Data sheet for SINAMICS V20
MLFB-Ordering data
6SL3210-5BE31-8UV0
Figure similar
Client order no. : Item no. :
Order no. : Consignment no. :
Offer no. : Project :
Remarks :
Rated data General tech. specifications
Input Power factor λ 0.72
Number of phases 3 AC Offset factor cos φ 0.95
Line voltage 380 ... 480 V -15 % +10 % Efficiency η 0.98
Line frequency 47 ... 63 Hz Filter class (integrated) Unfiltered
Output Ambient conditions
Number of phases 3 AC
Cooling External fan
Rated voltage 400 V
Installation altitude 1000 m (3281 ft)
Rated power (HO) 18.50 kW / 25.00 hp
Ambient temperature
Rated power (LO) 22.00 kW / 30.00 hp
Operation -10 ... 60 °C (14 ... 140 °F)
Rated current (HO) 38.00 A
Storage -40 ... 70 °C (-40 ... 158 °F)
Rated current (LO) 45.00 A
Relative humidity
Rated current (HO) at 480V 34.00 A
Max. operation 95 %
Rated current (LO) at 480V 40.00 A
Pulse frequency 4.00 kHz Communication
Output frequency 0 ... 550 Hz Communication USS, Modbus RTU
Standards
Compliance with standards CE, cULus, C-Tick (RCM), KC
CE marking EN 61800-5-1 /EN 60204-1 and EN
61800-3
Overload capability
Low Overload (LO)
110 % rated output current for 60 s, cycle time 300 s
High Overload (HO)
150 % rated output current for 60 s, cycle time 300 s
Technical data are subject to change! There may be discrepancies between calculated and rating plate values.
Generated Tue Jan 14 17:02:37 CET 2020
Page 1 of 2
Data sheet for SINAMICS V20
MLFB-Ordering data
6SL3210-5BE31-8UV0
Figure similar
Mechanical data Connections
Through-hole mounting / wall mounting / Max. motor cable length
Mounting position
side-by-side mounting
Shielded 50 m (164 ft)
Degree of protection IP20 / UL open type
Unshielded 100 m (328 ft)
Size FSE
Net weight 6.24 kg ( 13.76 lb )
Width 245.0 mm ( 9.65 in )
Height 264.5 mm ( 10.41 in )
Depth 209.0 mm ( 8.23 in )
Inputs / outputs
Standard digital inputs
Number 4
Digital outputs
Number as relay changeover contact 1
Number as transistor 1
Analog inputs
2 (Can be used as additional
Number
digital input)
Analog outputs
Number 1
Technical data are subject to change! There may be discrepancies between calculated and rating plate values.
Generated Tue Jan 14 17:02:37 CET 2020