Rev.
AL300ULXD-06082017
AL300ULXD
Power Supply/Charger
  Description
  Altronix AL300ULXD power supply/charger converts a 115VAC 60Hz or 230VAC
  50/60Hz input into a single 12VDC or 24VDC Class 2 Rated power-limited output.
                                                                                                                 AL300ULXD
   Specifications
   Input                                                                  Agency Listings
   	Voltage	             115VAC, 60Hz, 0.9A or                            	UL
   			                   230VAC, 50/60Hz, 0.45A.                          			 UL 294 (Access Control).
                                                                          			   UL 603 (Burglar Alarm Systems).
   Output                                                                 			   UL 1069 (Hospital Signaling and Nurse Call Equipment).
   	Voltage	             12VDC or 24VDC selectable.                       			   UL 1481 (Fire Protective Signaling Systems).
   	 Current	            2.5A continuos supply current.                   	 CE	 European Conformity
   	Other	               Class 2 Rated power-limited output.
   			                   Short circuit and thermal overload protection.   Physical and Environmental
   			                   Filtered and regulated.
                                                                          	 Dimensions (H x W x D)
                                                                          	 	 15.5” x 12” x 4.5” (393.7mm x 304.8mm x 114.3mm)
   Back-up Battery (not included)
                                                                          		 Enclosure accommodates up to two (2) 12VDC/12AH batteries.
   	Type	             Sealed lead acid or gel type.
                                                                          	 Product Weight	 11.7 lbs. (5.31 kg).
   	Failover	         Upon AC loss, instantaneous.
                                                                          	 Shipping Weight	 13.0 lbs. (5.9 kg).
                                                                          	Temperature
   Supervision
                                                                          		Operating		 0ºC to 49ºC (32ºF to 120ºF).
   	 AC Failure	         Form “C” contacts.
                                                                          		Storage		 -20ºC to 70ºC (-4ºF to 158ºF).
   	 Low Battery	        Form “C” contacts.
                                                                          	 Relative Humidity		       85% +/-5%.
   Indicators (LED)                                                       	 BTU/Hr. (approx.):
   	Input	               Input voltage is present.                        				 12VDC: 15 BTU/Hr.
   	 DC Output	          Powered.                                         				                        24VDC: 31 BTU/Hr.
                                     Altronix Corporation | 140 58th St | Brooklyn, NY 11220 USA
                      phone: +1 718.567.8181 | fax: +1 718.567.9056 | email: 