Realistic ambient air
temperature specification
       for ACC’s
       Johannes Pretorius
     ACC user’s group meeting 2012
        Gillette, Wyoming, USA
Overview
• Typical ACC temperature specification
• Trends from Matimba power station
• Measurements at Kendal power station
• Conclusion
• Acknowledgements
• References
2
Typical ACC temperature specification
• Typical South African weather stations
        • Dry bulb ambient air temperature @ 1.2-1.5m AGL
        • Wind speed & direction @ 9-10m AGL
• Green fields / absence of dedicated weather masts in
    area, info from weather bureau used for site weather
    specification
• Cooling systems (wet or dry) specification thus based on
    air temperature near ground level
3
 Matimba power station
• Temperature measurements taken at ACC inlet
• Temperature measurements on 60m high weather mast,
  located 500m away from ACC
  4
    Trends from Matimba
• Interesting trends from Matimba power station
• Weather mast & ACC air inlet temperatures indicate significant discrepancies
• Up to 10 °C difference between ground level and inlet temperature possible
                         45
                         40
                         35
                         30
        Temperature, C
                         25
                         20
                         15
                              ACC inlet temperature
                              Weather mast temperature, 1.2 m AGL          September 2005
                         10
                              Weather mast temperature, 40 m AGL
                                                                           Weathermast located 500 m
                                                                           from ACC
                          5
                          0
                          07 5
                          08 5
                          09 5
                          10 5
                          10 5
                          11 5
                          12 5
                          13 5
                          14 5
                          15 5
                          15 5
                          16 5
                          17 5
                          18 5
                          19 5
                          20 5
                          20 5
                          21 5
                          22 5
                          23 5
                          00 5
                          01 5
                          01 5
                          02 5
                          03 5
                          04 5
                          05 5
                               5
                            :4
                            :3
                            :2
                            :1
                            :0
                            :5
                            :4
                            :3
                            :2
                            :1
                            :0
                            :5
                            :4
                            :3
                            :2
                            :1
                            :0
                            :5
                            :4
                            :3
                            :2
                            :1
                            :0
                            :5
                            :4
                            :3
                            :2
                            :1
                          06
    5
                                                                    Time
Investigation
• Investigate whether similar trends are experienced on
    other sites
• Measurements at Eskom’s Kendal power station
        • Indirect dry cooling system, however from literature similar
          principle should apply
        • Air drawn into cooling system from higher heights than ground
          level
6
  Kendal power station
• 6 x 686 MW coal-fired
• Last Unit commissioned 1988
• Indirect dry cooling system
  7
Measurements at Kendal
K2 monitoring station:               Cooling towers:
• Located 2km SSE of Kendal PS       • Ambient temperature
                                       measured at approx. 25m AGL
• Ambient temperature measured
  at 1.2m AGL
                 Evaporation ponds
 2012/11/06                                                          8
Measurements at Kendal
• Measurements from cooling tower 1
• Measurements from cooling tower 2 for comparison (adjacent)
• Relatively good data available for 2005-2006
                Evaporation ponds
2012/11/06                                                      9
Measurements at Kendal
                                                              Average daily ambient temperatures:
                                                 Measured values at Kendal cooling towers vs. K2 weather station
                                                                         Feb, Apr, Jun 2005
                               35
                                        Cooling tower (Feb)
                                        Cooling tower (Apr)
                                        Cooling tower (Jun)
                               30
                                        K2 station (Feb)
                                        K2 station (Apr)
                                        K2 station (Jun)
Ambient air temperature [°C]
                               25
                               20
                               15
                               10
                               0
                                    0                     5                 10                   15                20
                                                                           Time of day [hours]
2012/11/06                                                                                                              10
        Measurements at Kendal
                                                              Average daily ambient temperatures:
                                                 Measured values at Kendal cooling towers vs. K2 weather station
                                                                         Feb, Apr, Jun 2006
                               35
                                        Cooling tower (Feb)
                                        Cooling tower (Apr)
                                        Cooling tower (Jun)
                               30
                                        K2 station (Feb)
                                        K2 station (Apr)
                                        K2 station (Jun)
Ambient air temperature [°C]
                               25
                               20
                               15
                               10
                               0
                                    0                     5                 10                   15                20
                                                                           Time of day [hours]
            2012/11/06                                                                                                  11
Measurements at Kendal
                                                      Average annual ambient air temperatures:
                                            Measure values at Kendal cooling towers vs. K2 weather station
                                                                       2005-2006
                               23
                               21
Ambient air temperature [°C]
                               19
                               17
                               15
                               13
                                                                                                             Cooling towers (2005)
                                                                                                             Cooling towers (2006)
                               11
                                                                                                             K2 station (2005)
                                                                                                             K2 station (2006)
                               9
                                    1   2     3        4       5        6           7    8        9          10         11           12
                                                                            Month
2012/11/06                                                                                                                           12
    Measurements at Kendal
•    Auxiliary cooling cells between turbine house and CT 2 & 5
•    Nighttime winds from E, SE
•    Potential effect on CT 1 & 2 measurements
•    Evaluate measurements from CT 4 & 5
                        Evaporation ponds
    2012/11/06                                                    13
                Measurements at Kendal
                                                             Average daily ambient temperatures:
                                                   Measured values at Kendal cooling towers - Unit 1&2 vs 4&5
                                                                        Feb, Apr, Jun 2005
                               35
                                        CT 1&2 (Feb)
                                        CT 1&2 (Apr)
                                        CT 1&2 (Jun)
                               30       CT 4&5 (Feb)
                                        CT 4&5 (Apr)
                                        CT 4&5 (Jun)
Ambient air temperature [°C]
                               25
                               20
                               15
                               10
                               0
                                    0                  5                    10                   15             20
                                                                           Time of day [hours]
                    2012/11/06                                                                                       14
Measurements at Kendal
                                                              Average daily ambient temperatures:
                                                    Measured values at Kendal cooling towers - Unit 1&2 vs 4&5
                                                                         Feb, Apr, Jun 2006
                                 35
                                          CT 1&2 (Feb)
                                          CT 1&2 (Apr)
                                          CT 1&2 (Jun)
                                 30
                                          CT 4&5 (Feb)
                                          CT 4&5 (Apr)
                                          CT 4&5 (Jun)
  Ambient air temperature [°C]
                                 25
                                 20
                                 15
                                 10
                                 0
                                      0                  5                   10                   15             20
                                                                            Time of day [hours]
2012/11/06                                                                                                            15
Measurements at Kendal
                                                   Average annual ambient air temperatures:
                                            Measure values at Kendal cooling towers - Unit 1&2 vs 4&5
                                                                    2005-2006
                               23
                                                                                 Anomaly for 2005 due to
                               21                                                 large amount of data
                                                                                     corrupt on unit 4
Ambient air temperature [°C]
                               19
                               17
                               15
                               13
                                                                                                                    CT 1&2 (2005)
                               11                                                                                   CT 1&2 (2006)
                                                                                                                    CT 4&5 (2005)
                                                                                                                    CT 4&5 (2006)
                               9
                                    1   2   3       4        5       6            7           8            9   10       11          12
                                                                         Month
   2012/11/06                                                                                                                       16
Measurements at Kendal – annual average
• Daytime = 06:00 – 21:00
                              Avg. annual        Avg. annual
                            temperature [°C]       daytime
                                               temperature [°C]
      K2                          16.7               19.2
      Cooling towers              17.2               18.1
• Does not seem like major difference
• However, dependent on specific site & plant operating hours
• For Matimba on average, temperature at 1.2m AGL is 4°C too low
  compared to what ACC actually experiences
• Also, e.g. peaking plant running in morning & evening – expected
  annual plant performance will differ significantly from actual
  performance
 17
                  Measurements at Kendal – annual distribution
                               Kendal 2005-2006 data, Ambient air temperature distribution comparison
                                Based on average temperatures measured at Kendal Cooling towers and K2 weather station,
                                                                Normalized for 1 year
                  1200
                                                                                                                   Cooling tower data
                                                                                                                   K2 data
                  1000
                   800
Hours per annum
                   600
                   400
                   200
                                                Evaporation ponds
                     0
                            (-1)-0
                               0-1
                               1-2
                               2-3
                               3-4
                               4-5
                               5-6
                               6-7
                               7-8
                               8-9
                             9-10
                           10-11
                           11-12
                           12-13
                           13-14
                           14-15
                           15-16
                           16-17
                           17-18
                           18-19
                           19-20
                           20-21
                           21-22
                           22-23
                           23-24
                           24-25
                           25-26
                           26-27
                           27-28
                           28-29
                           29-30
                           30-31
                           31-32
                           32-33
                           33-34
                           34-35
                           35-36
                           36-37
                           37-38
                           38-39
                           39-40
                           40-41
                           41-42
                           42-43
                         (-3)-(-2)
                         (-2)-(-1)
                                                                  Ambient air temperature [°C]
                  2012/11/06                                                                                                            18
Measurements at Kendal – implications
• Assume ACC designed according to Kendal K2
  temperature distribution
      • ACC will experience temperatures of air at higher levels, similar to
        those experienced at Kendal cooling towers
• ACC will in actual fact never see freezing conditions
      • ACC design could have done without anti-freezing features
      • More expensive
• ACC will in actual fact see max. ambient temperature
  10°C lower than design
      • Potentially oversized ACC design (depending on specification)
      • More expensive
 19
  Conclusion
• From Matimba & Kendal measurements, dry cooling systems experience
  air inlet temperatures similar to air at higher level instead of near ground
  level
• Important for ACC Purchaser to consider
        • ACC may experience different conditions to those specified in design
          specifications
        • Overall plant performance potentially affected
        • ACC may be more expensive than necessary & include unnecessary
          features
• Purchaser responsible to specify correct ACC design air inlet
  temperature
• Purchaser to develop knowledge
        • Sourcing appropriate data or installing weather mast at intended site
        • Weather mast at site & trending
  20
 Acknowledgement
 The contribution of the following people towards the knowledge of ACC
            operation & design within Eskom is acknowledged
                           Prof DG Kröger
                          Francois du Preez
                       Markus Jonker (Majuba)
                     Hein Goldschagg (Matimba)
Eskom Management for sponsoring the trip and permission to present the
                              paper
 21
      References
•   Du Preez, A. F., 1992, “The influence of cross-winds on the performance of dry-cooling towers,” PhD thesis, University of Stellenbosch,
    Stellenbosch, South Africa.
•   Du Preez, A.F., 2008, “Operational Characteristics of Existing Dry Cooling Systems in Eskom,” EPRI workshop on Advanced Cooling
    Technologies, Charlotte, North Carolina, USA.
•   Du Preez, A. F., 2008, “New coal units and suggestions for further improvement, EPRI Workshop on Advanced Cooling Technologies,”
    Charlotte, North Carolina, USA.
•   Du Preez, A. F., and Pretorius, J. P., 2009, “Specifications for large Air-cooled Condensers – Eskom perspective,” 14th IAHR Cooling tower
    and Air-cooled heat exchanger conference, Stellenbosch, South Africa.
•   Ham, A. J., and West, L. A., 1988, “Eskom’s advance into Dry Cooling,” VGB Kraftwerkstechnik, 68(9), pp. 808-812.
•   Kröger, D. G., 2004, Air-cooled heat exchangers and cooling towers, Pennwell Corp., Tulsa, Oklahoma.
•   Pretorius, J. P., and Du Preez, A. F., 2009, “Eskom cooling technologies,” 14th IAHR Cooling tower and Air-cooled heat exchanger
    conference, Stellenbosch, South Africa.
•   Trage, B., and Hintzen, F. J., 1989, “Design and construction of plants with Indirect Dry Cooling systems,” VGB Kraftwerkstechnik, 69(2), pp.
    164-170.
•   Van der Walt, N. T., West, L. A., Sheet, T. J., Kuball, D., 1976, “The design and operation of a dry cooling system for a 200 MW turbo-
    generator at Grootvlei Power Station, South Africa,” The South African Mechanical Engineer, 26, pp. 498-510.
•   Von Cleve, H. -H., 1984, “The Air-cooled condensing system for the 4000 MW Escom-Matimba Power Station/South Africa,” VGB
    Kraftwerkstechnik, 64(4), pp. 287-291.
•   Goldschagg, H., Maintenance of Air cooled condensers, 14th IAHR conference, Stellenbosch, South Africa, 2009.
       22