Setting PROFIsafe on Siemens PLC with TIA Portal
Commissioning instructions
Setting PROFIsafe on Siemens PLC with TIA Portal
Revisions
Version Date Changes
01 05.2016 First edition
Contact
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 16
32758 Detmold, Germany
T +49 5231 14-0
F +49 5231 14-292083
[email protected]
www.weidmueller.com
xxxxxx0000/01/05.2016 2
Setting PROFIsafe on Siemens PLC with TIA Portal
Contents
1. In s tall th e Weid m ülle r CP D - To o l 4
2. Cre a tin g a n ew pro je c t in S iem e n s TIA-P o rta l 5
3. In te g ratio n o f UR20-4DI-4DO-P N-FS P S a n d 10
UR20-8DI-P N-FS P S o n P ROFINET
3.1 Install a GSDML file
3.2 Add a UR20 safety module to the UR20 IO device
3.3 PROFIsafe parameter settings
4. Exa m p le s of wirin g a nd p a ra m ete r s e ttin g s o f s o m e 20
s a fe ty d e vic e s to u -re m o te
5. In te g ratio n o f UR20-4DI-4DO-P N-FS P S a n d 24
UR20-8DI-P N-FS P S o n P ROFIBUS
5.1 Install a GSD file.
5.2 Add a UR20 safety module to the UR20 DP slave
5.3 P ROFIs a fe p a ram e ter s e ttin g s
xxxxxx0000/01/05.2016 3
Setting PROFIsafe on Siemens PLC with TIA Portal
1. Install the Weidmüller CPD – Tool
Th e We id m ülle r CP D – To o l is a n e m b e d d e d pro g ra m for the c alc u latio n o f th e
c h e c k s u m in S TEP 7 o r TIA P o rta l d e p e n d in g o n th e pa ra m ete r s e t for th e m o d ule
UR20-4DI-4DO-P N-FS PS o r UR20-8DI-P N-FS PS
1) Unzip the file “Setup_xx.zip”
2) Start the program “setup.exe” and wait until the installation is finished
xxxxxx0000/01/05.2016 4
Setting PROFIsafe on Siemens PLC with TIA Portal
2. Creating a new project in Siemens TIA-Portal
Start TIA Portal from the desktop
1) Double click the symbol like this
2) After TIA has opened, switch to the “Portal view” if necessary
xxxxxx0000/01/05.2016 5
Setting PROFIsafe on Siemens PLC with TIA Portal
Create a new project
4.
2.
3.
xxxxxx0000/01/05.2016 6
Setting PROFIsafe on Siemens PLC with TIA Portal
Add new device
xxxxxx0000/01/05.2016 7
Setting PROFIsafe on Siemens PLC with TIA Portal
Choose the CPU
xxxxxx0000/01/05.2016 8
Setting PROFIsafe on Siemens PLC with TIA Portal
Save your Project
xxxxxx0000/01/05.2016 9
Setting PROFIsafe on Siemens PLC with TIA Portal
3. Integration of UR20-4DI-4DO-PN-FSPS and UR20-8DI-
PN-FSPS on PROFINET
Insert a PROFINET net work
1) Expand the tree “PROFINET interface [X2]”
2) Choose the IP address
3) Add new subnet
1 2
xxxxxx0000/01/05.2016 10
Setting PROFIsafe on Siemens PLC with TIA Portal
Advanced PROFINET settings
1) Open/Choose the folder “Net view”
2) Choose and expand Advanced options
3) Make further settings here
2
3
xxxxxx0000/01/05.2016 11
Setting PROFIsafe on Siemens PLC with TIA Portal
Install a GSDML file
1) Open “Options and click “install general station description file (GSD)
2) Open the path and choose the GSDML file to install
3) Push the button “install”. The files will installed
xxxxxx0000/01/05.2016 12
Setting PROFIsafe on Siemens PLC with TIA Portal
Install a GSDML file
1) To reopen the view “Devices & Networks” double click the line
xxxxxx0000/01/05.2016 13
Setting PROFIsafe on Siemens PLC with TIA Portal
Insert UR20 to the PROFINET line.
1) Expand the branch “Other field devices” and place UR20 by drag and drop
xxxxxx0000/01/05.2016 14
Setting PROFIsafe on Siemens PLC with TIA Portal
Further settings for UR20 PROFINET IO device.
1) Double click the symbol of UR20
2) Connect UR20 to the network PROFINET by choosing the subnet
3) Change the name of UR20 to a unique name according to the PROFINET requirements
xxxxxx0000/01/05.2016 15
Setting PROFIsafe on Siemens PLC with TIA Portal
Connect UR20 PN IO device into the PLC PN IO controller system
1) Mark and right mouse click “Not assigned”
2) Select the IO controller
1
2
xxxxxx0000/01/05.2016 16
Setting PROFIsafe on Siemens PLC with TIA Portal
UR20 PN IO device is connected into the PLC PN IO controller system
xxxxxx0000/01/05.2016 17
Setting PROFIsafe on Siemens PLC with TIA Portal
Add a UR20 safety module to the UR20 IO device
1) Change to the folder “Device view”
2) Choose a module e.g. “UR-4DI-4DO-PN-FSPS and place the module by drag and drop
xxxxxx0000/01/05.2016 18
Setting PROFIsafe on Siemens PLC with TIA Portal
PROFIsafe parameter settings
1) Set the Source F-Address (F-CPU)
2) Set the F-Address of the module with the DIP switches
NOTE: Each address change needs first an address set to “0” and power up the
module. Then set the new address and power up the module again.
3) Set the Destination F-Address (I/O Device or DP-Slave e.g UR20)according to the
DIP switches of the module
4) Set the check sum CRC getting from the CPD Tool (see the next page)
1 2
xxxxxx0000/01/05.2016 19
Setting PROFIsafe on Siemens PLC with TIA Portal
4. Examples of wiring and parameter settings of some
safety devices to u-remote
Connecting an emergency STOP button
• Wire the safety light curtain as shown below (e.g. CH2 and CH3)
• For this using the test pulses have to be disabled
Further information you will find in the u-remote safety manual.
xxxxxx0000/01/05.2016 20
Setting PROFIsafe on Siemens PLC with TIA Portal
PROFIsafe parameter settings of the UR20 module
1) The parameter is adjusted to “dual channel”
2) Start the device Tool by mark the module and right mouse click
xxxxxx0000/01/05.2016 21
Setting PROFIsafe on Siemens PLC with TIA Portal
Calculate the check sum
1) Confirm each parameter
2) Click the button “CRC calculate” to get the CRC value
3) Mark and copy the CRC value
4) Close the program
3 4
xxxxxx0000/01/05.2016 22
Setting PROFIsafe on Siemens PLC with TIA Portal
Adjust the CRC value of the UR20 module
1) Click on “PROFIsafe”. It will open the PROFIsafe settings of the module
2) Paste the CRC value into “F_iPar_CRC”
3) Download the configuration into the PLC
1 3
xxxxxx0000/01/05.2016 23
Setting PROFIsafe on Siemens PLC with TIA Portal
5. Integration of UR20-4DI-4DO-PN-FSPS and UR20-8DI-
PN-FSPS on PROFIBUS
Insert a PROFIBUS net work
1) Expand the tree “MPI/DP interface [X1]”
2) Add a new subnet and make further settings for PROFIBUS
xxxxxx0000/01/05.2016 24
Setting PROFIsafe on Siemens PLC with TIA Portal
Install a GSD file
1) Open “Options and click “install general station description file (GSD)
2) Open the path and choose the GSD file to install
3) Push the button “install”. The files will be installed
xxxxxx0000/01/05.2016 25
Setting PROFIsafe on Siemens PLC with TIA Portal
Reopen Devices and networks
1) To reopen the view “Devices & Networks” double click the line
xxxxxx0000/01/05.2016 26
Setting PROFIsafe on Siemens PLC with TIA Portal
Insert UR20 to the PROFIBUS line
1) Expand the branch “Other field devices” and place UR20 by drag and drop
xxxxxx0000/01/05.2016 27
Setting PROFIsafe on Siemens PLC with TIA Portal
Further settings for UR20 PROFIBUS DP slave.
1) Double click the symbol of UR20
2) Connect UR20 to the network PROFINET by choose the subnet
3) Change the DP address of UR20 according to the rotary switches of the UR20
coupler
xxxxxx0000/01/05.2016 28
Setting PROFIsafe on Siemens PLC with TIA Portal
Connect UR20 DP slave into the PLC PROFIBUS system
1) Mark and right mouse click “Not assigned”
2) Select the DP master
1
2
xxxxxx0000/01/05.2016 29
Setting PROFIsafe on Siemens PLC with TIA Portal
UR20 DP slave is connected into the PLC PROFIBUS system
xxxxxx0000/01/05.2016 30