EUROBOX SERIES
TYPES CM... SM... MM...
                                  Application
AUTOMATIC GAS BURNER CONTROL
                                  This range of electronic gas burner control systems has
SYSTEMS FOR GAS BURNERS AND GAS   been designed specifically for atmospheric and fan assisted
BURNING   APPLIANCES  WITH   OR   burners for intermittent operation (systems for non-
WITHOUT FAN                       permanent operation ).
                                  All these controls are provided with non-volatile lock-out,
                                  which means that a restart from the safety shut-down
                                  condition can only be accomplished by a manual reset of
                                  the system.
                                  The automatic burner control units of this series are suitable
                                  for:
                                  -combi boilers
                                  -heating boilers
                                  -warm air generators
                                  -radiant heaters
                                  -water heaters
                                  Due to the design and the variety of models they can be
                                  used also for the automation of ovens, cookers and in
                                  general in gas firing installations with atmospheric burner.
                                  Features
                                  Table 1 shows the main features of this series. Other
                                  important features are:
                                  − EC - Type certification (CE Reg. N° 63AQ0625) in
                                       accordance with Gas Appliance Directives 90/396 and
                                       93/68;
                                  − in accordance with EN298 (European standard for
                                       automatic gas burner control systems);
                                  − flame monitoring by the rectification property of the
                                       flame: ionization;
                                  − two independent safety contacts in series on the gas
                                       valve output;
                                  − electrical service life at max. loading >250.000
                                       operations;
                                  − inbuilt or remote reset facility;
                                  − inbuilt ignition device completely of solid state design
                                       and high efficiency;
                                  − auxiliary contact for low power ignition or main gas valve
                                       control for intermittent pilot systems (this contact is not
                                       isolated from the main supply voltage by reinforced
                                       isolation, therefore the relay contact is not suitable to
                                       supply SELV circuits - Safety Extra Low Voltage, e.g.
                                       24V);
                                  − different connections and fixings.
3989_r00                                                                                     1/6
TABLE 1                                  BURNER                                                                                                                   RESET                                                                         C O NNEC TIO N
                                              atmospheric without fan
                                                                                                                                                                                                            according to EN298 (2)
                                                                        atmospheric with fan
                                                                                                  auxiliary contact (1)
                                                                                                                                                                                      classification code
                                                                                                                          single electrode
                                                                                                                                             external igniter
             single flame
                                                                                                                                                                                                                                                                         Socket MG
                                                                                                                                                                                                                                                             Socket NG
                            dual flame
                                                                                                                                                                                                                                                  Socket R
                                                                                                                                                                                                                                     Socket P
                                                                                                                                                                remote
                                                                                                                                                                          inbuilt
C M 191          *                                    *                                                                                                         (B)       (A )      A M C LXN                                          *            *           *
SM 191           *                                    *                                                  *                                                                (A )      A M C LXN                                                                   *
SM 192                         *                      *                                                                                                         (B)       (A )      A M C LXN                                          *            *           *
C M 381          *                                                             *                                                                                (B)       (A )      FM C LXN                                           *            *                       *
C M 391          *                                                             *                                                                                          (A )      FM C LXN                                                                    *
SM 152                         *                      *                                                                                                         (B)       (A )      A M C LXN                                          *            *           *
SM 592                         *                      *                                                                                           *             (B)       (A )      A M C LXN                                          *            *           *
M M 191          *                                    *                                                                        *                                (B)       (A )      A M C LXN                                          *            *           *
M M 192                        *                      *                                                                        *                                (B)       (A )      A M C LXN                                          *            *           *
NOTE:      (A) Box type xxxxx.1 - xxxxx.2                                                      (1) : This contact is not isolated from the m ain supply voltage by reinforced
           (B) Box type xxxxx.3 - xxxxx.4                                                             isolation, therefore the relay contact is not suitable to supply SELV circuits -
                                                                                                      Safety Extra Low Voltage, e.g. 24V.
                                                                                                (2) : Flam e failure during TS causes spark restoration.
  TECHNICAL DATA                                                                                                                                                Minimum ionization current:           1.2µA
  Supply Voltage:                                  230V-50/60Hz                                                                                                                    on request:        0.5µA
        on request:                            110/120V-50/60Hz                                                                                                 -Recommended ionization current: 3 ÷ 5 times the
  Operating temperature range:                      -20°C +60°C                                                                                                  minimum ionization current
  Ambient humidity:                             95% max at 40°C                                                                                                 -Max. length of the cable:            1m
  Protection degree:                                                                                                                                            -Minimum insulation resistance of cable and flame detector
             socket NG:        IP 40    (after installation)                                                                                                     device to earth:                     ≥ 50MΩ
             socket P/R        IP 00                                                                                                                            -Max. parasitic capacitance of
  Times:                                                                                                                                                         detection probe:                     ≤ 1nF
  -Prepurge or waiting time (TW):       1,5/3/5/10/20/30/40 s                                                                                                   -Max. short circuit current:          < 200µA AC
   the waiting time for type SM152 is:      3/5/10/20/30/40 s                                                                                                   Ignition:
  -Safety time (TS):               3/5/8/10/20/30/40/50/60 s                                                                                                    -Ignition voltage:                    8 KV at 30pF loading
  -Drop out time on running flame failure:        <1s                                                                                                           -Repetition rate:                     25 Hz
  The times given on the burner control label correspond to                                                                                                     -Max.length of the cable:             2m
  the values guaranteed. The actual values differ slightly from                                                                                                 -Spark gap recommended:               2-4 mm
  the values given, pre-purge and waiting times are in fact                                                                                                     -Consumption:                         2,5 VA
  longer and safety time shorter than their nominal values.                                                                                                     -Spark energy:                        15 mJ
  Power consumption, at starting up:                                                                                                                            Weight:
             atmospheric burner                   10 VA                                                                                                         -with socket P or R:                  220 g
             atmospheric fan-assisted burner 12 VA                                                                                                              -with socket NG or MG:                275 g
  Power consumption, running:                                                                                                                                   Controls for special applications:
             atmospheric burner                    7 VA                                                                                                         On request it is possible to meet special requirements
             atmospheric fan-assisted burner       9 VA                                                                                                         concerning times, repetition rate of the sparks, minimum
  Contact rating:                       I max                                                                                                                   ionization current and operating cycle.
  -Thermostat:                          4 A cos ϕ = 0.4                                                                                                         CONSTRUCTION
  -EV1:                                 0.5 A cos ϕ = 0.4                                                                                                       The enclosure made of plastic material protects the control
  -EV2:                                 0.5 A cos ϕ = 0.4                                                                                                       from mechanical damage, dust and dirt from the conditions
  -EVG:                                 0.5 A cos ϕ = 0.4                                                                                                       of installation.The particular construction, consisting of four
  -Fan:                                 1 A cos ϕ = 0.4                                                                                                         printed circuit boards in order to form a "box" structure, has
  -Alarm:                               0.5 A cos ϕ = 1                                                                                                         allowed a reduction in the volume of the control unit.
  -Auxiliary contact:                   0.5 A cos ϕ = 0.4                                                                                                       A varistor protects the control from voltage transients on the
  -External ignition:                   1.5 A cos ϕ = 0.2                                                                                                       mains supply. An internal fuse protects the relays of the
  Max. length of the cables of                                                                                                                                  control box in case of short circuits on the outputs (valves,
  external components:                  1m                                                                                                                      fan and lock-out signal). This is not an accessible fuse and
  Fuse rating internal:                 4 A Fast                                                                                                                the control must be protected with a fuse of the fast blow
  Fuse rating external:                 3.15 A Fast                                                                                                             type suitable to the load connected and never exceeding
  Flame control:                                                                                                                                                3.15A.
  The ionization flame detector device makes use of the                                                                                                         Overall Dimensions
  rectification property of the flame.                                                                                                                          The control units of the EUROBOX series can be supplied
  The ionization flame detector device is not a safe to touch                                                                                                   with different executions of the enclosure depending on the
  output (no provision with protective impedances).                                                                                                             functions and the fixing system required.
 2/6                                                                                                                                                                                                                                                                     3989_r00
Enclosures are available with or without reset button and         screw terminal suitable for the CM381 control unit. Socket
can be provided or not with fixing brackets on the sides.         type P differentiates from type R on positions 8 and 10 for
Please note that the control units with fixing brackets on t he   the presence of standard holes to suit female fast-on
sides can only fit connecting sockets type P or R, as these       terminals of standard type (please see Fig. 4 and Fig. 5)
are provided with suitable hooks.                                 Regarding the connection of the control units, provisions
In the part reference the suffix describes the execution of       such as strain reliefs, sufficient earth terminals and neutral
the enclosure:                                                    terminals should be present in the appliance or in external
1 with reset button with fixing brackets                          connection boxes.
2 with reset button no fixing brackets
3 no reset button     with fixing brackets
4 no reset button     no fixing brackets
The possibility to use the enclosures without the reset
button is limited to those controls having the provision for
remote reset.
The following figure (fig. 1) shows the overall dimensions of
the controls.
                                                                                                                          Socket R
                                                     Fig.1
Accessories
The control units are usually supplied with inbuilt reset
button; there are versions with remote reset, with which we
can supply a suitable illuminated reset button (see Fig.2).
Cable holders/core hitches can be fitted on the sides of the
enclosures (see Fig.3).                                                                                            Socket NG
These accessories can be supplied upon request.                                                                         Fig.4
           RESET BUTTON         DRILLING PLAN
                                                                                                               Socket NG
                           RESET            NEUTRAL
                      LOCK-OUT S.
                                                       Fig.2
                                                                              Socket R
                                                                                                                         Fig.5
                                                      Fig.3       DIRECTIONS FOR THE USE
Connection                                                        − For technical-safety reasons a regulation shutdown must
As regards the interconnection system, different solutions           occur every 24 hours (systems for non-permanent
are possible; in fact, different types of connecting sockets         operation).
can be used: type NG and MG with a screw terminal board           − Automatic controls are safety devices and shall not be
or type P and R for fast-on terminals.The slots on socket R          opened. Responsibility and guarantee of the
are suitable for female fast-on terminals.Socket type MG             manufacturer is invalidated if the control is opened.
differentiates from type NG for the presence of an auxiliary      − The control must be connected and disconnected only
                                                                     without the main power.
3989_r00                                                                                                                    3/6
−   The control can be mounted in any position.                       within 1 second and after a recycling, the control
−   Avoid exposure of the control unit to dripping water.             proceeds to a non-volatile lock-out;
−   Ventilation and the lowest temperature ensures the            −   operating times and sequence are suitable;
    longest life of the control                                   −   the level of the flame signal is sufficient, see Fig.6 for the
− Make sure that the type (code and times) you are using              measuring test;
    is correct before installing or replacing the control.        −   the ignition probe(s) is (are) adjusted in the most stable
− For controls which are specified as IP00, the gas                   way for a spark gap between 2-4 mm;
    appliance in which the control is installed must provide      −   the intervention of limiters or safety devices causes a
    adequate protection against the risk of electrical shock          safety shut-down according to the application.
    (at least IP20).
Electrical installation
− The applicable national regulation and European
    standards (e.g. EN60335-1/prEN50165) regarding
    electrical safety must be respected.
− Live and neutral should be connected correctly, a
    mistake could cause a dangerous situation, i.e. the
    valves would still be live with the thermostats and limits
    switched off. Besides, if live-neutral polarity is not
    respected the control performs a non-volatile lock-out at
    the end of the safety time at starting up.
− Before starting check the cables carefully. Wrong
    connections can damage the control and compromise
    the safety.
− Take great care while connecting the lock-out signal and
    reset button: an inversion in the connection can damage
    the control.                                                                                                            Fig.6
− The earth terminal of the control, the metal frame of the
    burner and the earth on the mains supply must be well         Operation
    connected.                                                    At every start the control unit proceeds to a self-checking of
− Avoid putting the detection cable close to power or             its own components. During the pre-purge or waiting time
    ignition cables.                                              the internal circuit makes a test of the flame signal amplifier
− Use a heat resistant cable for the detection probe, well        circuit. A parasitic flame signal or fault in the amplifier
    insulated to ground and protected from possible               prevents the control from starting.
    moisture (or water in general).                               In the types with control of the fan, before the elapsing of
− Use an ignition cable as short and straight as possible         pre-purge time, the air pressure switch contacts are
    and keep it far from other conductors to reduce the           checked to prove their "no air flow" state.Only if the test is
    emission of electromagnetic interference (max.length          positive the fan is started and with the air pressure switch in
    <2m and insulation voltage >25KV).                            "air flow" state, pre-purge time begins.
In case of live-neutral network with unearthed neutral or live-   At the end of the waiting or pre-purge times the gas valve is
live network (with centre of the star not earthed) the control    energized and the ignition device is operated. If a flame is
can operate correctly by means of a built-in resistor.            detected during the safety time the ignition device is
IMPORTANT: in the event of "partial" short circuits or            inhibited and, in the suitable models, the indipendent
bad insulation between phase(s) and earth the voltage             auxiliary contact will switch from off to flame detected
on the ionization probe can be reduced until it causes            position or the second gas valve will be energized.
the lock-out of the control. In the presence of this kind         On the contrary, if the control doesn't detect a flame by the
of network it is advisable to use our isolation                   end of TS, it proceeds to non-volatile lock-out, the gas valve
transformer type AR1.                                             and the ignition device are switched off while the lock-out
Checking at start                                                 signal output is supplied.
Always check the control before the first start and also after    When the flame fails during the safety time, then the ignition
substitutions or a long period of non operation of the            device is activated within one second.
system. Before any ignition attempt make sure that the            The attached diagrams are useful to understand how each
combustion chamber is free from gas.                              control operates.
Then make sure that:                                              Reset of the control
− if the attempt to start occurs without the gas supply the       When a control has gone to non-volatile lockout, an interval
    control performs a non-volatile lock-out after TS;            of 10 seconds should be allowed before attempting to reset
− when stopping the gas flow (while the control is in             the control unit; if this time is not observed then the control
    running state) supply to the gas valve is interrupted         may not reset correctly.
4/6                                                                                                                       3989_r00
                                CONNECTION DIAGRAMS
           NOTE: the limit thermostat has to be wired in series to the live.
3989_r00                                                                       5/6
                                          OPERATING CYCLES
                                                   Eurobox Series
                                                Types CM... SM... MM...
BRAHMA S.p.A.
Via del Pontiere, 31
37045 Legnago (VR)
Tel. +39 0442 635211 - Telefax +39 0442 25683                    03/03/25 Subject to amendments without notice
http://www.brahma.it
E-mail : [email protected]
6/6                                                                                                   3989_r00