0% found this document useful (0 votes)
962 views4 pages

Combustion and Energy High Energy Ignition Systems Hei Igniters 200 Hep A6z 7j Datasheet - 2466 PDF

The document describes a high energy ignition module: - It is used for ignition of flares and boilers, producing sparks of up to 7 joules of energy at 2000 volts. - The module has LED indicators to show operating status and faults such as cable interruptions or short circuits. - It operates from a 12/24 volt DC power supply and has installation and safety certification for international use.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
962 views4 pages

Combustion and Energy High Energy Ignition Systems Hei Igniters 200 Hep A6z 7j Datasheet - 2466 PDF

The document describes a high energy ignition module: - It is used for ignition of flares and boilers, producing sparks of up to 7 joules of energy at 2000 volts. - The module has LED indicators to show operating status and faults such as cable interruptions or short circuits. - It operates from a 12/24 volt DC power supply and has installation and safety certification for international use.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

HIGH ENERGY IGNITION MODULE

200-HEP-A6Z 7J

200-HEP-A6Z 7J

COMBUSTION AND ENERGY - [email protected] - www.ce2k.com - Ph. +39.0341.260926 rev_04


HIGH ENERGY IGNITION MODULE

200-HEP-A6Z 7J
KEY FEATURES MECHANICAL FEATURES

• High energy ignition system • Electronic circuits


• Power discharge: 7J • Operating temp. range: - 40°C to + 85°C
• Output volt.: 2kV impulsive capacity • Storage temp. range: - 55°C to + 55°C
discharge • Dimensions: 89x74x118mm
• Degree of protection: IP20 • Unit weight: 500g
• Discharge frequency: < 0,6s to >8s • Enclosure: PVC
adjustable, preset to 5s • Connections: screw terminals
• Installation type: for DIN connector
• Booster function: 4x7J/s (as option) PART NUMBER

OPTIONS • 200-HEP-A6Z 7J
• 200-HEP-A6Z 7J + 48VDC CONVERTER
• High Energy Ignition Probe 200-HEF-5AA • 200-HEP-A6Z 7J + MDR (power supply
• Spark tip: 200-HEF-9A3 from 100 to 240VAC)
• Ex d IIC fix or portable version
APPLY TO
200-HEP-A6Z 7J

• Power supply from 100 to 240VAC with


dedicate power converter
• Flares
• Boilers
INSTALLATION

• Inside control local panel INTERNATIONAL REGULATION

• CE marking
ELECTRICAL FEATURES • UL for MDR power supply
• EAC for Russian market
• Nominal operating voltage: 2000V
• Consumption: < 1,6A MANUFACTURER
• Power supply 12/24VDC (from 10,5 to 28
VDC) Combustion and Energy Srl
• Electronics c/w temperature
compensation
• Discharge frequence regulation
• Fault relay (as option) - Max. applicable
voltage 60VDC/42VAC 0,2A
• 12-24VDC remote start (as option)

COMBUSTION AND ENERGY - [email protected] - www.ce2k.com - Ph. +39.0341.260926


rev_04
Document is subject to change without any notice
HIGH ENERGY IGNITION MODULE

200-HEP-A6Z 7J
89
+12/24VDC

12/24VDC
OVDC

DIP SETTING

7 7
7 7 74

200-HEP-A6Z 7J
SPARE HE OUTPUT #2

EARTH CONECTION
HE OUTPUT #1

4 3 2 1
ON HE MODULE, NO ADDITIONAL FUNCTION

4 3 2 1
ON
HE MODULE WILL WORK UNTIL 12 OR 24VDC IS APPLYED ON THE START RELAY
(Connect 12/24VDC to PIN 3 and 0V to PIN 4)

4 3 2 1 TIP AND CABLE FUNCTION CHECKING AVAILABLE


ON FAIL SAFE NORMAL CONDITION CONTACT CLOSED, FAULT CONDITION CONTACT OPEN
(See max. applicable voltage)

4 3 2 1
ON
FAULT CONTACT RELAY N.C.
(See max. applicable voltage)

4 3 2 1
ON HE MODULE FUNCTION BOOSTER ACTIVATED (4X7J/s)

4 3 2 1
ON HE MODULE FUNCTION BOOSTER WITH EXTERNAL START RELAY

rev_03 COMBUSTION AND ENERGY - [email protected] - www.ce2k.com - Ph. +39.0341.260926 rev_04


HIGH ENERGY IGNITION MODULE

200-HEP-A6Z 7J

• Led Red ON: when the HE module is sparking.


• Led Green ON: when the HE module is ON and waiting for spark.
• Led Red flashing continuously: cable interrupted or TIP not connected (reignition delay 30
seconds) - (This function is valid only if DIP 2 is ON)
• Led Red flashing continuously: cable interrupted or TIP in short circuit ( reignition delay 10
seconds) - (This function is valid only if DIP 2 is ON)
• Led Orange (green + red) flashing continuously: spark generator component or TIP are no more
efficently. (This function is valid only if DIP 2 is ON)

TOP VIEW SIDE VIEW

89 120
200-HEP-A6Z 7J

LATO C
74

rev_04 COMBUSTION AND ENERGY - [email protected] - www.ce2k.com - Ph. +39.0341.260926