Solar
Grid Tie
                                                                           System
                                                                            Luminous NXi Grid Tie systems are high
                                                                            efficiency power systems that can feed
                                                                            power from solar panels directly to grid.
                                                                            They are designed to quickly disconnect
                                                                            from the grid if the utility grid goes down
                                                                            (anti-islanding).
                   Single Phase (kW) 1.5/3/4/5
Range available:
                   Three Phase (kW)     6/10/15/20/25/30
                                 Features       Benefits
                    Transformerless design      High efficiency >97%
        Dual/Quad MPPT charge controllers       Complete utilization of PV arrays even in partial shading
                    Wide operating voltage      Extends the day utilization for harnessing maximum power
                             IP 65 enclosure    Completely dust and water proof so can be installed outside
                        Wifi communication      For efficient remote monitoring
              Compliance to IEC standards       Safe, reliable and approved for Govt. subsidies
                               Anti-Islanding   Ensures safety of line workers
     Disconnects from grid if grid goes down
      Technical Specification - Luminous NXi Solar Grid Tie Systems (Single/Three Phase )
Model                                 NXi 115 NXi 130 NXi 150 NXi 306 NXi 310 Nxi 315 NXi 320 NXi 325 NXi 330
Input (DC)
Max. DC power [kW]                      1.8          3.5         5.8        6.6          11          16.5         22    27.5       33
Max. DC voltage [V]                     450               600                                              1000
Rated voltage [V]                       60                120                                               600
Operating MPPT voltage range (Volts)  50-400            100-500                                          200-800
Start voltage [V]                       60                120                           330                             350
Max input current per MPPT (Amps)        10       10+10        15+15       15+15       18 + 18      18 + 18     18 x3   18x4      18x4
Number of MPPT                            1                2                  2           2            2           4      4        4
Number of DC Connection Sets per MPPT                 1                       2           4            4           8      8        8
Output (AC)
Rated AC Power [kW]                      1.5          3           5           6          10           15          20     25        30
Max. Transient Response [kW]           1650        3300        5000         6.5         10.8         16.2        21.6    27       32.5
Max. AC Current [A]                     9.2         15.7        23.8         10         16.7          25        33.2    41.7      47.8
Nominal AC voltage/ range                        180-270                              313-470                         304-460
Grid frequency/ range                                                              50Hz (47-52)
Power factor [cos φ]                                                           >0.8 leading... 0.8 lagging
Total harmonic distortion [THDi]                                                        <3%
Feed-in phase / connection phase               Single Phase                                           Three Phase
Efficiency
Max. efficiency                        96.70      97.50        97.80      98.20% 98.20%            98.30% 98.30%       98.40% 98.50%
MPPT efficiency                                                                       99.90%
Protection
                                            Internal over-voltage , Ground fault monitoring, Grid monitoring, AC short circuit current,
                                              Thermal, Anti-islanding protection, Insulation monitoring, Residual Current detection,
                                            Surge protection, Over current, , DC Reverse Polarity Protection, Short Circuit Protection,
Inbuilt Protections                                O/P Over Current Protection, O/P Over Voltage Protection, Grid Monitoring,
                                                                     Islanding Protection, Thermal Protection
Interface
DC connection                                                                    MC4 connectors
Display                                                                 LCD 2 x 20Z                                7" Color Display
Datalogger & communication                                                    RS485, WIFI/GPRS (optional)
General Data
Topology                                                                        Transformerless
Consumption at night [W]                                                               < 1W
Operating temperature range                                               -25°C to 60°C/-13°F to 140°F
Cooling method                                                                 Natural Convection
Ambient humidity                                                                     0-95%
Altitude                                                                             4000m
Noise [dBA]                                                                          < 30 dBA
Designed lifetime                                                                    > 20yrs
Enclosure type                                                                      NEMA 4X
Dimensions (H*W*D) [mm]                           339x565x172                    430 x 613 x 269                    530 x 700 x 356
Net weight [kg]                             5.6       13.8       15.5        29         29         30       57.2          58.2    58.2
Standards
Safety / EMC                                                            EN1000-6-1:2007;EN1000-6-3:2007
                                                                           IEC 62109-1,62109-2:AS3100
Utility Monitoring                                          Islanding protection, VA C FA C in accordance with UL 1741,
                                                          En50438, G59/3, AS4777, VDE 0126-1-1, VDE 4105, CEI 0-21, CQC