Rotamass Yokogawa PDF
Rotamass Yokogawa PDF
3 Series
Specifications Coriolis Mass Flow and Density Meter
with Marine Approval
GS 01R04B10-00E-E
RCCF31 + RCCR31
RCCS34 - 39/IR +
RCCY038/039
Features
Contents
Page 1
FEATURES
• ROTAMASS is a flowmeter for nearly all fluids, including
Principle of measurement Page 1
Performance specifications Page 2
high viscosity liquids, slurries and multi-phase media
Normal operating conditions Page 3
with a certain gas content
Mechanical specifications Page 4
• Field-mount and rack-mount remote converter available
Electrical specifications Page 4 • Refined digital signal processing enables accurate and
Remote cable specification Page 5 stable measurement
CE Declaration Page 5 • A special detector decoupling system makes the device
Hazardous area specifications Page 6 highly independent from external loads or vibrations.
Planning and installation hints Page 9 • Simple flow path means self-draining, simple cleaning.
Dimensions Page 11 • High accuracy and high stability over a wide flow range
Model-, suffix- and option- codes Page 14 • Accurate density measurement, up to +/- 0.0005 g/cm³
• Concentration measurement for solutions, suspensions
and emulsions (e.g. water cut)
ROTAMASS is a Coriolis mass flowmeter with highly
• Volume flow with reference density
refined digital signal processing electronics, so that accurate
• Temperature measurement
and stable mass flow measurement is achieved.
• One analog output, two pulse outputs or status-out and
one status-in as standard I/O
ROTAMASS employs a flame-proof type converter case
• Available in explosion proof versions (ATEX, IECEx,
suitable for use in the hazardous area together with its
INMETRO, NEPSI, KOSHA)
intrinsically safety type detector.
• American NTEP approval for Custody Transfer Measurement
(see GS 01R04B07-00E-E)
ROTAMASS´s signal processing, housing protection and its
• Wide process temperature range –200°C to 230°C
detector´s special decoupling system against external loads and
• Microprocessor-based multifunction capability
vibrations, realize high performance in real applications.
• EEPROM protects parameter settings and totalized
values during power failure.
• High visibly LCD display
PRINCIPLE OF MEASUREMENT • HART® communication function is available.
Mass flow measurement according to the Coriolis principle. • MODBUS® communication is available
For abrasive or highly corrosive fluids please contact your • EN, ASME or JIS flanges as standard, others on request
Yokogawa representative. • Type Approval acc. DNV Rules for classification of ships
Qnom is the water flow rate at about 1 bar pressure drop. Table 4: Accuracy (at calibration conditions):
The flowmeter has a default low cut of 0.05% of Qnom. Type Standard Option /K4 Option /K6
Liquid RCCS34 - 39/IR: RCCS34 0.003 g/cm³ 0.001 g/cm³ 0.0005 g/cm³
± 0.1% of flow rate ± zero stability / flow rate *100% RCCS36 0.0022 g/cm³ 0.001 g/cm³ 0.0005 g/cm³
Accuracy of volume flow : RCCS38 0.0015 g/cm³ 0.001 g/cm³ 0.0005 g/cm³
SQRT ( (mass flow error in %)² + (density error in %)²) RCCS39 0.0015 g/cm³ 0.001 g/cm³ 0.0005 g/cm³
RCCS9/IR 0.0015 g/cm³ ------ ------
Accuracy based on the frequency output includes the combined
effects of repeatability, linearity and hysteresis. Repeatability:
RCCS34-39/IR : ± 0.0005 g/cm³ (Std, /K4)
Repeatability of liquids: Static pressure effect:
± 0.05% ± (zero stability/2) / flow rate *100% Compensated if static pressure is set in the menu.
1.0
0.9
0.8 Specification of high performance density measurement
0.7
0.6 option /K6: Density calibration
0.5
0.4 Density range : 0.3 to 2.5 kg/l
0.3
Ambient temp. range : -10°C to 50°C (14°F to 122°F)
Error in %
0.2
0.1
0 Process temp. range Standard: -50°C to 150°C (58°F to 302°F)
-0.1
-0.2
-0.3
Minimum flow rate for specified accuracy:
-0.4
-0.5
- RCCS36 to RCCS39 : 700 kg/h (1543 lb/h)
-0.6
-0.7 - RCCS34 : 140 kg/h (308 lb/h)
-0.8
-0.9
-1.0
0 50 100 150 Maximum flow rate : Qnom
Flow in % of Qnom F10.EPS Repeatability : ±0.0002 g/cm³
Temperature measurement:
±(0.5°C+0.002*abs(Tmedium-20°C))
Table 2 : Zero stability Density accuracy : only for liquids, one phase
Model RCCS34 RCCS36 RCCS38 RCCS39
RCCS39 Process temperature influence :
/IR ±0.000015 g/cm³ * abs(Tmedium-20°C)
kg/h 0.15 0.5 1.6 5 13
lb/h 0.33 1.1 3.5 11 28.6 Temperature Measurement
Temperature measuring range of converter :
Pressure Dependency Standard, /LT, /MT : -200°C to 230°C (-328°F to 448°F)
The stiffness of the ROTAMASS tubes is slightly line pressure Accuracy:
dependent. The static pressure effect of mass flow and density Standard (-70°C to 150°C / -94°F to 302°F)
can be corrected by setting the static pressure manually via menu. : ±(0.5°C+0.005*abs(Tmedium-20°C))
Option /LT (-200°C to 150°C / -328°F to 302°F)
Table 3 : Static pressure effect on mass flow (if not corrected)
: ±(1.0°C+0.008*abs(Tmedium-20°C))
Model RCCS34 RCCS36 RCCS38 RCCS39
RCCS39 Option /MT (-70°C to 230°C / -94°F to 446°F)
/IR : ±(0.5°C+0.005*abs(Tmedium-20°C))
% of For process temperatures more than 80°C (176°F) higher
rate 0.00081 / 0.00346 / 0.00950 / 0.01058 / 0.0047 /
per bar (0.01175) (0.05018) (0.1378) (0.15345) (0.0682)
/ (psi)
GS 01R04B10-00E-E 3rd edition July 22, 2017-00 All Rights Reserved. Copyright © 2015, Rota Yokogawa
3
1)
The specified temperatures are defined by DNV classes for
piping systems. The de facto process temperature ranges of
ROTAMASS depend on the instrument configuration.
All Rights Reserved. Copyright © 2015, Rota Yokogawa GS 01R04B10-00E-E 3rd edition July 22, 2017-00
4
GS 01R04B10-00E-E 3rd edition July 22, 2017-00 All Rights Reserved. Copyright © 2015, Rota Yokogawa
5
Isolation Resistance of Converter Rotamass 3 series Coriolis mass flow and density meter is
When surge arrestors are removed a tailor-made product that is specifically designed to both be
- between power and ground terminal: >100 MΩ / 500 V DC installed and function within:
- between power and I/O terminals : >20 MΩ / 100 V DC - Large-scale fixed installations
- between I/O terminals and ground : >20 MΩ / 100 V DC - Means of transport for persons or goods, excluding electric
two-wheel vehicles which are not type-approved
The EU Directive 2011/65/EU (RoHS II) does not apply to this
Dielectric Strength product and is not part of its CE-Marking. This product must
When surge arrestors are removed not be used beyond its Intended Use. Please consider the
- between power and ground terminal : 1,500 V AC for 1 minute above if the intended installation location of your device is
inside European Economic Area.
Lightning Protection
Arresters 2000 A are inside of the converter for power
supply lines.
Electromagnetic Compatibility
Acc. IEC 61326-1: Class A, Table 2
IEC 61326-2-3
IEC 61000-3-2
IEC 61000-3-3
DNV standard for Certification No. 2.4, Class A
All Rights Reserved. Copyright © 2015, Rota Yokogawa GS 01R04B10-00E-E 3rd edition July 22, 2017-00
6
WARNING
Remote rack-mount converter RCCR31 must be installed in
safe area !
GS 01R04B10-00E-E 3rd edition July 22, 2017-00 All Rights Reserved. Copyright © 2015, Rota Yokogawa
7
WARNING
Remote rack-mount converter RCCR31 must be installed in
safe area !
All Rights Reserved. Copyright © 2015, Rota Yokogawa GS 01R04B10-00E-E 3rd edition July 22, 2017-00
8
Table 7 : Temperature classification for ATEX, IECEx, INMETRO, NEPSI and KOSHA certified flowmeter
RCCS34 to RCCS39/IR
without insulation
Temp. class Max. ambient Max. process
temperature temperature
T6 40°C / 104°F 40°C / 104°F
T5 55°C / 131°F 55°C / 131°F
70°C / 158°F 100°C / 212°F
T4
40°C / 104°F 120°C / 248°F
70°C / 158°F 160°C / 320°F
T3
40°C / 104°F 180°C / 356°F
T2 70°C / 158°F 220°C / 428°F
T1 70°C / 158°F 220°C / 428°F
GS 01R04B10-00E-E 3rd edition July 22, 2017-00 All Rights Reserved. Copyright © 2015, Rota Yokogawa
9
All Rights Reserved. Copyright © 2015, Rota Yokogawa GS 01R04B10-00E-E 3rd edition July 22, 2017-00
10
Density Measurement
There are 3 levels of density measurement. The standard adjustment and /K4 delivers an accuracy up to 0.001 g/cm³, if the fluid den-
sity is around 1 kg/l. However, at elevated temperatures the density error may increase. For option /K4 the instrument is
preheated ensuring long term stability. Option /K6 includes preheating, a full calibration at 3 different densities, increased temperature
measurement specification and individual adjustment of the fluid temperature dependency. Multi-phase flow can generate higher de-
viations. The higher the density differences of the single components are the more likely it is that a negative density error is generated.
Aeration has to be avoided fully to receive good density measurement.
For more information please see TI 01R04B04-05E ”Density Measurement with ROTAMASS”.
Note: Density specification under calibration condition only with flow direction “forward” according the arrow on the meter.
Table 8: Overview density-/volume- flow measurement:
Option Accuracy Certificate Description Typical Application
Standard ± 0.0015 g/cm³ to Standard (mass flow) - Standard adjustment with water and air - Process medium and environment are
± 0.02 g/cm³ factory calibration - Density constants given in mass flow approximately at room temperature, the density
certificate certificate range is 0.9 kg/l to 1.1 kg/l
Option /K4 ± 0.001 g/cm³ Standard (mass flow) - Thermal treatment of the sensor and - Improved volume flow accuracy
factory calibration special hardware design - Process medium up to 150°C, for higher
certificate - Standard adjustment with water and air temperature select option /MT
- Density constants given in mass flow - Density range is 0.9 kg/l to 1.1 kg/l
certificate
Option /K6 ± 0.0005 g/cm³ Separate factory - Thermal treatment of the sensor and - Density and concentration measurement in
density calibration special hardware design addition to the mass flow:
certificate - Density calibration with 3 different liquids - Process medium up to 150°C
- Individual adjustment of the fluid - Density range 0.3 kg/l to 2.5 kg/l
temperature dependency - Best volume flow accuracy
For marine application acc. DNV Type approval the process pressure is limited according section „Process pressure limit“ (page 3).
GS 01R04B10-00E-E 3rd edition July 22, 2017-00 All Rights Reserved. Copyright © 2015, Rota Yokogawa
11
DIMENSIONS
Remote field-mount Converter RCCF31
Without Display
17 (0.66)
Ø102 (4.01) 75 (2.95)
201(7.91)
(4.72)
91.6 (3.6)
120
Ø123(4.84)
(2.51)
(12)
305
122 (4.80)
64
29 32 29
(1.14) (1.25) (1.14)
85 (3.34)
124 122
(4.88) (4.80) 148 (5.82)
201(7.91)
(4.72)
120
91.6 (3.6)
Ø123 (4.84)
(12)
305
(2.51)
122 (4.80)
64
49 32 29
(1.92) (1.25) (1.14)
85 (3.34)
144 (5.66) 122 (4.80) 148 (5.82)
Dimensions in mm (inches)
Dimensios in mm
19-inch rack, acc. IEC / DIN EN 60297-3-101
Weight: 1.5 kg
All Rights Reserved. Copyright © 2015, Rota Yokogawa GS 01R04B10-00E-E 3rd edition July 22, 2017-00
12
(3.14)
80
98 (3.85)
H6
H5
H4
H1
L3 W1 Option /S2, /MT,
Option /LT with
L2
Hazardous Area Approval
W2
Note: The flange dimensions depend on size and pressure rating of the flange.
Model L1 L2 L3 H1 W1 W2 H4 H5 H6 Weight
mm 10-21 kg
RCCS34 see table 11 272 (10.7) 212 (8.35) 177 (6.97) 60 (2.36) 80 (3.15) 80 (3.15) 138 (5.43) 218 (8.58)
(inches) (22-46 lbs)
mm 15-35 kg
RCCS36 see table 11 400 (15.7) 266 (10.5) 230 (9.06) 76 (2.99) 90 (3.54) 80 (3.15) 138 (5.43) 218 (8.58)
(inches) (33-77 lbs)
mm 25-50 kg
RCCS38 see table 11 490 (19.3) 267 (10.5) 269 (10.6) 89 (3.5) 110 (4.33) 100 (3.94) 148 (5.82) 228 (8.97)
(inches) (55-110 lbs)
mm 60-103 kg
RCCS39 see table 11 850 (33.5) 379 (14.9) 370 (14.6) 129 (5.08) 160 (6.3) 135 (5.31) 166 (6.53) 245 (9.65)
(inches) (132-227 lbs)
Dimensions in mm (inches). Weights with smallest and biggest flanges.
GS 01R04B10-00E-E 3rd edition July 22, 2017-00 All Rights Reserved. Copyright © 2015, Rota Yokogawa
13
(2.2.8)
(3.85)
(10.47)
(7.32)
(6.93)
(21.9)
(21.9)
(27.19)
(6.63)
(35.12)
(4.02)
(6.93)
All Rights Reserved. Copyright © 2015, Rota Yokogawa GS 01R04B10-00E-E 3rd edition July 22, 2017-00
14
1)
see selection table „Process connection and materials“ (table 11)
GS 01R04B10-00E-E 3rd edition July 22, 2017-00 All Rights Reserved. Copyright © 2015, Rota Yokogawa
15
All Rights Reserved. Copyright © 2015, Rota Yokogawa GS 01R04B10-00E-E 3rd edition July 22, 2017-00
16
Hazardous Area Approvals 1) /KF1 ATEX Flame proof converter + Intrinsically safe detector output with /HP not for gas group IIC
/EF1 IECEx Flame proof converter + Intrinsically safe detector output with /HP not for gas group IIC
/UF1 INMETRO Flame proof converter + Intrinsically safe detector output with /HP not for gas group IIC
/NF1 NEPSI Flame proof converter + Intrinsically safe detector output with /HP not for gas group IIC
Marine Approval 2) /MC2 Marine approval acc. DNV piping class 2 not for thermal oil application
/MC3 Marine approval acc. DNV piping class 3 not for thermal oil application
Custody Transfer Measurement /Q20 NTEP approval 12-080A2, Accuracy class 0.3 acc. NIST Handbook 44 Only in combination with RCCS34 to 39
(Refer to GS 01R04B07-00E)
/Q21 NTEP approval 12-080A2, Accuracy class 0,3 acc. NIST Handbook 44, Heated Only in combination with RCCS39/IR; not with /Q01,
Products /Q20 (Refer to GS 01R04B07-00E)
High Driving Power /HP High Driving Power, recommended for combination with RCCS36 to 39, strongly
recommended for combination with RCCS39/IR, Please see „ Hazardous Area
Specifications“
Communication /MB2 Modbus communication protocol for all parameters and values not with /Q20, /Q21, /AP, /NM, /MB3
/MB3 Modbus communication protocol for all parameters and values incl. HART not with /MB2
Communication, analogue output, pulse/status output, status input
NAMUR Switch /NM One pulse output acc. EN 60947-5-6 (NAMUR) not with /AP
Active Pulse Output /AP One active pulse output not with /NM
Tag Number /BG With customer specified tag number on name plate max. 16 characters; the last 8 significant characters are
used for HART® Tag;
characters acc. Codepage 850 (Multi-lingual)
HART® Tag Number (Software Tag) /BT1 With customer specified tag number for HART® communication in converter 22 characters for long tag;
characters acc. Codepage 850 (Multi-lingual)
No Combination /NC No combination with detector
Epoxy Coating /X1 Epoxy coating of converter housing
Delivery to Korea /KC With KC-mark for Korea
Delivery to China /CN For delivery to China combination with Hazardous Area Approval only with /NF1
Concentration Measurement 4) /CST Standard concentration measurement not with /C
/C Advanced concentration measurement, details see table „Advanced Concentration not with /CST
Measurement Options“
Certificates /P2 Certificate of compliance with the order acc. EN 10204:2004 -2.1
/P3 Test Report acc. EN10204:2004-2.2(QIC) including the content of option /P2
Instruction Manuals /IE Quantity of instruction manuals in English = 1 to 3 selectable 5)
1)
Select affiliated RCCS3 with the same approval type (e.g. /KF with /KS1).
2)
Select affiliated RCCS3 with the same approval type (/MC2 or /MC3).
3)
Select affiliated converter RCCF31 with the same approval type (/Q20 or /Q21).
4)
For detailed information please see TI 01R04B04-04E-E. Option /K6 of RCCS3 is recommended with concentration measurement.
5)
If no instruction manual is selected, only a DVD with instruction manuals is shipped with the instrument. More than 3 manuals of one language on request available.
GS 01R04B10-00E-E 3rd edition July 22, 2017-00 All Rights Reserved. Copyright © 2015, Rota Yokogawa
17
Hazardous Area Approvals 1) /KS1 ATEX associated apparatus for intrinsically safe detector connection for gas group IIC with /HP not for gas group IIC
/ES1 IECEx associated apparatus for intrinsically safe detector output for gas group IIC with /HP not for gas group IIC
/US1 INMETRO associated apparatus for intrinsically safe detector output for gas group IIC with /HP not for gas group IIC
/NS1 NEPSI associated apparatus for intrinsically safe detector output for gas group IIC with /HP not for gas group IIC
Marine Approval 2) /MC2 Marine approval acc. DNV piping class 2 not for thermal oil application
/MC3 Marine approval acc. DNV piping class 3 not for thermal oil application
High Driving Power /HP High Driving Power, recommended for combination with RCCS36 to 39, strongly
recommended for combination with RCCS39/IR, Please see „ Hazardous Area
Specifications“
Active Pulse Output /AP One active pulse output not with /NM
NAMUR Switch /NM One pulse output acc. EN 60947-5-6 (NAMUR) not with /AP
Tag Number /BG With customer specified tag number on name plate max. 16 characters; the last 8 significant characters are
used for HART® Tag;
characters acc. Codepage 850 (Multi-lingual)
HART® Tag Number (Software Tag) /BT1 With customer specified tag number for HART® communication in converter 22 characters for long tag;
characters acc. Codepage 850 (Multi-lingual)
Communication /MB2 Modbus communication protocol for all parameters and values not with /AP, /NM, /MB3
/MB3 Modbus communication protocol for all parameters and values incl. HART not with /MB2
Communication, analogue output, pulse/status output, status input
No Combination /NC No combination with detector
Concentration Measurement 3) /CST Standard concentration measurement not with /C
/C Advanced concentration measurement, details see table „Advanced Concentration not with /CST
Measurement Options“
Subrack /SR2 Subrack for 2 converter RCCR31 with mounting
/SR4 Subrack for 4 converter RCCR31 with mounting
Delivery to Korea /KC With KC-mark for Korea
Delivery to China /CN For meters which are delivered to China combination with Hazardous Area Approval only with /NS1
Certificates /P2 Certificate of compliance with the order acc. EN 10204:2004 -2.1
/P3 Test Report acc. EN10204:2004-2.2(QIC) including the content of option /P2
Instruction Manuals /IE Quantity of instruction manuals in English = 1 to 3 selectable 4)
1)
Select affiliated RCCS3 with the same approval type (e.g. /KS1 with /KS1).
2)
Select affiliated RCCS3 with the same approval type (/MC2 or /MC3).
3)
For detailed information please see TI 01R04B04-04E-E. Option /K6 of RCCS3 is recommended with concentration measurement.
4)
If no instruction manual is selected, only a DVD with instruction manuals is shipped with the instrument. More than 3 manuals of one language on request available.
All Rights Reserved. Copyright © 2015, Rota Yokogawa GS 01R04B10-00E-E 3rd edition July 22, 2017-00
18
Advanced Concentration Measurement Options (others on request), recommended with Option /K6
Option Display Components Concentration Temp. range Source of concentration- / density table
range
/C00 --- --- --- --- Advanced concentration measurement function.
There are no pre-defined concentration setups (coefficients are set to zero).
The concentration coefficients will be set by customer making use of either
FieldMate or the stand- alone concentration tool and manual entry by HHT.
For more information, please contact your regional Yokogawa office.
/C01 °Brix Sugar / Water 0 - 85 °Brix 0 - 80°C PTB- Messages 100 5/90:
(32 - 176°F) „The density of watery Saccarose solutions after the introduction of the
international temperature scale of 1990 (ITS1990)“ Table 5
/C02 WT% NaOH / Water 2 - 50 WT% 0 - 100°C D´Ans-Lax, Handbook for chemists and physicists Vol.1, 3rd edition, 1967
(32 - 212°F)
/C03 WT% KOH / Water 0 - 60 WT% 54 - 100°C D´Ans-Lax, Handbook for chemists and physicists Vol.1, 3rd edition, 1967
(129 - 212°F)
/C04 WT% NH4NO3 / Water 1 - 50 WT% 0 - 80°C Data table on request
(32 - 176°F)
/C05 WT% NH4NO3 / Water 20 - 70 WT% 20 - 100°C Data table on request
(68 - 212°F)
/C07 WT% HNO3 / Water 50 - 67 WT% 10 - 60°C Data table on request
(50 - 140°F)
/C09 WT% H2O2 / Water 30 - 75 WT% 4 - 44°C Data table on request
(39.2 - 111.2°F)
/C10 WT% Ethylene Glycol / 10 - 50 WT% -20 - 40°C Data table on request
Water (-4 - 104°F)
/C11 WT% Amylum = starch / Water 33 - 43 WT% 35 - 45°C Data table on request
(95 - 113°F)
/C12 WT% Methanol / Water 35 - 60 WT% 0 - 40°C Data table on request
(32 - 104°F)
/C20 VOL% Alcohol / Water 55 - 100 VOL% 10 - 40°C Data table on request
(50 - 104°F)
/C21 °Brix Sugar / Water 40 - 80 °Brix 75 - 100°C Data table on request
(167 - 212°F)
/C30 WT% Alcohol / Water 66 - 100 WT% 15 - 40°C Standard Copersucar 1967
(59 - 104°F)
/C37 WT% Alcohol / Water 66 - 100 WT% 10 - 40°C Brazilian Standard ABNT
(50 - 104°F)
GS 01R04B10-00E-E 3rd edition July 22, 2017-00 All Rights Reserved. Copyright © 2015, Rota Yokogawa
19
RCCS39/IR
RCCS34
RCCS36
RCCS38
RCCS39
01A1 ½“-150 370 ---- ---- ---- ----
01A2 ½“-300 370 ---- ---- ---- ----
01A3 ½“-600 380 ---- ---- ---- ----
02A1 1“-150 370 500 ---- ---- ----
02A2 1“-300 370 500 ---- ---- ----
02A3 1“-600 390 520 ---- ---- ----
04A1 1½“-150 380 500 600 ---- ----
04A2 1½“-300 380 510 600 ---- ----
04A3 1½“-600 400 530 620 ---- ----
04A4 1½“-900 470 600 640 ---- ----
05A1 2“-150 ---- 510 600 ---- ----
Flanges according to ASME B16.5
All Rights Reserved. Copyright © 2015, Rota Yokogawa GS 01R04B10-00E-E 3rd edition July 22, 2017-00
20
Table 11 : Selection Table Process Connection and Materials, Installation Length in mm (continued)
RCCS39/IR
RCCS34
RCCS36
RCCS38
RCCS39
01J1 DN 15 10K 370 ---- ---- ---- ----
01J2 DN 15 20K 370 ---- ---- ---- ----
02J1 DN 25 10K 370 500 ---- ---- ----
Flanges according to JIS B 2220
GS 01R04B10-00E-E 3rd edition July 22, 2017-00 All Rights Reserved. Copyright © 2015, Rota Yokogawa
21
Table 11 : Selection Table Process Connection and Materials, Installation Length in inch
RCCS39/IR
RCCS34
RCCS36
RCCS38
RCCS39
01A1 ½“-150 14.57 ---- ---- ---- ----
01A2 ½“-300 14.57 ---- ---- ---- ----
01A3 ½“-600 14.96 ---- ---- ---- ----
02A1 1“-150 14.57 19.69 ---- ---- ----
02A2 1“-300 14.57 19.69 ---- ---- ----
02A3 1“-600 15.75 20.47 ---- ---- ----
04A1 1½“-150 14.96 19.69 23.62 ---- ----
04A2 1½“-300 14.96 20.08 23.62 ---- ----
04A3 1½“-600 15.35 20.87 24.21 ---- ----
04A4 1½“-900 18.5 23.62 25.2 ---- ----
05A1 2“-150 ---- 20.08 23.62 ---- ----
Flanges according to ASME B16.5
All Rights Reserved. Copyright © 2015, Rota Yokogawa GS 01R04B10-00E-E 3rd edition July 22, 2017-00
22
Table 11 : Selection Table Process Connection and Materials, Installation Length in inch (continued)
RCCS39/IR
RCCS34
RCCS36
RCCS38
RCCS39
01J1 DN 15 10K 14.57 ---- ---- ---- ----
01J2 DN 15 20K 14.57 ---- ---- ---- ----
02J1 DN 25 10K 14.57 19.69 ---- ---- ----
Flanges according to JIS B 2220
GS 01R04B10-00E-E 3rd edition July 22, 2017-00 All Rights Reserved. Copyright © 2015, Rota Yokogawa
23
RCCS39/IR
RCCS34
RCCS36
RCCS38
RCCS39
01A1 ½“-150 X ---- ---- ---- ----
01A2 ½“-300 X ---- ---- ---- ----
01A3 ½“-600 X ---- ---- ---- ----
01A5 ½“-900/1500 X ---- ---- ---- ----
02A1 1“-150 X X ---- ---- ----
02A2 1“-300 X X ---- ---- ----
02A3 1“-600 X X ---- ---- ----
02A5 1“-900/1500 X X ---- ---- ----
04A1 1½“-150 X ---- X ---- ----
04A2 1½“-300 X X X ---- ----
04A3 1½“-600 X X X ---- ----
04A4 1½“-900 ---- ---- X ---- ----
04A5 1½“-900/1500 X X ---- ---- ----
Flanges according to ASME B16.5
All Rights Reserved. Copyright © 2015, Rota Yokogawa GS 01R04B10-00E-E 3rd edition July 22, 2017-00
24
REGISTERED TRADEMARKS
HART® : Registered trademark of HART Communication Foundation, Austin, TX, USA
MODBUS® : Registered trademark of MODBUS Organization
YOKOGAWA EUROPE B. V.
Euroweg 2, 3825 HD Amersfoort, THE NETHERLANDS
Phone : 31-88-4641000 Fax : 31-88-4641111
GS 01R04B10-00E-E 3rd edition July 22, 2017-00 All Rights Reserved. Copyright © 2015, Rota Yokogawa