean Agent System
System Components
Flexible Discharge Hose Flexible Actuation Hose Cylinder Mounting Strap
Flexible hoses are used to Flexible Actuation hose is ¼" The MS Straps or brackets are
connect the agent storage stainless steel wire braided used to mount the cylinder in
cylinders to the manifold in hose. It is used in multiple vertical position.
multiple cylinders arrangement. cylinder bank systems to
Flex hoses are made out of connect pressure activated
Reinforce Rubber Hose. Hose is devices to the system.
available in 1.1/2”, 2" and 3"
size.
Electric Cum Manual 1-1/2” Manifold Check 180⁰ & 360⁰ Degree Nozzle
Actuator Valve
The Electric control head is an In case of multiple cylinder Fk1230 Nozzles are available
electromechanical device arrangements where the in two discharge patterns 180⁰
mounted on the master master and slave cylinders and 360⁰ degree.
cylinder actuation port. The share a common manifold or
Electric control head gets are connected in main/reserve Discharge nozzles have an
actuated/triggered only after arrangement, a manifold NPT female pipe thread for
receiving a 24 VDC, 2 amps check valve becomes a must. attachment to the discharge
signal from the fire alarm The manifold check valve piping network. The nozzles
panel or other similar source. prevents backflow from the are selected basis of the
Once actuated it will trigger manifold in case the system hazard to be protected
the master cylinder and be inadvertently discharged. against. It helps to achieve the
eventually open up the Manifold check valve to be best flow rate and distribution
discharge outlet of the installed in the vertical of FK1230 in the protected
cylinder. It also houses a position only. Please refer hazard area
manual release plunger which arrow mark during installation.
can be used to manually Part number/orifice for nozzle
trigger the cylinder actuation will be generated by FK1230
port. fire suppression system
design software.
The actuator also has a
supervisory switch. The
function of the supervisory
switch is to provide the signal
to control panel in case the
actuator is demounted or
removed from cylinder valve.
This makes it an important
feature as described in NFPA
5
System Components
Pressure Operated Control Manifold / Piping Agent Master Cylinder Adapter Kit
Head Discharge Pressure Switch
In multiple cylinder system, a The discharge pressure switch The master cylinder adapter kit
pressure operated control is activated by pressure from provides the means of
head is mounted on each the agent during discharge connecting the flexible
slave cylinder. On the and can be used to signal an actuation hose to the master
actuation of electric control control panel that the system and slave cylinder assembly.
head mounted on master has discharged. The pressure This enables system to
cylinder. Pressure from the switch incorporates a reset actuate the Slave Cylinder.
master cylinder is transferred button which has to be
to each pressure operated depressed following a
control head. Which enables it discharge.
to pneumatically actuate the
cylinder it is mounted on.
Male Tee Male Elbow
The male tee is primarily used The male elbow is used on the
in manifold system for last slave cylinder in manifold
connecting actuation hose system.
from one slave cylinder to the
next.
6 25 and 42 Bar, FK-5-1-12 Clean Agent System
Technical Specifications
FK1230 (FK-5-1-12) CLEAN AGENT FIRE
Seamless Cylinder
SUPPRESSION SYSTEM
Nomenclature Part Number
Type of System : Total Flooding System
34 Ltr. (84 lb.) Seamless Cylinder With 1-1/2" Valve Assembly, 25 Bar 12-250034-000
Name of Agent : Fk1230 (FK-5-1-12) (CF3CF2C(O) 34 Ltr. (84 lb.) Seamless Cylinder With 1-1/2" Valve Assembly, 42 Bar 12-420034-000
CF3)2) Design Code : NFPA-2001 Standard on Clean
Agent Fire Extinguishing Systems (Latest) 80 Ltr. (198 lb.)Seamless Cylinder With 2" Valve Assembly, 25 Bar 12-250080-000
Charging Pressure : 25 Bar (360 PSIG) Or 42 Bar 80 Ltr. (198 lb.)Seamless Cylinder With 1-1/2" Valve Assembly, 42 Bar 12-420080-000
(610 PSIG) 120 Ltr. (297 lb.) Seamless Cylinder With 2" Valve Assembly, 25 Bar 12-250120-000
Discharge Time : 10 seconds maximum. 120 Ltr. (297 lb.) Seamless Cylinder With 1-1/2" Valve Assembly, 42 Bar 12-420120-000
Operating Temperature : 0°C to 55°C (32°F to
140 Ltr. (346 lb.) Seamless Cylinder With 2" Valve Assembly 25 Bar 12-250140-000
130°F)
Design Concentration : Class A Fire : 4.5 % I Class B 140 Ltr. (346 lb.) Seamless Cylinder With 1-1/2" Valve Assembly, 42 Bar 12-420140-000
Fire : 5.9 % Min I Class C Fire : 4.5 %
Approved Agency : Underwriters Laboratories Inc.
(UL) DOT Cylinder
Nomenclature Part Number
A. CLEAN AGENT CYLINDER 15 Ltr. (36 lb.)DOT Cylinder With 1-1/2" Valve Assembly, 25 Bar 12-250036-000
Type : Seamless and DOT
29 Ltr. (72 lb.) DOT Cylinder With 1-1/2" Valve Assembly, 25 Bar 12-250072-000
Design Code : NFPA-2001 / IS 7285 (Part 2) / DOT
49Ltr. (121 lb.) DOT Cylinder With 1-1/2" Valve Assembly, 25 Bar 12-250121-000
Capacity : For Seamless 34, 80, 120 and 140 Ltrs.
And For DOT 15ltr, 29ltr, 49ltr, 80ltr, 104ltr, 148ltr, 80 Ltr. (198 lb.) DOT Cylinder With 2" Valve Assembly, 25 Bar 12-250198-000
227ltr and 369ltr, 104 Ltr. (258 lb.) DOT Cylinder With 2" Valve Assembly, 25 Bar 12-250258-000
Fill Density : 0.48kg/ltr to 1.12 kg/ltr. (30.0lb/ft³ to 148 Ltr. (367 lb.) DOT Cylinder With 2" Valve Assembly, 25 Bar 12-250367-000
70.0 Lb/ft³)
227 Ltr. (561 lb.) DOT Cylinder With 3" Valve Assembly, 25 Bar 12-250561-000
B. DISCHARGE NOZZLE 369 Ltr. (912 lb.) DOT Cylinder With 3" Valve Assembly, 25 Bar 12-250912-000
Type : 180 and 380 Degree
Material of Construction : Brass
Thread : NPT female thread Accessories for 25 & 42 Bar System
Size : 15NB, 20NB, 25NB, 32NB, 40NB & 50NB Nomenclature Part Number
(1/2", 3/4". 1", 1-1/4", 1-1/2" & 2")
Electric cum Manual Actuator (Electric Control Head) 14-000031-000
Nozzle Coverage Area : 13M X 13M ( 42.65 ft x 42.65
ft) Pressure Operated Control Heads (Pneumatic Actuator) 14-000032-000
1-1/2” Flexible Discharge Hose 14-000001-000
C. FLEXIBLE DISCHARGE HOSE 2” Flexible Discharge Hose 14-000002-000
Material of Construction : Reinforced Rubber Hose. 3” Flexible Discharge Hose 14-000003-000
Size : 40NB (1-1/2"), 50NB (2") and 80NB (3") ¼” Flexible Actuation Hose 14-000004-000
Master Cylinder Adapter Kit 14-000050-000
D. ELECTRIC CONTROL HEAD
Manifold / System Supervisory Switch 14-000081-000
Operation : Electrically and Manually by Manual
Plunger 1-1/2” Manifold Check Valve 14-000060-000
Operating Voltage : 24 VDC 2” Manifold Check Valve 14-000061-000
Operating Current : 2.0 A 3” Swing Type Manifold Check Valve 14-000062-000
Environmental Criteria : Indoor / Dry use only 360 Degree Nozzle 15-000001-xxx
180 Degree Nozzle 15-000002-xxx
Brass Male Tee 14-000051-000
Brass Male Elbow 14-000052-000
7
For More Information
www.cryptzo.net
Clean Agent Extinguishing Unit
Cryptzo Engineering Private Limited
Plot No. A-158 & 159, Vile Bagad
MIDC Industrial Area Mangaon, June 2018
Cryptzo Engineering Pvt. Ltd. All right reserved.
Dist-Raigad, Pin 402308, India
The Cryptzo is Trademark of Cryptzo Engineering Pvt. Ltd.
Tel. +91-22-41570555 This product is manufactured by Cryptzo Engineering Pvt. Ltd.