Transmission Polymeric Surge Arresters

ENERGY DIVISION
bow-epp-0016-08-06-2.qxd 08.11.2006 16:23 Uhr Seite 2

Station Class
Polymeric Surge Arresters

The essential feature of the internal construction is the


homogeneous resin and glass fibre bond over the
complete insulated surface of the ZnO varistor elements.
The arrester module has good conductivity even when
high cantilever loads are applied and provides a uniform
dielectric at the insulated surface of the ZnO elements.

• No air gap therefore no internal ionisation


• Light weight compared to porcelain
• Ease of installation
• Non shattering housing
• Vandal proof

Electrical Performance 110kV Surge Arresters - Estonia


Specification: IEC60099-4
Classification: 10kA
Voltage Rating: 3kV to 132kV
High Current Performance: 100kA
Line Discharge Class: 2
Energy Capability:
4.5kJ/kV at Ur according to IEC60099-4
(Clause 8.4.2 table 5 and 8.5.5)
HSR Rated Voltage to 48kV
2HSR Rated Voltage to 84kV
3HSR Rated Voltage to 126kV
Insulation Material: Silicone Rubber

Typical Applications
• ARC Furnace
• Transformers
Extended Creepage
• TLA Transmission Line Arresters
HSREP45 Surge Arrester
• Cable Terminations
• Substations

66kV Surge Arresters - Statkraft, Norway

2
bow-epp-0016-08-06-2.qxd 08.11.2006 16:23 Uhr Seite 3

Station Class
Polymeric Surge Arresters

Accessories

Corona Ring
(Above 84kV)
Stainless Steel Terminal Assembly L5
Die Cast Aluminium Sealing End Line Clamp
to suit cables
Aluminium End Block up to Ø35 mm

ZnO Varistor Element

L2
Line Clamp
Glass Fibre Wrap to suit cables
up to Ø16 mm

Silicone Rubber Housing

L6
Aluminium Stem
Ø30 x 80mm high

E5
Earth Clamp
to suit cables
up to Ø35 mm

E2
Earth Clamp
to suit cables
up to Ø16 mm

M5 E1
4 Hole Pedestal Base 2 x M10 x 20mm
127-140 PCD Hexagon headed
set screws and
spring washers

M3
Set of 4 Polyfibre Base
Insulators used with M5

Example: 3 HSRC 96 L1 E1 M0
M10
Single Polyfibre Base No. of Sections Mounting
Insulator
Arrester Housing Earth Terminal
Voltage Line Terminal

3
bow-epp-0016-08-06-2.qxd 08.11.2006 16:23 Uhr Seite 4

Station Class
Polymeric Surge Arresters

Protective Characteristics

Product code Rating Max Temporary Max residual voltage kV crest with current wave Steep
voltage cont. over- current
kV operating voltage Switching surge Lightning current residual
voltage capability 30/60 µS 8/20 µS voltage*
(COV) kV for 1 sec
(TOV) kV 125A 250A 500A 1000A 2000A 5kA 10kA 20kA 40kA 10kA 20kA
kV kV kV kV kV kV kV kV kV kV kV
crest crest crest crest crest crest crest crest crest crest crest
HSRA(P)6L1E1M0(5) 6 4.80 7.08 12.2 12.5 13.0 13.5 14.1 15.4 16.6 18.2 20.8 17.8 19.6
HSRA(P)9L1E1M0(5) 9 7.20 10.9 19.5 20.1 20.8 21.6 22.6 24.6 26.5 29.2 33.2 28.4 31.4
HSRA(P)10.5L1E1M0(5) 10.5 8.40 12.4 22.0 22.6 23.3 24.3 25.5 27.7 29.8 32.8 37.4 32.0 35.3
HSRA(P)12L1E1M0(5) 12 9.60 14.2 24.4 25.1 25.9 27.0 28.3 30.8 33.1 36.5 41.5 35.5 39.3
HSRA(P)15L1E1M0(5) 15 12.0 17.7 29.3 30.1 31.1 32.4 33.9 37.0 39.7 43.8 49.8 42.6 47.1
HSRB(P)15L1E1M0(5) 15 12.0 17.7 29.3 30.1 31.1 32.4 33.9 37.0 39.7 43.8 49.8 42.6 47.1
HSRB(P)18L1E1M0(5) 18 14.4 21.2 36.6 37.6 38.9 40.5 42.4 46.2 49.7 54.7 62.3 53.3 58.9
HSRB(P)21L1E1M0(5) 21 16.8 24.8 41.5 42.7 44.1 45.9 48.1 52.4 56.3 62.0 70.6 60.4 66.8
HSRB(P)24L1E1M0(5) 24 19.2 28.3 48.8 50.2 51.9 54.0 56.6 61.6 66.2 73.0 83.0 71.1 78.5
HSRB(P)27L1E1M0(5) 27 21.6 31.9 53.7 55.2 57.1 59.3 62.2 67.8 72.8 80.3 91.3 78.2 86.4
HSRB(P)30L1E1M0(5 30 24.0 35.4 58.6 60.2 62.3 64.7 67.9 73.9 79.4 87.6 99.6 85.3 94.3
HSRC(P)27L1E1M0(5) 27 21.6 31.9 53.7 55.2 57.1 59.3 62.2 67.8 72.8 80.3 91.3 78.2 86.4
HSRC(P)30L1E1M0(5) 30 24.0 35.4 58.6 60.2 62.3 64.7 67.9 73.9 79.4 87.6 99.6 85.3 94.3
HSRC(P)36L1E1M0(5) 36 28.8 42.5 70.8 72.8 75.2 78.2 82.0 89.3 96.0 106 120 103 114
HSRC(P)39L1E1M0(5) 39 31.2 46.0 78.2 80.3 83.0 86.3 90.5 98.6 106 117 133 114 126
HSRC(P)42L1E1M0(5) 42 33.6 49.6 83.0 85.3 88.2 91.7 96.2 105 113 124 141 121 134
HSRC(P)45L1E1M0(5) 45 36.0 53.1 87.9 90.3 93.4 97.1 102 111 119 131 149 128 141
2HSRB(P)30L1E1M0(5) 30 24.0 35.4 58.6 60.2 62.3 64.7 67.9 73.9 79.4 87.6 99.6 85.3 94.3
2HSRB(P)45L1E1M0(5) 45 36.0 53.1 87.9 90.3 93.4 97.1 102 111 119 131 149 128 141
2HSRB(P)48L1E1M0(5) 48 38.4 56.6 95.2 97.8 101 105 110 120 129 142 162 139 153
2HSRB(P)60L1E1M0(5) 60 48.0 70.8 117 120 125 129 136 148 159 175 199 171 189
2HSRC(P)48L1E1M0(5) 48 38.4 56.6 95.2 97.8 101 105 110 120 129 142 162 139 153
2HSRC(P)60L1E1M0(5) 60 48.0 70.8 117 120 125 129 136 148 159 175 199 171 189
2HSRC(P)72L1E1M0(5) 72 57.6 85.0 142 146 150 156 164 179 192 212 241 206 228
2HSRC(P)75L1E1M0(5) 75 60.0 88.5 147 151 156 162 170 185 199 219 249 213 236
2HSRC(P)84L1E1M0(5) 84 67.2 99.1 166 171 176 183 192 209 225 248 282 242 267
3HSRC(P)96L1E1M0(5) 96 76.8 113 188 193 200 208 218 237 255 281 320 274 302
3HSRC(P)108L1E1M0(5) 108 86.4 127 212 218 226 235 246 268 288 317 361 309 342
3HSRC(P)120L1E1M0(5) 120 96.0 142 234 241 249 259 272 296 318 350 399 341 377
3HSRC(P)126L1E1M0(5) 126 101 149 247 253 262 272 286 311 334 369 419 359 397

* Residual voltage correction factor as per IEC recommendation 10kV/10kA/m

4
bow-epp-0016-08-06-2.qxd 08.11.2006 16:23 Uhr Seite 5

Station Class
Polymeric Surge Arresters

Mechanical and Reference Information

Total Overall Recommended Recommended Maximun Drawing Data sheet


creepage height minimum minimum applied reference reference
mm mm phase distance cantilever
(nom) (max) centres line to earth load
mm mm N
M0 M5

600 228 140 33 2513 BOW-2-001 BOW-4-001 BOW-EPP-HSRA6/HSRAP6


600 228 145 49 2513 BOW-2-001 BOW-4-001 BOW-EPP-HSRA9/HSRAP9
600 228 160 57 2513 BOW-2-001 BOW-4-001 BOW-EPP-HSRA10.5/HSRAP10.5
600 228 170 65 2513 BOW-2-001 BOW-4-001 BOW-EPP-HSRA12/HSRAP12
600 228 200 82 2513 BOW-2-001 BOW-4-001 BOW-EPP-HSRA15/HSRAP15
930 321 200 82 1760 BOW-2-002 BOW-4-002 BOW-EPP-HSRB15/HSRBP15
930 321 230 98 1760 BOW-2-002 BOW-4-002 BOW-EPP-HSRB18/HSRBP18
930 321 255 114 1760 BOW-2-002 BOW-4-002 BOW-EPP-HSRB21/HSRBP21
930 321 285 130 1760 BOW-2-002 BOW-4-002 BOW-EPP-HSRB24/HSRBP24
930 321 315 147 1760 BOW-2-002 BOW-4-002 BOW-EPP-HSRB27/HSRBP27
930 321 340 163 1760 BOW-2-002 BOW-4-002 BOW-EPP-HSRB30/HSRBP30
1325 476 315 147 1210 BOW-2A-001 BOW-4-003 BOW-EPP-HSRC27/HSRCP27
1325 476 340 163 1210 BOW-2A-001 BOW-4-003 BOW-EPP-HSRC30/HSRCP30
1325 476 400 196 1210 BOW-2A-001 BOW-4-003 BOW-EPP-HSRC36/HSRCP36
1325 476 425 212 1210 BOW-2A-001 BOW-4-003 BOW-EPP-HSRC39/HSRCP39
1325 476 455 228 1210 BOW-2A-001 BOW-4-003 BOW-EPP-HSRC42/HSRCP42
1325 476 480 244 1210 BOW-2A-001 BOW-4-003 BOW-EPP-HSRC45/HSRCP45
1860 642 340 163 1400 BOW-2B-002 BOW-4-004 BOW-EPP-HSRC45/HSRCP45
1860 642 477 243 1400 BOW-2B-002 BOW-4-004 BOW-EPP-2HSRB30/2HSRBP30
1860 642 510 260 1400 BOW-2B-002 BOW-4-004 BOW-EPP-2HSRB45/2HSRBP45
1860 642 625 326 1400 BOW-2B-002 BOW-4-004 BOW-EPP-2HSRB60/2HSRBP60
2650 952 510 260 900 BOW-2B-003 BOW-4-005 BOW-EPP-2HSRC48/2HSRCP48
2650 952 625 326 900 BOW-2B-003 BOW-4-005 BOW-EPP-2HSRC60/2HSRCP60
2650 952 735 391 900 BOW-2B-003 BOW-4-005 BOW-EPP-2HSRC72/2HSRCP72
2650 952 765 408 900 BOW-2B-003 BOW-4-005 BOW-EPP-2HSRC75/2HSRCP75
2650 952 840 456 900 BOW-2B-003 BOW-4-005 BOW-EPP-2HSRC84/2HSRCP84
3975 1428 1213 518 600 BOW-2B-006 BOW-4-006 BOW-EPP-3HSRC96/3HSRCP96
3975 1428 1326 583 600 BOW-2B-006 BOW-4-006 BOW-EPP-3HSRC108/3HSRCP108
3975 1428 1436 648 600 BOW-2B-006 BOW-4-006 BOW-EPP-3HSRC120/3HSRCP120
3975 1428 1495 680 600 BOW-2B-006 BOW-4-006 BOW-EPP-3HSRC126/3HSRCP126

5
bow-epp-0016-08-06-2.qxd 08.11.2006 16:23 Uhr Seite 6

Station Class
Polymeric Surge Arresters

The series parallel construction comprises individual


surge arrester modules rated between 30 and 45kV
interconnected by means of corona free aluminium alloy
cross arm.
Each surge arrester module is completely impervious to
the ingress of moisture and utilises the high mechanical
strength properties of the ZnO varistors bonded by
cured resin impregnated glass fibre.
The seismic performance of the 500kV arrester has been
proven in two leading test facilities. Bonneville Power
USA performed at Portland State University and NEL
East Kilbride UK.
• No air gap therefore no internal ionisation 2P4SR168 - 132kV Surge Arresters -
• Light weight compared to porcelain Statkraft, Norway
• Ease of installation
• Non shattering housing
• Optimised voltage stress grading eliminates need to
oversize stress grading ring, therefore the compact
series parallel can be installed in tight spaces without
infringing electrical or surge safety clearances.
• The diameter of the series parallel design has been
calculated to reduce the radial field stress to a
minimum, even under adverse environmental
conditions.

Electrical Performance
Specification: IEC60099-4
Classification: 2PH Class 3 10kA
3P Class 3 & 4 10/20kA
4P Class 4 & 5 20kA
5P Class 5 20kA
High Current Performance: 100kA
Energy Capability: according to IEC60099-4
(Clause 8.4.2 table 5 and 8.5.5)
2PH Class 3 7.0kJ/kV at Ur 3P6SR252 - Statnet 300kV

3P Class 3 9.4kJ/kV at Ur
3P Class 4 10.8kJ/kV at Ur
4P Class 4 12.5kJ/kV at Ur
5P Class 5 16.4kJ/kV at Ur
Voltage Rating:
2PH Rated Voltage from 15kV to 168 kV
3P Rated Voltage from 60kV to 360 kV
4P Rated Voltage from 96kV to 468 kV
5P Rated Voltage from 288kV to 525 kV
Insulation: Silicone Rubber Housing

Typical Applications
• Substations
• Capacitor Banks
• DC Inter-Connections
• Power Transformers
• Cable Terminations
3P10SR360 - Damhead Creek 400kV - UK

6
bow-epp-0016-08-06-2.qxd 08.11.2006 16:23 Uhr Seite 7

Station Class
Polymeric Surge Arresters

2PH Series Parallel 3P Series Parallel

L5 L5
Line Clamp Line Clamp
to suit cables to suit cables
up to Ø35 mm up to Ø35 mm
Corona
Ring

Silicone
Rubber
Housed
Arrester
L3 Module L3
Line Clamp Line Clamp
to suit cables to suit cables
up to Ø16 mm up to Ø16 mm

Silicone
L2 L2
Rubber
Aluminium Stem Aluminium Stem
Housed
Ø30 x 80mm high Ø30 x 80mm high
Arrester
Module

Silicone
Aluminium
intersection
cross-arm
Aluminium
connecting
strap

Corona
Shield

E5
Earth Clamp E5
to suit cables Earth Clamp
up to Ø35 mm to suit cables
up to Ø35 mm

E2
Earth Clamp
to suit cables E2
up to Ø16 mm Earth Clamp
to suit cables
up to Ø16 mm
E1 M7
2 x M10 x 20mm E1
3 Polyfibre Base Insulators
Hexagon headed 2 x M10 x 20mm
connected to galvanised steel plate
M4 set screws and Hexagon headed
Set of 2 Polyfibre Base spring washers set screws and
Insulators spring washers

Example: 3P 8SR 336 L2 E2 M7


Parallel Paths Mounting
Series Stages Earth Terminal
Voltage Line Terminal

7
bow-epp-0016-08-06-2.qxd 08.11.2006 16:23 Uhr Seite 8

Station Class
Polymeric Surge Arresters

Protective Characteristics 2PH & 3P Class 3

Product code Rating Max Temporary Max residual voltage kV crest with current wave Steep
voltage cont. over- current
kV operating voltage Switching surge Lightning current residual
voltage capability 30/60 µS 8/20 µS voltage*
(COV) kV for 1 sec
(TOV) kV 125A 250A 500A 1000A 2000A 5kA 10kA 20kA 40kA 10kA 20kA
kV kV kV kV kV kV kV kV kV kV kV
crest crest crest crest crest crest crest crest crest crest crest
2PHSRC30L2E2M4 30 24.0 34.5 57.2 58.7 60.3 62.3 64.8 69.7 74.2 80.2 89.3 79.0 86.6
2PHSRC36L2E2M4 36 28.8 41.4 69.1 70.9 72.9 75.3 78.3 84.3 89.6 98.9 108 95.4 105
2PHSRC39L2E2M4 39 31.2 44.9 76.2 78.2 80.4 83.1 86.4 93.0 98.9 107 119 105 115
2PHSRC42L2E2M4 42 33.6 48.3 81.0 83.1 85.4 88.3 91.8 98.8 105 114 126 112 123
2P2HSRC48L2E2M4 48 38.4 55.2 95.3 97.8 101 104 108 116 124 134 149 132 144
2P2HSRC60L2E2M4 60 48.0 69.0 114 117 121 125 130 139 148 160 179 158 173
2P2HSRC75L2E2M4 75 60.0 86.3 146 147 151 156 162 174 185 200 223 197 217
2P2HSRC84L2E2M4 84 67.2 96.6 162 166 171 177 184 198 210 227 253 224 245
2P3HSRC96L2E2M4 96 76.8 110 186 191 196 203 211 227 241 261 290 257 282
2P3HSRC108L2E2M4 108 86.4 124 207 213 219 226 235 253 269 291 324 286 314
2P3HSRC120L2E2M4 120 96.0 138 229 235 241 249 259 279 297 321 357 316 346
2P4HSRC132L2E2M4 132 106 152 257 264 271 280 292 314 334 361 402 355 390
2P4HSRC138L2E2M4 138 110 159 267 274 281 291 302 325 346 374 417 369 404
2P4HSRC144L2E2M4 144 115 166 276 284 291 301 313 337 358 388 431 382 419
2P4HSRC150L2E2M4 150 120 173 286 182 302 312 324 349 371 401 446 395 433
2P4HSRC168L2E2M4 168 134 193 324 332 342 353 367 395 420 454 506 447 491
3P3SR96L2E2M7 96 76.8 113 183 188 192 198 205 219 232 249 272 247 267
3P3SR108L2E2M7 108 86.4 127 205 209 214 221 229 245 259 278 303 276 298
3P3SR120L2E2M7 120 96.0 141 226 231 236 244 253 270 285 306 335 304 328
3P4SR132L2E2M7 132 106 155 254 260 266 274 284 304 321 345 377 342 369
3P4SR144L2E2M7 144 115 169 273 279 285 295 305 326 345 370 405 368 397
3P4SR150L2E2M7 150 120 176 282 289 295 305 316 338 357 383 419 380 410
3P4SR168L2E2M7 168 134 197 320 327 335 346 358 383 404 434 474 431 465
3P5SR180L2E2M7 180 144 211 341 349 357 368 382 408 431 463 506 459 496
3P5SR192L2E2M7 192 154 225 365 373 381 394 408 436 461 495 541 491 530
3P5SR198L2E2M7 198 158 232 376 385 394 407 421 450 475 511 558 507 547
3P6SR120L2E2M7 120 96.0 141 226 231 236 244 253 270 285 306 335 304 328
3P6SR214L2E2M7 214 171 251 409 419 428 442 458 490 517 555 607 551 595
3P6SR228L2E2M7 228 182 267 438 448 458 473 490 523 553 594 649 589 636
3P6SR240L2E2M7 240 192 282 452 462 472 488 506 540 571 613 670 608 657
3P6SR252L2E2M7 252 202 296 480 491 502 518 537 574 606 651 712 646 698
3P7SR240L2E2M7 240 192 282 461 472 482 498 516 552 582 625 684 621 670
3P7SR264L2E2M7 264 211 310 510 522 534 551 571 611 645 692 757 688 742
3P7SR288L2E2M7 288 230 338 543 556 568 587 608 650 686 737 806 732 790
3P8SR288L2E2M7 288 230 338 546 558 571 590 611 653 689 740 809 735 794
3P8SR300L2E2M7 300 240 352 565 578 591 610 632 675 713 766 837 760 821
3P8SR312L2E2M7 312 250 366 602 616 630 651 674 720 761 817 893 811 876
3P8SR336L2E2M7 336 269 394 640 655 669 691 716 765 808 868 949 862 930
3P9SR336L2E2M7 336 269 394 635 650 664 686 711 760 802 862 942 856 923
3P9SR360L2E2M7 360 288 422 677 693 709 732 758 810 856 919 1005 913 985
3P10SR360L2E2M7 360 288 422 682 698 714 737 764 816 862 925 1012 919 992

* Residual voltage correction factor as per IEC recommendation 10kV/10kA/m

8
bow-epp-0016-08-06-2.qxd 08.11.2006 16:23 Uhr Seite 9

Station Class
Polymeric Surge Arresters

Mechanical and Reference Information 2PH & 3P Class 3

Total Overall Recommended Recommended Maximun Drawing Data sheet


creepage height minimum minimum applied reference reference
mm mm phase distance cantilever
(nom) (max) centres line to earth load
mm mm N

1325 488 546 163 4000 BOW-6-019 BOW-EPP-2PHSRC30


1325 488 603 196 4000 BOW-6-019 BOW-EPP-2PHSRC36
1325 488 631 212 4000 BOW-6-019 BOW-EPP-2PHSRC39
1325 488 659 228 4000 BOW-6-019 BOW-EPP-2PHSRC42
2650 970 716 261 2000 BOW-6-019 BOW-EPP-2P2HSRC48
2650 970 828 326 2000 BOW-6-019 BOW-EPP-2P2HSRC60
2650 970 969 408 2000 BOW-6-019 BOW-EPP-2P2HSRC75
2650 970 1054 456 2000 BOW-6-019 BOW-EPP-2P2HSRC84
3975 1454 1347 522 1000 BOW-6-019 BOW-EPP-2P3HSRC96
3975 1454 1460 587 1000 BOW-6-019 BOW-EPP-2P3HSRC108
3975 1454 1572 652 1000 BOW-6-019 BOW-EPP-2P3HSRC120
5300 1936 1685 717 500 BOW-6-019 BOW-EPP-2P4HSRC132
5300 1936 1741 750 500 BOW-6-019 BOW-EPP-2P4HSRC138
5300 1936 1798 782 500 BOW-6-019 BOW-EPP-2P4HSRC144
5300 1936 1854 815 500 BOW-6-019 BOW-EPP-2P4HSRC150
5300 1936 2023 913 500 BOW-6-019 BOW-EPP-2P4HSRC168
3975 1500 1612 522 2000 BOW-7-001 BOW-EPP-3P3SR96
3975 1500 1725 587 2000 BOW-7-001 BOW-EPP-3P3SR108
3975 1500 1838 652 2000 BOW-7-001 BOW-EPP-3P3SR120
5300 2000 1950 717 1875 BOW-7-001 BOW-EPP-3P4SR132
5300 2000 2064 782 1875 BOW-7-001 BOW-EPP-3P4SR144
5300 2000 2120 815 1875 BOW-7-001 BOW-EPP-3P4SR150
5300 2000 2290 913 1875 BOW-7-001 BOW-EPP-3P4SR168
6625 2500 2402 978 1750 BOW-7-001 BOW-EPP-3P5SR180
6625 2500 2515 1043 1750 BOW-7-001 BOW-EPP-3P5SR192
6625 2500 2571 1076 1750 BOW-7-001 BOW-EPP-3P5SR198
7950 3000 1838 650 1625 BOW-7-001 BOW-EPP-3P6SR120
7950 3000 2712 1163 1625 BOW-7-001 BOW-EPP-3P6SR214
7950 3000 2853 1239 1625 BOW-7-001 BOW-EPP-3P6SR228
7950 3000 2966 1304 1625 BOW-7-001 BOW-EPP-3P6SR240
7950 3000 3079 1369 1625 BOW-7-001 BOW-EPP-3P6SR252
9275 3500 2966 1304 1500 BOW-7-001 BOW-EPP-3P7SR240
9275 3500 3192 1435 1500 BOW-7-001 BOW-EPP-3P7SR264
9275 3500 3417 1565 1500 BOW-7-001 BOW-EPP-3P7SR288
10600 4000 3417 1565 1375 BOW-7-001 BOW-EPP-3P8SR288
10600 4000 3530 1630 1375 BOW-7-001 BOW-EPP-3P8SR300
10600 4000 3643 1695 1375 BOW-7-001 BOW-EPP-3P8SR312
10600 4000 3868 1826 1375 BOW-7-001 BOW-EPP-3P8SR336
11925 4500 3868 1826 1250 BOW-7-001 BOW-EPP-3P9SR336
11925 4500 4094 1956 1250 BOW-7-001 BOW-EPP-3P9SR360
13250 5000 4094 1956 1125 BOW-7-001 BOW-EPP-3P10SR360

9
bow-epp-0016-08-06-2.qxd 08.11.2006 16:23 Uhr Seite 10

Station Class
Polymeric Surge Arresters

Installations

3P9SR360 - Statnett - 400kV 4P13S444 - Indonesia - 500kV

4P8S260 - Skelton Grange - 275kV

10
bow-epp-0016-08-06-2.qxd 08.11.2006 16:23 Uhr Seite 11

Station Class
Polymeric Surge Arresters

4P Series Parallel

L5
Corona Ring Line Clamp
to suit cables
up to Ø35 mm

Silicone Rubber
Housed Arrester
Module

L3
Line Clamp
to suit cables
up to Ø16 mm

Silicone Aluminium
intersection cross-arm
L2
Aluminium Stem
Ø30 x 80mm high

Corona Shield

E5
Earth Clamp
to suit cables
up to Ø35 mm

E2
Earth Clamp
to suit cables
up to Ø16 mm

E1
M7 2 x M10 x 20mm
4 Polyfibre Base Insulators Hexagon headed
connected to galvanised steel plate set screws and
spring washers

Example: 4P 8SR 336 L2 E2 M7


Parallel Paths Mounting
Series Stages Earth Terminal
Voltage Line Terminal

11
bow-epp-0016-08-06-2.qxd 08.11.2006 16:23 Uhr Seite 12

Station Class
Polymeric Surge Arresters

Protective Characteristics 3P, 4P Class 4 & 5P

Product code Rating Max Temporary Max residual voltage kV crest with current wave Steep
voltage cont. over- current
kV operating voltage Switching surge Lightning current residual
voltage capability 30/60 µS 8/20 µS voltage*
(COV) kV for 1 sec
(TOV) kV 125A 250A 500A 1000A 2000A 5kA 10kA 20kA 40kA 10kA 20kA
kV kV kV kV kV kV kV kV kV kV kV
crest crest crest crest crest crest crest crest crest crest crest
3P3SR96L2E2M7-4 96 76.8 114 183 188 192 198 205 219 232 249 272 247 267
3P3SR108L2E2M7-4 108 86.4 128 205 209 214 221 229 245 259 278 303 276 298
3P3SR120L2E2M7-4 120 96.0 142 226 231 236 244 253 270 285 306 335 304 328
3P4SR120L2E2M7-4 120 96.0 142 226 231 236 244 253 270 285 306 335 304 328
3P4SR132L2E2M7-4 132 106 156 254 260 266 274 284 304 321 345 377 342 369
3P4SR144L2E2M7-4 144 115 170 273 279 285 295 305 326 345 370 405 368 397
3P4SR150L2E2M7-4 150 120 177 282 289 295 305 316 338 357 383 419 380 410
3P4SR168L2E2M7-4 168 134 199 320 327 335 346 358 383 404 434 474 431 465
3P5SR180L2E2M7-4 180 144 213 341 349 357 368 382 408 431 463 506 459 496
3P5SR192L2E2M7-4 192 154 227 365 373 381 394 408 436 461 495 541 491 530
3P5SR214L2E2M7-4 214 171 253 412 421 431 445 461 492 520 558 610 555 599
3P5SR228L2E2M7-4 228 182 270 435 445 455 470 487 521 550 590 645 586 633
3P6SR120L2E2M7-4 120 96.0 142 226 231 236 244 253 270 285 306 335 304 328
3P6SR214L2E2M7-4 214 171 253 409 419 428 442 458 490 517 555 607 551 595
3P6SR228L2E2M7-4 228 182 270 438 448 458 473 490 523 553 594 649 589 636
3P6SR240L2E2M7-4 240 192 284 452 462 472 488 506 540 571 613 670 608 657
3P6SR252L2E2M7-4 252 202 298 480 491 502 518 537 574 606 651 712 646 698
3P7SR240L2E2M7-4 240 192 284 461 472 482 498 516 552 582 625 684 621 670
3P7SR264L2E2M7-4 264 211 312 510 522 534 551 571 611 645 692 757 688 742
3P7SR288L2E2M7-4 288 230 341 543 556 568 587 608 650 686 737 806 732 790
3P8SR300L2E2M7-4 300 240 355 565 578 591 610 632 675 713 766 837 760 821
3P8SR312L2E2M7-4 312 250 369 602 616 630 651 674 720 761 817 893 811 876
3P8SR336L2E2M7-4 336 269 397 640 655 669 691 716 765 808 868 949 862 930
3P9SR336L2E2M7-4 336 269 397 635 650 664 686 711 760 802 862 942 856 923
3P9SR360L2E2M7-4 360 288 426 677 693 709 732 758 810 856 919 1005 913 985
3P10SR360L2E2M7-4 360 288 426 682 698 714 737 764 816 862 925 1012 919 992
4P3SR120L2E2M7 120 96.0 140 224 229 234 241 249 265 280 299 325 296 319
4P4SR132L2E2M7 132 106 154 252 257 264 271 280 298 314 337 366 333 359
4P8SR260L2E2M7 260 208 304 485 495 508 522 540 575 606 648 705 642 692
4P8SR330L2E2M7 330 264 386 615 629 645 663 685 729 769 823 894 815 878
4P9SR360L2E2M7 360 288 421 671 686 703 723 748 796 839 898 976 889 958
4P10SR336L2E2M7 336 269 393 629 643 659 678 701 746 786 842 915 833 898
4P10SR360L2E2M7 360 288 421 676 691 708 728 753 801 844 904 982 895 964
4P10SR396L2E2M7 396 317 463 839 857 879 904 934 994 1048 1122 1219 1111 1197
4P11SR396L2E2M7 396 317 463 846 864 886 912 942 1003 1057 1132 1230 1120 1207
4P11SR420L2E2M7 420 336 491 871 891 913 939 971 1033 1089 1166 1267 1154 1244
4P11SR444L2E2M7 444 355 519 922 943 967 994 1028 1094 1153 1235 1341 1222 1317
4P12SR420L2E2M7 420 336 491 867 886 908 934 966 1028 1083 1160 1260 1148 1237
4P12SR468L2E2M7 468 374 548 950 972 996 1025 1059 1127 1188 1272 1382 1259 1357
5P11SR444L2E2M7 444 355 488 922 943 967 994 1028 1094 1153 1235 1341 1222 1317
5P12SR420L2E2M7 420 336 462 867 886 908 934 966 1028 1083 1160 1260 1148 1237
5P12SR468L2E2M7 468 374 512 950 972 996 1025 1059 1127 1188 1272 1382 1259 1357

* Residual voltage correction factor as per IEC recommendation 10kV/10kA/m

12
bow-epp-0016-08-06-2.qxd 08.11.2006 16:23 Uhr Seite 13

Station Class
Polymeric Surge Arresters

Mechanical and Reference Information 3P, 4P Class 4 & 5P

Total Overall Recommended Recommended Maximun Drawing Data sheet


creepage height minimum minimum applied reference reference
mm mm phase distance cantilever
(nom) (max) centres lint to earth load
mm mm N

3975 1500 1612 522 2000 BOW-7-001 BOW-EPP-3P3SR96


3975 1500 1725 587 2000 BOW-7-001 BOW-EPP-3P3SR108
3975 1500 1838 652 2000 BOW-7-001 BOW-EPP-3P3SR120
5300 2000 1838 652 1875 BOW-7-001 BOW-EPP-3P4SR120
5300 2000 1950 717 1875 BOW-7-001 BOW-EPP-3P4SR132
5300 2000 2064 782 1875 BOW-7-001 BOW-EPP-3P4SR144
5300 2000 2120 815 1875 BOW-7-001 BOW-EPP-3P4SR150
5300 2000 2290 913 1875 BOW-7-001 BOW-EPP-3P4SR168
6625 2500 2402 978 1750 BOW-7-001 BOW-EPP-3P5SR180
6625 2500 2515 1043 1750 BOW-7-001 BOW-EPP-3P5SR192
6625 2500 2571 1076 1750 BOW-7-001 BOW-EPP-3P5SR214
6625 2500 2712 1163 1750 BOW-7-001 BOW-EPP-3P5SR228
7950 3000 1838 652 1750 BOW-7-001 BOW-EPP-3P6SR120
7950 3000 2712 1163 1625 BOW-7-001 BOW-EPP-3P6SR214
7950 3000 2853 1239 1625 BOW-7-001 BOW-EPP-3P6SR228
7950 3000 2966 1304 1625 BOW-7-001 BOW-EPP-3P6SR240
7950 3000 3079 1370 1625 BOW-7-001 BOW-EPP-3P6SR252
9275 3500 2966 1304 1500 BOW-7-001 BOW-EPP-3P7SR240
9275 3500 3192 1435 1500 BOW-7-001 BOW-EPP-3P7SR264
9275 3500 3417 1565 1500 BOW-7-001 BOW-EPP-3P7SR288
9275 3500 3530 1630 1375 BOW-7-001 BOW-EPP-3P8SR300
10600 4000 3643 1695 1375 BOW-7-001 BOW-EPP-3P8SR312
10600 4000 3868 1826 1375 BOW-7-001 BOW-EPP-3P8SR336
11925 4500 3868 1826 1250 BOW-7-001 BOW-EPP-3P9SR336
11925 4500 4094 1956 1250 BOW-7-001 BOW-EPP-3P9SR360
13250 5000 4094 1956 1125 BOW-7-001 BOW-EPP-3P10SR360
3975 1500 1848 652 2875 BOW-8-001 BOW-EPP-4P3SR120
5300 2000 1925 717 2750 BOW-8-001 BOW-EPP-4P4SR132
10600 4000 3156 1413 2250 BOW-8-001 BOW-EPP-4P8SR260
10600 4000 3814 1793 2250 BOW-8-001 BOW-EPP-4P8SR330
11925 4500 4095 1956 2125 BOW-8-001 BOW-EPP-4P9SR360
13250 5000 3870 1826 2000 BOW-8-001 BOW-EPP-4P10SR336
13250 5000 4096 1956 2000 BOW-8-001 BOW-EPP-4P10SR360
13250 5000 4435 2152 2000 BOW-8-001 BOW-EPP-4P10SR396
14575 5500 4435 2152 1875 BOW-8-001 BOW-EPP-4P11SR396
14575 5500 4660 2282 1875 BOW-8-001 BOW-EPP-4P11SR420
14575 5500 4885 2413 1875 BOW-8-001 BOW-EPP-4P11SR444
15900 6000 4660 2282 1750 BOW-8-001 BOW-EPP-4P12SR420
15900 6000 5110 2543 1750 BOW-8-001 BOW-EPP-4P12SR468
14575 5500 5089 2413 2200 BOW-25-001 BOW-EPP-5P11SR444
15900 6000 4863 2283 2000 BOW-25-001 BOW-EPP-5P12SR420
15900 6000 5315 2543 2000 BOW-25-001 BOW-EPP-5P12SR468

13
bow-epp-0016-08-06-2.qxd 08.11.2006 16:23 Uhr Seite 14

Station Class
Polymeric Surge Arresters

The PSRB surge arrester is available for applications up


to 220kV systems.
The design utilises a housing construction, which is a
resin and glass fibre strengthening sleeve over moulded
with Silicone Rubber outer insulating housing fitted with
aluminium flanges.
High cantilever mechanical strength is achieved on this
design with the internal assembly similar to that of the
porcelain Housed Surge Arrester.
The design has been tested to IEC and demonstrates a
63kA short circuit performance.
Routine tests are carried out to show that the
manufacturing conforms to the current international
standard.

Electrical Performance
Specification: IEC60099-4
Classification: Class 2 10kA
High Current Performance: 100kA
Pressure Relief 63 kA
Energy Capability:
5.0kJ/kV at Ur according to IEC60099-4
(Clause 8.4.2 table 5 & 8.5.5)
Voltage Rating: 60kV to 228kV PSRB3180 - Brazil - 220kV

Typical Applications
• Substations
• Power Transformers
• Cable Termination

14
bow-epp-0016-08-06-2.qxd 08.11.2006 16:23 Uhr Seite 15

Station Class
Polymeric Surge Arresters

Corona Ring
(150kV and above)

L5
Line Clamp
to suit cables
up to Ø35 mm

Grading Ring
(None <120kV) L3
(Ø610 120-150kV) Line Clamp
(Ø710 151-228kV) to suit cables
up to Ø16 mm

Silicone Rubber
Housed Arrester
Unit

L2
Aluminium Stem
Ø30 x 80mm high

L1 (as E1)
2 x M10 x 20mm
Hexagon headed
set screws and
spring washers

Die Cast
Aluminium
End Flange

E2
Earth Clamp
to suit cables
up to Ø16 mm

M3 E1
Diaphram Deflector Plate with 2 x M10 x 20mm
3 M16 Polyfibre Base Insulators Hexagon headed
equally spaced on 178 PCD set screws and
spring washers
Example: PSRB2 138 L2 E1 M3
Arrester Housing Mounting
Voltage Earth Terminal
Line Terminal

15
bow-epp-0016-08-06-2.qxd 08.11.2006 16:23 Uhr Seite 16

Station Class
Polymeric Surge Arresters

Protective Characteristics PSRB

Product code Rating Max Temporary Max residual voltage kV crest with current wave Steep
voltage cont. over- current
kV operating voltage Switching surge Lightning current residual
voltage capability 30/60 µS 8/20 µS voltage*
(COV) kV for 1 sec
(TOV) kV 125A 250A 500A 1000A 2000A 5kA 10kA 20kA 40kA 10kA 20kA
kV kV kV kV kV kV kV kV kV kV kV
crest crest crest crest crest crest crest crest crest crest crest
PSRB160L2E1M3 60 48.0 70.0 117 120 125 129 136 148 159 175 199 171 189
PSRB175L2E1M3 75 60.0 87.5 147 151 156 162 170 185 199 219 249 213 236
PSRB296L2E1M3 96 76.8 112 188 193 200 208 218 237 255 281 320 274 302
PSRB2108L2E1M3 108 86.4 126 212 218 226 235 246 268 288 317 361 309 342
PSRB2120L2E1M3 120 96.0 140 234 241 249 259 272 296 318 350 399 341 377
PSRB2132L2E1M3 132 106 154 259 266 275 286 300 327 351 387 440 377 416
PSRB2138L2E1M3 138 110 161 274 281 291 302 317 345 371 409 465 398 440
PSRB2150L2E1M3 150 120 175 293 301 311 324 339 370 397 438 498 426 471
PSRB2168L2E1M3 168 134 196 330 339 350 364 382 416 447 493 560 480 530
PSRB3198L2E1M3 198 158 231 388 399 412 429 450 490 526 580 660 565 624
PSRB3228L2E1M3 228 182 266 447 459 475 494 518 564 606 668 760 650 719

* Residual voltage correction factor as per IEC recommendation 10kV/10kA/m

Mechanical and Reference Information PSRB

Total Overall Recommended Recommended Maximun Drawing Data sheet


creepage height minimum minimum applied reference reference
mm mm phase distance cantilever
(nom) (max) centres line to earth load
mm mm kN

2378 1000 764 326 10 BOW-18-004 BOW-EPP-PSRB1-60


2378 1000 905 407 10 BOW-18-004 BOW-EPP-PSRB1-75
4756 2025 1103 522 5 BOW-18-005 BOW-EPP-PSRB2-96
4756 2025 1216 587 5 BOW-18-005 BOW-EPP-PSRB2-108
4756 2025 1738 652 5 BOW-18-005 BOW-EPP-PSRB2-120
4756 2025 1851 717 5 BOW-18-005 BOW-EPP-PSRB2-132
4756 2025 1908 750 5 BOW-18-005 BOW-EPP-PSRB2-138
4756 2025 2020 815 5 BOW-18-005 BOW-EPP-PSRB2-150
4756 2025 2290 913 5 BOW-18-005 BOW-EPP-PSRB2-168
7134 3025 2572 1076 3.5 BOW-18-006 BOW-EPP-PSRB3-198
7134 3025 2854 1239 3.5 BOW-18-006 BOW-EPP-PSRB3-228

16
bow-epp-0016-08-06-2.qxd 08.11.2006 16:23 Uhr Seite 17

Surge Counters

Meter – 6 digit cyclometer at least


5 counts/second
Minimum count current – 200 amps 8/20 microsecond
wave
Maximum High Current – 100kA 4/10 microsecond
Withstand wave
Nominal Residual – 5kV peak
Voltage at 100kA with
4/10 Microsecond Wave
Meter scale – 0 - 30mA (bilinear scale)
Ref SC13
SC13 leakage – 0 - 50mA (bilinear scale)
Ref SC13L Surge Counters SC12, SC13 designed to be used
with Surge Arresters
Both SC12/SC13 counters can be supplied with an
auxiliary contact rated 0.5 amps 250V for connection to
remote signalling equipment. If required put suffix AC
e.g. SC12/AC

Transmission Line Arrester “TLA”

Transmission Line surge arresters for systems up to 230 kV.

Specification: IEC60099-4
Classification: 10kA
Voltage Rating: 15kV to 192 kV
High Current Performance: 100kA
Line Discharge Class: 2
Energy Capability:
4.5kJ/kV at Ur according to IEC60099-4
(Clause 8.4.2 table 5 and 8.5.5)
TLA1 15 - 45 kV
TLA2 48 - 96 kV
TLA3 108 - 144kV
TLA4 150 - 192 kV
Insulation Material: Silicone Rubber

Vibration tested at National Engineering Laboratory - UK

TLA Applications
TLA5E -192
• Towers that have high footing resistance to impedance earth can cause
back flashover on to the line.

• Transmission lines with or without shielding wire which have abnormal


lightning activity

17
bow-epp-0016-08-06-2.qxd 08.11.2006 16:24 Uhr Seite 18

Additional Ranges

Other products in our range

DC traction surge arresters DC Traction surge arresters for system voltages


0.7-4kV (HE60MC) to EN50123-5
AC surge arresters for system voltages 15-25kV single
phase (HSR) to IEC 60099-4 & EN50123-5.

Contact us at: [email protected]

CSPA surge arresters Cable sheath surge arresters available for protection
of underground cables. Surge arrester modules used
for direct burried or installed in a link box.
(CSPA/CPA) to IEC 60099-4.

Contact us at: [email protected]

Airfield lighting box Airfield lighting control circuits are vulnerable to


lightning surges as they have an attractive low
impedance path. Protection of 4kV DC lighting
circuits. (2DCAFL4) to IEC 60099-4.

Contact us at: [email protected]

Spark gap Replaceable spark gap device with sparkover voltage


450-900V. Mainly used on railway networks to protect
earthing in conjunction with signalling (SPG).

Contact us at: [email protected]

Portable earth kits Portable earthing kit designed to ESI standards used
to protect utility engineers working on distribution or
transmission lines from accidental line switching.

Contact us at: [email protected]

Cable spiker kit Hydraulic Cable Spiker used to prove that a


disconnected underground cable is not live before site
work commences. 25 year product reliability (CSTE).

Contact us at: [email protected]

18
bow-epp-0016-08-06-2.qxd 08.11.2006 16:24 Uhr Seite 19

Energy Division is a worldwide leader with innovative solutions


from the power plant to the end user.

Other products and brochures available from Energy Division

Asset protection Insulation enhancement systems for substations and


overhead. Designed to prevent unplanned outages
due to accidential bridging.

Contact us at: [email protected]

Low-voltage surge arresters LV arresters are used to provide protection for LV


overhead lines, consumer in-house supplies,
distribution tranformers and other applicances.

Contact us at: [email protected]

Medium-voltage surge arresters Metal oxide varister, distribution arresters for indoor
and outdoor applications for protection of overhead
lines.

Contact us at: [email protected]

High-voltage surge arresters Porcelain and polymeric series parallel and single
column contructed arresters for protection of
transmission systems up to 550 kV. DC locomotives
and switchgear applications.

Contact us at: [email protected]

Polymeric insulators Insulators and insulating components/housings


providing reliable solutions for power utilities and
railway customers with installations in high pollution
environments and applications up to 400 kV.

Contact us at: [email protected]

Porcelain insulators Insulators for applications up to system voltages of


132 kV. This range of insulators offers a cost-effective
solution for low and medium polluted environments.

Contact us at: [email protected]

19
bow-epp-0016-08-06-2.qxd 24.11.2006 15:47 Uhr Seite 20

Additional Product Lines:

Energy Division
http://energy.tycoelectronics.com

Polymeric DC Traction
Surge Arrester

Transmission Porcelain Surge Arresters


Spark Gap Type SPG4/12

The SPG4 Spark Gap is designed for use with traction


circuits to provide virtually instantaneous protection of
both equipment and personnel from power system
faults. The unit also provides protection against
lightning generated voltages which would otherwise
cause damage to signalling and cable circuits.

The SPG4 is constructed in stainless steel of rugged


design allowing the SPG to be installed in harsh
environments such as track side locations without
additional weather protection.

Suitable for use on circuits where standing/induced


voltages do not exceed 110v RMS.

Fast operation – Typical 5 microseconds with 11kA fault


current.

Internal spark gap module unit easily replaced after fault


current operation.

Fail safe feature ensures safety to personnel and


equipment.

Service proven performance.

High internal impedance with low capacitance – does not


interfere with track signalling circuits.

ENERGY DIVISION ENERGY DIVISION

Transmission Surge Arresters Polymeric DC Traction Surge Spark Gap Type SPG4/12
Porcelain Arresters • Protection between overhead catenary
• Porcelain Housed Surge Arrester • Rolling Stock structure earth and system earth
• Track Side • Protection of single bonded power cable
circuits
• Protection of low voltage DC power supplies
• Protection of cathodic protection power
supplies.

Energy Division Energy Division Energy Division


http://energy.tycoelectronics.com http://energy.tycoelectronics.com http://energy.tycoelectronics.com

Airfield Lighting Box Type 2DCAFL4 Transmission Line Arrester “TLA” Surge Counters
Type SC12 & SC13

There are few places more exposed to direct lightning The Bowthorpe EMP range of Surge
strikes than an airfield. In such situations lightning Arrester monitoring instruments are
strikes within the vicinity of the airfield can result in fully tested for use with any
permanent damage to electrical equipment. manufacturers surge arrester. The
Airfield lighting circuits are particularly vulnerable as SC12 is a Surge Counter only, whilst
the associated cable networks present an attractive low the SC13 provides the additional
impedance path for lightning surge currents to earth. measurement of total leakage
The result of a nearby lightning strike can be current. The analogue instrument
permanent damage to the control circuits unless a provides a means of monitoring the
suitable lightning arrester is fitted to the lighting current through the arrester and the
control equipment. leakage current over the surface of
The Lightning Arrester Type 2DCAFL4 is designed to the arrester housing. Significant
protect airfield lighting control equipment from the changes after installation may
effects of direct or indirect lightning strikes. indicate a deterioration in the
arrester or a build up of surface
The arrester is provided with two metal oxide active
contamination.
elements which are connected in parallel with the
These instruments, which require no
supply cables. Installation requires only the cutting of
auxiliary supply, are designed for
the supply cables at a convenient place close to the
control equipment and connection of the arrester to a installation in the earth connections
good electrical earth. of a single surge arrester or
alternatively the SC12 may be used
Arrester 2DCAFL4 can be fitted to new equipment but with the common earth of a three
is primarily designed to be quickly installed on existing
phase set. Fully weatherproofed and
circuits.
sealed for life they are housed in a
one piece gravity die cast aluminium
case coated to enhance its already rear of the case providing a single
high degree of resistance to surface clearance hole for the galvanised
corrosion. The glass viewing window steel M12 bolt supplied.
is sealed in place, using a silicon
rubber adhesive, and a desiccator is The SC12 and SC13 are service
enclosed to ensure any residual proven and require no special
moisture trapped during sealing is maintenance or servicing apart from
absorbed for the service life of the general cleaning of the glass
counter. Mounting is effected by viewing window and the moulded
means of an integrally cast lug at the epoxy resin line terminal bushing.

Airfield Lighting Box Type 2DCAFL4 Transmission Line Arrester ‘TLA’ Surge Counters Type SC12 & SC13
• Protection of airfield lighting control • Switching over voltages are absorbed • Used in series with HV Surge Arresters
equipment. over the length of the line reducing the • SC12 Surge Counters.
severity of surge at the substation. • SC13 Combined Surge Counter with
• Transmission systems can be operated Leakage Current Meter.
even where sub-soil gives poor tower
footing resistance.

Tyco Electronics UK Ltd Bowthorpe EMP All of the above information, including drawings, illustrations and graphic designs, reflects our present understanding and
Stevenson Road, Brighton, East Sussex, is to the best of our knowledge and belief correct and reliable. Users, however, should independently evaluate the suitability
England BN2 0DF of each product for the desired application. Under no circumstances does this constitute an assurance of any particular quality
or performance. Such an assurance is only provided in the context of our product specifications or explicit contractual
Phone: +44 (0) 1273 692591 arrangements. Our liability for these products is set forth in our standard terms and conditions of sale. BOWTHORPE EMP is a
Fax: +44 (0) 1273 601741 trademark.
http://www.bowthorpe-emp.com

Energy Division – economical solutions for the electrical power industry: cable accessories,
connectors & fittings, electrical equipment, instruments, lighting controls, insulators &
insulation enhancement and surge arresters.

© Tyco Electronics BOW-EPP-0016-11-06