0% found this document useful (0 votes)
114 views

UT350

The document describes three applications for temperature control using Green 300 series controllers: 1) Controlling furnace temperature using a UT350 controller connected to a solid state relay and type K thermocouple input. 2) Controlling furnace temperature using a UT350 controller connected to a thyristor unit and type K thermocouple input. 3) Maintaining hot water temperature in a heat exchanger system using a UT350 controller connected to a pneumatic converter and Pt100 temperature sensor. Alarms are set to notify when temperature exceeds safe levels.

Uploaded by

renzomcueva
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
114 views

UT350

The document describes three applications for temperature control using Green 300 series controllers: 1) Controlling furnace temperature using a UT350 controller connected to a solid state relay and type K thermocouple input. 2) Controlling furnace temperature using a UT350 controller connected to a thyristor unit and type K thermocouple input. 3) Maintaining hot water temperature in a heat exchanger system using a UT350 controller connected to a pneumatic converter and Pt100 temperature sensor. Alarms are set to notify when temperature exceeds safe levels.

Uploaded by

renzomcueva
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 6

Application sheet for Green 300 series controllers

Number:
Title Furnace temperature control with Solid State Relay(SSR) AP35001

Control a furnace temperature by using UT350 temperature controller. Model


Purpose
UT350 can drive SSR as an actuator directly.
Application Electrical Furnace
File Name:
Controller UT350-00 UTAP3501.t3d

Loop Configuration:
UT350-00
Input Range: 0 - 1200deg C Temperature
Input Type: TC type K signal TIC
Output Type: Voltage pulse
Cycle time: 3sec.
Temperature Set-point: 700deg C
PID parameters
P=5%
I = 240sec.
D= 60sec.
SSR
Electrical
Furnace
Heater

AC Power
Supply

Wiring:
UT350-00
+

[12]
TC Input TC type K
[13] -

[16]
+

MV Heater
[17] -

Power supply Solid-state


[8]
[9] Relay
12VDC Voltage Pulse
[10]

Explanation
: This is simple example for temperature control. Model UT350 can read
the temperature from Type K sensor directly. Model UT350 also has very
powerful control functions, such as Auto-Tuning, SUPER function for
overshoot suppression, SUPER2 function for hunting suppression and
universal control output.
Customer can select a one control output from either Voltage Pulse, Relay
Contact or 4 - 20mA Current output.

1st Edition, August 2001


Application sheet for Green 300 series controllers
Number:
Title Furnace temperature control with Thyristor(SCR) AP35002
Measure the furnace temperature by using TC. PID Control for a furnace
Purpose temperature, temperature sensor is a TC and actuator is a SCR.

Application Electrical Furnace


UT350-00 File Name:
Controller UTAP3502.t3d

Loop Configuration:
UT350-00 UT350-00
Input Range : 0 - 1200deg C Temperature
Input Type : TC type K signal TIC TIC
Output Type : Current Output
Set-point : 700deg C
PID parameters
P= 5%
I= 240sec. 4 - 20mA
D= 60sec. Current signal Temperature signal

SCR SCR
Electrical AC Power
Furnace Supply thyristor
Heater

Wiring:
UT350-00
[12]
+

[13] TC Input - TC type K

[16] MV
+

Heater
[17]
4 - 20mA -
Power supply
[8]
[9] thyristor
[10]

Explanation
A 4 - 20mA current output is used to drive a Thyristor unit. Thyristor unit
:
can control the current for a heater.

1st Edition, August 2001


Application sheet for Green 300 series controllers
Number:
Title Heat-Exchanger Temperature control AP35003

Purpose Produce hot water with constant temperature by using plate type heat-exchanger.
Hot water for air conditioning and environment
Application chumber.
File Name:
Controller UT350-00 UTAP3503.t3d

Loop Configuration:
Pump UT350-00
Input Range: 0 - 100.0deg C Interlock Hi-Alarm
Input Type: Pt100ohm
Output Type: Current Output TIC
Set-point: 45deg C Temperature
ID parameters P = 30% signal
I = 40sec.
D = 5sec.
Alarm action : Hi-Alarm Current to
ON at 50deg C I/P Pneumatic
OFF at 48deg C Converter
Heat
Exchange
r
Hot water
2deg C Alarm
condition

Very Hot
Water water
50deg C

Wiring:
UT350-00
[11] A
Temperature Input B
[12]
[6] Do1 [13] B temperature sensor
Alarm output1 AL1 [7]
+

[16]
MV 4 - 20mA
STOP/RUN
Di2 [18] [17] - control valve
Stop during On [20]
[8]
[9]
Power supply
[10]

Explanation
Alarm set points are displayed on "Select Panel" for easy changing during
:
operation.
The ID control function will be stoped and a preset signal (0%) will be outputed
when the pump interlock signal will turn to on.
The current output signal is used to drive a control valve.

1st Edition, August 2001


Application sheet for Green 300 series controllers
Number:
Title Packaged Air Conditioner Temperature control AP35004
Control ON/OFF valve for cooling water and power switch for Heater to keep the
Purpose room temperature.

Application Packaged Air Conditioner


UT350-00 File Name:
Controller UTAP3504.t3d

Loop Configuration:
Input Range: 0 - 50deg C UT350-00
Input Range: Pt100 ohm TIC
Set-point: 25deg C
Deviation Hi-Alarm: 2deg C
Deviation Low-Alarm: 2deg C
Hi-Alarm hysteresis: 0.5deg C
Low-Alarm hysteresis: 0.5deg C
Temperature
signal

Cooling water
Heater ON AL2 Valve Open AL1 Heater
0.5deg C 0.5deg C Cooling water
Hysteresis Hysteresis

Air to Room
Feedback Fan
Room Air

SP
2deg C 2deg C
Dead band Dead band
HY2 HY1

Wiring: UT350-00
Magnetic Switch

Temperature Input Heater


A [11] AL2
Pt100 ohm B [12] [5]
B [13]

AL1
[6] Cooling water
SEQ
[7] Valve
Power supply
[8]
[9]
[10]

Explanation
:
This is a simple Heating / Cooling control example. Model UT350 has a Heating /
Cooling control function; however, two alarm outputs are enough to switch a ON/OFF
valve and a Heater.
1. If PV temperature is higher than (SP+2deg.C), a deviation Hi alarm turnes to ON.
Then, a cooling water valve is opened.
2. If PV temperature is lower than (SP-2deg.C), a deviation Low alarm turnes to ON.
Then, a heater switch is turned to on.

1st Edition, August 2001


Application sheet for Green 300 series controllers
Number:
Title Tank Level Control AP35005
Control a Tank level by using a pressure transmitter.
Purpose UT350 has a power supply function to a transmitter.

Application Tank Level Control


File Name:
Controller UT350-30 UTAP3505.t3d

Loop Configuration:
Input Range: 0 - 1,500mm
Input Type: 1.0 - 5.0VDC UT350-30
Output Range: 4 - 20mADC Level Signal LIC
Set-point: 1,200mm
PID parametersP = 10%
I = OFF
Transmitter
D = OFF
power supply
MR = 0% MV 4 - 20mA
MR (Manual Reset) is output when PV =SP.

Control Valve

Level
transmitter

Wiring:
UT350-30
12
Pressure Input 13 250ohm
+

Loop power 21
supply 22 Level transmitter
-
+

16
Power MV 17 4 - 20mA
-
supply 8
9

10

Explanation
Control the tank level by Proportional control with Manual Reset function.
: Proportional control may occur small offset; however, the control response is
very fast.
UT350 has two types of power supply function to a two-wire transmitter.
All types of UT350 can supply 14.5VDC power to a transmitter.
Model UT350-3_ can supply 21.6VDC power to a transmitter.
A 14.5VDC will be enough for almost all analog type 2-wire transmitter.
A 21.6VDC will be used to drive microprocessor based 2-wire transmitter.

1st Edition, August 2001


Application sheet for Green 300 series controllers
Number:
Title Pump outlet pressure control AP35006

Purpose Control the voltage & frequency of a pump to control the pump outlet pressure.

Application Pump outlet pressure control


File Name:
Controller UT350-00 UTAP3506.t3d

Loop Configuration:
Input Range: 0 - 1.00 MPa
Input Type: 0.40 - 2.00 VDC
Output Range: 4 - 20mADC UT350-00
Set-point: 0.7MPa Pressure Input
PIC
PID parameters P =150% Transmitter
I = 20sec. power supply
D = OFF
MV
4 - 20mA

R
Start Signal Inverter
Pressure
transmitter
P

Wiring:
UT350-00
Pressure Input
[12]
[13] 100 ohm
RUN/STOP signal
[18]
+

ON: STOP Di2 [14] Pressure


[20] [15] - transmitter
Loop power supply
+

[16]
MV
[17]
4 - 20mA
-
P
Power supply
[8]
[9] Inverter
[10]

Explanation
Model UT350 has a RUN/STOP function.
:
RUN mode(Di is ON): PID control
STOP mode(Di2 is OFF): PID computation is stopped.
Preset MV is outputed as MV.
UT350 can control the pump pressure without overshoot, because control
output starts from 0%.
UT350 can supply 14.5VDC power to a transmitter.

1st Edition, August 2001