Names and Functions of Parts : User's Manual

This document provides instructions for operating an AT02 Series PID temperature controller. It describes the parts of the controller including displays for process value (PV) and set value (SV), and status indicator lights. It also summarizes how to set the input type, control mode, and user level using the DIP switches and buttons. Safety precautions are noted on the reverse side.

Uploaded by

SHAM
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
411 views2 pages

Names and Functions of Parts : User's Manual

This document provides instructions for operating an AT02 Series PID temperature controller. It describes the parts of the controller including displays for process value (PV) and set value (SV), and status indicator lights. It also summarizes how to set the input type, control mode, and user level using the DIP switches and buttons. Safety precautions are noted on the reverse side.

Uploaded by

SHAM
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

AT02 SERIES PID *Names and Functions of Parts*

TEMPERATURE CONTROLLER
User's Manual
RESTRICTIONS ON USE
When using this product in applications
AT-502 Upper Display
Displays PV values (current
that require particular safety or when LEDs o
PV C temperature, etc.) or setup
using this product in important facilities, AT: Lit when the auto items.
please pay attention to the safety of the tuning is ON.
overall system and equipment. Install fail- OUT: Lit when the control
safe mechanisms, perform redundancy output is ON. SV Lower Display
checks and periodic inspections and ALM: Lit when the alarm
Displays SV values (set
adopt other appropriate safety measures output is ON.
AT OUT ALM LOCK temperature, etc.) and
when it is necessary. This product is rated LOCK: Lit when the key other parameter values.
at Class Ⅱ . Serviced by trained and is locked.
skilled personnel only. SET Key :
Used to change numeric
ATTENTION ! values.
1.Please read the SAFETY PRECAUTION SET Key :
section on reverse side before use of Switches the display. Hold
this product. down for 3 seconds to
Key :
switch modes. Used to shift setup items or
2.Please read this user's manual before parameter digits.
use for proper operation.
3.Please safe guard this user's manual.

*Function Setting* *User Level Setting* *PID Control Setting*


Warning! Please make sure the power is off, before 1 Set the DIP switch to PID Control before proceeding.
making any changes on the DIP switch. Power ON
o
ON
PV C
DIP Switch All displays are
1 2 3 4 5 6 1 2 3 4 5 6 lit for 3 seconds. SV
1 Start with
K Type 0~1200 C O
ON OFF OFF AT OUT ALM LOCK Operation Mode. PV
o
C Current PV value
J Type 0~500 C
O
ON ON OFF
Input type 2 The IC version SV Current SV value
R Type 0~1700 C O
ON OFF ON
is displayed for PV
o
C tic AT OUT ALM LOCK
PT-100 -50~400 C OFF ON ON
O

about 6 seconds.
ON/OFF CONTROL OFF SV IC version 2 Press SET key for
Control Mode
PID CONTROL ON AT OUT ALM LOCK 3 seconds to PV
o
C LVL
RELAY OFF enter Parameter
Output Mode. SV uSr
DC 24V (for SSR) ON 3 Operation Mode
is displayed. PV
o
C Current PV value AT OUT ALM LOCK

Function NONE OFF


Lock ALL EXCEPT SV ON SV Current SV value 3 Press key
List of Alarm Function : AT OUT ALM LOCK once and key PV
o
C LVL
SV+AS1
once to enter Pid
Level. Pid
1 Deviation High Alarm OFF
SV
ON
PV
4 Press SET key
AS1:
SV

once to setup PV
o
C Alarm Setting AT OUT ALM LOCK
SV+AS1 Alarm Setting.
2 Deviation Low Alarm ON
SV
OFF
PV SV 200.0~200.0 C O

4 Press SET key for


P1:
AT OUT ALM LOCK 3 seconds to PV
o
C Proportional Band (P)
3 Process High Alarm OFF
AS1
ON
PV
setup Proportional
Band. SV 0.1~300.0 C O

5 Press SET key


At:
once to setup o

4 Process Low Alarm ON


AS1
OFF
PV
Auto Tunning.
PV C Auto Tunning AT OUT ALM LOCK

SV-AS1 SV+AS1
SV YES / no 5 Press SET key
5 Deviation High/Low Alarm ON OFF ON
i1:
SV
PV AT OUT ALM LOCK once to setup PV
o
C Integral Time (I)
Integral Time.
SV-AS1 SV+AS1
6 Band Alarm OFF ON OFF 6 Press SET key SV 0~7200sec
SV
PV PoF: (Set 0 for P Control)
once to setup PV PV
o
C PV Offset AT OUT ALM LOCK

7 Deviation High Alarm (Standby) Offset.


O

8 Deviation Low Alarm (Standby) SV -200.0~200.0 C 6 Press SET key


d1:
once to setup o

9 Process High Alarm (Standby) AT OUT ALM LOCK

Derivative Time.
PV C Derivative Time (D)

10 Process Low Alarm (Standby)


7 Press SET key SV 0~1800sec
11 Deviation High/Low Alarm (Standby) once to setup SV PV
o
C
SoF:
SV Offset AT OUT ALM LOCK
(Set 0 for P Control)

12 Band Alarm (Standby) Offset.


O
SV -200.0~200.0 C 7 Press SET key
*Key Lock Setting* AT OUT ALM LOCK once to setup PV
o
C
Ct1:
Relay Cycle Time
Relay Cycle Time.
Under User Level, press key
8 Press SET key SV 0~65sec
PV
o
C for 3 second to enter Key Lock
Mode. once to return to PV
o
C Current PV value AT OUT ALM LOCK

Operation Mode.
SV Set Lock Number according to
the level of protection. SV Current SV value 8 Press SET key
AT OUT ALM LOCK Ct2:
AT OUT ALM LOCK once to setup PV
o
C SSR Cycle Time
SSR Cycle Time.
List of Key Lock Mode :
usr Pid SEt ArG
*SV Lock Setting* SV 0~65sec
AT OUT ALM LOCK

Others ○ × × × PV
o
C
Under Operation Mode, press
+ key for 1 seconds to
9 Press
× ×
SET key
0022 ○ ○ lock the SV value.
once to setup o
PV C Fuzzy
SV And press key for 1 seconds
0 111 ○ ○ ○ × AT OUT ALM LOCK
again to unlock the SV value.
Fuzzy.
SV On/OFF
11 2 2 ○ ○ ○ ○ AT OUT ALM LOCK

Symbol-○: Can display and can be set


× : Can't display nor can't be set 10 Press key for 3 seconds to return to Operation Mode.
*ON/OFF Control Setting* *Set Level Setting* 10 Press SET key
FiLt:
once to setup PV
o
C Filter value
Set the DIP switch to ON/OFF Control before proceeding. 1 Start with Filter.
Operation Mode. PV
o
C Current PV value SV 0~120sec
AT OUT ALM LOCK
1 Start with SV Current SV value
Operation Mode. PV
o
C Current PV value AT OUT ALM LOCK
11 Press key for 3 seconds to return to Operation Mode.
SV Current SV value 2 Press key for
SET
3 seconds to
*Argument Level Setting*
o
AT OUT ALM LOCK PV C LVL
enter Parameter
Mode. uSr
2 Press key for
SET SV
This is used to display or hide arguments under user
3 seconds to o
C
level. Arguments can be arranged in any order, but may
PV LVL AT OUT ALM LOCK

enter Parameter not repeated.


Mode. SV uSr 3 Press key 1 Start with
AT OUT ALM LOCK once and key PV
o
C LVL Operation Mode. PV
o
C Current PV value
twice to enter
SEt Level. SV SEt SV Current SV value
3 Press key
once and key PV
o
C LVL AT OUT ALM LOCK AT OUT ALM LOCK

once to enter
Pid Level. SV Pid 4 Press SET key for 2 Press SET key for
AF1:
AT OUT ALM LOCK 3 seconds to PV
o
C Alarm Function 3 seconds to PV
o
C LVL
setup Alarm enter Parameter
Function. SV 1~12 Mode. SV uSr
4 Press SET key for
HSt: See List of
3 seconds to PV
o
C Hysteresis AT OUT ALM LOCK AT OUT ALM LOCK
Alarm Function
setup Hysteresis.
O
SV 0.0~200.0 C 5 Press SET key 3 Press key
AH1:
AT OUT ALM LOCK once to setup PV
o
C Alarm Hysteresis
once and key PV
o
C LVL
Alarm Hysteresis. three times to
SV -200.0~200.0 C O enter ArG Level. SV ArG
5 Press key for 3 seconds to return to Operation Mode.
AT OUT ALM LOCK AT OUT ALM LOCK

6 Press SET key 4 Press SET key for


Act:
once to setup 3 seconds to
*SV Value Setting*
o o
PV C Control Action PV C 1-2
Control Action. setup 1-2.
1 Start with SV Hearting / Cooling SV select 1: non,
Operation Mode. o
AS1, At, PoF,
PV C Current PV value AT OUT ALM LOCK AT OUT ALM LOCK
SoF

SV Current SV value 7 Press SET key 5 Press SET key


dP:
AT OUT ALM LOCK once to setup PV
o
C Decimal Point once to setup PV
o
C 1-3
Decimal Point. 1-3.
2 Press key SV 0 / 0.0 SV select 1: non,
once to setup SV. o
AS1, At, PoF,
PV C Current PV value AT OUT ALM LOCK AT OUT ALM LOCK
SoF

SV Current SV value 8 Press SET key 6 Press SET key


LSP:
AT OUT ALM LOCK once to setup PV
o
C Low Set Point
once to setup PV
o
C 1-4
Low Set Point. 1-4.
3 Press SV Temperature range SV select 1: non,
key to change o varies with Input AS1, At, PoF,
PV C Current PV value AT OUT ALM LOCK AT OUT ALM LOCK
SoF
value and press type
key to SV Current SV value 9 Press SET key 7 Press SET key
move the cursor. HSP:
AT OUT ALM LOCK once to setup PV
o
C High Set Point
once to setup PV
o
C 1-5
High Set Point. 1-5.
4 Press key once to return to Operation Mode. SV Temperature range SV select 1: non,
varies with Input AS1, At, PoF,
AT OUT ALM LOCK AT OUT ALM LOCK
type SoF

8 Press key for 3 seconds to return to Operation Mode.

*TERMINAL LAYOUT * *DIMENSIONS(mm)*


AT-502 AT-402 / 602 / 902
A a AT02 series A B a b

AT-402 48 96 45.5 +0.5


-0 91 +0.5
-0
100~240V
50/60 Hz

12 11 1 11
AC/DC

AT-502 48 48 45.5 +0.5 45.5 +0.5


100~240V

-0 -0
50/60 Hz

1 6
AC/DC

2 12
B b Panel Cutout
ALM

2 7
COM
NO
3 13
Device AT-602 96 48 91 +0.5
-0 45.5 +0.5
-0
SSR

NO
3 8 +0.5
A
AT-702 72 72 67.5 67.5 +0.5
OUT

COM 4 14 -0 -0
NC
OUT

4 9 B +0.5
NC 5 15 AT-902 96 96 91 -0 91 +0.5
-0
5 10 B
6 16
ALM

14 13
7 17

SSR A 8 18 *SAFETY PRECAUTION*


B 9 19 This manual uses the following symbols to ensure safe operation of this controller.
AT-702 B 10 20 WARNING Warnings are indicated when mishandling this controller might result in death or serious injury to user.
CAUTION Cautions are indicated when mishandling this controller might result in minor injury to the user, or only
physical damage to the controller.
100~240V
50/60 Hz

1 8 A
AC/DC

WARNING
2 9 B
Note this incorrect wiring of this controller can damage it and lead to other hazards. Make sure the controller has been
NO
3 10 B correctly wired before turning the power ON.
COM
Before wiring, or removing / mounting the controller, be sure to turn the power OFF. Failure to do so might cause
OUT

4 11 electric shock.
NC

5 12 Do not touch electrically charged parts such as the power terminals. Doing so might cause electric shock.
Do not disassemble the controller. Doing so might cause electric shock or faulty operation.
6 13
ALM

SSR

CAUTION
7 14 Use the controller within the operating ranges recommended in the specification (temperature, humidity, voltage,
shock, mounting direction, atmosphere and etc.). Failure to do so might cause fire or faulty operation.
Do not block ventilation holes. Doing so might cause fire or faulty operation.
Do not allow lead clippings, chips or water to enter the controller case. Doing so might cause fire or faulty operation.

ANLY ELECTRONICS CO., LTD. M-AT02-O-A


http://www.anly.com.tw Printed in Taiwan