0% found this document useful (0 votes)
938 views46 pages

Structural Report 1.0 PDF

This structural design report summarizes the design criteria and considerations for a proposed 2-storey residential house in Mabalacat, Pampanga. It includes the materials strengths, load cases considered such as dead, live, and seismic loads. Load combinations are defined for ultimate limit states for concrete and steel design, and service limit states for steel and foundation design per NSCP 2015 standards. Design of structural elements such as the roof, beams, columns, and foundation will be presented.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
938 views46 pages

Structural Report 1.0 PDF

This structural design report summarizes the design criteria and considerations for a proposed 2-storey residential house in Mabalacat, Pampanga. It includes the materials strengths, load cases considered such as dead, live, and seismic loads. Load combinations are defined for ultimate limit states for concrete and steel design, and service limit states for steel and foundation design per NSCP 2015 standards. Design of structural elements such as the roof, beams, columns, and foundation will be presented.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 46

STRUCTURAL ANALYSIS AND DESIGN REPORT STRUCTURAL DESIGN BY:

ENGR. KARL ANTHONY V. TAN


PROJECT: PROPOSED 2-STOREY RESIDENTIAL HOUSE CIVIL ENGINEER
[email protected]
LOCATION: MABALACAT, PAMPANGA

PERSPECTIVE/PICTORIAL VIEW TABLE OF CONTENTS


A. PERSPECTIVE/PICTORIAL VIEW
B. STRUCTURAL DESIGN DATA AND
CRITERIA
C. STRUCTURAL MODELING AND
BOUNDARY CONDITION
D. STRUCTURAL LOADING
E. STRUCTURAL ANALYSIS
F. ROOF FRAMING DESIGN
G. BEAM DESIGN
H. COLUMN DESIGN
I. FOUNDATION DESIGN

PREPARED BY: ENGR. KARL ANTHONY V. TAN


DATE: APRIL 12, 2019
B. STRUCTURAL DESIGN DATA AND
CONSIDERATION
Structural Design Criteria and Considerations

The design criteria and considerations used by the engineer are based on NSCP 2015. Some load factors are used
to cover miscellaneous and accidental loads made in the structure. Materials strength and specifications, Load Cases, load
combinations and load calculations are explain briefly in this context.

1. Code and Standard

The design of structural engineering systems for the project is in accordance with the laws and
regulations imposed by the Philippine government. The current issue or edition of the document at the
time of design will be applied. The codes to be used is NSCP 2015.

2. Materials Strength

Concrete Strength @ 28 days (fc’) : 20.7 MPa

Reinforcements Yield Strength (Fy) :


Main Reinforcement
D12 and smaller : 276 MPa
D16 and above : 414 Mpa

Elastic Modulus of Elasticity (Es) : 200,000 Mpa

Density
Concrete : 24 kN/m3
Steel : 76 kN/m3

Gross Allowable soil bearing Capacity : 90 kPa

Hot Rolled Sections (Fy) : 250 MPa


Hot Rolled Sections (Fu) : 400 MPa

Other Materials
Other materials such as anchor bolts, embedded metal, shear connectors will be shown in
structural drawings if applicable.
3. Load Cases

3.1. Dead Load (Self Weight)

Selfweight of the structure is automatically computed by the computer analysis program used
by the engineer. A Load Factor of 1 is used in the design. The densities inputted in the
program are the densities stated above hereon.

3.2. Super Dead (Super Imposed Dead Load)

Dead load of structure is computed using specific density using minimum dead load in NSCP
2015. This Load Cases includes Roofing Materials, Ceiling Materials, masonry, beams,
columns, slabs and other pertinent imposed dead load on the structure.

Roof Dead Load : 0.8 kPa


GI sheet 0.05 kPa
Purlins 0.05 kPa
Ceiling : 0.2 kPa
(Gypsum board & metal furring)
Toppings (25mm thick) : 0.6 kPa
Wall Loads
4 inch-CHB : 1.9 kPa
5 inch-CHB : 2.4 kPa
6 inch-CHB : 2.9 kPa
8 inch-CHB : 3.8 kPa

Structural Design and Consideration Rev.0


*Add 0.24 kPa for each face plastered
Utilities : 0.1 kPa
Floor Finish (Ceramic tile) : 0.5 kPa
Movable Partition : 0.5 kPa (Residential)
1.0 kPa (Office)
Water Proofing Membrane : 0.07 kPa
(Bituminous smooth surface)

3.3. Live Load

Live load on the structure is computed using specific values given in the table of NSCP.

3.3.1. Offices / Units = 2.40 KPa


3.3.2. Residential = 1.90 KPa
3.3.3. Balcony = 2.90 KPa
3.3.4. Multipurpose Area / Conference Room = 4.80 KPa
3.3.5. Lobby / Corridors = 3.80 KPa

3.4. Roof Live Load


Roof Live load is used for construction and maintenance purposes. 1.0 kPa is used as per
NSCP 2015.

3.5. Wind Load


Wind Load Used in computation is based on NSCP 2015 or ASCE. Parameters used was
based on specific location of the project in the Philippines.

3.6. Seismic Load


Seismic Load Used in computation is based on NSCP 2015 or UBC 1997. Parameters used is
based on specific seismic zone area in the Philippines.

4. Load Combinations

4.1 (Ultimate) The Following Load Combinations are used in Concrete Design and Steel Design Using LRFD.

4.1.1 1.4DL
4.1.2 1.2DL + 1.6LL + 0.5RLL
4.1.3 1.2DL + 1.6RLL + 0.5W
4.1.4 1.2DL + W + 0.5LL + 0.5RLL
4.1.5 1.2DL + EQX + 0.3EQZ + 0.5LL
4.1.6 1.2DL + EQX - 0.3EQZ + 0.5LL
4.1.7 1.2DL - EQX + 0.3EQZ + 0.5LL
4.1.8 1.2DL - EQX - 0.3EQZ + 0.5LL
4.1.9 1.2DL + EQZ + 0.3EQX + 0.5LL
4.1.10 1.2DL + EQZ - 0.3EQX + 0.5LL
4.1.11 1.2DL - EQZ + 0.3EQX + 0.5LL
4.1.12 1.2DL - EQZ - 0.3EQX + 0.5LL

(NOTE: EQ INCLUDES THE VERITCAL EFFECT OF EARTHQUAKE)

4.2 (Service) The Following Load Combinations are used in Steel Design Using ASD.

4.2.1 DL
` 4.2.2 DL + LL
4.2.3 DL + RLL
4.2.4 DL + 0.75LL + 0.75RLL
4.2.5 DL + 0.6W
4.2.6 DL + 0.72EQX + 0.22EQZ
4.2.7 DL + 0.72EQX - 0.22EQZ
4.2.8 DL - 0.72EQX + 0.22EQZ
4.2.9 DL - 0.72EQX - 0.22EQZ

Structural Design and Consideration Rev.0


4.2.10 DL + 0.72EQZ + 0.22EQX
4.2.11 DL + 0.72EQZ - 0.22EQX
4.2.12 DL - 0.72EQZ + 0.22EQX
4.2.13 DL - 0.72EQZ - 0.22EQX

(NOTE: EQ INCLUDES THE VERITCAL EFFECT OF EARTHQUAKE)

5.3 (Foundation) The Following Load Combinations are used in Design of Foundation for Service Condition.

4.3.1 DL + 0.75LL + 0.75RLL + 0.75W


4.3.2 DL + 0.75LL + 0.75RLL + 0.54EQX + 0.16EQZ
4.3.3 DL + 0.75LL + 0.75RLL + 0.54EQX - 0.16EQZ
4.3.4 DL + 0.75LL + 0.75RLL - 0.54EQX + 0.16EQZ
4.3.5 DL + 0.75LL + 0.75RLL - 0.54EQX - 0.16EQZ
4.3.6 DL + 0.75LL + 0.75RLL + 0.54EQZ + 0.16EQX
4.3.7 DL + 0.75LL + 0.75RLL + 0.54EQZ - 0.16EQX
4.3.8 DL + 0.75LL + 0.75RLL - 0.54EQZ + 0.16EQX
4.3.9 DL + 0.75LL + 0.75RLL - 0.54EQZ - 0.16EQX
4.3.10 DL + W
4.3.11 0.6DL + 0.72EQX + 0.22EQZ
4.3.12 0.6DL + 0.72EQX - 0.22EQZ
4.3.13 0.6DL - 0.72EQX + 0.22EQZ
4.3.14 0.6DL - 0.72EQX - 0.22EQZ
4.3.15 0.6DL + 0.72EQZ + 0.22EQX
4.3.16 0.6DL + 0.72EQZ - 0.22EQX
4.3.17 0.6DL - 0.72EQZ + 0.22EQX
4.3.18 0.6DL - 0.72EQZ - 0.22EQX
4.3.19 DL + LL
4.3.20 DL + LL + 0.72EQX + 0.22EQZ
4.3.21 DL + LL + 0.72EQX - 0.22EQZ
4.3.22 DL + LL - 0.72EQX + 0.22EQZ
4.3.23 DL + LL - 0.72EQX - 0.22EQZ
4.3.24 DL + LL + 0.72EQZ + 0.22EQX
4.3.25 DL + LL + 0.72EQZ - 0.22EQX
4.3.26 DL + LL - 0.72EQZ + 0.22EQX
4.3.27 DL + LL - 0.72EQZ - 0.22EQX

5. Computer Softwares

To give the designer a more accurate values of design forces to be used in the design, the designer used
computer software and tools to obtain optimum quality and economy in the design. The following computer
software will be used.

5.1 STAAD.Pro V8i : Bently


5.2 ETABS 2016 : Computer and Structure Institute
5.3 Safe : Computer and Structure Institute
5.4 SP Column : Structure Point
5.5 Staad RCDC : Bentley
5.6 Staad Advanced Foundation : Bentley
5.7 Microsoft Excel : Microsoft

6. Factors of Safety
The following Factors of safety is used.

6.1 Overturning Moment : 1.5


6.2 Sliding : 1.5
6.3 Uplift : 1.1
6.4 Accidental Load : 2.0

Structural Design and Consideration Rev.0


C. STRUCTURAL MODELING NAD BOUNDARY
CONDITION
THREE DIMENSIONAL STRUCTURAL MODEL

BOUNDARY CONDITION (FIXED)


D. STRUCTURAL LOADING
Seismic Load Parameters

Occupancy Category Standard Occupancy


Stucture Height (hn) 6.7 m
Structure Type Concrete Structure
Importance Factor (Iw) 1.00
Soil Type Stiff Soil Profile (SD)
Seismic Zone Number 4
Seismic Zone Factor (Z) 0.4
Distance From known seismic source 10 km
Seismic Source type A
Near Source Factor (Na) 1
Near Source Factor (Nv) 1.2
Seismic Coefficient (Ca) 0.44
Seismic Coefficient (Cv) 0.768
Basic Seismic Force Resisting Frame Special Reinforced Concrete Moment Frames

Seismic Numerical Coefficient (R) 8.5


Ct 0.0731
Structural Time Period (s): 0.299
Maximum Base Shear 0.129 x W
Minimum Base Shear 0.048 x W
Governing Base Shear 0.129 x W

DESIGN RESPONSE SPECTRA
1.2
1.1 1.1

1
Spectral Acceleration (m/s2)

0.8

0.611
0.6
0.44 0.423
0.4 0.324
0.262
0.22
0.19 0.167
0.2

0
0 0.5 1 1.5 2 2.5 3 3.5 4 4.5 5
Period (Seconds)

* Seismic Analysis is based on Unified Building Code (1997). No part of


this file shall be disclosed to third party without prior written approval
of the designer.
DEAD LOAD

LIVE LOAD
SEISMIC LOAD (X-DIR.)

SEISMIC LOAD (Z-DIR.)


E. STRUCTURAL ANALYSIS
DEFLECTIONS UNDER GOVERNING LOAD CASE (DEAD +
LIVE + SEISMIC)

SAMPLE SHEAR DIAGRAM UNDER GOVERNING LOAD CASE


(DEAD + LIVE + SEISMIC)
SAMPLE MOMENT DIAGRAM UNDER GOVERNING LOAD
CASE (DEAD + LIVE + SEISMIC)

SAMPLE AXIAL DIAGRAM UNDER GOVERNING LOAD CASE


(DEAD + LIVE + SEISMIC)
F. ROOF FRAMING DESIGN
STAAD.Pro CODE CHECKING - (AISI) MEMBER# 80 SECTION: JWE4X102CS LEN: 730.00 GOV.LOC: 730.00
PURLINS DESIGN STATUS: PASS RATIO = 0.428 GOV.MODE: Tension Eccent GOV.LOAD: 103
RESISTANCES: AX.TENS: 147.53 ECC.TENS: 0.00 COMPRESS: 126.01
(BIAXIAL BENDING) BEND. Z: 6.11 BEND. Y: 2.25 SHEAR Z: 37.71 SHEAR Y: 33.07
FYLD: 250.00 COLD WORK FYLD: 308.16 FU: 400.00 A: 624.62 AE: 624.62
UNITS ARE: MM, KN, KNM, MPA IZ: 1.0607E+06 IZE: 1.0607E+06 IY: 3.3437E+05 IYE: 3.3437E+05
SZE_T: 2.0880E+04 SZE_C: 2.0880E+04 SYE_T: 8.2411E+03 SYE_C: 1.4584E+04
MEMBER# 76 SECTION: JWE4X102CS LEN: 730.00 GOV.LOC: 730.00 MEMBER# 81 SECTION: JWE4X102CS LEN: 730.00 GOV.LOC: 730.00
STATUS: PASS RATIO = 0.109 GOV.MODE: Tension Eccent GOV.LOAD: 103 STATUS: PASS RATIO = 0.966 GOV.MODE: Tension Eccent GOV.LOAD: 103
RESISTANCES: AX.TENS: 147.53 ECC.TENS: 147.53 COMPRESS: 126.01 RESISTANCES: AX.TENS: 147.53 ECC.TENS: 0.00 COMPRESS: 126.01
BEND. Z: 6.11 BEND. Y: 2.25 SHEAR Z: 37.71 SHEAR Y: 33.07 BEND. Z: 6.11 BEND. Y: 2.25 SHEAR Z: 37.71 SHEAR Y: 33.07
FYLD: 250.00 COLD WORK FYLD: 308.16 FU: 400.00 A: 624.62 AE: 624.62 FYLD: 250.00 COLD WORK FYLD: 308.16 FU: 400.00 A: 624.62 AE: 624.62
IZ: 1.0607E+06 IZE: 1.0607E+06 IY: 3.3437E+05 IYE: 3.3437E+05 IZ: 1.0607E+06 IZE: 1.0607E+06 IY: 3.3437E+05 IYE: 3.3437E+05
SZE_T: 2.0880E+04 SZE_C: 2.0880E+04 SYE_T: 8.2411E+03 SYE_C: 1.4584E+04 SZE_T: 2.0880E+04 SZE_C: 2.0880E+04 SYE_T: 8.2411E+03 SYE_C: 1.4584E+04
MEMBER# 77 SECTION: JWE4X102CS LEN: 1161.10 GOV.LOC: 0.00 MEMBER# 82 SECTION: JWE4X102CS LEN: 1161.10 GOV.LOC: 0.00
STATUS: PASS RATIO = 0.784 GOV.MODE: Bending Bi-ax GOV.LOAD: 103 STATUS: PASS RATIO = 0.157 GOV.MODE: Bending Bi-ax GOV.LOAD: 103
RESISTANCES: AX.TENS: 0.00 ECC.TENS: 0.00 COMPRESS: 0.00 RESISTANCES: AX.TENS: 0.00 ECC.TENS: 0.00 COMPRESS: 0.00
BEND. Z: 6.11 BEND. Y: 2.25 SHEAR Z: 37.71 SHEAR Y: 33.07 BEND. Z: 6.11 BEND. Y: 2.25 SHEAR Z: 37.71 SHEAR Y: 33.07
FYLD: 250.00 COLD WORK FYLD: 308.16 FU: 400.00 A: 624.62 AE: 624.62 FYLD: 250.00 COLD WORK FYLD: 308.16 FU: 400.00 A: 624.62 AE: 624.62
IZ: 1.0607E+06 IZE: 1.0607E+06 IY: 3.3437E+05 IYE: 3.3437E+05 IZ: 1.0607E+06 IZE: 1.0607E+06 IY: 3.3437E+05 IYE: 3.3437E+05
SZE_T: 2.0880E+04 SZE_C: 2.0880E+04 SYE_T: 1.4584E+04 SYE_C: 8.2411E+03
MEMBER# 78 SECTION: JWE4X102CS LEN: 1050.67 GOV.LOC: 788.00
STATUS: PASS RATIO = 0.139 GOV.MODE: Bending Bi-ax GOV.LOAD: 103 MEMBER# 83 SECTION: JWE4X102CS LEN: 1050.68 GOV.LOC: 0.00
RESISTANCES: AX.TENS: 0.00 ECC.TENS: 0.00 COMPRESS: 0.00 STATUS: PASS RATIO = 0.139 GOV.MODE: Bending Bi-ax GOV.LOAD: 103
BEND. Z: 6.11 BEND. Y: 2.25 SHEAR Z: 37.71 SHEAR Y: 33.07 RESISTANCES: AX.TENS: 0.00 ECC.TENS: 0.00 COMPRESS: 0.00
FYLD: 250.00 COLD WORK FYLD: 308.16 FU: 400.00 A: 624.62 AE: 624.62 BEND. Z: 6.11 BEND. Y: 2.25 SHEAR Z: 37.71 SHEAR Y: 33.07
IZ: 1.0607E+06 IZE: 1.0607E+06 IY: 3.3437E+05 IYE: 3.3437E+05 FYLD: 250.00 COLD WORK FYLD: 308.16 FU: 400.00 A: 624.62 AE: 624.62
SZE_T: 2.0880E+04 SZE_C: 2.0880E+04 SYE_T: 1.4584E+04 SYE_C: 8.2411E+03 IZ: 1.0607E+06 IZE: 1.0607E+06 IY: 3.3437E+05 IYE: 3.3437E+05
SZE_T: 2.0880E+04 SZE_C: 2.0880E+04 SYE_T: 1.4584E+04 SYE_C: 8.2411E+03
MEMBER# 79 SECTION: JWE4X102CS LEN: 1331.00 GOV.LOC: 0.00
STATUS: PASS RATIO = 0.214 GOV.MODE: Bending Bi-ax GOV.LOAD: 103 MEMBER# 84 SECTION: JWE4X102CS LEN: 1050.68 GOV.LOC: 1050.68
RESISTANCES: AX.TENS: 0.00 ECC.TENS: 0.00 COMPRESS: 0.00 STATUS: PASS RATIO = 0.139 GOV.MODE: Bending Bi-ax GOV.LOAD: 103
BEND. Z: 6.11 BEND. Y: 2.25 SHEAR Z: 37.71 SHEAR Y: 33.07 RESISTANCES: AX.TENS: 0.00 ECC.TENS: 0.00 COMPRESS: 0.00
FYLD: 250.00 COLD WORK FYLD: 308.16 FU: 400.00 A: 624.62 AE: 624.62 BEND. Z: 6.11 BEND. Y: 2.25 SHEAR Z: 37.71 SHEAR Y: 33.07
IZ: 1.0607E+06 IZE: 1.0607E+06 IY: 3.3437E+05 IYE: 3.3437E+05 FYLD: 250.00 COLD WORK FYLD: 308.16 FU: 400.00 A: 624.62 AE: 624.62
SZE_T: 2.0880E+04 SZE_C: 2.0880E+04 SYE_T: 1.4584E+04 SYE_C: 8.2411E+03 IZ: 1.0607E+06 IZE: 1.0607E+06 IY: 3.3437E+05 IYE: 3.3437E+05
SZE_T: 2.0880E+04 SZE_C: 2.0880E+04 SYE_T: 8.2411E+03 SYE_C: 1.4584E+04
MEMBER# 85 SECTION: JWE4X102CS LEN: 1050.67 GOV.LOC: 1050.67
STATUS: PASS RATIO = 0.214 GOV.MODE: Bending Bi-ax GOV.LOAD: 103

RESISTANCES: AX.TENS: 0.00 ECC.TENS: 0.00 COMPRESS: 0.00


BEND. Z: 6.11 BEND. Y: 2.25 SHEAR Z: 37.71 SHEAR Y: 33.07
FYLD: 250.00 COLD WORK FYLD: 308.16 FU: 400.00 A: 624.62 AE: 624.62
IZ: 1.0607E+06 IZE: 1.0607E+06 IY: 3.3437E+05 IYE: 3.3437E+05
SZE_T: 2.0880E+04 SZE_C: 2.0880E+04 SYE_T: 8.2411E+03 SYE_C: 1.4584E+04

MEMBER# 86 SECTION: JWE4X102CS LEN: 1331.10 GOV.LOC: 332.78


STATUS: PASS RATIO = 0.192 GOV.MODE: Bending Bi-ax GOV.LOAD: 103
RESISTANCES: AX.TENS: 0.00 ECC.TENS: 0.00 COMPRESS: 0.00
BEND. Z: 6.11 BEND. Y: 2.25 SHEAR Z: 37.71 SHEAR Y: 33.07
FYLD: 250.00 COLD WORK FYLD: 250.00 FU: 400.00 A: 624.62 AE: 624.62
IZ: 1.0607E+06 IZE: 1.0607E+06 IY: 3.3437E+05 IYE: 3.3437E+05
SZE_T: 2.0880E+04 SZE_C: 2.0880E+04 SYE_T: 8.2411E+03 SYE_C: 1.4584E+04
Flexure Capacity Of I-Shaped Section (Hot Rolled)
Section: C6x8.2

1. Member Property
Lb = 0.6 m
2. Material Property
Fy = 250 MPa Fu = 400 MPa
E = 200,000 MPa G = 77,200 MPa
3. Section Property
2
Ag = 1,541.93 mm rx = 59.44 mm
d = 152.40 mm ry = 13.61 mm
bf = 48.77 mm Ix = 5.45 x 106 mm4
tf = 8.71 mm Iy = 0.29 x 106 mm4
tw = 5.08 mm Zx = 84.19 x103 mm3
Sx = 71.28 x103 mm3 Zy = 18.60 x103 mm3
Sy = 8.00 x103 mm3 J = 30,634.63 mm4
k = 20.64 mm Cb = 1
xna = 4.89 mm
4. Element Classification
b/t = 5.60
1/2
0.38(E/Fy) = 10.75
1/2
1.0(E/Fy) = 28.28
Flange is compact
h/tw = 18.45
3.76(E/Fy)1/2 = 106.35
1/2
5.70(E/Fy) = 161.22
Web is compact
4. Unbraced length Limit for Plastic Yielding (Lp)
Lp = 0.68 m
5. Unbraced length Limit for lateral torsion inelastic buckling (L r)
Warping Constant (Cw)
Cw = 1,262,118,572.74 mm6
effective radius of fyration (rts)=
rts= 16.32 mm
ho = 143.69 mm
Lr = 2.99 m
6. For Compact Sections
Moment Capacity Due to Yielding (Mn1)
Mnx1 = 21.05 kN-m
Mny1 = 3.20 kN-m
Moment Capcity Due to Lateral Torsional Buckling (Mn2)
Fcr = - Mpa.
Mnx2 = - kN-m
7. For Non-Compact or Slender Sections (This Section is Not Applicable)
Moment Capcity Due to Lateral Torsional Buckling (Mn1)
Fcr = - MPa
Mnx1 = - kN-m
Moment Capcity Due to Flange Local Buckling (Mn2)
kc = -
Mnx2 = - kN-m
Fcr = N/A MPa
Mny2 = N/A kN-m
8. Ultimate Moment Capacity (Mu)
Mux = 37.88 kN-m
Muy = 5.76 kN-m
Flexure Capacity Of I-Shaped Section (Hot Rolled)
Section: C4x4.5

1. Member Property
Lb = 0.6 m
2. Material Property
Fy = 250 MPa Fu = 400 MPa
E = 200,000 MPa G = 77,200 MPa
3. Section Property
Ag = 890.32 mm2 rx = 41.40 mm
d = 101.60 mm ry = 11.61 mm
bf = 40.13 mm Ix = 1.52 x 106 mm4
tf = 7.52 mm Iy = 0.12 x 106 mm4
tw = 3.18 mm Zx = 34.33 x103 mm3
Sx = 29.99 x103 mm3 Zy = 8.54 x103 mm3
Sy = 4.34 x103 mm3 J = 13,402.65 mm4
k = 19.05 mm Cb = 1
xna = 11.33 mm
4. Element Classification
b/t = 5.34
1/2
0.38(E/Fy) = 10.75
1/2
1.0(E/Fy) = 28.28
Flange is compact
h/tw = 15.26
3.76(E/Fy)1/2 = 106.35
1/2
5.70(E/Fy) = 161.22
Web is compact
4. Unbraced length Limit for Plastic Yielding (Lp)
Lp = 0.58 m
5. Unbraced length Limit for lateral torsion inelastic buckling (L r)
Warping Constant (Cw)
Cw = 233,894,739.76 mm6
effective radius of fyration (rts)=
rts= 13.30 mm
ho = 94.08 mm
Lr = 2.97 m
6. For Compact Sections
Moment Capacity Due to Yielding (Mn1)
Mnx1 = 8.58 kN-m
Mny1 = 1.74 kN-m
Moment Capcity Due to Lateral Torsional Buckling (Mn2)
Fcr = 1,284.50 Mpa.
Mnx2 = 8.55 kN-m
7. For Non-Compact or Slender Sections (This Section is Not Applicable)
Moment Capcity Due to Lateral Torsional Buckling (Mn1)
Fcr = 1,284.50 MPa
Mnx1 = 8.55 kN-m
Moment Capcity Due to Flange Local Buckling (Mn2)
kc = -
Mnx2 = - kN-m
Fcr = N/A MPa
Mny2 = N/A kN-m
8. Ultimate Moment Capacity (Mu)
Mux = 15.39 kN-m
Muy = 3.13 kN-m
G. BEAM DESIGN
Beam Number: B1 Date: 12-Apr-19
Project Name: PROPOSED 2-STOREY RESIDENTIAL HOUSE Engineer: ENGR. KARL ANTHONY V TAN

Material Properties:
fc' =
fy =
21
414
Mpa.
Mpa.
fyt =
db =
276
16
Mpa
mm.
dby =
cc =
10
40
mm.
mm.
dbt = 10 mm.
Result: PASSED
General Geometry:
b = 200 mm. Number of ties (Vertical) 2= legs
h = 400 mm. Number of ties (horizontal)
2 = legs

DESIGN FORCES
END SPAN MIDDLE SPAN MINOR AXIS End Span Forces
Mu = 33.19 kN-m 5.74 kN-m 0 LC Shear-Y kN Shear-Z kN Torsion kNm Moment-Y kNm Moment-Z kNm Remarks
Tu = 0.00 kN-m 0.00 kN-m 0.00 kN-m Min Shear Y 112 -35.1 0 0 0 33.187 PASSED
Vu = 35.10 kN 18.00 kN 0.00 kN Max Shear Y 115 25.358 0 0 0 16.674 PASSED
Top Bars: Top Layer 2 pcs. Top Layer 2 pcs. First Layer: 5 pcs. Min Shear Z 101 14.38 0 0 0 2.136 PASSED
No. Of Layers 1 layers No. Of Layers 1 layers Second Layer: 0 pcs. Max Shear Z 101 14.38 0 0 0 2.136 PASSED
Bottom Bars: Bottom Layer 2 pcs. Bottom Layer 2 pcs. First Layer: 5 pcs. Min Torsion 118 17.274 0 0 0 5.228 PASSED
No. Of Layers 1 layers No. Of Layers 1 layers Second Layer: 0 pcs. Max Torsion 129 6.35 0 0 0 -1.819 PASSED
d= 342.00 d' = 58.00 d = 342.00 d' = 58.00 d = 142.00 d' = 58.00 Min Moment Y 101 14.38 0 0 0 2.136 PASSED
Ru = 1.576315979 0.272685993 0 Max Moment Y 101 14.38 0 0 0 2.136 PASSED
ρ = 0.003992365 0.000663771 0 Min Moment Z 124 -1.735 0 0 0 -13.266 PASSED
Asreq = 273.077773 45.40195054 0 Max Moment Z 112 -35.1 0 0 0 33.187 PASSED
ρmin = 0.003381643 0.000882816 0
Asmin = 231.3043478 60.38459422 0
ẞ1 = 0.85 0.85 0.85
ρbal = 0.021685533 0.021685533 0.021685533
Asbal = 1483.290455 1483.290455 1231.738273
Type = Singly Reinforced Singly Reinforced Doubly Reinforced Mid Span Forces
a(theo) = - - 5.026548246 LC Shear-Y kN Shear-Z kN Torsion kNm Moment-Y kNm Moment-Z kNm Remarks
c(theo) = - - 5.913586171 Min Shear Y 112 -22.267 0 0 0 5.565 PASSED
As' = - - 1005.309649 Max Shear Y 115 12.525 0 0 0 -1.566 PASSED
ɛy = - - 0.00207 Min Shear Z 101 1.728 0 0 0 -5.619 PASSED
ɛs'= - - -0.02642377 Max Shear Z 101 1.728 0 0 0 -5.619 PASSED
Judgement = - - fs <> fy Min Torsion 118 4.441 0 0 0 -5.227 PASSED
c = - - 83.07362843 Max Torsion 129 -1.784 0 0 0 -4.017 PASSED
a = - - 70.61258417 Min Moment Y 101 1.728 0 0 0 -5.619 PASSED
fs = - - 181.0944983 Max Moment Y 101 1.728 0 0 0 -5.619 PASSED
Asprovided = 402.1238597 402.1238597 1005.309649 Min Moment Z 112 -9.434 0 0 0 -9.698 PASSED
torsion bar = 0 pcs. 0 pcs. 0 pcs. Max Moment Z 124 -18.002 0 0 0 5.741 PASSED
Stirrups = No
Tulimit = 1.521415131 1.521415131 1.521415131
Remarks: Neglect Torsion Neglect Torsion Neglect Torsion 2-16mm 2-16mm
Additional As = 0 0 0
total As req = 273.077773 60.38459422 0
Judement = OK OK OK
ρbal = 0.021685533 0.021685533 0.05708376
ρ = 0.005879004 0.005879004 0.035398227 B1
a = 46.63285095 46.63285095 116.5821274
Mu = 47.74879023 47.74879023 40.68143542 200 x 400
Judgement = OK OK OK
Vu = 35.1 22.267
Vc = 52.24136292 53.28619018
Vs = - -
Section is ADEQUATE
Spacing: 1-10mm. @ 50 mm. , 11 @ 75 mm. o.c. Rest @ 150 mm. o.c.
2-16mm 2-16mm

LEGENDS:
End Mid
db = Longitudinal Bar Diameter fc' = Concrete Strength at 28 days
1-10mm. @ 50 mm. , 11 @ 75 mm. o.c. Rest @ 150 mm. o.c.
dby = Stirrups Diameter fy = Yield Strength of Longitudinal Bars
dbt = Torsional Bar Diameter fyt = Yield Strength of Stirrups
cc = Concrete Cover

* This Document is presented and calculated conforming to National Structural Code of the Philippines 2010 Ed. Or American Concrete Institute 2008 Ed.
It is property of the designer signed above and contains information which is proprietary.
No other use of this document is to be made without the prior written consent of the Designer.
Beam Number: B2 Date: 12-Apr-19
Project Name: PROPOSED 2-STOREY RESIDENTIAL HOUSE Engineer: ENGR. KARL ANTHONY V TAN

Material Properties:
fc' =
fy =
21
414
Mpa.
Mpa.
fyt =
db =
276
16
Mpa
mm.
dby =
cc =
10
40
mm.
mm.
dbt = 10 mm.
Result: PASSED
General Geometry:
b = 200 mm. Number of ties (Vertical) 2= legs
h = 400 mm. Number of ties (horizontal)
2 = legs

DESIGN FORCES
END SPAN MIDDLE SPAN MINOR AXIS End Span Forces
Mu = 56.82 kN-m 3.64 kN-m 0 LC Shear-Y kN Shear-Z kN Torsion kNm Moment-Y kNm Moment-Z kNm Remarks
Tu = 0.00 kN-m 0.00 kN-m 0.00 kN-m Min Shear Y 118 -47.367 0 0 0 37.537 PASSED
Vu = 62.56 kN 15.89 kN 0.00 kN Max Shear Y 117 62.561 0 0 0 56.816 PASSED
Top Bars: Top Layer 3 pcs. Top Layer 2 pcs. First Layer: 5 pcs. Min Shear Z 101 46.154 0 0 0 35.524 PASSED
No. Of Layers 1 layers No. Of Layers 1 layers Second Layer: 0 pcs. Max Shear Z 101 46.154 0 0 0 35.524 PASSED
Bottom Bars: Bottom Layer 2 pcs. Bottom Layer 2 pcs. First Layer: 5 pcs. Min Torsion 127 30.01 0 0 0 23.346 PASSED
No. Of Layers 1 layers No. Of Layers 1 layers Second Layer: 0 pcs. Max Torsion 112 48.961 0 0 0 36.867 PASSED
d= 342.00 d' = 58.00 d = 342.00 d' = 58.00 d = 142.00 d' = 58.00 Min Moment Y 101 46.154 0 0 0 35.524 PASSED
Ru = 2.698646117 0.1729877 0 Max Moment Y 101 46.154 0 0 0 35.524 PASSED
ρ = 0.007103658 0.000419889 0 Min Moment Z 117 0.146 0 0 0 -26.545 PASSED
Asreq = 485.8902042 28.72042499 0 Max Moment Z 117 62.561 0 0 0 56.816 PASSED
ρmin = 0.003381643 0.000558453 0
Asmin = 231.3043478 38.19816523 0
ẞ1 = 0.85 0.85 0.85
ρbal = 0.021685533 0.021685533 0.021685533
Asbal = 1483.290455 1483.290455 1231.738273
Type = Singly Reinforced Singly Reinforced Doubly Reinforced Mid Span Forces
a(theo) = - - 5.026548246 LC Shear-Y kN Shear-Z kN Torsion kNm Moment-Y kNm Moment-Z kNm Remarks
c(theo) = - - 5.913586171 Min Shear Y 118 -17.879 0 0 0 -1.926 PASSED
As' = - - 1005.309649 Max Shear Y 117 33.42 0 0 0 -0.782 PASSED
ɛy = - - 0.00207 Min Shear Z 101 19.161 0 0 0 -3.849 PASSED
ɛs'= - - -0.02642377 Max Shear Z 101 19.161 0 0 0 -3.849 PASSED
Judgement = - - fs <> fy Min Torsion 127 12.657 0 0 0 -2.366 PASSED
c = - - 83.07362843 Max Torsion 112 19.821 0 0 0 -4.695 PASSED
a = - - 70.61258417 Min Moment Y 101 19.161 0 0 0 -3.849 PASSED
fs = - - 181.0944983 Max Moment Y 101 19.161 0 0 0 -3.849 PASSED
Asprovided = 603.1857895 402.1238597 1005.309649 Min Moment Z 117 8.641 0 0 0 -25.586 PASSED
torsion bar = 0 pcs. 0 pcs. 0 pcs. Max Moment Z 130 -15.893 0 0 0 3.642 PASSED
Stirrups = No
Tulimit = 1.521415131 1.521415131 1.521415131
Remarks: Neglect Torsion Neglect Torsion Neglect Torsion 3-16mm 2-16mm
Additional As = 0 0 0
total As req = 485.8902042 38.19816523 0
Judement = OK OK OK
ρbal = 0.021685533 0.021685533 0.05708376
ρ = 0.008818506 0.005879004 0.035398227 B2
a = 69.94927643 46.63285095 116.5821274
Mu = 69.00303671 47.74879023 40.68143542 200 x 400
Judgement = OK OK OK
Vu = 62.561 33.42
Vc = 52.24136292 53.28619018
Vs = 31.17330374 -
Section is ADEQUATE
Spacing: 1-10mm. @ 50 mm. , 11 @ 75 mm. o.c. Rest @ 150 mm. o.c.
2-16mm 2-16mm

LEGENDS:
End Mid
db = Longitudinal Bar Diameter fc' = Concrete Strength at 28 days
1-10mm. @ 50 mm. , 11 @ 75 mm. o.c. Rest @ 150 mm. o.c.
dby = Stirrups Diameter fy = Yield Strength of Longitudinal Bars
dbt = Torsional Bar Diameter fyt = Yield Strength of Stirrups
cc = Concrete Cover

* This Document is presented and calculated conforming to National Structural Code of the Philippines 2010 Ed. Or American Concrete Institute 2008 Ed.
It is property of the designer signed above and contains information which is proprietary.
No other use of this document is to be made without the prior written consent of the Designer.
Beam Number: B3 Date: 12-Apr-19
Project Name: PROPOSED 2-STOREY RESIDENTIAL HOUSE Engineer: ENGR. KARL ANTHONY V TAN

Material Properties:
fc' =
fy =
21
414
Mpa.
Mpa.
fyt =
db =
276
16
Mpa
mm.
dby =
cc =
10
40
mm.
mm.
dbt = 10 mm.
Result: PASSED
General Geometry:
b = 200 mm. Number of ties (Vertical) 2= legs
h = 400 mm. Number of ties (horizontal)
2 = legs

DESIGN FORCES
END SPAN MIDDLE SPAN MINOR AXIS End Span Forces
Mu = 74.80 kN-m 45.85 kN-m 0 LC Shear-Y kN Shear-Z kN Torsion kNm Moment-Y kNm Moment-Z kNm Remarks
Tu = 0.00 kN-m 0.00 kN-m 0.00 kN-m Min Shear Y 112 -72.728 0 0 0 74.799 PASSED
Vu = 72.73 kN 66.64 kN 0.00 kN Max Shear Y 114 75.863 0 0 0 35.191 PASSED
Top Bars: Top Layer 2 pcs. Top Layer 2 pcs. First Layer: 5 pcs. Min Shear Z 101 62.572 0 0 0 17.285 PASSED
No. Of Layers 2 layers No. Of Layers 1 layers Second Layer: 0 pcs. Max Shear Z 101 62.572 0 0 0 17.285 PASSED
Bottom Bars: Bottom Layer 2 pcs. Bottom Layer 2 pcs. First Layer: 5 pcs. Min Torsion 131 42.39 0 0 0 16.287 PASSED
No. Of Layers 1 layers No. Of Layers 1 layers Second Layer: 0 pcs. Max Torsion 116 62.964 0 0 0 12.847 PASSED
d= 321.50 d' = 58.00 d = 342.00 d' = 58.00 d = 142.00 d' = 58.00 Min Moment Y 101 62.572 0 0 0 17.285 PASSED
Ru = 4.02032657 2.177593106 0 Max Moment Y 101 62.572 0 0 0 17.285 PASSED
ρ = 0.011153584 0.005627083 0 Min Moment Z 112 42.472 0 0 0 -45.559 PASSED
Asreq = 717.1754375 384.8925107 0 Max Moment Z 112 -72.728 0 0 0 74.799 PASSED
ρmin = 0.003381643 0.003381643 0
Asmin = 217.4396135 231.3043478 0
ẞ1 = 0.85 0.85 0.85
ρbal = 0.021685533 0.021685533 0.021685533
Asbal = 1394.37977 1483.290455 1231.738273
Type = Singly Reinforced Singly Reinforced Doubly Reinforced Mid Span Forces
a(theo) = - - 5.026548246 LC Shear-Y kN Shear-Z kN Torsion kNm Moment-Y kNm Moment-Z kNm Remarks
c(theo) = - - 5.913586171 Min Shear Y 112 -66.635 0 0 0 45.846 PASSED
As' = - - 1005.309649 Max Shear Y 114 71.615 0 0 0 11.688 PASSED
ɛy = - - 0.00207 Min Shear Z 101 58.384 0 0 0 -1.991 PASSED
ɛs'= - - -0.02642377 Max Shear Z 101 58.384 0 0 0 -1.991 PASSED
Judgement = - - fs <> fy Min Torsion 131 39.698 0 0 0 3.204 PASSED
c = - - 83.07362843 Max Torsion 116 58.716 0 0 0 -6.544 PASSED
a = - - 70.61258417 Min Moment Y 101 58.384 0 0 0 -1.991 PASSED
fs = - - 181.0944983 Max Moment Y 101 58.384 0 0 0 -1.991 PASSED
Asprovided = 804.2477193 402.1238597 1005.309649 Min Moment Z 112 46.72 0 0 0 -31.345 PASSED
torsion bar = 0 pcs. 0 pcs. 0 pcs. Max Moment Z 112 -66.635 0 0 0 45.846 PASSED
Stirrups = No
Tulimit = 1.521415131 1.521415131 1.521415131
Remarks: Neglect Torsion Neglect Torsion Neglect Torsion 4-16mm 2-16mm
Additional As = 0 0 0
total As req = 717.1754375 384.8925107 0
Judement = OK OK OK
ρbal = 0.021685533 0.021685533 0.05708376
ρ = 0.012507741 0.005879004 0.035398227 B3
a = 93.2657019 46.63285095 116.5821274
Mu = 82.36743208 47.74879023 40.68143542 200 x 400
Judgement = OK OK OK
Vu = 75.863 71.615
Vc = 49.1099362 53.28619018
Vs = 52.04073047 42.20047649
Section is ADEQUATE
Spacing: 1-10mm. @ 50 mm. , 11 @ 75 mm. o.c. Rest @ 150 mm. o.c.
2-16mm 2-16mm

LEGENDS:
End Mid
db = Longitudinal Bar Diameter fc' = Concrete Strength at 28 days
1-10mm. @ 50 mm. , 11 @ 75 mm. o.c. Rest @ 150 mm. o.c.
dby = Stirrups Diameter fy = Yield Strength of Longitudinal Bars
dbt = Torsional Bar Diameter fyt = Yield Strength of Stirrups
cc = Concrete Cover

* This Document is presented and calculated conforming to National Structural Code of the Philippines 2010 Ed. Or American Concrete Institute 2008 Ed.
It is property of the designer signed above and contains information which is proprietary.
No other use of this document is to be made without the prior written consent of the Designer.
Beam Number: B4 Date: 12-Apr-19
Project Name: PROPOSED 2-STOREY RESIDENTIAL HOUSE Engineer: ENGR. KARL ANTHONY V. TAN

Material Properties:
fc' =
fy =
20.7 Mpa.
414 Mpa.
fyt =
db =
276
16
Mpa
mm.
dby =
cc =
10
40
mm.
mm.
dbt =
Type:
10 mm.
Rect. Beam
Result: PASSED
General Geometry: bw: 250 mm.
b = 250 mm. Number of ties (Vertical) 2= legs
h = 500 mm. Number of ties (horizontal)
2 = legs

DESIGN FORCES
END SPAN MIDDLE SPAN MINOR AXIS End Span Forces
Mu = 148.81 kN-m 23.04 kN-m 0 LC Shear-Y kN Shear-Z kN Torsion kNm Moment-Y kNm Moment-Z kNm Remarks
Tu = 0.00 kN-m 0.00 kN-m 0.00 kN-m Min Shear Y 125 -1.305 0 0 0 -53.022 PASSED
Vu = 124.28 kN 90.74 kN 0.00 kN Max Shear Y 114 124.935 0 0 0 148.521 PASSED
Top Layer 4 pcs. Top Layer 3 pcs. First Layer: 5 pcs. Min Shear Z 101 105.642 0 0 0 110.87 PASSED
Top Bars:
No. Of Layers 2 layers No. Of Layers 1 layers Second Layer: 0 pcs. Max Shear Z 101 105.642 0 0 0 110.87 PASSED
Bottom Layer 4 pcs. Bottom Layer 3 pcs. First Layer: 5 pcs. Min Torsion 119 115.897 0 0 0 128.37 PASSED
Bottom Bars:
No. Of Layers 1 layers No. Of Layers 1 layers Second Layer: 0 pcs. Max Torsion 101 16.406 0 0 0 -99.075 PASSED
d= 428.33 d' = 58.00 d = 442.00 d' = 58.00 d = 192.00 d' = 58.00 Min Moment Y 101 105.642 0 0 0 110.87 PASSED
Ru = 3.60493573 0.524058794 0 Max Moment Y 101 105.642 0 0 0 110.87 PASSED
ρ = 0.009848718 0.001285277 0 Min Moment Z 114 28.595 0 0 0 -115.911 PASSED
Asreq = 1054.633594 142.0231142 0 Max Moment Z 115 124.282 0 0 0 148.814 PASSED
ρmin = 0.003381643 0.001709418 0
Asmin = 362.1175523 188.8907419 0
ẞ1 = 0.85 0.85 0.85
ρbal = 0.02137574 0.02137574 0.02137574
Asbal = 2288.985454 2362.019231 1026.035503
Type = Singly Reinforced Singly Reinforced Singly Reinforced Mid Span Forces
a(theo) = - - - LC Shear-Y kN Shear-Z kN Torsion kNm Moment-Y kNm Moment-Z kNm Remarks
c(theo) = - - - Min Shear Y 125 16.259 0 0 0 -44.668 PASSED
As' = - - - Max Shear Y 114 91.396 0 0 0 21.981 PASSED
ɛy = - - - Min Shear Z 101 74.675 0 0 0 5.389 PASSED
ɛs'= - - - Max Shear Z 101 74.675 0 0 0 5.389 PASSED
Judgement = - - - Min Torsion 119 82.359 0 0 0 12.374 PASSED
c = - - - Max Torsion 128 45.192 0 0 0 -3.914 PASSED
a = - - - Min Moment Y 101 74.675 0 0 0 5.389 PASSED
fs = - - - Max Moment Y 101 74.675 0 0 0 5.389 PASSED
Asprovided = 1206.371579 603.1857895 1005.309649 Min Moment Z 112 34.83 0 0 0 -74.271 PASSED
torsion bar = 0 pcs. 0 pcs. 2 pcs. Max Moment Z 115 90.743 0 0 0 23.036 PASSED
Stirrups = No
Tulimit = 2.950212477 2.950212477 2.950212477
Remarks: Neglect Torsion Neglect Torsion Neglect Torsion 6-16mm 3-16mm
Additional As = 0 0 0
total As req = 1054.633594 188.8907419 0
Judement = OK OK OK
ρbal = 0.02137574 0.02137574 0.02137574
ρ = 0.011265727 0.005458695 0.020943951 B4
a = 113.5408545 56.77042725 94.61737874
Mu = 167.0153156 92.9586928 54.19823605 250 x 500
Judgement = OK OK OK
Vu = 124.935 91.396
Vc = 81.19995788 85.46658913
Vs = 85.38004212 36.3947442
Section is ADEQUATE
Spacing: 1-10mm. @ 50 mm. , 10 @ 100 mm. o.c. Rest @ 200 mm. o.c.

4-16mm 3-16mm
LEGENDS:
End Span Mid Span
db = Longitudinal Bar Diameter fc' = Concrete Strength at 28 days
dby = Stirrups Diameter fy = Yield Strength of Longitudinal Bars 1-10mm. @ 50 mm. , 10 @ 100 mm. o.c. Rest @ 200 mm. o.c.
dbt = Torsional Bar Diameter fyt = Yield Strength of Stirrups
cc = Concrete Cover

* This Document is presented and calculated conforming to National Structural Code of the Philippines 2010 Ed. Or American Concrete Institute 2008 Ed.
It is property of the designer signed above and contains information which is proprietary.
No other use of this document is to be made without the prior written consent of the Designer.
Beam Number: B5 Date: 12-Apr-19
Project Name: PROPOSED 2-STOREY RESIDENTIAL HOUSE Engineer: ENGR. KARL ANTHONY V. TAN

Material Properties:
fc' =
fy =
20.7 Mpa.
414 Mpa.
fyt =
db =
276
16
Mpa
mm.
dby =
cc =
10
40
mm.
mm.
dbt =
Type:
10 mm.
Rect. Beam
Result: PASSED
General Geometry: bw: 250 mm.
b = 250 mm. Number of ties (Vertical) 2= legs
h = 500 mm. Number of ties (horizontal)
2 = legs

DESIGN FORCES
END SPAN MIDDLE SPAN MINOR AXIS End Span Forces
Mu = 114.10 kN-m 31.10 kN-m 0 LC Shear-Y kN Shear-Z kN Torsion kNm Moment-Y kNm Moment-Z kNm Remarks
Tu = 0.00 kN-m 0.00 kN-m 0.00 kN-m Min Shear Y 112 -82.664 0 0 0 114.101 PASSED
Vu = 82.66 kN 59.18 kN 0.00 kN Max Shear Y 115 38.202 0 0 0 39.46 PASSED
Top Layer 4 pcs. Top Layer 2 pcs. First Layer: 5 pcs. Min Shear Z 101 19.924 0 0 0 4.892 PASSED
Top Bars:
No. Of Layers 1 layers No. Of Layers 1 layers Second Layer: 0 pcs. Max Shear Z 101 19.924 0 0 0 4.892 PASSED
Bottom Layer 2 pcs. Bottom Layer 2 pcs. First Layer: 5 pcs. Min Torsion 119 28.018 0 0 0 19.676 PASSED
Bottom Bars:
No. Of Layers 1 layers No. Of Layers 1 layers Second Layer: 0 pcs. Max Torsion 116 -51.518 0 0 0 29.02 PASSED
d= 442.00 d' = 58.00 d = 442.00 d' = 58.00 d = 192.00 d' = 58.00 Min Moment Y 101 19.924 0 0 0 4.892 PASSED
Ru = 2.595747198 0.70755672 0 Max Moment Y 101 19.924 0 0 0 4.892 PASSED
ρ = 0.006816576 0.001744894 0 Min Moment Z 124 -5.797 0 0 0 -31.66 PASSED
Asreq = 753.2316691 192.8107496 0 Max Moment Z 112 -82.664 0 0 0 114.101 PASSED
ρmin = 0.003381643 0.002320709 0
Asmin = 373.6714976 256.4382969 0
ẞ1 = 0.85 0.85 0.85
ρbal = 0.02137574 0.02137574 0.02137574
Asbal = 2362.019231 2362.019231 1026.035503
Type = Singly Reinforced Singly Reinforced Singly Reinforced Mid Span Forces
a(theo) = - - - LC Shear-Y kN Shear-Z kN Torsion kNm Moment-Y kNm Moment-Z kNm Remarks
c(theo) = - - - Min Shear Y 112 -59.179 0 0 0 31.102 PASSED
As' = - - - Max Shear Y 127 14.581 0 0 0 -3.231 PASSED
ɛy = - - - Min Shear Z 101 -6.261 0 0 0 -7.342 PASSED
ɛs'= - - - Max Shear Z 101 -6.261 0 0 0 -7.342 PASSED
Judgement = - - - Min Torsion 119 1.459 0 0 0 -6.714 PASSED
c = - - - Max Torsion 116 -40.582 0 0 0 5.228 PASSED
a = - - - Min Moment Y 101 -6.261 0 0 0 -7.342 PASSED
fs = - - - Max Moment Y 101 -6.261 0 0 0 -7.342 PASSED
Asprovided = 804.2477193 402.1238597 1005.309649 Min Moment Z 127 8.97 0 0 0 -10.259 PASSED
torsion bar = 0 pcs. 0 pcs. 0 pcs. Max Moment Z 112 -59.179 0 0 0 31.102 PASSED
Stirrups = No
Tulimit = 2.950212477 2.950212477 2.950212477
Remarks: Neglect Torsion Neglect Torsion Neglect Torsion 4-16mm 2-16mm
Additional As = 0 0 0
total As req = 753.2316691 256.4382969 0
Judement = OK OK OK
ρbal = 0.02137574 0.02137574 0.02137574
ρ = 0.00727826 0.00363913 0.020943951 B5
a = 75.69390299 37.8469515 94.61737874
Mu = 121.1095938 63.39012683 54.19823605 250 x 500
Judgement = OK OK OK
Vu = 82.664 59.179
Vc = 83.79077366 85.46658913
Vs = 26.42789301 -
Section is ADEQUATE
Spacing: 1-10mm. @ 50 mm. , 10 @ 100 mm. o.c. Rest @ 200 mm. o.c.

2-16mm 2-16mm
LEGENDS:
End Span Mid Span
db = Longitudinal Bar Diameter fc' = Concrete Strength at 28 days
1-10mm. @ 50 mm. , 10 @ 100 mm. o.c. Rest @ 200 mm. o.c.
dby = Stirrups Diameter fy = Yield Strength of Longitudinal Bars
dbt = Torsional Bar Diameter fyt = Yield Strength of Stirrups
cc = Concrete Cover

* This Document is presented and calculated conforming to National Structural Code of the Philippines 2010 Ed. Or American Concrete Institute 2008 Ed.
It is property of the designer signed above and contains information which is proprietary.
No other use of this document is to be made without the prior written consent of the Designer.
Beam Number: B6 Date: 12-Apr-19
Project Name: PROPOSED 2-STOREY RESIDENTIAL HOUSE Engineer: ENGR. KARL ANTHONY V. TAN

Material Properties:
fc' =
fy =
20.7 Mpa.
414 Mpa.
fyt =
db =
276
16
Mpa
mm.
dby =
cc =
10
40
mm.
mm.
dbt =
Type:
10 mm.
Rect. Beam
Result: PASSED
General Geometry: bw: 250 mm.
b = 250 mm. Number of ties (Vertical) 2= legs
h = 500 mm. Number of ties (horizontal)
2 = legs

DESIGN FORCES
END SPAN MIDDLE SPAN MINOR AXIS End Span Forces
Mu = 139.81 kN-m 89.32 kN-m 0 LC Shear-Y kN Shear-Z kN Torsion kNm Moment-Y kNm Moment-Z kNm Remarks
Tu = 0.00 kN-m 0.00 kN-m 0.00 kN-m Min Shear Y 130 51.555 0 0 0 -0.797 PASSED
Vu = 108.05 kN 100.88 kN 0.00 kN Max Shear Y 117 108.05 0 0 0 139.811 PASSED
Top Layer 4 pcs. Top Layer 4 pcs. First Layer: 5 pcs. Min Shear Z 101 102.66 0 0 0 132.292 PASSED
Top Bars:
No. Of Layers 2 layers No. Of Layers 2 layers Second Layer: 0 pcs. Max Shear Z 101 102.66 0 0 0 132.292 PASSED
Bottom Layer 3 pcs. Bottom Layer 3 pcs. First Layer: 5 pcs. Min Torsion 101 81.456 0 0 0 -1.189 PASSED
Bottom Bars:
No. Of Layers 1 layers No. Of Layers 1 layers Second Layer: 0 pcs. Max Torsion 115 107.482 0 0 0 138.873 PASSED
d= 428.33 d' = 58.00 d = 428.33 d' = 58.00 d = 192.00 d' = 58.00 Min Moment Y 101 102.66 0 0 0 132.292 PASSED
Ru = 3.386843101 2.16372693 0 Max Moment Y 101 102.66 0 0 0 132.292 PASSED
ρ = 0.009170079 0.005594627 0 Min Moment Z 115 85.976 0 0 0 -1.38 PASSED
Asreq = 981.9625798 599.0913196 0 Max Moment Z 117 108.05 0 0 0 139.811 PASSED
ρmin = 0.003381643 0.003381643 0
Asmin = 362.1175523 362.1175523 0
ẞ1 = 0.85 0.85 0.85
ρbal = 0.02137574 0.02137574 0.02137574
Asbal = 2288.985454 2288.985454 1026.035503
Type = Singly Reinforced Singly Reinforced Singly Reinforced Mid Span Forces
a(theo) = - - - LC Shear-Y kN Shear-Z kN Torsion kNm Moment-Y kNm Moment-Z kNm Remarks
c(theo) = - - - Min Shear Y 130 56.098 0 0 0 25.219 PASSED
As' = - - - Max Shear Y 117 100.882 0 0 0 89.32 PASSED
ɛy = - - - Min Shear Z 101 95.592 0 0 0 84.382 PASSED
ɛs'= - - - Max Shear Z 101 95.592 0 0 0 84.382 PASSED
Judgement = - - - Min Torsion 124 61.211 0 0 0 54.093 PASSED
c = - - - Max Torsion 115 100.313 0 0 0 88.657 PASSED
a = - - - Min Moment Y 101 95.592 0 0 0 84.382 PASSED
fs = - - - Max Moment Y 101 95.592 0 0 0 84.382 PASSED
Asprovided = 1206.371579 1206.371579 1005.309649 Min Moment Z 130 56.098 0 0 0 25.219 PASSED
torsion bar = 0 pcs. 0 pcs. 2 pcs. Max Moment Z 117 100.882 0 0 0 89.32 PASSED
Stirrups = No
Tulimit = 2.950212477 2.950212477 2.950212477
Remarks: Neglect Torsion Neglect Torsion Neglect Torsion 6-16mm 6-16mm
Additional As = 0 0 0
total As req = 981.9625798 599.0913196 0
Judement = OK OK OK
ρbal = 0.02137574 0.02137574 0.02137574
ρ = 0.011265727 0.011265727 0.020943951 B6
a = 113.5408545 113.5408545 94.61737874
Mu = 167.0153156 167.0153156 54.19823605 250 x 500
Judgement = OK OK OK
Vu = 108.05 100.882
Vc = 81.19995788 82.82395704
Vs = 62.86670879 51.6853763
Section is ADEQUATE
Spacing: 1-10mm. @ 50 mm. , 10 @ 100 mm. o.c. Rest @ 200 mm. o.c.

3-16mm 3-16mm
LEGENDS:
End Span Mid Span
db = Longitudinal Bar Diameter fc' = Concrete Strength at 28 days
1-10mm. @ 50 mm. , 10 @ 100 mm. o.c. Rest @ 200 mm. o.c.
dby = Stirrups Diameter fy = Yield Strength of Longitudinal Bars
dbt = Torsional Bar Diameter fyt = Yield Strength of Stirrups
cc = Concrete Cover

* This Document is presented and calculated conforming to National Structural Code of the Philippines 2010 Ed. Or American Concrete Institute 2008 Ed.
It is property of the designer signed above and contains information which is proprietary.
No other use of this document is to be made without the prior written consent of the Designer.
H. COLUMN DESIGN
Column Number: C1 Date: April 12, 2019
Project Name: Proposed 2-Storey Residence Designed by: KARL ANTHONY V. TAN

I. Design Parameters Judgement: SAFE


Cross Section Properties
B = 200 mm. H = 400 mm. cc = 40 mm. fyt = 276.00 Mpa.

Materials Strength

fc'= 21.00 Mpa. fy = 414.00 Mpa. Es = 200 Gpa.

Rebar Arrangement
db = D16
Y-axis

Number of bars along Y-axis: 2


Number of bars along Z-axis: 3
Total number of Bars: 6

Z-axis
Shear Capacity (Design of Lateral Ties) Cross Section :
modification factor (λ) = 1.00
number of legs (Z) = 2.00
number of legs (Y) = 3.00
dby = D10 Spacing = 200 mm. (for lateral ties)
Design Loads:
Pu = 174.01 kN Muz = 50.54 kN.m. Muy = 4.79 kN.m.
Vuz = 2.867 kN Vuy = 27.20 kN
Calculation Summary

Min.S Max S. Note: Column Splice Shall be Located midheight


Bar Spacing Check:
41.00 285.51 of Column with lap length equal to 840 mm.
Sactual(z) = 84.00 OK OK with Lateral Ties spaced not more than 150
Sactual(y) = ##### OK OK mm.

ß1 = 0.85
Balanced Condition: Due to My: Du to Mz:
cby = 84.02 mm. c = 170.19 mm. c = 153.12 mm.
Pby= 361.54 kN Pny= 1309.90 kN Pnz= 367.00 kN
ebz= 131.46 mm. ez= 27.54 mm. ey= 290.45 mm.
cbz = 202.37 mm.

Section Capacities: Check Spacing for Crack Control:


Pn = 353.06 kN Sminy = 1716.64 mm OK
Pcy = 1178.91 kN OK Sminz = 572.215 mm OK
Pcz = 289.34 kN OK
Mcy = 32.47 kN-m OK LATERAL TIES
Mcz = 84.04 kN-m OK 1 @ 50 from face of support
Vuycap = 71.12 kN OK Provide 9 @ 50 mm. o.c.
Vuyzcap = 175.75 kN OK Rest @ 200 mm. o.c.

Load Case/Combo Mark P V2 V3 T M2 M3 Remarks


kN kN kN kN-m kN-m kN-m
Pmax 328.961 -24.382 -30.711 0 0 0 SAFE
Pmin -64.132 25.067 5.805 0 2.903 -12.534 SAFE
V2Max 285.322 29.547 10.476 0 0 0 SAFE
V2Min 106.765 -29.436 -2.987 -0.178 1.925 -43.258 SAFE
V3Max 290.865 4.387 40.304 0 0 0 SAFE
V3Min 199.96 -3.335 -39.075 0 0 0 SAFE
Tmax 25.256 -3.093 5.877 0.761 -10.726 0.996 SAFE
Tmin 12.487 -1.245 -0.353 -0.91 0.895 3.278 SAFE
M2Max 122.949 -3.284 13.208 0.367 24.03 2.181 SAFE
M2Min 199.112 -3.335 -39.075 0 -19.537 1.668 SAFE
M3Max 98.2 -29.436 -2.987 -0.178 -7.634 50.936 SAFE
M3Min 174.01 27.197 2.867 -0.356 4.793 -50.542 SAFE
Interaction Diagram in Y-Direction
1600

1400

1200
Ultimate Axial capacity

1000

800

600

400

200

0
-5 0 5 10 15 20 25 30 35 40 45
Ultimate Moment Capacity

Y-Interaction Actual Y Stress

Interaction Diagram in Z-Direction


1400

1200

1000
Ultimate Axial capacity

800

600

400

200

0
-20 0 20 40 60 80 100
-200

-400
Ultimate Moment Capacity

Z-Interaction Actual Z Stress

Reinforced Concrete Column Design V.9 Programmed by: JPS Engg.


Column Number: C2 Date: April 12, 2019
Project Name: Proposed 2-Storey Residence Designed by: KARL ANTHONY V. TAN

I. Design Parameters Judgement: SAFE


Cross Section Properties
B = 300 mm. H = 300 mm. cc = 40 mm. fyt = 276.00 Mpa.

Materials Strength

fc'= 21.00 Mpa. fy = 414.00 Mpa. Es = 200 Gpa.

Rebar Arrangement
db = D16
Y-axis

Number of bars along Y-axis: 3


Number of bars along Z-axis: 3
Total number of Bars: 8

Cross Section : Z-axis


Shear Capacity (Design of Lateral Ties)
modification factor (λ) = 1.00
number of legs (Z) = 2.00
number of legs (Y) = 3.00
dby = D10 Spacing = 200 mm. (for lateral ties)
Design Loads:
Pu = 225.472 kN Muz = 69.96 kN.m. Muy = 10.08 kN.m.
Vuz = 5.761 kN Vuy = 34.96 kN
Calculation Summary

Min.S Max S. Note: Column Splice Shall be Located midheight


Bar Spacing Check:
41.00 285.51 of Column with lap length equal to 840 mm.
Sactual(z) = 92.00 OK OK with Lateral Ties spaced not more than 150
Sactual(y) = 92.00 OK OK mm.

ß1 = 0.85
Balanced Condition: Due to My: Du to Mz:
cby = 143.20 mm. c = 258.56 mm. c = 105.62 mm.
Pby= 595.16 kN Pny= 1522.42 kN Pnz= 282.12 kN
ebz= 167.85 mm. ez= 44.70 mm. ey= 310.27 mm.
cbz = 143.20 mm.

Section Capacities: Check Spacing for Crack Control:


Pn = 274.40 kN Sminy = 1144.43 mm OK
Pcy = 1370.17 kN OK Sminz = 762.953 mm OK
Pcz = 226.48 kN OK
Mcy = 61.24 kN-m OK LATERAL TIES
Mcz = 70.27 kN-m OK 1 @ 50 from face of support
Vuycap = 138.53 kN OK Provide 6 @ 75 mm. o.c.
Vuyzcap = 109.02 kN OK Rest @ 200 mm. o.c.

Load Case/Combo Mark P V2 V3 T M2 M3 Remarks


kN kN kN kN-m kN-m kN-m
Pmax 292.389 40.056 11.564 0 0 0 SAFE
Pmin 5.492 0.485 1.138 0.246 1.98 -4.224 SAFE
V2Max 292.389 40.056 11.564 0 0 0 SAFE
V2Min 54.653 -36.32 8.087 0 0 0 SAFE
V3Max 177.811 -21.425 53.227 0 0 0 SAFE
V3Min 220.769 -11.289 -55.435 0 0 0 SAFE
Tmax 35.868 2.006 -17.134 1.274 35.699 2.06 SAFE
Tmin 31.513 5.353 -4.117 -1.293 6.473 21.694 SAFE
M2Max 43.689 -6.314 -21.905 -0.49 41.745 -12.263 SAFE
M2Min 206.197 -8.993 -31.052 -1.009 -61.608 14.265 SAFE
M3Max 162.07 -34.58 -13.199 -0.309 -31.136 57.346 SAFE
M3Min 225.472 34.962 -5.761 0.328 -10.078 -69.957 SAFE
Interaction Diagram in Y-Direction
1800

1600

1400

1200
Ultimate Axial capacity

1000

800

600

400

200

0
-10 0 10 20 30 40 50 60 70 80 90 100
-200

-400
Ultimate Moment Capacity

Y-Interaction Actual Y Stress

Interaction Diagram in Z-Direction


1600

1400

1200

1000
Ultimate Axial capacity

800

600

400

200

0
-10 0 10 20 30 40 50 60 70 80 90
-200

-400
Ultimate Moment Capacity

Z-Interaction Actual Z Stress

Reinforced Concrete Column Design V.9 Programmed by: JPS Engg.


Column Number: C3 Date: April 12, 2019
Project Name: Proposed 2-Storey Residence Designed by: KARL ANTHONY V. TAN

I. Design Parameters Judgement: SAFE


Cross Section Properties
B = 300 mm. H = 400 mm. cc = 40 mm. fyt = 276.00 Mpa.

Materials Strength

fc'= 21.00 Mpa. fy = 414.00 Mpa. Es = 200 Gpa.

Rebar Arrangement
db = D16
Y-axis

Number of bars along Y-axis: 3


Number of bars along Z-axis: 3
Total number of Bars: 8

Z-axis
Shear Capacity (Design of Lateral Ties) Cross Section :
modification factor (λ) = 1.00
number of legs (Z) = 2.00
number of legs (Y) = 3.00
dby = D10 Spacing = 200 mm. (for lateral ties)
Design Loads:
Pu = 397.587 kN Muz = 73.59 kN.m. Muy = 12.50 kN.m.
Vuz = 12.004 kN Vuy = 55.35 kN
Calculation Summary

Min.S Max S. Note: Column Splice Shall be Located midheight


Bar Spacing Check:
41.00 285.51 of Column with lap length equal to 840 mm.
Sactual(z) = 92.00 OK OK with Lateral Ties spaced not more than 150
Sactual(y) = ##### OK OK mm.

ß1 = 0.85
Balanced Condition: Due to My: Du to Mz:
cby = 143.20 mm. c = 286.39 mm. c = 205.85 mm.
Pby= 812.42 kN Pny= 2130.15 kN Pnz= 936.56 kN
ebz= 146.80 mm. ez= 31.44 mm. ey= 185.09 mm.
cbz = 202.37 mm.

Section Capacities: Check Spacing for Crack Control:


Pn = 919.61 kN Sminy = 1144.43 mm OK
Pcy = 1917.13 kN OK Sminz = 572.215 mm OK
Pcz = 842.90 kN OK
Mcy = 60.27 kN-m OK LATERAL TIES
Mcz = 156.01 kN-m OK 1 @ 50 from face of support
Vuycap = 140.98 kN OK Provide 6 @ 75 mm. o.c.
Vuyzcap = 182.25 kN OK Rest @ 200 mm. o.c.

Load Case/Combo Mark P V2 V3 T M2 M3 Remarks


kN kN kN kN-m kN-m kN-m
Pmax 470.345 32.321 -24.309 0 0 0 SAFE
Pmin 14.477 -11.105 8.271 -0.161 7.503 11.92 SAFE
V2Max 457.226 35.905 -19.844 0 0 0 SAFE
V2Min 397.587 -55.349 12.004 1.028 -12.5 -73.588 SAFE
V3Max 273.92 -8.416 46.066 0 0 0 SAFE
V3Min 156.766 16.929 -37.072 0 0 0 SAFE
Tmax 397.587 -55.349 12.004 1.028 -12.5 -73.588 SAFE
Tmin 266.855 30.559 -0.287 -1.013 3.626 47.615 SAFE
M2Max 376.425 -32.554 19.754 0.872 39.156 63.509 SAFE
M2Min 221.464 8.956 -19.008 -0.853 -32.549 -14.989 SAFE
M3Max 386.881 -55.349 12.004 1.028 25.912 103.527 SAFE
M3Min 397.587 -55.349 12.004 1.028 -12.5 -73.588 SAFE
Interaction Diagram in Y-Direction
2500

2000
Ultimate Axial capacity

1500

1000

500

0
-20 0 20 40 60 80 100 120

-500
Ultimate Moment Capacity

Y-Interaction Actual Y Stress

Interaction Diagram in Z-Direction


2500

2000
Ultimate Axial capacity

1500

1000

500

0
-20 0 20 40 60 80 100 120 140 160 180

-500
Ultimate Moment Capacity

Z-Interaction Actual Z Stress

Reinforced Concrete Column Design V.9 Programmed by: JPS Engg.


I. FOUNDATION DESIGN
Footing Mark: F1 Date: April 12, 2019
Project Name: PROPOSED 2-STOREY RESIDENTIAL HOUSE Designed by: KARL ANTHONY TAN
Judgement : PASSED

hp
Lpz Lz
D
4 Pcs. Of 16 mm. bar
Lpx dia. Bothways
hf

Lx y

z x

Foundation Property Material Property


Lx = 1000 mm. hf = 300 mm. fc' = 20.7 Mpa. ϒwater = 10 kN/m3
Lz = 1000 mm. Df = 1200 mm. fy = 414 Mpa. μ= 0.5 (Soil to Concrete)
Lpx = 250 mm. hp = 900 mm. ϒsoil = 18 kN/m3 db = 16 mm
Lpz = 250 mm. cc = 75 mm. ϒconc. = 24 kN/m3

Net Soil Bearing Capacity


qall = 90 kPa. (Long Term) qall = 119.7 kPa. (Short Term)

Minimum Thickness: 300 mm Factor of Safety: Location of G.W.L.


Maximum Spacing: 300 mm Overturning = 1 3,000 mm.
Minimum Dimension: 700 mm Sliding = 1.5 Column Location
Buoyancy = 1.1 Corner

SERVICE LOAD COMBINATIONS

MY
LC LC Definition Force-X kN Force-Y kN Force-Z kN MX kNm MZ kNm qu (kPa) Soil Stress BUOY. OM Sliding
kNm

301 DL + 0.75LL + 0.75RLL + 0.45W+X 4.44 49.35 6.28 0.00 0.00 0.00 49.35 0.41 1.10 1.00 1.50
302 DL + 0.75LL + 0.75RLL + 0.45W-X 4.44 49.35 6.28 0.00 0.00 0.00 49.35 0.41 1.10 1.00 1.50
303 DL + 0.75LL + 0.75RLL + 0.45W+Z 4.44 49.35 6.28 0.00 0.00 0.00 49.35 0.41 1.10 1.00 1.50
304 DL + 0.75LL + 0.75RLL + 0.45W-Z 4.44 49.35 6.28 0.00 0.00 0.00 49.35 0.41 1.10 1.00 1.50
305 DL + 0.75LL + 0.75RLL + 0.54EQX 9.78 36.98 10.97 0.00 0.00 0.00 36.98 0.31 1.10 1.00 1.50
306 DL + 0.75LL + 0.75RLL - 0.54EQX -0.90 61.73 1.58 0.00 0.00 0.00 61.73 0.52 1.10 1.00 1.50
307 DL + 0.75LL + 0.75RLL + 0.54EQZ 5.06 100.32 -2.51 0.00 0.00 0.00 100.32 0.84 1.10 1.00 1.50
308 DL + 0.75LL + 0.75RLL - 0.54EQZ 3.82 -1.62 15.07 0.00 0.00 0.00 1.62 0.01 1.10 1.00 1.50
309 0.6DL + 0.6W+X 2.41 27.93 3.47 0.00 0.00 0.00 27.93 0.23 1.10 1.00 1.50
310 0.6DL + 0.6W-X 2.41 27.93 3.47 0.00 0.00 0.00 27.93 0.23 1.10 1.00 1.50
311 0.6DL + 0.6W+Z 2.41 27.93 3.47 0.00 0.00 0.00 27.93 0.23 1.10 1.00 1.50
312 0.6DL + 0.6W-Z 2.41 27.93 3.47 0.00 0.00 0.00 27.93 0.23 1.10 1.00 1.50
313 0.6DL + 0.7EQX 9.33 11.89 9.56 0.00 0.00 0.00 11.89 0.10 1.10 1.00 1.50
314 0.6DL - 0.7EQX -4.51 43.98 -2.61 0.00 0.00 0.00 43.98 0.37 1.10 1.00 1.50
315 0.6DL + 0.7EQZ 3.22 94.00 -7.92 0.00 0.00 0.00 94.00 0.79 1.10 1.00 1.50
316 0.6DL - 0.7EQX 1.60 -38.14 14.87 0.00 0.00 0.00 38.14 0.32 1.10 1.00 1.50
317 DL + LL + RLL 4.58 50.29 6.44 0.00 0.00 0.00 50.29 0.56 1.10 1.00 1.50
318 DL + LL + 0.6W+X 4.63 49.74 6.41 0.00 0.00 0.00 49.74 0.42 1.10 1.00 1.50
319 DL + LL + 0.6W-X 4.63 49.74 6.41 0.00 0.00 0.00 49.74 0.42 1.10 1.00 1.50
320 DL + LL + 0.6W+Z 4.63 49.74 6.41 0.00 0.00 0.00 49.74 0.42 1.10 1.00 1.50
321 DL + LL + 0.6W-Z 4.63 49.74 6.41 0.00 0.00 0.00 49.74 0.42 1.10 1.00 1.50
322 DL + LL + 0.7EQX 11.54 33.69 12.49 0.00 0.00 0.00 33.69 0.28 1.10 1.00 1.50
323 DL + LL - 0.7EQX -2.29 65.78 0.32 0.00 0.00 0.00 65.78 0.55 1.10 1.00 1.50
324 DL + LL + 0.7EQZ 5.44 115.81 -4.99 0.00 0.00 0.00 115.81 0.97 1.10 1.00 1.50
325 DL + LL - 0.7EQZ 3.82 -16.33 17.80 0.00 0.00 0.00 16.33 0.14 1.10 1.00 1.50
ULTIMATE LOADS
Momen
Moment-X Moment-
LC LC Definition Force-X kN Force-Y kN Force-Z kN t-Y Muz Mux Vu
kNm Z kNm
kNm
101 1.4DL 5.62 65.17 8.10 0.00 0.00 0.00 4.58 4.58 13.26
102 1.2DL + 1.6LL + 0.5RLL 5.77 61.23 7.95 0.00 0.00 0.00 4.31 4.31 12.45
103 1.2DL + 1.6RLL + 0.5LL 5.05 58.33 7.31 0.00 0.00 0.00 4.10 4.10 11.87
104 1.2DL + 1.6RLL + 0.5W+X 4.75 56.74 7.00 0.00 0.00 0.00 3.99 3.99 11.54
105 1.2DL + 1.6RLL + 0.5W-X 4.75 56.74 7.00 0.00 0.00 0.00 3.99 3.99 11.54
106 1.2DL + 1.6RLL + 0.5W+Z 4.75 56.74 7.00 0.00 0.00 0.00 3.99 3.99 11.54
107 1.2DL + 1.6RLL + 0.5W-Z 4.75 56.74 7.00 0.00 0.00 0.00 3.99 3.99 11.54
108 1.2DL + 1.0W+X + 0.5LL + 0.5RLL 5.10 57.73 7.27 0.00 0.00 0.00 4.06 4.06 11.74
109 1.2DL + 1.0W-X + 0.5LL + 0.5RLL 5.10 57.73 7.27 0.00 0.00 0.00 4.06 4.06 11.74
110 1.2DL + 1.0W+Z + 0.5LL + 0.5RLL 5.10 57.73 7.27 0.00 0.00 0.00 4.06 4.06 11.74
111 1.2DL + 1.0W-Z + 0.5LL + 0.5RLL 5.10 57.73 7.27 0.00 0.00 0.00 4.06 4.06 11.74
112 1.2DL + 1.0EQX + 0.5LL 15.01 34.54 15.95 0.00 0.00 0.00 2.43 2.43 7.02
113 1.2DL - 1.0EQX + 0.5LL -4.75 80.38 -1.44 0.00 0.00 0.00 5.65 5.65 16.35
114 1.2DL + 1.0EQZ + 0.5LL 6.28 151.84 -9.02 0.00 0.00 0.00 10.68 10.68 30.88
115 1.2DL - 1.0EQX + 0.5LL 3.97 -36.93 23.54 0.00 0.00 0.00 2.60 2.60 7.51
116 0.9DL + 1.0W+X 3.62 41.90 5.21 0.00 0.00 0.00 2.95 2.95 8.52
117 0.9DL + 1.0W-X 3.62 41.90 5.21 0.00 0.00 0.00 2.95 2.95 8.52
118 0.9DL + 1.0W+Z 3.62 41.90 5.21 0.00 0.00 0.00 2.95 2.95 8.52
119 0.9DL + 1.0W-Z 3.62 41.90 5.21 0.00 0.00 0.00 2.95 2.95 8.52
120 0.9DL + 1.0EQX 13.50 18.98 13.90 0.00 0.00 0.00 1.33 1.33 3.86
121 0.9DL - 1.0EQX -6.26 64.82 -3.48 0.00 0.00 0.00 4.56 4.56 13.18
122 0.9DL + 1.0EQZ 4.77 136.28 -11.07 0.00 0.00 0.00 9.58 9.58 27.72
123 0.9DL - 1.0EQZ 2.46 -52.49 21.49 0.00 0.00 0.00 3.69 3.69 10.68

LC LC Definition Force-Y kN Dowels n Dowels


101 1.4DL 65.17 Not Required -
102 1.2DL + 1.6LL + 0.5RLL 61.23 Not Required -
103 1.2DL + 1.6RLL + 0.5LL 58.33 Not Required -
104 1.2DL + 1.6RLL + 0.5W+X 56.74 Not Required -
105 1.2DL + 1.6RLL + 0.5W-X 56.74 Not Required - No Dowels Required
106 1.2DL + 1.6RLL + 0.5W+Z 56.74 Not Required -
107 1.2DL + 1.6RLL + 0.5W-Z 56.74 Not Required -
108 1.2DL + 1.0W+X + 0.5LL + 0.5RLL 57.73 Not Required -
109 1.2DL + 1.0W-X + 0.5LL + 0.5RLL 57.73 Not Required - 400
110 1.2DL + 1.0W+Z + 0.5LL + 0.5RLL 57.73 Not Required -
111 1.2DL + 1.0W-Z + 0.5LL + 0.5RLL 57.73 Not Required -
112 1.2DL + 1.0EQX + 0.5LL 34.54 Not Required -
113 1.2DL - 1.0EQX + 0.5LL 80.38 Not Required -
114 1.2DL + 1.0EQZ + 0.5LL 151.84 Not Required -
115 1.2DL - 1.0EQX + 0.5LL -36.93 Not Required -
116 0.9DL + 1.0W+X 41.90 Not Required -
117 0.9DL + 1.0W-X 41.90 Not Required -
118 0.9DL + 1.0W+Z 41.90 Not Required -
119 0.9DL + 1.0W-Z 41.90 Not Required -
120 0.9DL + 1.0EQX 18.98 Not Required -
121 0.9DL - 1.0EQX 64.82 Not Required -
122 0.9DL + 1.0EQZ 136.28 Not Required -
123 0.9DL - 1.0EQZ -52.49 Not Required -
Footing Mark: F2 Date: April 12, 2019
Project Name: PROPOSED 2-STOREY RESIDENTIAL HOUSE Designed by: KARL ANTHONY TAN
Judgement : PASSED

hp
Lpz Lz
D
5 Pcs. Of 16 mm. bar
Lpx dia. Bothways
hf

Lx y

z x

Foundation Property Material Property


Lx = 1200 mm. hf = 300 mm. fc' = 20.7 Mpa. ϒwater = 10 kN/m3
Lz = 1200 mm. Df = 1200 mm. fy = 414 Mpa. μ= 0.5 (Soil to Concrete)
Lpx = 250 mm. hp = 900 mm. ϒsoil = 18 kN/m3 db = 16 mm
Lpz = 250 mm. cc = 75 mm. ϒconc. = 24 kN/m3

Net Soil Bearing Capacity


qall = 90 kPa. (Long Term) qall = 119.7 kPa. (Short Term)

Minimum Thickness: 300 mm Factor of Safety: Location of G.W.L.


Maximum Spacing: 300 mm Overturning = 1 3,000 mm.
Minimum Dimension: 700 mm Sliding = 1.5 Column Location
Buoyancy = 1.1 Corner

SERVICE LOAD COMBINATIONS

MY
LC LC Definition Force-X kN Force-Y kN Force-Z kN MX kNm MZ kNm qu (kPa) Soil Stress BUOY. OM Sliding
kNm

301 DL + 0.75LL + 0.75RLL + 0.45W+X 1.47 111.28 1.75 0.00 0.00 0.00 77.28 0.65 1.10 1.00 1.50
302 DL + 0.75LL + 0.75RLL + 0.45W-X 1.47 111.28 1.75 0.00 0.00 0.00 77.28 0.65 1.10 1.00 1.50
303 DL + 0.75LL + 0.75RLL + 0.45W+Z 1.47 111.28 1.75 0.00 0.00 0.00 77.28 0.65 1.10 1.00 1.50
304 DL + 0.75LL + 0.75RLL + 0.45W-Z 1.47 111.28 1.75 0.00 0.00 0.00 77.28 0.65 1.10 1.00 1.50
305 DL + 0.75LL + 0.75RLL + 0.54EQX -14.17 104.18 3.62 0.00 0.00 0.00 72.35 0.60 1.10 1.00 1.50
306 DL + 0.75LL + 0.75RLL - 0.54EQX 17.11 118.38 -0.12 0.00 0.00 0.00 82.21 0.69 1.10 1.00 1.50
307 DL + 0.75LL + 0.75RLL + 0.54EQZ 6.87 108.92 -5.65 0.00 0.00 0.00 75.64 0.63 1.10 1.00 1.50
308 DL + 0.75LL + 0.75RLL - 0.54EQZ -3.94 113.64 9.15 0.00 0.00 0.00 78.92 0.66 1.10 1.00 1.50
309 0.6DL + 0.6W+X 0.76 59.79 1.06 0.00 0.00 0.00 41.52 0.35 1.10 1.00 1.50
310 0.6DL + 0.6W-X 0.76 59.79 1.06 0.00 0.00 0.00 41.52 0.35 1.10 1.00 1.50
311 0.6DL + 0.6W+Z 0.76 59.79 1.06 0.00 0.00 0.00 41.52 0.35 1.10 1.00 1.50
312 0.6DL + 0.6W-Z 0.76 59.79 1.06 0.00 0.00 0.00 41.52 0.35 1.10 1.00 1.50
313 0.6DL + 0.7EQX -19.51 50.59 3.48 0.00 0.00 0.00 35.13 0.29 1.10 1.00 1.50
314 0.6DL - 0.7EQX 21.03 69.00 -1.36 0.00 0.00 0.00 47.91 0.40 1.10 1.00 1.50
315 0.6DL + 0.7EQZ 7.77 56.73 -8.53 0.00 0.00 0.00 39.40 0.33 1.10 1.00 1.50
316 0.6DL - 0.7EQX -6.25 62.86 10.65 0.00 0.00 0.00 43.65 0.36 1.10 1.00 1.50
317 DL + LL + RLL 1.54 115.16 1.75 0.00 0.00 0.00 79.97 0.89 1.10 1.00 1.50
318 DL + LL + 0.6W+X 1.54 109.51 1.71 0.00 0.00 0.00 76.05 0.64 1.10 1.00 1.50
319 DL + LL + 0.6W-X 1.54 109.51 1.71 0.00 0.00 0.00 76.05 0.64 1.10 1.00 1.50
320 DL + LL + 0.6W+Z 1.54 109.51 1.71 0.00 0.00 0.00 76.05 0.64 1.10 1.00 1.50
321 DL + LL + 0.6W-Z 1.54 109.51 1.71 0.00 0.00 0.00 76.05 0.64 1.10 1.00 1.50
322 DL + LL + 0.7EQX -18.73 100.31 4.13 0.00 0.00 0.00 69.66 0.58 1.10 1.00 1.50
323 DL + LL - 0.7EQX 21.81 118.71 -0.71 0.00 0.00 0.00 82.44 0.69 1.10 1.00 1.50
324 DL + LL + 0.7EQZ 8.55 106.45 -7.88 0.00 0.00 0.00 73.92 0.62 1.10 1.00 1.50
325 DL + LL - 0.7EQZ -5.47 112.57 11.30 0.00 0.00 0.00 78.17 0.65 1.10 1.00 1.50
ULTIMATE LOADS
Momen
Moment-X Moment-
LC LC Definition Force-X kN Force-Y kN Force-Z kN t-Y Muz Mux Vu
kNm Z kNm
kNm
101 1.4DL 1.77 139.52 2.47 0.00 0.00 0.00 13.12 13.12 19.71
102 1.2DL + 1.6LL + 0.5RLL 1.96 138.17 2.05 0.00 0.00 0.00 12.99 12.99 19.52
103 1.2DL + 1.6RLL + 0.5LL 1.65 133.55 2.14 0.00 0.00 0.00 12.56 12.56 18.86
104 1.2DL + 1.6RLL + 0.5W+X 1.51 128.63 2.16 0.00 0.00 0.00 12.09 12.09 18.17
105 1.2DL + 1.6RLL + 0.5W-X 1.51 128.63 2.16 0.00 0.00 0.00 12.09 12.09 18.17
106 1.2DL + 1.6RLL + 0.5W+Z 1.51 128.63 2.16 0.00 0.00 0.00 12.09 12.09 18.17
107 1.2DL + 1.6RLL + 0.5W-Z 1.51 128.63 2.16 0.00 0.00 0.00 12.09 12.09 18.17
108 1.2DL + 1.0W+X + 0.5LL + 0.5RLL 1.65 127.34 2.11 0.00 0.00 0.00 11.97 11.97 17.99
109 1.2DL + 1.0W-X + 0.5LL + 0.5RLL 1.65 127.34 2.11 0.00 0.00 0.00 11.97 11.97 17.99
110 1.2DL + 1.0W+Z + 0.5LL + 0.5RLL 1.65 127.34 2.11 0.00 0.00 0.00 11.97 11.97 17.99
111 1.2DL + 1.0W-Z + 0.5LL + 0.5RLL 1.65 127.34 2.11 0.00 0.00 0.00 11.97 11.97 17.99
112 1.2DL + 1.0EQX + 0.5LL -27.30 111.37 5.55 0.00 0.00 0.00 10.47 10.47 15.73
113 1.2DL - 1.0EQX + 0.5LL 30.62 137.66 -1.37 0.00 0.00 0.00 12.94 12.94 19.44
114 1.2DL + 1.0EQZ + 0.5LL 11.67 120.14 -11.61 0.00 0.00 0.00 11.29 11.29 16.97
115 1.2DL - 1.0EQX + 0.5LL -8.35 128.89 15.79 0.00 0.00 0.00 12.12 12.12 18.21
116 0.9DL + 1.0W+X 1.14 89.69 1.58 0.00 0.00 0.00 8.43 8.43 12.67
117 0.9DL + 1.0W-X 1.14 89.69 1.58 0.00 0.00 0.00 8.43 8.43 12.67
118 0.9DL + 1.0W+Z 1.14 89.69 1.58 0.00 0.00 0.00 8.43 8.43 12.67
119 0.9DL + 1.0W-Z 1.14 89.69 1.58 0.00 0.00 0.00 8.43 8.43 12.67
120 0.9DL + 1.0EQX -27.82 76.55 5.04 0.00 0.00 0.00 7.20 7.20 10.81
121 0.9DL - 1.0EQX 30.10 102.84 -1.87 0.00 0.00 0.00 9.67 9.67 14.53
122 0.9DL + 1.0EQZ 11.15 85.32 -12.12 0.00 0.00 0.00 8.02 8.02 12.05
123 0.9DL - 1.0EQZ -8.87 94.07 15.29 0.00 0.00 0.00 8.84 8.84 13.29

LC LC Definition Force-Y kN Dowels n Dowels


101 1.4DL 139.52 Not Required -
102 1.2DL + 1.6LL + 0.5RLL 138.17 Not Required -
103 1.2DL + 1.6RLL + 0.5LL 133.55 Not Required -
104 1.2DL + 1.6RLL + 0.5W+X 128.63 Not Required -
105 1.2DL + 1.6RLL + 0.5W-X 128.63 Not Required - No Dowels Required
106 1.2DL + 1.6RLL + 0.5W+Z 128.63 Not Required -
107 1.2DL + 1.6RLL + 0.5W-Z 128.63 Not Required -
108 1.2DL + 1.0W+X + 0.5LL + 0.5RLL 127.34 Not Required -
109 1.2DL + 1.0W-X + 0.5LL + 0.5RLL 127.34 Not Required - 300
110 1.2DL + 1.0W+Z + 0.5LL + 0.5RLL 127.34 Not Required -
111 1.2DL + 1.0W-Z + 0.5LL + 0.5RLL 127.34 Not Required -
112 1.2DL + 1.0EQX + 0.5LL 111.37 Not Required -
113 1.2DL - 1.0EQX + 0.5LL 137.66 Not Required -
114 1.2DL + 1.0EQZ + 0.5LL 120.14 Not Required -
115 1.2DL - 1.0EQX + 0.5LL 128.89 Not Required -
116 0.9DL + 1.0W+X 89.69 Not Required -
117 0.9DL + 1.0W-X 89.69 Not Required -
118 0.9DL + 1.0W+Z 89.69 Not Required -
119 0.9DL + 1.0W-Z 89.69 Not Required -
120 0.9DL + 1.0EQX 76.55 Not Required -
121 0.9DL - 1.0EQX 102.84 Not Required -
122 0.9DL + 1.0EQZ 85.32 Not Required -
123 0.9DL - 1.0EQZ 94.07 Not Required -
Footing Mark: F3 Date: April 12, 2019
Project Name: PROPOSED 2-STOREY RESIDENTIAL HOUSE Designed by: KARL ANTHONY TAN
Judgement : PASSED

hp
Lpz Lz
D
5 Pcs. Of 16 mm. bar
Lpx dia. Bothways
hf

Lx y

z x

Foundation Property Material Property


Lx = 1400 mm. hf = 300 mm. fc' = 20.7 Mpa. ϒwater = 10 kN/m3
Lz = 1400 mm. Df = 1200 mm. fy = 414 Mpa. μ= 0.5 (Soil to Concrete)
Lpx = 250 mm. hp = 900 mm. ϒsoil = 18 kN/m3 db = 16 mm
Lpz = 250 mm. cc = 75 mm. ϒconc. = 24 kN/m3

Net Soil Bearing Capacity


qall = 90 kPa. (Long Term) qall = 119.7 kPa. (Short Term)

Minimum Thickness: 300 mm Factor of Safety: Location of G.W.L.


Maximum Spacing: 300 mm Overturning = 1 3,000 mm.
Minimum Dimension: 700 mm Sliding = 1.5 Column Location
Buoyancy = 1.1 Corner

SERVICE LOAD COMBINATIONS

MY
LC LC Definition Force-X kN Force-Y kN Force-Z kN MX kNm MZ kNm qu (kPa) Soil Stress BUOY. OM Sliding
kNm

301 DL + 0.75LL + 0.75RLL + 0.45W+X 9.26 159.92 2.20 0.00 0.00 0.00 81.59 0.68 1.10 1.00 1.50
302 DL + 0.75LL + 0.75RLL + 0.45W-X 9.26 159.92 2.20 0.00 0.00 0.00 81.59 0.68 1.10 1.00 1.50
303 DL + 0.75LL + 0.75RLL + 0.45W+Z 9.26 159.92 2.20 0.00 0.00 0.00 81.59 0.68 1.10 1.00 1.50
304 DL + 0.75LL + 0.75RLL + 0.45W-Z 9.26 159.92 2.20 0.00 0.00 0.00 81.59 0.68 1.10 1.00 1.50
305 DL + 0.75LL + 0.75RLL + 0.54EQX 4.64 181.98 9.72 0.00 0.00 0.00 92.85 0.78 1.10 1.00 1.50
306 DL + 0.75LL + 0.75RLL - 0.54EQX 13.87 137.86 -5.32 0.00 0.00 0.00 70.34 0.59 1.10 1.00 1.50
307 DL + 0.75LL + 0.75RLL + 0.54EQZ 8.17 126.65 -14.88 0.00 0.00 0.00 64.62 0.54 1.10 1.00 1.50
308 DL + 0.75LL + 0.75RLL - 0.54EQZ 10.34 193.19 19.28 0.00 0.00 0.00 98.57 0.82 1.10 1.00 1.50
309 0.6DL + 0.6W+X 4.73 88.07 1.08 0.00 0.00 0.00 44.93 0.38 1.10 1.00 1.50
310 0.6DL + 0.6W-X 4.73 88.07 1.08 0.00 0.00 0.00 44.93 0.38 1.10 1.00 1.50
311 0.6DL + 0.6W+Z 4.73 88.07 1.08 0.00 0.00 0.00 44.93 0.38 1.10 1.00 1.50
312 0.6DL + 0.6W-Z 4.73 88.07 1.08 0.00 0.00 0.00 44.93 0.38 1.10 1.00 1.50
313 0.6DL + 0.7EQX -1.26 116.66 10.82 0.00 0.00 0.00 59.52 0.50 1.10 1.00 1.50
314 0.6DL - 0.7EQX 10.71 59.47 -8.66 0.00 0.00 0.00 30.34 0.25 1.10 1.00 1.50
315 0.6DL + 0.7EQZ 3.32 44.94 -21.07 0.00 0.00 0.00 22.93 0.19 1.10 1.00 1.50
316 0.6DL - 0.7EQX 6.13 131.19 23.22 0.00 0.00 0.00 66.94 0.56 1.10 1.00 1.50
317 DL + LL + RLL 9.71 164.30 2.33 0.00 0.00 0.00 83.83 0.93 1.10 1.00 1.50
318 DL + LL + 0.6W+X 9.88 158.15 2.44 0.00 0.00 0.00 80.69 0.67 1.10 1.00 1.50
319 DL + LL + 0.6W-X 9.88 158.15 2.44 0.00 0.00 0.00 80.69 0.67 1.10 1.00 1.50
320 DL + LL + 0.6W+Z 9.88 158.15 2.44 0.00 0.00 0.00 80.69 0.67 1.10 1.00 1.50
321 DL + LL + 0.6W-Z 9.88 158.15 2.44 0.00 0.00 0.00 80.69 0.67 1.10 1.00 1.50
322 DL + LL + 0.7EQX 3.90 186.75 12.18 0.00 0.00 0.00 95.28 0.80 1.10 1.00 1.50
323 DL + LL - 0.7EQX 15.87 129.56 -7.31 0.00 0.00 0.00 66.10 0.55 1.10 1.00 1.50
324 DL + LL + 0.7EQZ 8.48 115.02 -19.71 0.00 0.00 0.00 58.69 0.49 1.10 1.00 1.50
325 DL + LL - 0.7EQZ 11.29 201.28 24.58 0.00 0.00 0.00 102.69 0.86 1.10 1.00 1.50
ULTIMATE LOADS
Momen
Moment-X Moment-
LC LC Definition Force-X kN Force-Y kN Force-Z kN t-Y Muz Mux Vu
kNm Z kNm
kNm
101 1.4DL 11.03 205.49 2.52 0.00 0.00 0.00 24.26 24.26 21.33
102 1.2DL + 1.6LL + 0.5RLL 12.58 197.40 3.13 0.00 0.00 0.00 23.31 23.31 20.49
103 1.2DL + 1.6RLL + 0.5LL 10.19 191.66 2.31 0.00 0.00 0.00 22.63 22.63 19.89
104 1.2DL + 1.6RLL + 0.5W+X 9.18 185.98 1.99 0.00 0.00 0.00 21.96 21.96 19.30
105 1.2DL + 1.6RLL + 0.5W-X 9.18 185.98 1.99 0.00 0.00 0.00 21.96 21.96 19.30
106 1.2DL + 1.6RLL + 0.5W+Z 9.18 185.98 1.99 0.00 0.00 0.00 21.96 21.96 19.30
107 1.2DL + 1.6RLL + 0.5W-Z 9.18 185.98 1.99 0.00 0.00 0.00 21.96 21.96 19.30
108 1.2DL + 1.0W+X + 0.5LL + 0.5RLL 10.37 184.90 2.43 0.00 0.00 0.00 21.83 21.83 19.19
109 1.2DL + 1.0W-X + 0.5LL + 0.5RLL 10.37 184.90 2.43 0.00 0.00 0.00 21.83 21.83 19.19
110 1.2DL + 1.0W+Z + 0.5LL + 0.5RLL 10.37 184.90 2.43 0.00 0.00 0.00 21.83 21.83 19.19
111 1.2DL + 1.0W-Z + 0.5LL + 0.5RLL 10.37 184.90 2.43 0.00 0.00 0.00 21.83 21.83 19.19
112 1.2DL + 1.0EQX + 0.5LL 1.91 222.67 16.40 0.00 0.00 0.00 26.29 26.29 23.11
113 1.2DL - 1.0EQX + 0.5LL 19.01 140.97 -11.44 0.00 0.00 0.00 16.65 16.65 14.63
114 1.2DL + 1.0EQZ + 0.5LL 8.45 120.21 -29.16 0.00 0.00 0.00 14.19 14.19 12.48
115 1.2DL - 1.0EQX + 0.5LL 12.47 243.43 34.11 0.00 0.00 0.00 28.74 28.74 25.26
116 0.9DL + 1.0W+X 7.09 132.10 1.62 0.00 0.00 0.00 15.60 15.60 13.71
117 0.9DL + 1.0W-X 7.09 132.10 1.62 0.00 0.00 0.00 15.60 15.60 13.71
118 0.9DL + 1.0W+Z 7.09 132.10 1.62 0.00 0.00 0.00 15.60 15.60 13.71
119 0.9DL + 1.0W-Z 7.09 132.10 1.62 0.00 0.00 0.00 15.60 15.60 13.71
120 0.9DL + 1.0EQX -1.46 172.95 15.54 0.00 0.00 0.00 20.42 20.42 17.95
121 0.9DL - 1.0EQX 15.64 91.25 -12.30 0.00 0.00 0.00 10.78 10.78 9.47
122 0.9DL + 1.0EQZ 5.09 70.49 -30.02 0.00 0.00 0.00 8.32 8.32 7.32
123 0.9DL - 1.0EQZ 9.10 193.71 33.25 0.00 0.00 0.00 22.87 22.87 20.10

LC LC Definition Force-Y kN Dowels n Dowels


101 1.4DL 205.49 Not Required -
102 1.2DL + 1.6LL + 0.5RLL 197.40 Not Required -
103 1.2DL + 1.6RLL + 0.5LL 191.66 Not Required -
104 1.2DL + 1.6RLL + 0.5W+X 185.98 Not Required -
105 1.2DL + 1.6RLL + 0.5W-X 185.98 Not Required - No Dowels Required
106 1.2DL + 1.6RLL + 0.5W+Z 185.98 Not Required -
107 1.2DL + 1.6RLL + 0.5W-Z 185.98 Not Required -
108 1.2DL + 1.0W+X + 0.5LL + 0.5RLL 184.90 Not Required -
109 1.2DL + 1.0W-X + 0.5LL + 0.5RLL 184.90 Not Required - 200
110 1.2DL + 1.0W+Z + 0.5LL + 0.5RLL 184.90 Not Required -
111 1.2DL + 1.0W-Z + 0.5LL + 0.5RLL 184.90 Not Required -
112 1.2DL + 1.0EQX + 0.5LL 222.67 Not Required -
113 1.2DL - 1.0EQX + 0.5LL 140.97 Not Required -
114 1.2DL + 1.0EQZ + 0.5LL 120.21 Not Required -
115 1.2DL - 1.0EQX + 0.5LL 243.43 Not Required -
116 0.9DL + 1.0W+X 132.10 Not Required -
117 0.9DL + 1.0W-X 132.10 Not Required -
118 0.9DL + 1.0W+Z 132.10 Not Required -
119 0.9DL + 1.0W-Z 132.10 Not Required -
120 0.9DL + 1.0EQX 172.95 Not Required -
121 0.9DL - 1.0EQX 91.25 Not Required -
122 0.9DL + 1.0EQZ 70.49 Not Required -
123 0.9DL - 1.0EQZ 193.71 Not Required -
Footing Mark: F4 Date: April 12, 2019
Project Name: PROPOSED 2-STOREY RESIDENTIAL HOUSE Designed by: KARL ANTHONY TAN
Judgement : PASSED

hp
Lpz Lz
D
6 Pcs. Of 16 mm. bar
Lpx dia. Bothways
hf

Lx y

z x

Foundation Property Material Property


Lx = 1600 mm. hf = 300 mm. fc' = 20.7 Mpa. ϒwater = 10 kN/m3
Lz = 1600 mm. Df = 1200 mm. fy = 414 Mpa. μ= 0.5 (Soil to Concrete)
Lpx = 250 mm. hp = 900 mm. ϒsoil = 18 kN/m3 db = 16 mm
Lpz = 250 mm. cc = 75 mm. ϒconc. = 24 kN/m3

Net Soil Bearing Capacity


qall = 90 kPa. (Long Term) qall = 119.7 kPa. (Short Term)

Minimum Thickness: 300 mm Factor of Safety: Location of G.W.L.


Maximum Spacing: 300 mm Overturning = 1 3,000 mm.
Minimum Dimension: 700 mm Sliding = 1.5 Column Location
Buoyancy = 1.1 Corner

SERVICE LOAD COMBINATIONS

MY
LC LC Definition Force-X kN Force-Y kN Force-Z kN MX kNm MZ kNm qu (kPa) Soil Stress BUOY. OM Sliding
kNm

301 DL + 0.75LL + 0.75RLL + 0.45W+X -1.31 196.52 4.03 0.00 0.00 0.00 76.76 0.64 1.10 1.00 1.50
302 DL + 0.75LL + 0.75RLL + 0.45W-X -1.31 196.52 4.03 0.00 0.00 0.00 76.76 0.64 1.10 1.00 1.50
303 DL + 0.75LL + 0.75RLL + 0.45W+Z -1.31 196.52 4.03 0.00 0.00 0.00 76.76 0.64 1.10 1.00 1.50
304 DL + 0.75LL + 0.75RLL + 0.45W-Z -1.31 196.52 4.03 0.00 0.00 0.00 76.76 0.64 1.10 1.00 1.50
305 DL + 0.75LL + 0.75RLL + 0.54EQX -11.62 192.46 1.34 0.00 0.00 0.00 75.18 0.63 1.10 1.00 1.50
306 DL + 0.75LL + 0.75RLL - 0.54EQX 8.99 200.58 6.73 0.00 0.00 0.00 78.35 0.65 1.10 1.00 1.50
307 DL + 0.75LL + 0.75RLL + 0.54EQZ -5.14 193.80 -16.25 0.00 0.00 0.00 75.70 0.63 1.10 1.00 1.50
308 DL + 0.75LL + 0.75RLL - 0.54EQZ 2.51 199.24 24.32 0.00 0.00 0.00 77.83 0.65 1.10 1.00 1.50
309 0.6DL + 0.6W+X -0.48 103.04 2.32 0.00 0.00 0.00 40.25 0.34 1.10 1.00 1.50
310 0.6DL + 0.6W-X -0.48 103.04 2.32 0.00 0.00 0.00 40.25 0.34 1.10 1.00 1.50
311 0.6DL + 0.6W+Z -0.48 103.04 2.32 0.00 0.00 0.00 40.25 0.34 1.10 1.00 1.50
312 0.6DL + 0.6W-Z -0.48 103.04 2.32 0.00 0.00 0.00 40.25 0.34 1.10 1.00 1.50
313 0.6DL + 0.7EQX -13.84 97.78 -1.17 0.00 0.00 0.00 38.20 0.32 1.10 1.00 1.50
314 0.6DL - 0.7EQX 12.88 108.30 5.81 0.00 0.00 0.00 42.31 0.35 1.10 1.00 1.50
315 0.6DL + 0.7EQZ -5.44 99.51 -23.98 0.00 0.00 0.00 38.87 0.32 1.10 1.00 1.50
316 0.6DL - 0.7EQX 4.48 106.57 28.61 0.00 0.00 0.00 41.63 0.35 1.10 1.00 1.50
317 DL + LL + RLL -1.48 204.78 4.09 0.00 0.00 0.00 79.99 0.89 1.10 1.00 1.50
318 DL + LL + 0.6W+X -1.45 189.38 4.04 0.00 0.00 0.00 73.98 0.62 1.10 1.00 1.50
319 DL + LL + 0.6W-X -1.45 189.38 4.04 0.00 0.00 0.00 73.98 0.62 1.10 1.00 1.50
320 DL + LL + 0.6W+Z -1.45 189.38 4.04 0.00 0.00 0.00 73.98 0.62 1.10 1.00 1.50
321 DL + LL + 0.6W-Z -1.45 189.38 4.04 0.00 0.00 0.00 73.98 0.62 1.10 1.00 1.50
322 DL + LL + 0.7EQX -14.81 184.12 0.55 0.00 0.00 0.00 71.92 0.60 1.10 1.00 1.50
323 DL + LL - 0.7EQX 11.90 194.64 7.52 0.00 0.00 0.00 76.03 0.64 1.10 1.00 1.50
324 DL + LL + 0.7EQZ -6.41 185.85 -22.26 0.00 0.00 0.00 72.60 0.61 1.10 1.00 1.50
325 DL + LL - 0.7EQZ 3.50 192.91 30.33 0.00 0.00 0.00 75.36 0.63 1.10 1.00 1.50
ULTIMATE LOADS
Momen
Moment-X Moment-
LC LC Definition Force-X kN Force-Y kN Force-Z kN t-Y Muz Mux Vu
kNm Z kNm
kNm
101 1.4DL -1.12 240.43 5.41 0.00 0.00 0.00 34.23 34.23 19.10
102 1.2DL + 1.6LL + 0.5RLL -2.02 242.01 4.94 0.00 0.00 0.00 34.46 34.46 19.23
103 1.2DL + 1.6RLL + 0.5LL -1.34 239.54 4.81 0.00 0.00 0.00 34.11 34.11 19.03
104 1.2DL + 1.6RLL + 0.5W+X -1.01 230.72 4.73 0.00 0.00 0.00 32.85 32.85 18.33
105 1.2DL + 1.6RLL + 0.5W-X -1.01 230.72 4.73 0.00 0.00 0.00 32.85 32.85 18.33
106 1.2DL + 1.6RLL + 0.5W+Z -1.01 230.72 4.73 0.00 0.00 0.00 32.85 32.85 18.33
107 1.2DL + 1.6RLL + 0.5W-Z -1.01 230.72 4.73 0.00 0.00 0.00 32.85 32.85 18.33
108 1.2DL + 1.0W+X + 0.5LL + 0.5RLL -1.30 222.61 4.75 0.00 0.00 0.00 31.70 31.70 17.69
109 1.2DL + 1.0W-X + 0.5LL + 0.5RLL -1.30 222.61 4.75 0.00 0.00 0.00 31.70 31.70 17.69
110 1.2DL + 1.0W+Z + 0.5LL + 0.5RLL -1.30 222.61 4.75 0.00 0.00 0.00 31.70 31.70 17.69
111 1.2DL + 1.0W-Z + 0.5LL + 0.5RLL -1.30 222.61 4.75 0.00 0.00 0.00 31.70 31.70 17.69
112 1.2DL + 1.0EQX + 0.5LL -20.37 207.39 -0.26 0.00 0.00 0.00 29.53 29.53 16.48
113 1.2DL - 1.0EQX + 0.5LL 17.79 222.42 9.71 0.00 0.00 0.00 31.67 31.67 17.67
114 1.2DL + 1.0EQZ + 0.5LL -8.37 209.87 -32.84 0.00 0.00 0.00 29.88 29.88 16.67
115 1.2DL - 1.0EQX + 0.5LL 5.80 219.95 42.29 0.00 0.00 0.00 31.32 31.32 17.48
116 0.9DL + 1.0W+X -0.72 154.56 3.48 0.00 0.00 0.00 22.01 22.01 12.28
117 0.9DL + 1.0W-X -0.72 154.56 3.48 0.00 0.00 0.00 22.01 22.01 12.28
118 0.9DL + 1.0W+Z -0.72 154.56 3.48 0.00 0.00 0.00 22.01 22.01 12.28
119 0.9DL + 1.0W-Z -0.72 154.56 3.48 0.00 0.00 0.00 22.01 22.01 12.28
120 0.9DL + 1.0EQX -19.80 147.05 -1.51 0.00 0.00 0.00 20.94 20.94 11.68
121 0.9DL - 1.0EQX 18.36 162.08 8.46 0.00 0.00 0.00 23.08 23.08 12.88
122 0.9DL + 1.0EQZ -7.80 149.52 -34.09 0.00 0.00 0.00 21.29 21.29 11.88
123 0.9DL - 1.0EQZ 6.36 159.61 41.04 0.00 0.00 0.00 22.73 22.73 12.68

LC LC Definition Force-Y kN Dowels n Dowels


101 1.4DL 240.43 Not Required -
102 1.2DL + 1.6LL + 0.5RLL 242.01 Not Required -
103 1.2DL + 1.6RLL + 0.5LL 239.54 Not Required -
104 1.2DL + 1.6RLL + 0.5W+X 230.72 Not Required -
105 1.2DL + 1.6RLL + 0.5W-X 230.72 Not Required - No Dowels Required
106 1.2DL + 1.6RLL + 0.5W+Z 230.72 Not Required -
107 1.2DL + 1.6RLL + 0.5W-Z 230.72 Not Required -
108 1.2DL + 1.0W+X + 0.5LL + 0.5RLL 222.61 Not Required -
109 1.2DL + 1.0W-X + 0.5LL + 0.5RLL 222.61 Not Required - 100
110 1.2DL + 1.0W+Z + 0.5LL + 0.5RLL 222.61 Not Required -
111 1.2DL + 1.0W-Z + 0.5LL + 0.5RLL 222.61 Not Required -
112 1.2DL + 1.0EQX + 0.5LL 207.39 Not Required -
113 1.2DL - 1.0EQX + 0.5LL 222.42 Not Required -
114 1.2DL + 1.0EQZ + 0.5LL 209.87 Not Required -
115 1.2DL - 1.0EQX + 0.5LL 219.95 Not Required -
116 0.9DL + 1.0W+X 154.56 Not Required -
117 0.9DL + 1.0W-X 154.56 Not Required -
118 0.9DL + 1.0W+Z 154.56 Not Required -
119 0.9DL + 1.0W-Z 154.56 Not Required -
120 0.9DL + 1.0EQX 147.05 Not Required -
121 0.9DL - 1.0EQX 162.08 Not Required -
122 0.9DL + 1.0EQZ 149.52 Not Required -
123 0.9DL - 1.0EQZ 159.61 Not Required -
Footing Mark: F5 Date: April 12, 2019
Project Name: PROPOSED 2-STOREY RESIDENTIAL HOUSE Designed by: KARL ANTHONY TAN
Judgement : PASSED

hp
Lpz Lz
D
7 Pcs. Of 16 mm. bar
Lpx dia. Bothways
hf

Lx y

z x

Foundation Property Material Property


Lx = 2000 mm. hf = 300 mm. fc' = 20.7 Mpa. ϒwater = 10 kN/m3
Lz = 2000 mm. Df = 1200 mm. fy = 414 Mpa. μ= 0.5 (Soil to Concrete)
Lpx = 250 mm. hp = 900 mm. ϒsoil = 18 kN/m3 db = 16 mm
Lpz = 250 mm. cc = 75 mm. ϒconc. = 24 kN/m3

Net Soil Bearing Capacity


qall = 90 kPa. (Long Term) qall = 119.7 kPa. (Short Term)

Minimum Thickness: 300 mm Factor of Safety: Location of G.W.L.


Maximum Spacing: 300 mm Overturning = 1 3,000 mm.
Minimum Dimension: 700 mm Sliding = 1.5 Column Location
Buoyancy = 1.1 Corner

SERVICE LOAD COMBINATIONS

MY
LC LC Definition Force-X kN Force-Y kN Force-Z kN MX kNm MZ kNm qu (kPa) Soil Stress BUOY. OM Sliding
kNm

301 DL + 0.75LL + 0.75RLL + 0.45W+X -14.76 317.06 -10.67 0.00 0.00 0.00 79.26 0.66 1.10 1.00 1.50
302 DL + 0.75LL + 0.75RLL + 0.45W-X -14.76 317.06 -10.67 0.00 0.00 0.00 79.26 0.66 1.10 1.00 1.50
303 DL + 0.75LL + 0.75RLL + 0.45W+Z -14.76 317.06 -10.67 0.00 0.00 0.00 79.26 0.66 1.10 1.00 1.50
304 DL + 0.75LL + 0.75RLL + 0.45W-Z -14.76 317.06 -10.67 0.00 0.00 0.00 79.26 0.66 1.10 1.00 1.50
305 DL + 0.75LL + 0.75RLL + 0.54EQX -21.60 325.07 -12.05 0.00 0.00 0.00 81.27 0.68 1.10 1.00 1.50
306 DL + 0.75LL + 0.75RLL - 0.54EQX -7.91 309.05 -9.28 0.00 0.00 0.00 77.26 0.65 1.10 1.00 1.50
307 DL + 0.75LL + 0.75RLL + 0.54EQZ -18.78 335.09 -15.60 0.00 0.00 0.00 83.77 0.70 1.10 1.00 1.50
308 DL + 0.75LL + 0.75RLL - 0.54EQZ -10.73 299.03 -5.74 0.00 0.00 0.00 74.76 0.62 1.10 1.00 1.50
309 0.6DL + 0.6W+X -7.65 174.03 -6.15 0.00 0.00 0.00 43.51 0.36 1.10 1.00 1.50
310 0.6DL + 0.6W-X -7.65 174.03 -6.15 0.00 0.00 0.00 43.51 0.36 1.10 1.00 1.50
311 0.6DL + 0.6W+Z -7.65 174.03 -6.15 0.00 0.00 0.00 43.51 0.36 1.10 1.00 1.50
312 0.6DL + 0.6W-Z -7.65 174.03 -6.15 0.00 0.00 0.00 43.51 0.36 1.10 1.00 1.50
313 0.6DL + 0.7EQX -16.52 184.41 -7.95 0.00 0.00 0.00 46.10 0.39 1.10 1.00 1.50
314 0.6DL - 0.7EQX 1.22 163.64 -4.36 0.00 0.00 0.00 40.91 0.34 1.10 1.00 1.50
315 0.6DL + 0.7EQZ -12.87 197.40 -12.54 0.00 0.00 0.00 49.35 0.41 1.10 1.00 1.50
316 0.6DL - 0.7EQX -2.44 150.66 0.24 0.00 0.00 0.00 37.66 0.31 1.10 1.00 1.50
317 DL + LL + RLL -15.43 326.06 -10.81 0.00 0.00 0.00 81.52 0.91 1.10 1.00 1.50
318 DL + LL + 0.6W+X -15.64 315.93 -10.72 0.00 0.00 0.00 78.98 0.66 1.10 1.00 1.50
319 DL + LL + 0.6W-X -15.64 315.93 -10.72 0.00 0.00 0.00 78.98 0.66 1.10 1.00 1.50
320 DL + LL + 0.6W+Z -15.64 315.93 -10.72 0.00 0.00 0.00 78.98 0.66 1.10 1.00 1.50
321 DL + LL + 0.6W-Z -15.64 315.93 -10.72 0.00 0.00 0.00 78.98 0.66 1.10 1.00 1.50
322 DL + LL + 0.7EQX -24.51 326.32 -12.52 0.00 0.00 0.00 81.58 0.68 1.10 1.00 1.50
323 DL + LL - 0.7EQX -6.77 305.55 -8.93 0.00 0.00 0.00 76.39 0.64 1.10 1.00 1.50
324 DL + LL + 0.7EQZ -20.85 339.30 -17.11 0.00 0.00 0.00 84.83 0.71 1.10 1.00 1.50
325 DL + LL - 0.7EQZ -10.42 292.56 -4.33 0.00 0.00 0.00 73.14 0.61 1.10 1.00 1.50
ULTIMATE LOADS
Momen
Moment-X Moment-
LC LC Definition Force-X kN Force-Y kN Force-Z kN t-Y Muz Mux Vu
kNm Z kNm
kNm
101 1.4DL -17.85 406.06 -14.36 0.00 0.00 0.00 77.72 77.72 20.65
102 1.2DL + 1.6LL + 0.5RLL -19.81 394.54 -13.09 0.00 0.00 0.00 75.52 75.52 20.06
103 1.2DL + 1.6RLL + 0.5LL -16.40 377.21 -12.67 0.00 0.00 0.00 72.20 72.20 19.18
104 1.2DL + 1.6RLL + 0.5W+X -14.96 364.26 -12.44 0.00 0.00 0.00 69.72 69.72 18.52
105 1.2DL + 1.6RLL + 0.5W-X -14.96 364.26 -12.44 0.00 0.00 0.00 69.72 69.72 18.52
106 1.2DL + 1.6RLL + 0.5W+Z -14.96 364.26 -12.44 0.00 0.00 0.00 69.72 69.72 18.52
107 1.2DL + 1.6RLL + 0.5W-Z -14.96 364.26 -12.44 0.00 0.00 0.00 69.72 69.72 18.52
108 1.2DL + 1.0W+X + 0.5LL + 0.5RLL -16.64 366.06 -12.58 0.00 0.00 0.00 70.07 70.07 18.61
109 1.2DL + 1.0W-X + 0.5LL + 0.5RLL -16.64 366.06 -12.58 0.00 0.00 0.00 70.07 70.07 18.61
110 1.2DL + 1.0W+Z + 0.5LL + 0.5RLL -16.64 366.06 -12.58 0.00 0.00 0.00 70.07 70.07 18.61
111 1.2DL + 1.0W-Z + 0.5LL + 0.5RLL -16.64 366.06 -12.58 0.00 0.00 0.00 70.07 70.07 18.61
112 1.2DL + 1.0EQX + 0.5LL -29.42 375.84 -15.10 0.00 0.00 0.00 71.94 71.94 19.11
113 1.2DL - 1.0EQX + 0.5LL -4.07 346.16 -9.98 0.00 0.00 0.00 66.26 66.26 17.60
114 1.2DL + 1.0EQZ + 0.5LL -24.20 394.38 -21.67 0.00 0.00 0.00 75.49 75.49 20.05
115 1.2DL - 1.0EQX + 0.5LL -9.29 327.61 -3.41 0.00 0.00 0.00 62.71 62.71 16.66
116 0.9DL + 1.0W+X -11.48 261.04 -9.23 0.00 0.00 0.00 49.96 49.96 13.27
117 0.9DL + 1.0W-X -11.48 261.04 -9.23 0.00 0.00 0.00 49.96 49.96 13.27
118 0.9DL + 1.0W+Z -11.48 261.04 -9.23 0.00 0.00 0.00 49.96 49.96 13.27
119 0.9DL + 1.0W-Z -11.48 261.04 -9.23 0.00 0.00 0.00 49.96 49.96 13.27
120 0.9DL + 1.0EQX -24.15 275.88 -11.79 0.00 0.00 0.00 52.81 52.81 14.03
121 0.9DL - 1.0EQX 1.20 246.20 -6.67 0.00 0.00 0.00 47.12 47.12 12.52
122 0.9DL + 1.0EQZ -18.93 294.43 -18.36 0.00 0.00 0.00 56.36 56.36 14.97
123 0.9DL - 1.0EQZ -4.03 227.65 -0.10 0.00 0.00 0.00 43.57 43.57 11.58

LC LC Definition Force-Y kN Dowels n Dowels


101 1.4DL 406.06 Not Required -
102 1.2DL + 1.6LL + 0.5RLL 394.54 Not Required -
103 1.2DL + 1.6RLL + 0.5LL 377.21 Not Required -
104 1.2DL + 1.6RLL + 0.5W+X 364.26 Not Required -
105 1.2DL + 1.6RLL + 0.5W-X 364.26 Not Required - No Dowels Required
106 1.2DL + 1.6RLL + 0.5W+Z 364.26 Not Required -
107 1.2DL + 1.6RLL + 0.5W-Z 364.26 Not Required - No hooks Required
108 1.2DL + 1.0W+X + 0.5LL + 0.5RLL 366.06 Not Required -
109 1.2DL + 1.0W-X + 0.5LL + 0.5RLL 366.06 Not Required -
110 1.2DL + 1.0W+Z + 0.5LL + 0.5RLL 366.06 Not Required -
111 1.2DL + 1.0W-Z + 0.5LL + 0.5RLL 366.06 Not Required -
112 1.2DL + 1.0EQX + 0.5LL 375.84 Not Required -
113 1.2DL - 1.0EQX + 0.5LL 346.16 Not Required -
114 1.2DL + 1.0EQZ + 0.5LL 394.38 Not Required -
115 1.2DL - 1.0EQX + 0.5LL 327.61 Not Required -
116 0.9DL + 1.0W+X 261.04 Not Required -
117 0.9DL + 1.0W-X 261.04 Not Required -
118 0.9DL + 1.0W+Z 261.04 Not Required -
119 0.9DL + 1.0W-Z 261.04 Not Required -
120 0.9DL + 1.0EQX 275.88 Not Required -
121 0.9DL - 1.0EQX 246.20 Not Required -
122 0.9DL + 1.0EQZ 294.43 Not Required -
123 0.9DL - 1.0EQZ 227.65 Not Required -

You might also like