Armorblock 2-Port Ethernet/Ip Module: Installation Instructions
Armorblock 2-Port Ethernet/Ip Module: Installation Instructions
Table of Contents
Topic Page
Overview 4
Product Dimensions 8
Specifications 15
2 ArmorBlock 2-Port EtherNet/IP Module
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages
resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the
many variables and requirements associated with any particular installation, Rockwell Automation, Inc.
cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits,
equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell
Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
SHOCK HAZARD: Labels may be on or inside the equipment (for example, drive or
motor) to alert people that dangerous voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment (for example, drive or
motor) to alert people that surfaces may reach dangerous temperatures.
IMPORTANT Identifies information that is critical for successful application and understanding of the
product.
Additional Resources
Resource Description
Pinout Guide for 1732 ArmorBlock 2 Port Detailed description of how to wire your module.
Ethernet Block, publication 1732E-WD001
1732E EtherNet/IP ArmorBlock supporting Detailed description of how to install, configure and use
Sequence of Events, your 1732E-IB16M12SOEDR module.
publication 1732E-UM002
Integrated Architecture and CIP Sync Detailed explanation on how to set up and use
Configuration, publication IA-AT003 ArmorBlock modules in a CIP Sync application.
Industrial Automation Wiring and Grounding More information on proper wiring and grounding
Guidelines, publication 1770-4.1 techniques.
Overview
The EtherNet/IP ArmorBlock is a 24V DC I/O module that communicates via
EtherNet/IP. The sealed IP65, IP67 and IP69K housing of these modules requires no
enclosure. I/O connectors are sealed M12 style.
EtherNet/IP networks use advanced network technology, for example,
producer/consumer communication, to increase network functionality and throughput.
Module Identification
(1) Protective Earth is provided for the grounding of field devices and is internally connected to each Pin 5 of the M12 I/O
connectors. See I/O Connectors on page 9.
(2) Functional Earth grounds the I/O block’s EtherNet/IP communication circuitry which is designed to mitigate the effect of
noise on the network. See EtherNet/IP Connector on page 10.
2. Line up the small notch on the switch with the number setting you wish to use.
Valid settings range from 001…254.
3. Cycle power.
Set Network Address
44233
When the switches are set to a valid number, the I/O block’s IP address is 192.168.1.xxx
(where xxx represents the number set on the switches). The I/O block’s subnet mask is
255.255.255.0 and the gateway address is set to 0.0.0.0. When the I/O block uses the
network address set on the switches, the I/O block does not have a host name assigned to it
or use any Domain Name Server.
If the switches are set to an invalid number (for example, 000 or a value greater than 254
excluding 888), the I/O block checks to see if DHCP is enabled. If DHCP is enabled, the
I/O block asks for an address from a DHCP server. The DHCP server also assigns other
Transport Control Protocol (TCP) parameters.
If DHCP is not enabled, the I/O block uses the IP address (along with other TCP
configurable parameters) stored in nonvolatile memory.
Product Dimensions
Refer to the mounting dimensions illustration to help you mount the module.
Module Dimensions
43.25 mm
65 mm
(1.70 in.)
(2.56 in.)
26.5 mm
(1.04 in.)
LINK 1 LINK 2
179 mm
(7.05 in.)
169 mm
(6.65 in.)
44946
If you mount the module in an area that is subject to shock or vibration, we recommend
you use a flat and a lock washer to mount the module. Mount the flat and the lock washer
as shown in the mounting illustration. Torque the mounting screws to 1.13 Nm (10 in-lb).
Lock washer
I/O Connectors
Self-configuring Connector
EtherNet/IP Connector
ATTENTION: Make sure all connectors and caps are securely tightened to
properly seal the connections against leaks and maintain IP enclosure
requirements.
IMPORTANT Use the 1585D–M4DC–H: Polyamide small body unshielded or the 1585D–
M4DC–SH: Zinc die-cast large body shielded mating connectors for the
D-Code M12 female network connector.
Attach the mini-style 4-pin connector to the mini-style 4-pin receptacle as shown below.
Mini-style 4-Pin Input Male Receptacle
(View into receptacle)
Pin 1 Output power+
4 2
Pin 2 Sensor/MDL power+
Pin 3 Sensor/MDL power-
3 1 Pin 4 Output power-
44809
Auxiliary Power is based on a 4-pin connector system and is used to provide 24V DC
power to I/O modules and other devices. Running separate power to these devices is most
typically used for I/O devices with output connections to prevent power supply
interruption due to switching of outputs. However, some devices require separate auxiliary
power to power them regardless of the presence of outputs.
Depending on the devices used, it may be possible to provide power through only one pair
of the four available pins, and in this case the other available pair may be used for single
channel E-stop through the use of special E-stop drop or power T-ports and shorting
plugs. Allen-Bradley E-stop T-ports and shorting plugs are red in color for
easy identification.
Network address
Auxiliary power
switches
44945
Link Link
status status
indicator indicator
LINK 1 LINK 2
Module Module
status status
indicator indicator
Auxiliary power
indicator
44945
Specifications
1732E ArmorBlock 2-Port EtherNet Module Input – 1732E-8X8M12DR,
1732E-IB16M12R, 1732E-IB16M12DR, 1732E-IB16M12SOEDR,
1732E-16CFGM12R
Attribute Value
Number of inputs 8 – 1732E-8X8M12DR
16 – all other modules
Input type Sink, 24V DC
Voltage, off-state input, max 5V DC
Voltage, on-state input, max 30V DC
Voltage, on-state input, nom 24V DC
Voltage, on-state input, min 11V DC
Current, off-state input, max 1.5 mA @ 5V DC
Current, on-state input, max 5 mA @ 30V DC
Voltage, sensor source, max 30V DC
Voltage, sensor source, min 10V DC
Input delay time
ON to OFF 0…16000 μs
OFF to ON
Isolation voltage 50V (continuous), Basic Insulation Type, Inputs and Sensor Power
to Network.
No isolation between individual Inputs or between
Network channels.
Type tested at 707V DC for 60 s.
General Specifications
Attribute Value
Voltage, auxiliary power, max 30V DC
Voltage, auxiliary power, min 12V DC
Current, Ethernet system power, max (pins 0.4 A – 1732E-OB16M12R, 1732E-OB16M12DR
2, 3 sensor source/module power) 0.8 A – 1732E-8X8M12DR
1.2 A – 1732E-IB16M12R, 1732E-IB16M12DR,
1732E-IB16M12SOEDR,1732E-16CFGM12R
Current, auxiliary power, max per output 4 A – 1732E-8X8M12DR
module (pins 2, 3 sensor source/module 8 A – all other modules
power plus pins 1, 4 for output loads)
Current, sensor source, per input, max 50 mA
Current, sensor source, per connector, max 100 mA
Communication rate EtherNet/IP
10/100 Mbps
Full or half-duplex
100 meter per segment
General Specifications
Attribute Value
Isolation voltage 50V (continuous), Basic Insulation Type, Inputs and Sensor
Power to Network
No isolation between individual Inputs or between
Network channels
Type tested at 707V DC for 60 s
Status indicators Module status - red/green
Network status - red/green
Link status - green/yellow
Auxiliary power - green
I/O LED - yellow
I/O LED - yellow/red – 1732E-*DR modules only
Dimensions (HxWxD), approx. 179 x 65 x 43.25 mm
(7.05 x 2.56 x 1.70 in.)
Weight, approx. 0.34 kg (0.75 lb)
Enclosure type rating Meets IP65/66/67/69K (when marked), and Type 4X with
receptacle dust caps or cable termination.
Wiring category(1) 1 – on signal ports
1 – on power ports
1 – on communications port
(1) Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and
Grounding Guidelines, publication 1770-4.1.
Environmental Specifications
Attribute Value
Temperature, IEC 60068-2-1 (Test Ad, Operating Cold),
operating IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20…60 °C (-4…140 °F)
Temperature, 60 °C (140 °F)
surrounding, max.
Temperature, storage IEC 60068-2-1 (Test Ab, Unpackaged Non-operating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Non-operating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Non-operating Thermal Shock):
-40…85 °C (-40…185 °F)
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5…95% noncondensing
Vibration IEC 60068-2-6 (Test Fc, Operating):
5 g @ 10... 500 Hz
Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock):
30 g
Environmental Specifications
Attribute Value
Shock, non-operating IEC 60068-2-27 (Test Ea, Unpackaged Shock):
50 g
Emissions CISPR 11
Group 1, Class A
ESD immunity IEC 61000-4-2:
6 kV contact discharges
8 kV air discharges
Radiated RF immunity IEC 61000-4-3:
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz
10V/m with 200 Hz 50% Pulse 100% AM @ 900 Mhz
10V/m with 200 Hz 50% Pulse 100% AM @ 1890 Mhz
3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B immunity IEC 61000-4-4:
±4 kV @ 5 kHz on power ports
±3 kV @ 5 kHz on signal ports
±3 kV @ 5 kHz on communications ports
Surge transient IEC 61000-4-5:
immunity ±1 kV line-line(DM) and ±2 kV line-earth(CM) on power ports
±1 kV line-line(DM) and ±2 kV line-earth(CM) on signal ports
±2 kV line-earth(CM) on communications ports
Conducted RF IEC 61000-4-6:
immunity 10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
Certifications
Certification (when Value
product is marked)(1)
For an additional level of technical phone support for installation, configuration and troubleshooting, we
offer TechConnect support programs. For more information, contact your local distributor or Rockwell
Automation representative, or visit http://www.rockwellautomation.com/support/.
Installation Assistance
If you experience a problem within the first 24 hours of installation, please review the information that's
contained in this manual. You can also contact a special Customer Support number for initial help in getting
your product up and running.
United States Contact your distributor. You must provide a Customer Support case number
(call the phone number above to obtain one) to your distributor to complete
the return process.
Outside United States Please contact your local Rockwell Automation representative for the return
procedure.
Documentation Feedback
Your comments will help us serve your documentation needs better. If you have any suggestions on how to
improve this document, complete this form, publication RA-DU002, available at
http://www.rockwellautomation.com/literature/.
Allen-Bradley, Rockwell Automation, ArmorBlock, and TechConnect are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.