BS 7671 On Site Guide Green 17th Edition by IET PDF
BS 7671 On Site Guide Green 17th Edition by IET PDF
ON-SITE GUID,E
BS 7671:2008 (2011) -I
m
IETWi:ring Regulations
17th Edition
Incorporating Amendment No. 1
:;a The Institution of Engineering and Technology is registered as a Charity in England & Wales
(no. 2H014) and Scotland (no. SC038698).
:a
The Institution of Engineering and Technology is the new
institution formed by the joining together of the IEE (The
Institution oi Electrical Engineers) and the IIE (The Institution
of Incorporated Engineers). The new lnstftution is the inheritor
:;B of the IEE brand and all its products and services, sudh as this
one. which we hope you will find useful. The IEE is a registered
trademark of the Institution of Engineering and Technology.
Coope:rating organisations 6
Prefa0e 7
Foreword 9
Section I Introduction 11
1.1 Scope 11
1.2 Building Regulations 12
1.3 Basic information required 14
:a Section l
2.1
The electric-al supply
General layout of equipment
15
15
2.2 Functi.011 of components 17
2.3 Separation •Of gas installation pipevvork from other services 18
On-Site Guide IS
e The Institutionof Engineering and Tedlnorogy
::g
=a Section 5
5.1 Isolation
lsolation and .switching 45
45
:;a 5.2
5.3
Switching off for mechanical maintenance
Emergency S\l\l'itching
46
46
:a 5.4
5.5
Functional switching
Firefignter's switch
47
47
:;B Section 6
6.1
Labelling
Additional protection
49
49
6.2 Retention of a dangerous electrical charge 49
6.3 'Mlere �he operator cannot observe the operation of sv.ritchgear and controlgear 49
6.4 Unexpected presence of nominal voltage exceeding 230 V 49
6.5 Connection of earthing and bonding conductors 50
6.6 Purpose of s'Nitchgear and controlgear 50
6.7 Identification of protective devices so
6.8 Identification of isolators 50
6.9 Isolation requiring more than one device so
6.1 0 Periodic inspection and testing 51
6.11 Diagrams 51
6.12 Residual current devices 51
:a
6.13 Warning notice - non-standard colours 52
6.14 Warning notke - alternative supplies 52
6.15 Warning notice - high protective conductor OJrrent 53
6.16 Warning notice - photovoltaic .systems 54
Section 7 Fina11 drcuits
=a
55
7. 1 Final circuits 55
7.2 Standard final circuits 68
7.3 Installation considerations 73
7.4 Proximity to electrical and other services 75
7.5 Earthing requirements for the installation of equipment having high protective
conductor current n
7.6 Electrical supplies to furniture 79
=9 Section 8 locations containing a bath or shower 81
8.1 Summary of requirements 81
8.2 Shower cubide in a room used for other purposes 84
8.3 Underfloor heating systems 84
Section 9 Inspection and testing 85
9.1 Inspection and testing 85
9.2 Inspection 85
9.3 Testing 87
14
11.2 General-purpose RCCBs to BS 4293 106
On-Site Guide
e The Institutionof Engineeringand Tedlnorogy
::g
=a 11.3 General�purpose RCCBs to BS EN 67008 or RCBOs to BS EN 61009 106
:;a
11.4 RCD protected socket-outlets to BS 7288 106
11.5 Additional protection 106
11 .6 Integral test device 107
:a 11. 7 Multipole RCDs
Appendix A Maximum demand and diversity
107
109
:;B Appendix B Maximum permissible measured earth fault loop impedance 113
Appendix D Methods of support for cables,. conductors and wiring systems 127
15
Index 193
On-Site Guide
e The Institution of Engineering and Tedlnorogy
::g
=a
:;a Cooperating
:a
:;B
organisations
The IET acknowledges the invaluable contribution made by the following organisations
in the preparation •Ofthis guide.
BEAMA Installation Ltd. ERA Technology Ltd
P. Sayer IEng M I H GCGI M.W. Coates BEng
British Cables Assodation Electrical Safety Council
I. Collings BEng (Hons) CEng MIMechE G. Gundry
M. Gauoher Health and Safety Executive
C.K. Reed ilEng MIET
:a
K. Morton BSc CEng FIET
British Electrotechnical & Allied IHEEM
Manufacturers Association Ltd Eur Ing P. Harris BEng(Hons) FIHEEM MIEE
P. Still MIEE MCIBSE
British Gas/Micropower Council
=a
Institution of Engineering and
P. Gibson Technology
British Standards Institution G.D. Cronshaw CEng AET
P. Calver - Chairman BSI FW0/3 P.E. Donnachie BSc CEng FlET
A.S. Khan MEng(Hons) MIET MIEEE - PEL Eur Ing D. Locke BEng(Hons) CEng MIET
37/1, GEL 81 MIEEE
6ur Ing L. Markwell MSc BSc(Hons) CEng
City & Ciuilds of London Institute MIEE MCIBSE LCGI LCC
H.R. Lovegrove IEng FIET
=9 Department for Co.mmunities and Local
I.M. Reeve BTech CEng MIET
National Inspection Council for
Gov,ernment Electrical Installation Con.trading
K. Broml e y lM. Maltby Smith BSc(Hons) PG Dip Cert
Electrical Contractors' .Association Ed IEng MIET
C. Flynn IEng MIET (Elec) CGI NAPlT
Electrical Contractors· Association of W.R. Allan BEng(Hons)
Scotland t/a SELECT Safety Assessment Federation
R. Cairney IEng MIET I. Trueman CEng MSOE MBES MIET
M.M. Dllncan IEng MIET MILP
=9 ENA
Society of Electrical and Mechanical
Engineers serving Local Government
:;a T. Haggis
ESSA
C.J. Tanswell CEng MIET MCIBSE
UHMA
P. Yates MSc MIEE Dr s. Newberry
==3
I'
Revised, compiled and edited
M. Coles BEng(Hons) MIEE, The Institution of Engineering and Technology, 2011
On-Site Guide
e The Institutionof EngineeringandTedlnorogy
::g
=a
:;a
:a
:;B
The On-Site Guide is one of a number of publications prepared by the IET to provide
guidance on certain aspects of BS 7671 :2008(2011) Requirements for Electrical
Jnstollotions (/ET Wiring Regulations, 17th Edition, incorporating Amendment No. 7).
BS 7671 is a joint publication of the British Standards Institution and the Institution of
Engineering and Technology.
110.1 The scope generally follows that of BS 7671. The Gu;de includes material not induded in
8S 7671, provides background t o the intentions of BS 7671 and gives other sources of
informat;on, however, it does not ensure compliance with BS 7671. It is a simple guide
:a to the requirements of BS 7671 and electrical installers should always consult BS 7671
to satisfy themselves of compliance.
It is expected that persons carrying out work in accordance with this guide will be
=a
competent to do so.
HSR25, Electrical installations in the United Kingdom which comply with the JET Wiring
EWR Regulations, 85 7671, must comply with all relevant statutory regulations, such as the
Regulation
16
Electricity at Work Regulations 1989, the Building Regulations and, where relevant, the
Electricity Safety, QuaHty and Continuity Regulations 2002 and Amendment 2006.
114.1 It cannot be guaranteed that 18S 7671 complies with all relevant statutory regu'lations.
=9 It is, therefore, essential to establish which statutory and other appropriate regulations
115. l
apply and to install according1y; for example, an installation in licensed premises may
have requirements which differ from or are additional to BS 7671 and these will take
precedence.
=9
:;a
==3
On-Site Guide
e The Institution of Engineering and Tedlnorogy
I'
::g
=a
:;a
:a
:;B
:a
=a
=9
=9
:;a
==3
On-Site Guide
e The Institutionof EngineeringandTedlnorogy
18
::g
=a
:;a
:a
:;B
Part 1 This Guide is concerned with Hmited application of BS 7671 in accordance with paragraph
1.1: Scope.
BS 7671 and the On-Site Guide are not design guides.
It is essential to prepare a design and/or schedule of the work to be done prior to
commencement or alteration of ar1 electrical installation and to provide all necessary
information and operating instrnctions of any equipment suppHed to the user on
completion.
:a Any specification should set out rt-le detailed design and provide sufficient information to
enable competent persons to carry out the installation and commissioning.
The specification must provide for all the commissioning procedures that will be required
=a
and for the production of any operation and maintenance manual and building logbook.
The persons or organ,sations who may be concerned in the preparation of the
specification indude:
the Designer(s)
► the lnstaller(s)
the Electricity Distributor
=9 ►
►
the Installation Owner and/or User
the Architect
► the Local Building Control Au;thority/Standards division or Approved Inspector
► the Fire Prevention Officer
► the CDM Coordinator
► all Regulatory Authorities
► any Licensing Authority
► the Health and Safety Executive.
In producing the specification, advice should be sought from the installa,tion owner and/
=9 or user as to the intended use. Often, such as in a speculative building, the detailed
intended use is unknown. In those circumstances the specification and/or the operation
:;a and maintenance manual and butlding logbook must set out the basLS of use for which
the instaUation is suitable.
==3 Precise details of each item of equipment should be obtained from the manufacturer
and/or supplier and compliance with appropriate standards confirmed.
On-Site Guide
e The Institutionof EngineeringandTedlnorogy
19
::g
=a The opera,tion and maintenance manual must include a description of how d'le installed
system is to operate and must include all commissioning records. The manual should also
:;a include manufacturers' technical data for all items of switchgear, luminaires, accessories,
etc. and any special instructions that may be needed.
:a Part L 2010 of the Building Regulations of England and Wales requires that building
owners or operators are provided with summary information relating to a new or
:;B refurbished building wh[ch includes building services information and the maintenance
requirements in a building logbook. Information on how to develop and assemble a
building logbook can be obtained from CIBSE:
Tel.: 020 8772 3618
Website: www.cibse.org
Address: CIBSE
222 Balham High Road
London
SW12 9BS
The Health and Safety at Work etc. Act 1974 Section 6 and the Construction (Design
and Management) Regulations 2007 are concerned with the provision of information.
Guldance on the preparati.on of technical manuals is given in BS 4884 series Technical
:a manuals and BS 4940 series Technical information on construction products and
services. The size and complexity of the installation will dictate the nature and extent of
the manual.
=a
=9
=9
:;a
==3
On-Site Guide
e The Institution of Engineering and Tedlnorogy
I'
::g
=a
:;a
:a
:;B
I.I Scope
This Guide is for installers (for s;mplicity, the term installer has been used for electricians
and electrical. installers). It covers the following installations:
a domestic and similar installations, including off-peak supplies, supplies to
associated garages, outbuildings and the like
b small industrial and commercial single- and three-phase instanations.
:a Part 7 N01TE: Special Installations or Locatfons (Part 7 o,f 85 7671) are generally exduded from
this Guide, as are installations for electric vehicle charging equipment. Advice, however,
is given on installations in locations containing a bath or shower and underfloor heating
installations.
=a 313.l
This Guide is restricted to installations:
at a supply frequency of 50 hertz
ii at a nominal voltage of 230 V a.c. single-phase or 400/230 V a.c. three-phase
iii supplied through a, distributor's cut-out having a fuse or fuses rated at 100 A
or less to one of the following standards:
- BS 88-2
- BS 88-3
=9 - BS 88-6
- BS 1361 Type U
NO·TE: BS 1361 was withdrawn in March 2010 and replaced by BS 88-3; BS 88-6 was
withdrawn in March 2010 and replaced by BS 88-:2 but fuses complying with these
withdrawn standards wHI be found in existing insta'llations for many years to come.
iv typical maximum values of earth fault loop impedance, Ze, for TN earthing
arrangements outside the consumer's installation commonly quoted by
=9 distributors aire as follows:
► TN-C-S arrangement - 0.35 Q, see Figure 2.1 (i)
On-Site Guide 1 1 1
e The Institutionof EngineeringandTedlnorogy
::g
=a This Guide also contains information which may be required in general installation work,
:;a
for exampIle, conduit and trunking capacities, bending radH of cables, etc.
The Guide introduces the use of standard circuits, which a;re discussed in Section 7,
:a
i
however, because of s mplification, this Guide may not give the most economical result.
This Guide is not a replacement for BS 7671 which should always be consulted.
:;B Defined terms according to Part 2 of BS 7671 are used.
In compliance with the definiti.ons of BS 7671, throughout this Guide the term line
ronductor is used instead of phase conductor and live part is used to refer to a conductor
or conductive part intended to be energised in normal use, induding a neutral conductor.
The terminals of electrical equipment are identified by the letters L, N and E (or PE).
Further infonnation is available in the series of Guidance Notes published by the IET.
NO,JE: For darification:
the distributor of electricity ls deemed to be the organisation owning fhe
electrical supply equipment, and
the supplier of e'lectricity is the organisation from whom electricity is
:a purchased.
On-Site Guide 1 1 2
e The Institutionof EngineeringandTedlnorogy
::g
=a Part J Heat producing appliances;
:;a
Part K Protection from fuUing;
Part L Conservation of fuel and power: energy efficient lighting;
Part M Access to and use of buildings: heights of switcnes, socket-outlets and
:a Part P
consumer units;
Electrical safet y- dwellings.
:;B NO,fE: Guidance is available for each part of the Building Regulations in the form
of Approved Documents which can be freely downloaded from the Department for
Communities and Local Government (DCLG) website: www.planningportal.gov.uk
=a -
example, blocks of flats
a range of mounting heights of switches and socket-outlets, etc
- separate switching for concealed socket-outlets, for example, behind white
goods in kitchens
- conseivation of fuel and power in buildings.
With regard to electrical installations in Scodand, the requirements of the above are
deemed to be satisfied by complying with BS 7671.
=9 NOTE.: The handbooks may be obtained from the Building Standards Division of the
Scottish Government from website:
www.sootland.gov.u k/Topics/Built-Environment/Building/:Building-standards/
publications/p ubtech
:;a
==3
On-Site Guide 1 1 3
e The Institutionof EngineeringandTedlnorogy
::g
=a 313.1 1.3 Basic information required
:;a Before starting work on an installation which requires a new electrical supply, the installer
should establish the following information with the local distributor:
:a the number of live conductol"S required by the design
ii the distributor's requirement for cross-sectional area and length of meter tails
:;B iii the maximum prospective fault current (lpf) at the supply term;nals
iv the typical maximum earth fault loop impedance (Ze) of the earth fault path
outside the consumer's installation
v the type and rating of the distributor's fusible out-out or protective device
544. l vi the distributor's requirement regarding the size of main protective bonding
conductors
vii the conductor arra ngement and system earthing
312 viii the arrangements for the incoming cable and metering.
132.16 For additions and alterations to existing installations, installers should satisfy themselves
as to the suitability of the supply, the distributor's equipment and the earthing
arrangements.
:a
=a
=9
=9
:;a
==3
:a
conductors pipe pipe
consumer's tails
L.A:BEl (see Figure 6.5)
elect:rieiity
isolator
switch
=a RCBOs
•••••
10mm2
main switch
=9 16mm1
lOOA_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
gas meter
wate< gas
service service
pipe pipe
=9 NOTE: An electricity isolator switch may not always be insta11ed by the distributor.
:;a
==3
On-Site Guide 1 1 5
e The Institutionof EngineeringandTedlnorogy
T Figure 2.1(11) TN-S earthing arrangement (cable sheath earth)
drc.uit protectJve metal water metillgas
conductors pipe pipe
consumer', tllib
-■
'""' efe<ttiCity
tsolatot
SWilCh
RCBOs
■
main switch
16mrw
gas fflffer
water gas
service service
pipe pipe
NOTE: An electricity isolator switch may not always be installed by the distributor.
• . . !! • •
main switch
gas meter
NOTE I : An electricity isolator switch may not always be insta,!ed by the distributor.
On-Site Guide
e The Institutionof EngineeringandTedlnorogy
I'
::g
=a 542.3. 1 NOTE 2: See Table 4.4(ii) for further information regarding the sizing of the earthing conductor for a TT
earthing arrangement.
:;a
:a 2.2 Fundion. of components
2.2.1 Distributor's cut-out
:;B This will be sealed to prevent the fuse being withdrawn by unauthorised persons. When
the meter tails and consumer unit are installed in accordance with the requirements •Of
the distributor, the cut-out may be assumed to provide fault current protection up to the
consumer's main switd,.
As the cut-out is the property of the distributor, installers must not cut seals and withdraw
cut-out fuses without permission. When removal of the cut-out for isolation is required,
the supplier of electricity should be contacted to arrange disconnection and subsequent
reconnection.
NOTE: The supplier of electricity may not be the same organisation as the distributor.
On-Site Guide 1 1 7
e The Institution of Engineering and Tedlnorogy
::g
=a 2.2.5 Consumel's controlgear
:;a 530.3.4 A consumer unit (to BS EN 60439-3 Annex ZA) is for use on singie-phase installations
up to 100 A and may include the following components:
:a a double-pole isolator
fuses, circuit-breakers or RCBOs for protection against overload and fault
:;B currents
RCDs for additional protection against electric shock
► RCDs for fault protection.
ltematively, a separate main switch and dIBtribution board may be provided.
=a
-
"Y Figure 2.3 Separation from gas pipes and gas metering equipment
Separation of at least 25 ITVT1 to be
' ;..,_ proYlded b domestic pipework up
' ,
' to 35 mm. For pipework over 35 mm
then SO mm separation Is requlred.
Theseparatlondlstanrecan be reduced
if the gas pipe Is PVC wrapped or a barrier
of etectrkally ln5Ulatltig material Is Interposed
=9 4 - supply c.able or
dlstributioo cable
1minimum
.,_ diSunce
=9
150mm
:;a
Separation of at least 150 mm to be provided,
between a gas meter (and a = l a t e d fittl ng s) and
electrical equipment. unless a non-c-0mbustlble
barrier of insulatlng materl.a'I ls Interposed
==3
On-Site Guide
c The lnstirution of 8'1gineering and Technofogy
I'
::g
=a 2.4 Portable generators
:;a 551.4.4 It is recognised that generators will be used occasionally as a temporary or short-term
means of supplying electricity, for example:
:a ► use on a construction site
► used to supply stalls on street markets
:;B ► external gathering or function attended by the general public, such as a
country show.
Temporary generators can be divided into two dasses, i.e. portable and mobile:
► portable generators with an electrical output rating of up to l 0 kVA are used
for small-scale work for short-term use, i.e. less than one day, and
► mobile generators are those used for longer per;ods and can be in excess of
lO kVA output.
This guide considers three scenarios relating to the use of portable generators; see 2.4.1
to 2.4.3.
551 For information relating to the permanent use of generators see IET Guidance Notes 5
and 7 and Section 551 of 8S 7671:2008(2011).
:a Where generators are used to supply concession vehicles, such as burger vans, see Section
717 Mobi,le and Transportable Units of BS 7671 :2008(2011) and IET Guidance Note 7.
It is extremely important to note that a portable generator used with floating earth should
only be used to supply equipment ,n the following permutations:
► one or more items of Class II equipment
=9 ► one item of Class I equipment
one or more items of Class II and one item of Class I equipment.
:;a
►
==3 More than one item of Class I equipment should not be used simultaneously as faults
I'
can be presented as voltages and operati ves can provide a path for current flowing
between exposed-conductive-parts of faulty electr:ica'I equipment.
On-Site Guide
e The Institution of Engineering and Tedlnorogy
::g
=a T Figure :Z.4.1 Portable generator used with a floating earth
:;a
:a
:;B C1.1rrenN.1sing
equipment
Socket-outlet
with overcurrent
protection
Generator
=a
method of supply is used, extreme care should be taken to ensure that there is no
intended or casual interconnection with any other electrical system, such as extraneous-
conductive-parts or exposed-conductive-parts from other electrical systems.
RCD protection at 30 mA is required for all circuits supplied in this manner.
Socket-outlets
=9 ---------------
Generator
with overcurrent
protection and ROD
protection at 30 rnA
•
:;a •
==3
On-Site Guide 1 2 0
c The lnstirutionof 8'1gineering and Technofogy
::g
=a 2.4.3 Portable generator referenced to the general mass
:;a BS 7430:
of the earth
Where there are extraneous-conductive-parts or exposed-conductive-parts from other
:a 1998 e[ectrical systems present, generator reference earthing, by means of an earth electrode
to the general mass of the earth, should be instaUed. See Figure 2.4.3(i).
:;B Note that this does not create a TT supply arrangement; the supply will be TN-S in form
from the generator, the neutral or star point being referenced to the general mass of the
earth.
Where an earth electrode is supplied it will need to be tested by the standard method
using a proprietary earth electrode resistance tester; see 10.3.5.2.
Note that an earth fault loop impedance tester cannot be used for this test as the
earth electrode is not used as a means of earthing, it is used to reference the portable
generator to the general mass of the earth and does not form part of the earth loop.
As the earth e'lectrode is used for referencing and not as a means of earthing, its
resistance shou'ld, ideally, be less than 200 0 .
Table 54.l If buried, generator reference earthing and/or bonding conductors should be sized
543.3.1 in accordance with Tabl.e 54.1 and suitably protected in accordance with Regulation
543.3.l For example, a 16 mm 2 conductor would generally be adequate for short-term
use where no mechanical protection is provided.
=9
\ ------==---
t----= Generator
-So-ck_e_t·o-u-tle-ts
with overcurrent
protection and ROD
protection at 30 mA
=9
:;a
Earth electrode
==3
On-Site Guide 1 2 1
e The Institutionof EngineeringandTedlnorogy
::g
=a Where restrictions, such as concreted/paved areas or the portable generator is being
used some distance above ground level, make it impossible t o install an earth electrode,
:;a simultaneously accessible metal parts, i.e. accessible extraneous-conductive-parts and/
or exposed-conductive-parts from other electrical systems, may be bonded to the main
:a earthing terminal of the generator. See Figure 2.4.3(ii).
Where separate accessible extraneous-conductive-parts and/or exposed-conductive-
:;B parts from other electirical, systems are connected together, protective conductors can
544.1. 1 be si,zed in ac-eordance with Regulation 544.1.1. For example, a 16mm2 conductor would
generaUy be adequate for short-term use \Nii ere no mechanical protection is provided.
:a
--- ----------rl
.,i:;.,,-_ --- ...... --,.--'-<-
Socket-outlets
Generator with overcurrent
protectlon and RCO
=a
protectlon at 30 mA
=9
=9
:;a
==3
c
On-Site Guide
The lnstirutionof 8'1gineeringandTechnofogy
122
::g
=a
:;a
:a
:;B
:a 434
Functions i and Hare carr,ied out usually by one device, Le. a fuse or circuit-breaker.
Function iii may be carried out by the fuse or dro.Jit-breaker provided for functions i and
411 ii or by an RCD.
=a
An RCBO, being a unit with a combined circuit-breaker and RCD, will carry out functions
i, ii and iii.
=9 ►
►
fuses to 8S 88-2, :SS 88-3, 8S 88-6, 8S 1361 and BS 3036
miniature circuit-breakers to BS 3871-1 types 1, 2 and 3
► cirouit-breakers to BS EN 60898 types 8 1 C and D, and
► residual current circuit-breakers with integral overcurrent protection (RCBOs)
to BS EN 61009-1 and IEC 62325.
On-Site Guide
e The Institutionof EngineeringandTedlnorogy
12:S
::g
=a 3.4 Protection agains,t electric shock
:;a J.4.1 Au,tomatic disconnection of supply
:a 411 Automatic disconnection of supply (ADS) is the most the common method of protection
411.l against electric shock. There are two elements to automatic disconnection of supply,
basic protection and foultprotection.
:;B
4n,2 3.4.1.1Basic protection
41 1.1 Basic protection is the physical barrier between persons/livestock and a live part.
416 Examples of basic pro tection are:
=a 411.3.1.2
411.3.2
►
►
protective equipotential bonding, and
automatic disconnection in case of a fault.
Fault protection is provided by Hmiting the magnitude and duration of voltages that
may appear under earth fault conditions between simultaneously accessible exposed-
c.onductive-parts of equipment and between them and extraneous-conductive-parts or
earth.
On-Site Guide 1 2 4
c The lnstirutionof 8'1gineering and Technofogy
::g
=a 414.4.4 ► have no exposed-conductive-parts connected to earth or to exposed-
:;a
conductive-parts or protective conductors ,of another circuit.
PELV
:a 414.4.1 Protective extra-low vo'ltage (PELV) systems must meet all the requirements for SELV,
except that the circuits are not electrically separated from earth.
:;B 414.4.5 For SELV and PELV systems basic protection need not be provided if voltages do not
exceed those given in Table 3.4.3.
:a
411
:J.S .Automatic disconnedion
3.5.1 Standard circuits
=a For the standard final circuits given in Section 7 of this Guide, the correct disconnection
time is obtained for the protectwe devices by 'limiting the maximum circuit 'lengths.
On-Site Guide 1 2 5
e The Institutionof EngineeringandTedlnorogy
::g
=a 3.6 Residual current devices (RCDs)
:;a RCD is the generic term for a device that operates when the residual current in the circuit
reaches a predetermined value. The RCD is, therefore1 the main component in an RCCB
:a (residual current operated circuit-breaker without integral overcurrent protection) or
one of the functions of an RCBO (residual current operated circuit-breaker with integral
:;B overcurrent pmtection )..
:a
similar
522.6.103 v i for cables without earthed metallic covering installed in walls or partitions
with metal parts (not including screws or nails) and not protected by earthed
steel conduit or the like.
On-Site Guide 1 2 6
c Thelnstirution of 8'1gineering and Technofogy
::g
=a 411.3.3(a)3.6.2.l Installations under the control of skiHed or instructed persons
522.6.102 BS 7671 :2008(2011) permits RCDs, where usually provided for additional protection, to
:;a 522.6.103 be omitted where the installation is under the control of a skilled or instructed person.
:a 411.3.3(i)
415.1.1
The decision as to which socket-outlets or circuits do not require add;tional protection
by RCDs should be taken by the designer of the electrical installation and only after
:;B consultation with an appropriate person in the dient's organisation. An appropriate
person would be one who is able to ensure that the socket-outlets or circuits in question
are, and will remain, under the supervision of skilled or instructed persons.
Wherever a designer so chooses to omit RCO protection, traceable confirmation must
be obtained from the client to identify the reason for the omission and such confirmation
must be included within the documentation handed over to the dient upon completion
of the work.
Where no such confirmation can be obtained, RCD protection shou'ld not be omitted.
=a a TN conduit instaHati.ons
Where cables in walls or partitions have an earthed metallic covering or are installed in
steel conduit or similar, 30 mA RCD protection is still required in tl1e following cases:
► circuits of locations containing a bath or shower
► protection at socket-oudets not exceeding 20 A
► mobile equipment not exceeding 32 A for use outdoors
=9 ► the arrangement in Fi,gure 3.6.3(i).
=9
:;a
==3
On-Site Guide 1 2 7
e The Institutionof EngineeringandTedlnorogy
::g
=a T Figure 3.6.3(1) Typica'I split consumer unit with one 30 mA RCD, suitable for TN
installations with cables in walls or partitions having an earthed
:;a metaUic covering or endosed in earthed steel conduit or the like
:a
other circuits to .socket-outlets, locations
circuits containing a bath or shower, mobile
equipment outdoors with current
:;B rating not exc ding 32 A
••••
1 1111
:a 'Main switch'
=a b T T conduit installations
For instaHations forming part of a TT system, all drwits must be RCD protected. If cables
in waits or partitions have an earthed metallic covering or are installed in earthed steel
conduit, 30 mA RCDs will be required for:
circuits of locations containing a bath or shower
=9 circuits with socket-outlets not exceeding 20 A
mobile equipment not exceeding 32 A for use outdoors.
The remainder of the installation would require protection by a 100 mA RCD (see Figure
3.6.3(ii)).
=9
:;a
==3
On-Site Guide 1 2 8
e The Institutionof Engineeringand Tedlnorogy
::g
=a T Figure 3.6.3(11) Typical split consumer unit with time-delayed RCD as main
:;a
switch, suitable for TT and TN installations with cables in walls
or partitions havin_g an earthed meta'llic covering or endosed in
earthed steel conduit or the like
:a other circuits to socket-outlets, locations
circuits containing a bath or shower, mobile
:;B equipment outdoors with current
rating not exceeding 32 A
• • ••••
• " • . . .
• • • •••
l 11 1 1
=a
to meter tails
For instaUations forming part of a TT system with cables installed in walls or partitions
having no earthed metallic covering or not installed in earthed conduit or the like, protection
by 30 mA RCDs will be required for all circu its, see Figures 3.63(iii) and 3.6.3(iv).
The endosures of RCDs or consumer units incorporating RCDs in TT installations should
=9 have an all-insulated or Gass U construction or additional precautions, as may be
recommended by the manufacturer, need to be taken to prevent faults to earth on the
supply side of the 100 mA RCD.
c RCBOs
The use of RCBOs will m;nimize inc.onvenience in the event of a fault and is applkabte
to all systems. See Figure 3.6.3(iH).
Such a consumer unit arrangement also easily allows individual drcuits, such as to
spedficaUy labelled socket-oudets or fire alarms, to be protected by a cirruit-breaker
=9 without RCD protection. Such circuits will usually need to be installed in earthed metal
conduit or wired with earthed metal-sheathed cables.
:;a
==3
:a -■
:;B -
W
l I
. . .... .. _J
·1 1 111111
30mARCBOs
:a
d Split board with two 30 mA RCDs
The division of an installation into two pa;rts with separate 30 mA RCDs will ensure that
=a part of the installation will remain on supply in the event of a fault, see Figure 3.6.3(iv).
T Figure J.6.J(lv) Split consumer unit with separate main switch and two 3 0 mA
RCOs
final circuits fina•I circuits
=9
II
=9
main switch 30 mA 30mA
(isolator) RCD RCD
labelled
==3
On-Site Guide
e The Institutionof EngineeringandTedlnorogy
130
::g
=a e Three-way split board with two 30 mA RC,Ds
:;a The three-way division of an installation can provide ways unprotected by RCDs for, say,
fire systems and for two separate 30 mA RCDs to ensure that part of the installation
:a win remain on supply in the event of a fault. Unprotected circults will usually need to
be instaUed in eartfied metal conduit or wired with earthed metal-sheathed cables, see
Figure 3.6.3 (v).
:;B
� Figure J.6.3(v) Three-way split consumer unit with separate main switch, two
30 mA RCDs and circuits without RCD protection
final circuits
II
final circuits
:a • • ••••
[l . . . . ....
I'
• • • •••
1 1111
=a main switch
�ll
30mA 30mA
(isolator) RCD RCD
labelled
'Main switch'
=9
:;a GN 1
443.2.6
For more information, see IET Guidance Note l.
Damage can occur when the surge or transient overvoltage, a5 the result of lightning or
==3 electrical switching, exceeds the impulse withstand vo'ltage rating of e'lectrical equipment
Table 44.3 - t h e levels ,of which are defined in Table 44.3.
On-Site Guide I S I
e TheInstitution of EngineeringandTedlnorogy
::g
=a Surges from electrical switching events are created when large inductive loads, such as
motors or air conditioning units, switch off and rel.ease stored energy which dissipates as
:;a a transient over voltage. Switching surges are, in general, not as severe as lightning surges
but are more repetitive and can reduce equipment lifespan.
:a Over:vo!tages of atmospheric origin, in particular, can present a risk of fire and e'lectric
shock owing to a dangerous filashover.
:;B 443 ► Section 443 of BS 7671 :2008(2011) has requirements for the protection of
persons, llvestock and property from injury and damage as a consequence of
overvoltage
534 ► Section 534 has requirements for the setection and insta'llation of surge
protective devices.
N:Q,TE 1: Section 534 applies to a.c. power circuits only. When the need for power SPDs
is identified, additional SPDs on other services such as telecommunications lines and
equipment is also recommended. See BS EN 62305 and BS EN 61643.
NQ,TE 2: Some electronic equipment may have protection levels lower than Category I
of Table 44.3.
:a 443
3.7.2 Anan,gements for protection against overv ,oltages
Protection according to Section 443 can only be achieved if transient overvoltages are
534 limited to values lower than those given in Table 44.3, requiring the correct selection and
installation of suitable SPDs.
=a 3.7.2.1 Where SPD protection may not be required
443.1 Protection against overvoltages of atmospheric origin is not required in the follovving
fable 44.3 circumstances but, in each case, the impulse withstand voltage of equipment must meet
the requirements of Table 44.3 of BS 7671:2008(2011):
443.2.1 ► the installation . supplied by a completely buried low voltage system and
=9 443.2 ..2
does not indude overhead lines
► installations which include overhead lines but where the e-0nsequential losses
are tolerable, e.g. typical urban dwellin& storage unit or farm building.
If there are risks of direct strikes to or near the strucrure or to the low voltage distribution
line, overvoltage protection by SPDs is required in ace-0rdance with BS EN 62305
Protection against lightning.
On-Site Guide 1 3 2
c The lnstirutionof 8'1gineeringandTechnofogy
::g
=a The flow chart in Figure 3.7.2.2 will a[d the decision-making process for electrical
:;a
installations within the soope of this Guide. See IET Guidance Note 1 for more information.
:a T figure 3.7.2.l SPD decision flow chart for installations within the scope of this
Guide
YES
Ove:rhead line supplying the
building at risk of direct strike -
see BS E.N 62305 (443.1.1)
=a Installation presents
higher ri k (e.g. fire) or requires
YES
(534.2.6)
=9
:;a
==3
On-Site Guide
e The Institutionof EngineeringandTedlnorogy
I'
::g
=a 3..7.3 Types of SPD protection
:;a 534.l
534.2
For the protection of a.c. power circuits, SPDs are allocated a type number:
Type 1 SPDs are only used where there is a risk of direct 'lightning current
and, typically, are installed at tfie origin of the installation
Type 2 SPDs are used at distri bution boards
:;B Type 3 SPDs are used near termina'I equipment
See also Table 3.7.3.
Appendix Combined Type SPDs are dassified with more than one Type, e.g. Type 1 & 2, Type 2
16 & 3, and can provide both lightning current with overvoltage protection in addition to
protection between all conductor combinations (or modes of protection) within a sing[e
unit. Combined Type SPDs provide high surge current handling combined with better
overvoltage protection levels (Up) - t h e latter being a performance parameter of an SPD.
=9
:;a
==3
On-Site Guide
c The lnstirutionof 8'1gineeringand Technofogy
134
::g
=a 3..7.4 Coordination and selection of surge protection
:;a 534.2.3.6 Where a number of SPDs are required to operate in conjunction with each other they
must be coordinated to ensure the correct type of protection is instaHed where required;
:a see Figure 3.7.4.
SPD protection should be coordinated as follows:
:;B ► choose the correct type of SPD for the installation and site in the correct
location
► refer to Tables 44.3 and 44.4 of BS 7671 (impulse withstand voltage)
534.2.3.1.1 ► choose SPDs with a protection level (Up) sufficiently 'lower than the impulse
withstand voltage or lower than the impulse immunity of the equipment to
be protected
choose SPDs of the same make or manufacture.
NQ,TE: Coordinated SPDs must be of the same make or manufacture unless the
designer is satisfied that devices of different makes wiU coordinate as required.
=9
=9
:;a
==3
:a lead length (a + b) should preferably not exceed 0.5 m but in no case exceed 1.0 m;
see Figure 3.7.5.
OCPD
a
'. •· ...
SPD E/1
:a b
=a
Main earthing terminal or
-L,, connecting conductor bar
=9
:;a
==3
On-Site Guide
c Thelnstirution of 8'1gineeringandTechnofogy
136
::g
=a 3..7.6 Methods o,f connection
:;a 534.2.2 Primariliy, the installation of SPDs must follow the manufacturer's instructions but
minimum SPD connections at the origin of the electrical supply are usually made as
:a those shown in Figure 3.7.6(i) (TN-C-S, TN-S, TT) and Figure 3.7.6(ii) (TT - SPDs
upstream of RCD):
:;B Type 1 SPDs should be installed upstream from any RCD to avoid unwanted tripping.
Where this cannot be avoided, the RCD should be of the time-delayed or S-type.
RCD
Protective
conductor
N
:a
=a
=9
=9
:;a
==3
On-Site Guide
e The Institution of Engineering and Tedlnorogy
I'
::g
=a 534.2.S(ii) T Figure 3.7.&(H) SPDs on supply side of RCD
:;a O CPD1
l1
:a L2
u
:;B
N
ProtectiVe
conductor
OCPO 2
I
I
L---
:a
- -
=a NOTE:
SPDs.
See Appendix 16 of BS 7671 :2008(2011) for further information regarding the connection of
=9
=9
:;a
==3
On-Site Guide
c The lnstirution of 8'1gineeringand Technofogy
138
::g
=a
:;a Earthing and
:a
:;B
bonding
4.1 Protective earthing
The purpose of protective earthing is to ensure that, in the event of a fault, such as
between a line conductor and an exposed-conductive-part, sufficient current flows to
operate the protective device, i.e. fuse to blow, circuit-breaker to operate or RCO to
operate, in the required time.
411.4.2 1Every exposed-conductive-port (a conductive part of equipment that can be touched
:a
411.5.l and which is not a live part but which may become live under fault conditions) shall
be connected by a protective conductor to the main earthing terminal and, hence, the
means of earthing for the installation.
=9
4.3 Main protective bonding of metallic services
:;a (Figures 2.l(i) to 2.l(iii))
==3 The purpose of protective equipotential bonding is to reduce the voltages between the
various exposed-conductive-parts and extraneous-conductive-parts of an installation,
dur1ng a fault to earth and in the event of a fault on the distributor's network.
On-Site Guide I S9
e The Institutionof Engineeringand Tedlnorogy
::g
=a 411.3.1.2 Main protective bonding conductors are required to connect extraneous-conducti-ve-
:;a
Part 2 parts to the main earthing terminal of the ;nstallation. An extraneous-conductive-part
is a conductive part, such as a metal pipe, liable to introduce earth potential into the
installation or building. It is common, particularly under certain fault conditions on the
:a LV supp'ly network, for a potentia'I, to exist between true earth, i.e. the general mass of
Earth and the earth of the electrical system. Therefore, buned metallic parts which enter
:;B the building are to be bonded to the main earthing terminal of the electrical installation.
Examples of extraneous-conductive-parts are:
metallic installation pipes
ii metallic gas installation pipes
iii other installation pipework, for example, heating oil
iv structural steelwork of the building where rising from he ground
v lightning protection systems (where required by BS EN 62305).
It is also necessary to consider not just metallic supply pipework but also internal metallic
pipework whtch may have been buried in the ground for convenience, for example, central
heating pipework cast into the concrete or buried in the screed of a floor at ground level.
Such metallic pipes would normally be considered to be extraneous-conductive-parts.
T Table 4.4(1) Earthing conductor and main protective bonding conductor sizes
(copper equivalent) for TN-S and TN-C-S supplies
Une conductor or mm l 4 6 10 16 25 35 50 70
=9 neutral onductor of
PME sup,plies
542.3 Ellrthlns conductor m nr 6 6 10 16 16 16 25 35
543.1 not buried or buried
anclprotlldlld
a p l n s t COffOlion and
mechankal clamap -
INnolal
544.1.l Main protective bonding mm1 6 6 6 10 10 10 16 25
condudor - see notes
lable 54.8 Main pnll8c.tlN bondlns mnr 10 10 10 10 10 10 16 25
:;a condudor for PME
supplies (TN-C-5)
Notes:
543.2.4 1 Protective conductors (including earthing and bonding conductors) of 10 mm2 cross-sectional area
or less shall be copper.
:;a
mm2 copper or greater for TN·S and TN·C·S supplies,
542.3.1 J Buried earthing conductors must be at least
Table 54.1 25 mm 2 copper if not protected against corros;on
:a
► 50 mm2 stee'I if not protected against corrosion
► 16 mm2 copper if not protected against mechanical damage but protected against c-0rrosion
16 mm 2 coated steel if not protected against medhanical damage but protected ag�inst
:;B 4
corrosion.
The distributor should be consulted when in doubt.
Table 4.4(11), Copper earthing conductor cross sectional area (csa) for TT
supp'lies
Buried N o t buried
Unprotected Protected Protected Unprotected Protected Protected
against against against against
corrosion corrosion and corrosion corrosion and
mechanical mechanical
damage damage
mm 2 mm 2 mm 2 mm 2 mm 2 mm 2
:a 25
Notes:
16 2.5 4 4 2.5
On-Site Guide 1 4 1
e The Institutionof EngineeringandTedlnorogy
::g
=a Where there is a plastic incom;ng seNice and a metal installation within the premises,
main bonding is recommended unless it has been confirmed that any metallic pipework
:;a within the building is not introducing earth potential (see 4.3).
:a 544.1.2 II main bonding connections are to be applied to the consumer's side of any meter,
main stop valve or insulating insert and, where practicable, within 600 mm of the meter
outlet union or point of entry to the building if the meter is extemat
:;B
4.6 Supplementary equipotential bonding
The purpose of supplementary equipotential bonding is to reduce the voltage between
the various exposed-conductive-parts and extraneous-conductive-parts of a location
during a fault to earth.
NQ,TE: Where a required disconnection time cannot be achieved, supplementary
bonding must be applied, however, this is outside the scope of this Guide. See
Regulations 411.3.2.5 and 411.3.2.6 and Guidance Note 1.
The cross sectional area of supplementary bonding conductors is given in Table 4.6.
:a ►
►
metaUic boiler pipework
metaUic furniture in kitchens
► metallic pipes to wash hand basins and WCs
:;B 701.415.2 ► locations containing a bath or shO\l'i.ler, providing the conditions of Regulation
701.415.2 are met.
NOTE: Metallic waste pipes deemed to be extra,neous-oonductive-parts must be
connected by main protective bonding conductors to the main earthing terminal; see
also 4.3.
On-Site Guide 1 •s
e The Institutionof Engineering and Tedlnorogy
::g
=a 542.2.5 vi lead sheaths and metal coverings of cables, which must meet all the fo'llo'Ning
:;a
conditions:
a adequate precautions t o prevent excessive deterioration by corrosion
b the sheath or covering shall be in effective contact with 'Earth
:a c the consent of the owner of fhe cable shall be obtained
d arrangements shall exist for the owner of the electrical installation to
:;B be warned of any proposed change to the cable which might affect its
suitability as an earth electrode.
=a
f acilitate measurement of external earth fault loop impedance, Ze.
NOTE: For TN-S and TN-C-S installations, advice about the availability of an earthing
fac;lity and the precise arrangements for connection should be obtained from the
distributor or supplier.
=9
=9
:;a
==3
On-Site Guide
c The lnstirutionof 8'1gineeringand Technofogy
I"
::g
=a
:;a Isolation and I
:a
:;B
switching
537.2 5.1 Isolation
132.15.1 5..1..1 Requirement
Means .of isolation should be provided:
at the origin of the installation
537.1.4 A main linked switch or circuit-breaker should be provided as a means of
isolation and of interrupting the supply on load.
:a For single-phase household and similar supplies that may be operated by
unskilled persons, a double-pole device must be used for both TT and TN
systems.
For a three-phase supply to an installation forming part of a TT system, an
=a isola,tor must interrupt the line and neutral conductors. In a TN-S or TN-C-S
system only the line conductors need be interrupted.
ii for every circuit
537.2.1.1 Other than at the orig;n of the installation, every circuit or group of circuits
that may have to be isolated without interrupting the supply to other circuits
should be provided with its own isolating device. The device must switch aH
live conductors in a TT system and all line conductors in a TN system.
=9 531.2.1.2 iii for every item of equipment
iv for every motor
132.1 s.2 Every fix.ed electric motor should be provided with a readily accessible and
easily operated device to switch off the motor and all associated equipment
induding any automatic circuit-breaker. The device must be so placed as to
prevent danger.
537.1.3 v for every supply.
537.3.1.l A means of switching off for mechanical maintenance is required where mechanical
maintenance may involve a risk of injury- for example, from mechanical movement of
machinery or hot items when replacing lamps.
537.3.1.2 The means of switching off for mechanical maintenance must be able to be made
seoure to prevent electrically powered equipment from becoming unintentionally started
during the mechanical maintenance, unless the means of switching off is continuously
under the control of the person performing the maintenance.
Each device for switching off for mechanical maintenance must:
537.3.2.1 where practicable, be inserted in the main supply circuit
537.3.2.1 ii be capable of switching the full load current
:a
537.3.2.2 iii be manually operated
537.3.2.2 iv have either an externally visible contact gap or a clearly and reliably indicated
OFF position. An ind;cator light should not be relied upon
537.3.2.3 v be designed and/or installed so as to prevent inadvertent or unintentional
switching on
=a 537.3.2.4 vi be installed and durably marked so as to be readily identifiable and
convenient for use.
537.3.2.6 A plug and socket---0utlet or similar device of rating not exceeding 16 A may be used for
switching off for mechanical maintenance.
I"
currents where appropriate
On-Site Guide
c The lnstirutionof 8'1gineeringandTechnofogy
::g Is
=a 537.4.2.3 ii hand operated and directly interrupt the main circuit where practicable
537.4.2.4 iii dearly identified, preferably by colour. If a colour is used, this should be red
:;a with a contrasting background
iv· readily accessible at the place where danger might occur and, 'Nhere
:a
537.4.2.5
appropriate, at any additional remote position from which that danger can be
removed
:;B 537.4.2.6 v of the latching type or capable •Ofbeing restrained in the 'OFF' or 'STOP'
position, unless both the means of operation and re-energizing are under the
control of the same person. The release of an emergency switching device
must not re-energize the relevant part of the installation; it must be necessary
to take a further action, such as pushing a 'start' button
537.4.2.7 vi so placed and durably marked so as to be readily identifiable and convenient
for its intended use.
:a
530.3.2 Switches must not be installed in the neutral conductor alone.
537.5.1.3 A'II current using equipment requiring control shall be controlled by a switch.
537.5.2.3 Off-load isolators, fuses and links must not be used for functional switching.
=a NOTE: Table 53.4 of BS 7671 :2008(2011) permits the use of drcuit breakers for
functional switching purposes but, in each case, the manufacturer should be consulted
to establish suitability.
=9
:;a
==3
On-Site Guide 1 4 7
e The Institutionof EngineeringandTedlnorogy
::g
=a
:;a
:a
:;B
:a
=a
=9
=9
:;a
==3
On-Site Guide 1 4 8
e The Institutionof EngineeringandTedlnorogy
::g
=a
:;a
:a
:;B
The foHow;ng durable labels are to be securely fixed on or adjacent to installed equipment
=9
&.4 Unexpected presence of nominal voltage
:;a exceeding 230 V
==3 514_10.1 Where a nominal voltage exceeding 230 V to earth exists and it would not normally be
expected, a warning label stating the maximum voltage present must be provided where
it can be seen before gaining access to live parts.
On-Site Guide 1 4 9
e The Institutionof EngineeringandTedlnorogy
::g Is
=a 6.5 Connedion of earthing and bonding
:;a conductors
:a
514.13.1 A permanent label to BS 951 Figure 6.5 must be permanently fixed in a visible position
at or near the point of connection o
every earthing conductor to an earth electrode,
:;B ii every protective bonding conductor to extraneous-conductive-parts, and
iii at the main earth terminal, where it is not part of the main switchgear.
l.
i
')i'li'I,: rl ) ' I
i'I I.· ·- \ I\ I . / /
:a
&.& Purpose o f switchgear and controlgear
=a 514.1.1 Unless there is no possibility of confusion, a label indicating the purpose of each item of
switchgear and controlgear must be fixed on or adjacent to the gear. It may be necessary
to label the item controlled, in addition to its controlgear.
150
identify the appropriate isolating devices, where equipment or an enclosure contains live
parts which cannot be isolated by a single device.
On-Site Guide
c The lnstirutionof 8'1gineering and Technofogy
::g Is
=a &.1 o Periodic inspection ,and testing
:;a s14.12. 1 A notice of durable material indelibly marked with the words as F;gure 6.10 must be fixed
in a prominent pos;tion at or near the origin of every installation. The person carrying
:a out the initial verific.ation must complete the notice and it must be updated after each
periodic inspection.
:;B
T Figure &.10 Label for periodic inspection and testing
IMPORTANT
This installation should be periodically inspected and tested and
a report on its condition obtained, as prescribed in the IET Wiring
Regulations BS 7671 Requirements for Electrical Installations.
=a 6.11 Diagra111s
514.9.l A diagram, chart or schedule must be provided indicating:
the number of points, size and type of cables for each circuit,
ii the method of providing protection against e'lectric shod,
iii information to identify devices for protection, isolation and switching, and
=9 iv any circuit or equipment vulnerable during a typical test, e.g. SELV power
supply units of lighting cirruits which could be damaged by an insulation test.
For simple installations, the foregoing information may be given in a schedule, with a
durable copy pmvided within or adjacent to the distribution board or consumer unit.
:;a
==3
On-Site Guide 1 5 1
e The Institutionof EngineeringandTedlnorogy
::g Is
=a T Figure 6.12 Label for the testing of a residual current device
CAUTION
This installation has wiring colours to
two versions of BS 7671.
:;a
which is used as an additional source of supply in parallel with another source, normaHy
the distributor's supply, warning notices must be affixed at the following locations in the
installation:
==3 a at the origin of the installation
b at the meter position, if remote from the origin
On-Site Guide 1 5 2
c Thelnstirution of 8'1gineeringandTechnofogy
Is
c at the consumer unit or distribution board to which the additional or
alternative supply is connected
d at all points of isolation of all sources of supply.
The warning notice must have the wording in Figure 6.14.
WARNING
MULTIPLE SUPPLIES
ISOLATE ALL ELECTRICAL SUPPLIES
BEFORE CARRYING OUT WORK
ISOLATE MA.INS AT
ISOLATE ALTERNATIVE SUPPLIES AT
WARNING
HIGH PROTECTIVE CONDUCTOR
CURRENT
The following circuits have a high protective
conductor current:
On-Site Guide 1 5 !
e The Institutionof EngineeringandTedlnorogy
Is
&.16 Waming notice - photovoltaic systems
=9 112.537.2.2 A:11junction boxes (PV generator and PV array boxes) must carry a warning label indlcating
that parts inside the boxes may still be live after isolation from the PV converter (Figure
:a 6.16).
:;B T Figure 6.16 Label advising of live parts within enclosures in a PV system
WARNING
PVSYSTEM
Parts inside this box or enclosure may still
be live after isolation from the supply.
:a
=a
=9
=9
:;a
==3
On-Site Guide
c The lnstirutionof 8'1gineeringand Technofogy
154
::g
=a
:;a
:a
:;B
:a where:
lp = 230
On-Site Guide 1 5 5
e The Institutionof EngineeringandTedlnorogy
T Table 7.1 (I) Maximum cable length for a 230 V final circuit in domestic premises and similar using 70 •c thermoplastic (PVC)
insulated and sheathed flat cable
Protective device Cable size Allowed installation methods Maximum length (m) (note 1)
- z.- "-0.8- Q-TN-S -:z.-" 0.35
(mm2)
Rating (A) Type (note 2) - - -Q-TN-C-S
-
RCD 30 No RCD RCD 30 No RCD
mA mA
1 2 3 4 5 6 7 8
Ring final circuits (5% voltage drop, load distributed)
30 BS 1361 2.5/1.5 l 00, 102, A, C 111 59Zs 111 111
8S3036 2.5/1.5 100,102. A, C 111 49zs Ill Ill
30 BS 1361 4.0/1.5 }100,101,102,A,C 183 69zs 183 159zs
BS 3036 183 57zs 183 147zs
},...,.,_,.,
32 as se-2.2. as 88-6 2.5/1.5 106 41zs 106 106
cb/RCBOlp!B 106 106 106 106
cb/RCBO l p ! C NPsc NPzs 82se 63ZS
cb/RCBO l p ! D NPsc NPzs 2sc lzs
0 32 BS 88-2 2.5/1.5 100,102, A. C 106 4lzs 106 106
32 8S88-2 4.0/1.5 100,101,102. A, C 176 48zs 176 138zs
g·.,. 32 BS 88·3 2.5/1.5 l 00, 102, A, C 106 27ZS 106 104ZS
32 8S88-3 4.0/1.5 I00,101,I02.A, C 176 32zs 176 122zs
1:
ooo
!!I=,,
32 BS 88-2.2, BS 88-6
cb/RCBO Type B
cb/RCBO Type C
4.0/1.5
} 100.10,.,ou c
176
176
NPsc
47ZS
127zs
NPzs
176
176
l33sc
137ZS
176
73zs
o..v,
cb/RCBO Type D NPsc NPzs 3sc lzs
[- Lighting circuits (3% voltage drop, load distributed)
a.f2
,2<5:
- < t'D 5 BS 1361 l.0/1.0 } 100,101,102,103, A. C 71 71 71 71
Ill
BS 3036 71 71 71 71
OI
'Y Table 7.1 (i) continued
Protective device cable size Allowed installation methods Maximum length (m) (note 1)
(mm') (note 2)
Rating (A) Type ------------
Z. s 0.8 C TN-S Z. s 0.35 0 TN-C-S
RCD 30 No RCD RCD 30 No RCD
mA mA
1 2 3 4 5 6 7 8
Lighting circuits (3% voltage drop, load distributed)
5 BS 1361 1.5/1.0 } 100,101,102,103, A, C 108 108 108 108
BS 3036 108 108 108 108
5 8S88-3 1.0/1.0 100,101,102,103, A. C 71 71 71 71
5 BS 88-3 1.5/1.0 100. 101,102,103, A. C 108 108 108 108
6 BS 88-2.2, BS 88-6 1.0/1.0 59 59 59 59
cb/RCBO Type B } 100, IOI, 102,ICJ3, A, C 59 59 59 59
cb/RCBO Type C 59 59 59 59
cb/RCBO Type D 25sc 25zs 365c 36zs
6 BS 88-2 1.0/1.0 100,101,102,103, A. C 59 59 59 59
6 BS 88-2.2, BS 88-6 1.5/1.0 90 90 90 90
0 cb/RCBOTypeB } 100,101,102,103, A,C 90 90 90 90
'ft cb/RCBOTypeC 90 83:zs 90 90
cb/RCBO2tP.! D 38sc 30zs 53sc 43:zs
g·.,. 6 BS 88-2 1.5/1.0 100,101,102,103, A. C 90 90 90 90
10 BS 88-2.2, BS 88-6 1.0/1.0 35 35 35 35
cb/RCBO Type B }•oo. 35 35 35 35
1:
IOI, 102,A,C
cb/RCBO Type C 34sc 34D 35 35
ooo cb/RCBO Type D 8sc 8zs 18sc 18zs
!!I=,,
o..v, 10 BS 88-2.2, BS 88-6 1.5/1.0 52 52 52 52
[ ' cb/RCBO Type B }1 0 0 . 10 1 , IOSA,C 52 52 52 52
a.f2 cb/RCBO Type C Slsc 41zs 52 52
,2<5:
-< ,,, cb/RCBO Type D 12sc 9zs 27sc 22zs
"'...
• Table 7,1(1) continued
Protedive device cable size Allowed installation methods Maximum length (m) (note 1)
Rating (A) Type (mm2 ) (note l )
------------
z. s 0.8 Q TN-5
RCD 30 No RCD
z. s 0.lS Q TN-C-5
RCD 30 No RCD
mA mA
I 2 l 4 5 6 7 8
Lighting circuits (3% voltage drop, load distributed)
10 BS 88·2 1.0/1.0 100, 101, 102, A. C 35 35 35 35
10 BS88-2 1.5/1.0 100, 101, 10:Z. A, C 52 52 52 52
15 BS 1361 1.5/1.0 100, 102, C 36 36 36 36
15 85 1361 2.5/1.5 100, 101, 10:Z. A, C 58 58 58 58
16 BS 88-2.2, BS 88-6 1.5/1.0 33 33 33 33
cb/RCBO Type B } 100,102, C 33 33 33 33
cb/RCBO Type C 21sc 17zs 33 30zs
cb/RCBO Type D NPsc NPzs 12sc 10zs
16 85 88-2.2, BS 88-6 2.5/1.5 53 53 53 53
0 cb/RCB01'ype8 } 100. 101, 10>. A, C 53 53 53 53
"ft cb/RCBO Type C 35sc 27zs 53 46D
cb/RCBO 1'ype D NPsc NPn 20sc 15zs
g·.,. 16 BS 88-2 1.5/1.0 100, 102,C 33 33 33 33
16 BS88-2 2.5/1.5 100, 101, 10:Z. A, C 53 53 53 53
1:
ooo
!!I=,,
16
16
BS 88-3
8588-3
1.5/1.0
2.5/1.5
100, 102, C
100, 101, 10:Z. A, C
33
53
33
53
33
53
33
53
o..v, Radial final drcuits (5'111volta1e drop, terminal load)
[- 5 851361 1.0/1.0 56 56 56 56
a_f;' 100, 101, 10:Z. 103, A, C
,2<5:
- < t'D BS3036 56 56 56 56
1:
cb/RCBO Type D 8sc 8zs 18sc 18zs
10 BS 88-2.2. BS 88-6 1.5/1.0 39 39 39 39
ooo cb/RCBO 1ype B 39 39 39 39
!!I=,, } 100, IOI, 10,. 103,A, C
o..v,
cb/RCBO 1ype C 39 39 39 39
[ ' cb/RCBO 1ype D Ilse 9zs 27sc 22zs
a.f2
,2<5:
-< ,,, 10 BS 88-2 1.0/1.0 100, 101, 102, A, C 26 26 26 26
Ill
IO
T Table 1.1 (I) continued
Protedive device cable size Allowed installation methods Maximum length (m) (note 1)
Rating (A) Type (mm2 ) (note l )
------------
z. s 0.8 Q TN-5
RCD 30 No RCD
z.s 0.lS Q TN-C-5
RCD 30 No RCD
mA mA
I 2 l 4 5 6 7 8
Radial final circuits (51\11 voltage drop, terminal load)
10 BS 88·2 1.5/1.0 100, 101, 102, 103, A. C 39 39 39 39
15 BS 1361 1.0/1.0 C 17 17 17 17
8S3036 NP NPol NPol NPol NPol
15 BS 1361 1.5/1.0 100,102,C 26 26 26 26
BS 3036 NP NPol NPol NPol NPol
15 BS 1361 2.5/1.S 1DO, 101, 102. A. C 43 43 43 43
8S3036 1D0,102, C 45 45 45 45
15 BS 1361 4.0/1.5 100, 101, 102, 103, A. C 72 72 72 72
BS 3036 100. 101. 102, A. C 75 75 75 75
0
'ft
16 BS 88-2.2, BS 88-6
cb/RCBOTypeB
cb/RCBO Type C
1.0/1.0
}c 16
16
145c
16
16
14D
16
16
16
16
16
16
cb/RCBO Type D NPsc NPD 85c 8D
g·.,. 16 BS 88-2 1.5/1.0 100, 102, C 24 24 24 24
16 8S88-2 2.5/1.S 100, 101, 102. A. C 40 40 40 40
1:
ooo
!!I=,,
16
16
BS 88-2
BS88-3
4.0/1.5
1.5/1.0
100, 101, 102, 103, A. C
1DO, 102, C
66
24
66
24
66
24
66
24
o..v,
16 BS 88-3 2.5/1.5 100, 101, 102, A. C 40 40 40 40
[ '
a.f2 16 8S88-3 4.0/1.S 1DO, 101, 102, 103, A, C 66 66 66 66
,2<5:
-< ,,,
OI
0
'Y Table 7.1 (i) continued
Protective device cable size Allowed installation methods Maximum length (m) (note 1)
(mm') (note 2)
Rating (A) Type ------------
Z. s 0.8 C TN-S Z. s 0.35 0 TN-C-S
RCD 30 No RCD RCD 30 No RCD
mA mA
1 2 3 4 5 6 7 8
Radial final drcults (5Cl'D vofta1e drop. terminal load)
16 BS 88-2.2, BS 88-6 1.5/1.0 24 24 24 24
cb/RCBO Type B 100, 102, C 24 24 24 24
cb/RCBO Type C 21sc 17zs 24 24
cb/RCBO Type D NPsc NPD Ilse lOzs
16 BS 88-2.2, BS 88-6 2.5/1.5 100, 101, 102, A, C 40 40 40 40
cb/RCBO Type B 40 40 40 40
cb/RCBO Type C 35sc 27zs 40 40
cb/RCBO Type D NPsc NPIS 20sc 15zs
16 BS 88-2.2, BS 88-6 4.0/1.5 66 66 66 66
cb/RCBO Type B } 100, 101, 10,. 103, "- C 66 66 66 66
cb/RCBO Type C 57sc 31zs 66 54zs
cb/RCBO lype D NPsc NPzs 33sc 18zs
0 20 BS 88•2.2, BS 88·6 2.5/1.5 100, 102,A,C 31 31 31 31
"ft BS 1361 100, 102, A, C 31 31 31 31
g'.,. BS 3036 NP NPol NPol NPol NPol
::, cb/RCBO Type B 31 31 31 31
2. cb/RCBO Type C } 100, 102, A. C 19sc 14zs 31 31
1:oo
cb/RCBO Type D NPsc NPIS 12sc 9zs
20 BS 88-2.2, BS 88-6 4.0/1.5 100, 101, 102, A, C 53 48zs 53 53
o BS 1361 100. 101. 102, A, C 53 44zs 53 53
!!I=,
o..v, 8S3036 C 57 48zs 57 57
[- cb/RCBO Type B 53 53 53 53
a_f;' cb/RCBO Type C 100, 101, 10:Z. A, C 31sc 17zs 53 39zs
-
,2<5:
- < t'D
cb D NPsc NPzs 20sc llzs
CII
T Table 1.1 (I) continued
Protedive device cable size Allowed installation methods Maximum length (m) (note 1)
Rating (A) Type (mm2 ) (note l )
------------
z. s 0.8 Q TN-5
RCD 30 No RCD
z.s 0.lS Q TN-C-5
RCD 30 No RCD
mA mA
I 2 l 4 5 6 7 8
Radial final drcults (51\11 voltage drop, terminal load)
20 BS 88-2.2. BS 88-6 6.0/2.5 100,101,102, 103,A,C 81 77D 81 81
BS 1361 100, 101,102, 103, A, C 81 71zs 81 81
8S3036 100, 102, A, C 85 171$ 85 85
cb/RCBO Type B 81 81 81 81
cb/RCBO Type C } 100, 101,102, 103, A. C 47sc 277$ 81 632s
cb/RCBO Type D NPsc NPzs 30lc 17zs
20 BS 88-2 2.5/1.5 100, 102,A. C 31 31 31 31
20 8S88-2 4.0/1.S 100, 101, 102, A, C 48sc 48sc 53 53
20 BS 88-2 6.0/2.5 100, 101,102, 103, A, C nsc. 77SC. 81 81
20 BS88-3 2.5/1.5 100, 102, A, C 31 31 31 31
0
"ft 20 BS 88-3 4.0/1.5 100, 101, 102, A, C 53 53 53 53
20 8588-3 100,101,102. 103,A,C 81 81 81 81
g·.,. 6.0/2.5
},
25 BS 88-2.2, BS 88-6 2.5/1.5 26 26 26 26
cb/RCBO Type B 26 26 26 26
1:
cb/RCBO Type C 6sc 5zs 26 24zs
cb/RCBO Type D NPsc NPzs 6sc 4zs
ooo 25 BS 88-2.2, BS 88-6 4.0/1.5 42 31zs 42 42
!!I=,,
o..v,
cb/RCBO Type B 42 42 42 42
[- cb/RCBO Type C
} 11111, 102. A. C
IDie 6D 42 28zs
a_f;' cb/RCBQ D NPsc NPD 9sc 5zs
,2<5:
- < t'D
OI
w
T Table 7.1 (I) continued
Protective device cable size Allowed installation methods Maximum length (m) (note 1)
(mm') (note 2)
Rating (A} Type ------------
Z. s 0.8 C TN-S Z. s 0.35 0 TN-C-S
RCD 30 No RCD RCD 30 No RCD
mA mA
1 2 3 4 5 6 7 8
Radial final dn:ults (5C!'D vofta1e drop. terminal load)
25 BS 88-2.2, BS 88-6 6.0/25 64 50zs 64 64
cb/RCBO Type B 100, 101, 102, A, C 64 64 64 64
cb/RCBO Type C 16sc 9zs 64 45zs
cb/RCBO Type D NPsc NPzs 145c 8zs
25 BS 88-2 2.5/1.5 C 26 23zs 26 26
25 8S88-2 4.0/1.5 100, 102, A. C 42 27zs 42 42
25 BS 88-2 6.0/2.5 100,101, 102,A.C 64 44zs 64 64
30 BS 1361 4.0/1.5 C 36 17zs 36 36
8S3036 NP NPol NPol NPol NPol
30 BS 1361 6.0/2.5 100, 102, A. C 53 27zs 53 53
BS 3036 C 57 23zs 57 57
0
'ft 30 BS 1361 10.0/4.0 100, 101, 102, 103, A, C 90 45zs 90 90
853036 100. 102, A. C 93 37zs 93 93
g·.,.
},
32 BS 88·2.2, BS 88·6 4.0/1.5 33 l lzs 33 33
cb/RCBO Type B 33 31zs 33 33
cb/RCBO Type C NPsc NPzs 33 18ZS
1:
ooo
!!I=,,
32
cb/RCBO Type D
BS 88-2.2, BS 88-6
cb/RCBO Type B
6.0/25
NPsc
49
49
NPzs
19zs
49
lsc
49
49
NPzs
49
49
o..v, 100,102, A, C
cb/RCBO Type C NPsc NPzs 49 29zs
[ ' cb D NPsc NPzs 1SC 1zs
a_f;'
,2<5:
-< ,,,
..
OI
T Table 1.1 (I) continued
Protedive device cable size Allowed installation methods Maximum length (m) (note 1)
Rating (A) Type (mm2 ) (note l )
------------
z. s 0.8 Q TN-5
RCD 30 No RCD
z.
s 0 . l S Q TN-C-5
RCD 30 No RCD
mA mA
I 2 l 4 5 6 7 8
Radial final drcults (51\11 voltage drop, terminal load)
32 BS 88-2.2. BS 88-6 10.0/4.0 81 31zs 81 81
cb/RC801ypeB 100, 101, 10:Z. 103, A, C
81 81 81 81
cb/RCBO 1ype C NPsc NPZ5 81 47ZS
cb/RCBO'JweD NPsc NPD 2K 1D
32 BS 88·2 4.0/1.S C 33 12zs 33 33
32 8S88-2 &.o/25 100, 102. A, C 49 19zs 49 49
32 BS 88·2 10/4.0 100, 101, 102. 103, A. C 81 31ZS 81 81
32 8S88-3 4.o/1.5 C 33 8D 33 30zs
32 BS 88-3 6.0/2.S 100, 102, A. C 49 13zs 49 48zs
0 32 8S88-3 10/4.0 100, 101, 102. 103, A, C 81 21ZS 81 79zs
},
40 BS 88-2.2, BS 88-6 6.0/2.5 43 43 43 43
g·.,. cb/RCBO Type B 43 20zs 43 43
cb/RCBO Type C NPsc NPzs 30sc 17zs
cb/RCBO Type D NPsc NPzs NPsc NPzs
1:
ooo
!!I=,,
40 BS 88-2.2, BS 88-6
cb/RCBOlypeB
cb/RCBO 'Jwe
C
10.0/4.o
}100.10>. A , C
66
66
NPsc
66
45zs
NPD
66
66
51sc
66
66
29zs
o..v,
cb/RCBO lype D NPsc NPZ5 NPsc NPZ5
[ ' 40 BS 88·2.2, BS 88-6 16.0/6.0 104 104 104 104
a.f2
,2<5:
-< ,,, cb/RCBO Type B } 100, 101, 102, llll, A, C
104 68zs 104 104
•
cb/RCBO Type C NPsc NPzs 81SC 44ZS
Ill cb/RCBO Type D NPsc NPzs NPsc NPzs
T T a b l e 7.1 (I) continued
Protective device cable size Allowed installation methods Maximum length (m) (note 1)
Rating (A} (mm') (note 2) Z. s 0.8 C TN-S Z. s 0.35 0 TN-C-S
Type ------- -------
RCD 30 No RCD RCD 30 No RCD
mA mA
1 2 3 4 5 6 7 8
Radial f i n a l d n : u l t s (5C!'D vofta1e drop. terminal load)
40 BS 88-2 6.0/2.S C 43 NPls 43 3Szs
40 8S88-2 10.0/4.0 100, 102, A, C 66 NPzs 66 57zs
40 BS 88-2 16.0/6.0 100, 101, 102, 103, A. C 104 NPls 104 B7zs
45 BS 1361 6.0/2.S C 21sc NPad 35 22ad
853036 NP NPol NPol NPol NPol
45 BS 1361 10.0/4.0 100, 102, C 36sc Sad 58 58
BS 3036 C 62 62 62 62
45 BS 1361 16.0/6.0 100, 101, 102, A, C 581c 31D 91 91
8S3036 102,C 97 97 97 97
45 BS 88·3 6.0/2.5 C 35 NPls 35 21zs
45 B588-3 10.0/4.0 100, 102, C SB NPzs SB 34zs
45 BS 88-3 16.0/6.0 100, 101, 102, A, C 91 NPls 91 51zs
Notes to Table 7.1 (i):
Voltage drop is the limiting constraint on the circuit cable length unless marked as follows:
► ad Limited by reduced csa of protective conductor (adiabatic limit)
► ol uble/device/toad combination not allowed in any of the installation conditions
► zs Limited by earth fault loop impedance z..
► sc Limited by line to neutral loop impedance (short-circuit).
l The allowed installation methods are listed, see Tables 7.1 (ii) and 7.1 (iii) for further description.
l NP - Not Permi11ed, prohibiting factor as note t.
For application of RCOs and RCBOs, see 3.6.3.
::g
=a T Table 7. lfli) Installation reference methods and cable ratings for 70 °C
:;a
thermoplastic. (PVC) insulated and sheathed flat cable with
protective conductor
=9
:;a
==3
On-Site Guide
e The Institution of Engineering and Tedlnorogy
I"
::g
=a T Table 7.1 flil) Installation methods spedfically for flat twin and earth cables in
:;a
thermali insulation
:a Method to
be used to
determine
:;B Number Examples Description
cunent-cerrying
capacity
100 Installation methods for flat Table 405
twin and earth c.able dipped
direct to a wooden joist, or
touching the plasterboard
ceiling surface, above a
plasterboard ceiling with
thermal insulation not
exceeding 100 mm in thickness
having a minimum U value of
0.1 W)m2K
101 lnstalation methods for flat Table4D5
:;a Notes:
t Q u d q the inner wall Sl.lface
1 Wherever practicable, a cable should be fixed in a position such that it will not be covered with
==3 1
thermal insulation.
Regulation 523.9, BS 5803•5: Appendix C Avoidance of overheating of electric cables', Building
egulations Approved 'Document B an ermal Insulation: avoiding risks, BR 262, BRE 2001 refer.
On-Site Guide 1 6 7
e The Institutionof EngineeringandTedlnorogy
::g
=a 7.1 Standard final circuits
:;a 7.2.1 Grouping of circuit cables
:a The tables assume heating {including water heating) cables are not grouped.
For cables •of household or similar installations (heating and water heating excepted), if
:;B the following rules are fol'lowed, derating for grouping is not necessary:
Cables are not grouped, that is, th e y are separated by at least two cable
diameters when installed under thermal insulation, namely installation
methods lOQ, 101, 102 and 103.
ii Cables clipped direct (including in cement or plaster) are dipped side by side
in one layer and separated by at least one cable diameter.
iii Cables above ceilings are dipped to joists as per installation methods 100 to
103 of Table 4A2 of SS 7671.
For other groupings, amblent temperatures h1gher than 3 0 °C or enclosure in thermal
insulation, cabte csa will need to be increased as per Appendix F of this Guide.
=a The total number of fused spurs is unlimited but the number of non-fused spurs is not to
exceed the total number of socket--outlets and items of stationary equipment connected
directly in the circ1uit.
A non fused spur feeds only one twin socket-outlet or one permanently connected item
of electrical equipment. Such a spur is connected to a circuit at the terminals of socket-
outlets or at junction boxes or at the origin of the circuit in the distribution board.
=9 A fused spur ,is connected to the circuit through a fused connection unit, the rating of
the fuse in the unit not exceeding that of the cable forming the spur and, in any event,
not exceeding 13 A The number of socket-outlets which may be supplied by a fused
spur is unlimited.
The circuit is assumed to have a load of 20 A at the furthest point and the balance to
the rating of the protective device evenly distributed. (For a 32 A device this equates to
a load of .26 .A at the furthest point.)
168
lengths wi'II need to be reduc.ed where voltage drop is the Hmiting factor, or halved where
load is aB at the extremity.
On-Site Guide
e The Institutionof Engineeringand Tedlnorogy
::g
=a The most onerous installation condition acceptable for the load and device rating is
presumed when cal.rulating the limiting voltage drop. If the installation conditions are not
:;a the most onerous a;Howed (see column 4 of Table 7.1 (i)) the voltage drop will not be as
great as presumed in the table.
:a 7.2.4 RCDs
:;B Where circuits have residual current protection, the Hmiting factor is often the maximum
loop impedance that will result in operation of the overcurrent device within 5 seconds
for a short-circuit (line to neutral) fault. (See note 1 to Table 7.1 (i) and limiting factor sc.)
=a with metal parts (not including screws or nails) and not protected by earthed
steel conduit or the like.
RCD protedion can be omitted in the following circumstances:
411.3.3(b) specific labelled socket-outlets, for example, a socket-outlet for a freezer.
However, the circuit cables must not require RCD protection as per v and vi
above, that is, circuit cables must be endosed in earthed steel conduit or
have an earthed metal sheath or be at a depth of at least 50 mm in a waH or
partition without metal parts
411.3.J(a) ii socket outf et circuits in situations where the use of equipment and work
on the building fabric and electrical installation is controUed by skilled or
instructed persons, for example, in some industrial and commercial locations;
l s e e 3.6.2.2. I
Cables install.ed on the surface do not specifically require RCD protection, however, RCD
411.S.2 protection may be required for other reasons, such as where the installation forms part
of a TT system and the earth fault loop impedance values for the overcurrent protective
device cannot be met.
On-Site Guide 1 6 9
e The Institutionof EngineeringandTedlnorogy
::g
=a 41L3.3{b) It is expected that all socket-outlets in a dwelling will have RCD protection at 30 mA,
however, the exception of Regulation 411.3.3 can be applied in certain cases.
:;a
7.2.6 n systems
:a For TT systems the figures for TN-C-S systems, with RCDs, may be used provided that:
On-Site Guide 1 7 0
c The lnstirutionof 8'1gineeringand Technofogy
::g
=a T Table 7.2.7(1), Rated short-circuit capacities
:a M6
M9
6
9
Circuit-breakers to BS EN 60898• lcn lcs
and RCBOs to BS EN 61,009 1.5 (15)
=a
3.0 ,(3.0)
6 (6.0)
10 ,(7.5)
15 {7.5)
20 ,(10.0)
25 {12.5)
* Two S:hort-circuit capacities are defined in BS E 60898 and BS EN 61009:
=9 For domesti.c installations the prospective faulc rurrent is unlikely to exceed 6 kA, up to which value the
lcn will equal tcs.
:;a The shon-circuit capadty of devices to BS EN 60947·2 ts as speci fied by the manufacturer.
==3
On-Site Guide 1 7 1
e The Institutionof EngineeringandTedlnorogy
::g
=a ii Circuit load characteristics
:;a 553.1.1.3 a Semi-endosed fuses. Fuses should preferably be of the cartridge type.
However, semi endosed fuses to BS 3036 are still permitted for use
:a breaker type
1
(D. I s to 5 s)
2.7 to 4 In Domestic and commercial installations having little
B 3 to 5 In or no switching surge
2 4 t o 7 In General use in commercial/industrial installations
=a C
3
5 to 10 In
7 to 10 In
where the use of fluorescent lighting, small motors,
etc., can produce switching surges that would
operate a Type 1 or B circuit-breaker. 1ype C or 3
may be necessary in highly inductive circuits such as
banks of fluorescent lighting
4 10 to 50 In N'ot suitable for general use
D 10 to 201 0 Suitable for transformers, X-ray mac-hines, industrial
=9 welding equipment, etc., where high inrush currents
may occur
NOTE: I" is the nominal rating of the circuit-breaker.
m Cable current-carrying capacities
For guidance on the coordination of device and cable ratings see Appe11dix F.
iv Disconnection times
411.3.2.2 The protective device must operate within the required disconnection time as
=9 411.3.2.3
411.3.2.4
appropriate for the circuit. Appendix B provides maximum permissible measured
earth foult loop impedances for fuses, circuit-breakers and RCBOs.
:;a 411.8.3
==3
On-Site Guide
c The lnstirutionof 8'1gineeringand Technofogy
172
::g
=a 7.3 lnstaHation considera:fions
:;a 7.3.1 Floors and ceilings
:a 522.6,100 Where a low voltage cable is installed under a floor or above a ceiling it must be run in
suoh a position that it is not 1;able to be damaged by contact with the floor or ceiling or
the fixings thereof. A cable passing through a joist or ceiling support must:
:;B be at least 50 mm from the top or bottom, as appropriate, or
ii have earthed armouring or an earthed metal sheath, or
iii be enclosed in earthed steel conduit or trunking, or
iv be provided with mechanical protection sufficient to prevent penetration •Of
the cable by nails, sorews and the like NOTE: the requirement to prevent
penetration ;s difficult to meet), or
414 v form part of a SELV or PELV circuit.
:a Maximum depth
of notch should be
0.125 x joist depth
Maximum diameter
of hole should be
0.25 x joist depth
=a Notches on top
in a zone between
0.07 and 0.25 x span
----
=9
Holes on oentre line
in a zone between
Span
=9
:;a
Notes:
On-Site Guide I 73
e The Institution of Engineering and Tedlnorogy
::g
=a 7.3.2 Walls and partitions
:;a s22.s.101 A cable concealed in a wall or partition must:
be at least 50 mm from the surface, or
:a ii have earthed armouring or an earthed metal sheath, or
iii be enclosed in earthed steel conduit or trunking, or
:;B iv be provided with mechanical protection sufficient to prevent penetration of
the cable by nails, screws and the like NOTE: the requirement to prevent
penetration ;s difficult to meet), or
v be installed either hori2ontally within 150 mm of the top of the wall or
partition or vertic-ally within 150 mm of the angle formed by two walls, or run
horizontally or vertically to an accessory or consumer unit (see Figure 7.3.2),
or
414 v i form part of a SELV or PELV circuit.
In domest,ic and similar installations, cables not installed as per i, ii, iii or iv but complying
with v must be protected by a 30 mA RCD.
522.6.102 In domestic and similar installations, cables installed in walls or partitions with a metal or
part metal construction must be either:
:a a
b
m,
installed as ii, iv or vi above, or
protected by a 30 mA RCO.
For instaUations under the supervision of a skilled or instructed person, such as
=a
commercial or industrial where only authorized equipment is used and only skilled
persons will work on the building, RCD protection as described above is not required.
NOTE.: Domestic or similar insta'llations are not considered to be under the supervision
of skilled or instructed persons.
=9
Room2
=9 Room 1
:;a
==3
On-Site Guide 1 7 4
c Thelnstirution of � n g andTechnofogy
::g
=a 528 7.4 Proximity t o eledrical and other services
:;a 528.3 Electrical and all other services must be protected from any harmfu'I mutual effects
foreseen as likely under conditions of normal service. For example, cables should not be
:a in oontact with or run alongside hot pipes.
:a
Band I circuit: Circuit that is nominally extra-low voltage, i.e. not exceeding 5 0
V a.c. or 120 V d.c. For example, SELV, PELV, telecommunications, data and
signalling
Band II circuit: Cirwit that is nominally low voltage, i.e. 51 to 1000 V a.c. and
121 to 1500 V d.c. Telecommunication cables that are generally ELV but have
=a ringing vo[tages exceeding 5 0 V are Band L
s2s.1, NOTE.: Fire alarm and emergency lighting circuits must be separated from other cables
Note 2 and from each other, in compliance with '8S 5839 and BS 5266.
=9 V a.c. or 900 V d.c. to earth (Band II), and telecommunications cables (Band f).
Voltage to earth Nonnal separation Exceptions to nonnal separation
On-Site Guide 1 7 5
e The Institutionof EngineeringandTedlnorogy
::g
=a T Table 7. 4.2(11) Internal cables
:;a Minimum separa.tion distances between intemaf low voltage electricity supply
cables operating in excess of SO V a.c. or 120 V d.c. to earth, but not exceeding 600
:a
V a.c. or 900 V d.c. to earth (Band II), and telecommunications cables (Band l).
Voltage to earth Normal separation Exceptions to normal separation
distances distances, plus conditions to exception
:;B Exceeding 50 V a.c. so mm 50 mm separation need not be
or 120 V doc., but not maintained, provided that
exceeding 600 V a.c. (i) the LV cables are enclosed in
or900V d.c. separate conduit which, if metallk,
is earthed in accordanc:e with
BS 7671, OR
(ii) the LV cables are enclosed in
separate trunking which, if metallic,
is earthed in ac.cordanc:e with BS
7671, OR
(iii) the LV cable is of the mineral
insulated type or is of earthed
armoured construction.
:a Notes:
1 Where the LV cables share the same tray then the normal sepa ration should be met
2 Where LV and telecommunications cables are obliged to cross. additional insulation should be
provided at �he crossing point; this is not necessary if either cable is armoured.
=9 Under these circumstances, if Hne and neutral conductors or switch feeds and switch
wires are not run dose together, there may be interference with the induction loop.
:;a This can occur when a conventional two-way lighting circuit is ;nstalled. Th;s effect can
be reduced by connecting as shown in Figure 7.4.4.
==3
:;a
:a switch feed
line neutral
:;B
f-switch
wire
light point
2-way switch
cores grouped
together
:a
=a 2-way switch
=9 Table s1 NOTE: Black/grey switch conductors to be identified in accordance with Table Kl.
:;a connected by means of an industrial plug and socket complying with BS EN 60309-2.
!Equipment having a protective conductor current exceeding 10 mA should be connected
==3 by one of the following methods:
On-Site Guide
e The Institutionof EngineeringandTedlnorogy
177
::g
=a permanently connected to the wiring of the installation, with tlie protective
conductor selected in accordance with Regulation 543.7.1.103. The
:;a permanent connection to the wiring may be by means of a flexible cable
ii a flexible cable with an industrial plug and socket to BS EN 60309-2, provided
:a that either:
a the protective conductor of the associated flexible cable is of cross-
:;B sectional area not less than 2.5 mm 2 for plugs up to 16 A and not less
than 4 mm 2 for plugs rated above 16 A, or
b the protective conductor of the associated flexible cable is of cross-
sectional area not less than that of the line conductor
iii a protective c-0nductor complying with Section 543 with an earth monitoring
system to BS 4444 installed which, in the event of a continuity fault occurring
in the protective conductor, automatica\ly disconnects the supply to the
equipment.
7.5.2 Circuits
543.7.1.103 The wiring of every final circuit and distribution circuit having a protective conductor
current likely to exceed 10 mA must have high integrity protective conductor connections
complying with one or more of the following:
:a a single protective conductor having a cross•sectional area not less than 10
mm 2, oomplying with Regulations 543.2 and 543.3
ii a single copper protective conductor having a csa not less than 4 mm2,
=a
complying with Regulations 543.2 and 543.3, the protective conductor being
enclosed to provide additional protection against mechanical damage, for
example within a flexibl.e conduit
543.7.1.104 iii two individual protective conductors, eadh complying with Section 543, the
ends being terminated independently
543.7.1.103 iv earth monitoring or use of double-wound transformer.
543.7.1.105 NOTE: Distribution boards are to indicate circuits with high protective conductor currents (see 6.15).
On-Site Guide
c The lnstirution of 8'1gineering and Technofogy
I'
::g
=a T Figure 7.5.J(i) Ring final circuit supplying socket-outlets
:;a
:a Distribution
board
PE
-. -- • •
Soc:ket-ou lets must have two
terminals for protective conductors
:;B Separate
connections One termrnal to be used for each
prot.ectfve conductor
Minimum size of 1.5 mm2
. . •· -. •
.. .-
I I •
'Y Figure 7.5.J(H), Radial fina'I circuit supplying socket-outlets with duplicate
protective oonductors
P£ Separate
connections
:a
Duplicate protective conductor. Keep dose
to circuit conductors to reduce EMC effects
I(
Distribution
=a
board
• • • • . ·• . -
Socket-outlets must have two termlnal.s for protective conductors
One lerminal to be used for each protective conductor
Minimum size of l.S mm 2
=9
7.6 Eledrical supplies to furniture
Where electrical equipment is insta,lled within purpose-built items of furniture, such as
cupboa,rds, shop displays or lecterns, and supplied from a p!ug and socket arrangement,
no specific standard exists for such installations, therefore guidance is given here which,
essentially, follows the principles of BS 7671. For electrical systems in office furniture and
educationa,I furniture, BS 6396:2008 currently exists for installations which are supplied
via a 13 A as 1363 plug.
=9 The following points should be adhered to:
On-Site Guide 1 7 9
e The Institutionof EngineeringandTedlnorogy
::g
=a ► cables of Band I and Band II circuits, which are often hidden beneath the
desk, should be sufficiently mechanically protected from damage caused by
:;a movement of chairs, storage of materials and the movement of feet and legs
► cable management systems or containment, such as conduit or trunking,
:a should be installed to aUow the safe routing, protection and separation of
cables through the equipment
:;B ► long-term use of multi-gang extension leads should be avoided by installing
a sufficient number of socket-outlets to supply the equipment to be used;
employers should not allow ad hoe solutions to be created by users. See also
see BS 6396:2008
► ensure that cables are sufficiently protected and c,annot become trapped
or damaged where des ks are designed to be extended or altered to suit
different activities or users.
543.2.1 There is no general requirement to ensure electrical continuity across the metallic frame
543.2.6 of an item of forniture unless the frame has been designed to be used as a protective
conductor.
:a
=a
=9
=9
:;a
==3
On-Site Guide
c The lnstirutionof 8'1gineering and Technofogy
180
::g
B
=a
:;a Locations containing
:a
:;B
a bath or showelr
:a 701.512.2
edge of the bath or shower basin)
iii protection against ingress •Of water is specified for equipment within the
zones, see Table 8.1 and Figures 8.1 (i) to 8.1 (iii)
701.512.3 iv there are restrictions as to where appliances, switchgear and wiring
=a
accessories may be installed, see Table 8.1 and Figures 8.1 (i) to 8.1 (iii).
701.415.2 Supplementary bonding of locations containing a bath or shower is required unless all
the following requirements are m e t
411.3.2.2 ► all circuits of the location meet the required disconnection times,
701.411.3.3 ► all circuits of the location have additional protection by 30 mA RCDs, and
411.3.1.2 ► all extraneous conductive parts within the location are effectively connected
=9
:;a
==3
On-Site Guide 1 8 1
e The Institutionof EngineeringandTedlnorogy
::g la
=a T Table 8.1 Requirements for equipment (current-using and accessories) in a
:;a
location containing a bath or shower
=9
:;a
==3
On-Site Guide
e The Institutionof EngineeringandTedlnorogy
182
la
T Figure 8.1 (i) Zone dimensions in a location containing a bath
Section Plan
---------------------
Zonel Zone 2 Outside Zones
r
Window re<:er1s Zone 2 ZoneO Zone2 Outside Zones
2.2Sm
0.6m ..
Zon.eO
S - thickness of partition
T Figure 8.1(11) Zones in a location containing a shower with basin and with
permanent fixed partition
Section Plan
_,..- Recess above ceiling
•
wminaire ZoneO Zone2
Zonel Zone2 Outside Zones
s
i0.6 -S) m
Sm S = thickness of ,partition
Shower
0.6m •
ZoneO
On-Site Guide
e The Institutionof EngineeringandTedlnorogy
I'
::g la
=a T Figure 8.1 (Iii) Zones in a location containing a shower without a basin, but with
a partition
:;a Section .Plan
:a Celllng
l
ZoneO Axed water
outlet
:;B Zone1 Zone1 Outside Zones
Y 1.2m
'.
Outside Zones
2..2.Sm
in-.
=a
8.3 Underfloor heating systems
8.3.1 Locations containin!1 a bath and shower
701.753 Underfloor heat;ng installations in locations containing a bath and shower should have
an overall earthed metallic grid or the heating cable should have an earthed metalHc
=9 sheath, which must be connected to the protective conductor of the supply circuit.
On-Site Guide
c The lnstirutionof 8'1gineering and Technofogy
184
::g
=a
:;a lnspedion and
:a
:;B
testing
9.1 Inspection and testing
610.1 Every installation must be inspected and tested during erection and on completion before
being put into service to verify, so far as is reasonably practicab'le, that the requirements
of the Regulations have been met.
Precautions must be taken to avoid danger to persons and to avoid damage to property
and installed equipment during inspection and testing.
:a
631.4 If the inspection and tests are satisfactory, a signed Electrical Installation Certificate
632.l together with a Schedule of Inspections and a Schedule of Test Results (as in Appendix
632.3 G) are to be given to the person ordering the work.
Inspection
=a 9.J
9.2.1 Procedure and purpose
611.l Inspection must precede testing and must normally be done with that part of the
installation under inspection disconnected from the supply.
611.2 The purpose of the inspection is to verify that equipment is:
:;a 433
525
iv selection of conductors for current-carrying capacity and voltage drop, in
accordance with the design
v connection of single-pole devices for protection or switching in line
==3
132.14.1
conductors only
526 v i correct connection of accessories and equipment (in.eluding polarity)
On-Site Guide 1 8 5
e The Institutionof EngineeringandTedlnorogy
::g
=a 527.2 vii. presence of fire barriers, su;table seals and protection against thermal effects
viii methods of protection against electric shock:
:;a
410.3.3
a basic protection and fault protection, i.e.
:a 414 SELV
PHV
412 double insulation
:;B reinforced insulation
b basic protection, i.e.
416.l insulation of live parts
416.2 ► barriers or enclosures
c fault protection
411 automatic disconnection of supply
The following to be confirmed for presence and sized in accordance
with the design:
- earthing conductor
- circuit protective conductors
- protective bonding conductors
:a - earthing arrangements for combined protective and functional
purposes
- presence of adequate arrangements for alternative source(s),
where applicable
=a - PELV
- choice and setting of protect;ve and monitoring devices (for fault
and/or overcurrent protection)
413 electrical separation
418.3
415.1 d additional protection by RCDs
132.11 ix prevention of mutual detrimental influence (refer to 7.4)
=9 537 x presence of appropriate devices for isolation and switching correctly located
445 xi presence of undervoltage protective devices (where appropriate)
514 xii labeHing of protective devices induding circuit-breakers, RCDs, fuses, switches
and te rm inals, main earthing and bonding connections
522 xiii selection of equipment and protective measures appropriate to external
influences
132.12 xiv adequacy of ac.cess to switchgear and equipment
514 x v presence of danger notices and other warning signs (see Section 6)
514.9 xvi presence of diagrams, instructions and s;milar information
=9 522 xvii erection methods.
:;a
==3
On-Site Guide
c The lnstirutionof 8'1gineeringand Technofogy
186
::g
=a 9.3 Testing
:;a Testing must include the relevant tests from the fo'llowing checklist.
:a s12.1 When a test shows a, failure to comply, the failure must be corrected. The test must then
be repeated, as must any earlier test tl,a,t could have been influenced by the failure.
:a
conductor only, tli at bayonet and Edison screw lampholders (except for E14
and E27 to, BS EN 60238) have their outer contacts connected to the neutral
conductor and that wiring has been correctly connected to socket-outlets and
other accessories
612.7 iv earth electrode resistance (TT systems)
=a 612.9
612.11
v earth fault loop impedance (TN systems)
vi prospective short-circuit current and prospective earth fault current, if not
determined by enquiry of the distributor
61 2 .13 vii. function al testing, 1ind udi ng:
► testing of RCDs
► operation of all sV!Jitchgear
=9 612.14 viii verification of voltage drop (not normally required during initial verification).
=9
:;a
==3
On-Site Guide
e The Institutionof EngineeringandTedlnorogy
187
::g
=a
:;a
:a
:;B
:a
=a
=9
=9
:;a
==3
On-Site Guide
e The Institutionof EngineeringandTedlnorogy
188
::g
=a
:;a
:a
Guidance on
initial testing of
ID
:;B
installations
10.1 Safety and equipment
HSR25, Electrical testing involves danger. The Electricity at Work Regulations 1989 state that working
EWR on live conductors is permissible provided that it ;s reasonable in all the circumstances
Regulation
for the work to be carried out and that suitable precautions are taken to prevent injury.
14
On-Site Guide 1 8 9
e The Institutionof EngineeringandTedlnorogy
10.2 Sequence .of tests
NOTE: The advice given does not preclude other test methods.
612.1 Tests should be carried out in the following sequence:
On-Site Guide
c The lnstirution of 8'1gineering and Technofogy
190
::g
=a Test method 1 can only be used to measure (R 1 + R i ) for an 'all-insulated' installation,
:;a
such as an installation wired in 'twin and earth'. Installations incorporating steel conduit,
steel trunking, MICC and PVC/SWA cables wm produce parallel paths to protective
conductors. Such installations should be inspected for soundness of construction and
:a test method 1 or 2 used to prove continuity.
:a
ceiling rose ,
at end •Ofclrru i't
_,.. .
.·•i� p o ra ry llnk
=a • •
•
N
•L •••••
L J J J JJ JJ J J
main switch off,
all fuses removed.
drcuit-breaken and RCBOs off
=9 lamps removed
Continuitytestmethod2
Connect one terminal of the test instrument to a long test lead and connect this to the
instaHation main earthing termina'L
Connect the other terminal of the instrument to another test lead and use this to make
=9 t
contact w i h the protective conductor at various points on the circuit, such as luminaires,
switches, spur outlets, etc. (see Figure 10.3.l (ii)).
:;a If the instrument does not Include an 'auto•nuU' facility, or this is not used, the res;stance of
the test leads should be measured and deducted from the resistance readings obtained.
==3 The resistance of the protective oonductor R 2 is recorded on the Schedule of Test
Results; see Appendix G.
On-Site Guide 1 9 1
e The Institutionof EngineeringandTedlnorogy
::g
=a T Figure 10.J.lfii) Continuity test method 2
:a at end of crroult
• • •••••••••
L f.llJJJJlJ
main switch off,
all fuses removed,
c1rcuit•breakers and RCBOs off
lamps removed
test instrument ·
:a
ii Continuity of the earthing condudor and protedive bonding
condudors
=a Continuity test method 2
For main bondin& connect one terminal of the test instrument to a long test lead and
connect this to the installation main earthing terminal. C.onnect the other terminal of the
instrumentto another test lead and use this to make contact with the protective bonding
conductor at its further end, such as at its connection to the incoming metal water, gas
or oil service.
=9 The Continuity and connection verified boxes on the Electrical lnstaHation Certificate
should be ticked if the continuity and connection of the earthing conductor and of each
main bonding conductor are satisfactory. The details of the material and the cross
sectional areas of the conductors must also be recorded.
Ste;p 1
==3
192
The line, neutral and protective conductors are identified at the distribution board and
the end-to-end resistance of each is measured separately (see Figure 10.3.2(i)). These
On-Site Guide
c The lnstirution of 8'1gineering and Technofogy
::g
=a resistances are r1, rn and r2 respectively. A finite reading confirms that there is no open
:;a
circuit on the ring conductors under test. The resistance values obtained should be
the same (within 0.05 Q) if the conductors are all of the same size. If the protective
conductor has a reduced csa the resistance r2 of the protective conductor loop will be
:a proportionally higher than that of the line and neutral loops, for example, 1.67 times for
2.5/1.5 mm 2 cab'le. If these relationships are not achieved then either the conductors
:;B are incorrectly identified or there is something wrong at one or more of the accessories.
Y Figure 10.S.2(1) Step 1: The end-to-end resistances of the line, neutral and
protective conductors are measured separatel,y
:a
Step 2
=9 The line and neutral conductors are then connected together at the distribution board
so that the outgoing line conductor is connected to the returning neutral conductor and
vlce versa (see Figure 10.3.2(ii)). The resistance between line and neutral conductors
is measured at each socket-outlet. The readings at each of the socket-outlets wired into
the ring will be substantially the same and the value will be approximately one-quarter
of the resistance of the line plus the neutral loop resistances, i.e. (r1 + rn)/4.. Any socket-
outlets wired as spurs will have a higher resistance value due to the resistance of the
spur conductors.
=9 NOTE: Where sing1e-core cables are used, care should be taken to verify that the
line and neutral conductors of opposite ends of the ring circuit are connected together.
:;a An error in this respect will be apparent from the readings taken at the socket-outlets,
progresswely increasing in value as readings are taken towards the midpoint of the ring,
then decreasing again towards the other end of the ring.
==3
On-Site Guide 1 9 !
e The Institutionof EngineeringandTedlnorogy
::g
=a T Figure 1O.J.:Z(li) Step 2: The line and neutral conductors are cross-connected
:;a
and the resistance measured at each socket-outlet
:a
:;B =
- line
cpc
- neutral
Step 3
The above step is then repeated, this time with the line and cpc cross-connected at
:a
the distribution board (see Figure 10.3.2(iii)). The resistance between line and earth
is measured at each socket-outlet The readings obtained at each of the socket outlets
wired into the dng will be substantially the same and the value will be approximately
one-quarter ·of the resistance of the line plus cpc loop reststances, i.e. (r 1 + ri)/4. As
before, a higher resistance value will be measured at any socket outlets wired as spurs.
=a The hi.ghest value recorded represents the maximum (R 1 + Rv of the circuit and is
recorded on the Schedule of Test Results. The value can be used to determine the earth
fault I.cop impedance (Zs) of the cirouit to verify compliance with the 'loop impedance
requirements of BS 7671 (see 10.3.6).
T Figure 10.3.2(1ii) Step 3: The line conductors and cpc are cross-connected and
the resistance measured at each socket-outlet
=9
- line
- cpc
- neutral
=9
:;a •connection for taking '
reading5 of Ri + R2
at sockets
�----'
==3
194
This sequence of tests also verifies the polarity of each socket-outJet, except that where
the testing has been carrled out at the terminals on the reverse of the accessories; a
On-Site Guide
e The Institutionof Engineeringand Tedlnorogy
::g
=a visual inspection is required to •Confirm correct polarity connections, and dispenses with
the need for a separate polarity test.
:;a
10.3.3 Insulation resistance
:a
612.3
Pre-test checks
:;B a Pilot or indicator lamps and capacitors are disconnected from circuits to
prevent misleading test values from being obtained
b If a circuit indudes vo!tage sensitive electronic devices such as RCCBs,
RCBOs or SRCDs incorporating electronic amplifiers, dimmer switches, touch
switches, delay timers, power controllers, electronic starters or controlgear for
fiuorescent lamps, etc., either:
1 the devices must be temporarily disconnected, or
2 a measurement should be made between the live conductors (line and
neutral) connected together and the protective earth only.
ii Tests
Tests should be carried out using the appropriate d.c. test voltage specified in Table 10.3.3.
The tests should be made at the distribution board or consumer unit wi h the main
:a switch off.
When testing simple installations, i.e. those consisting of one consumer unit only, the
installation could be tested as a whol.e with aU fuses in place, switches and circuit-
breakers dosed, lamps removed and other current-using equipment disconnected; see
=a Figure 10.3.3(i).
T figure 10.3.3(1) Insulation resistance test of the whole installation
=9 zr-i·
switch on
-.
main switch off
circuit-breakers closed
mair1 protective
==3 When testing individual cirouits, it is important to remove the fuse or open the circuit-
breaker of that circuit; this ensures that no other circuits at the board influence the result
of the test.
On-Site Guide 1 9 5
e The Institutionof ErlgineeringandTedlnorogy
::g
=a Where the removal of lamps and/or the disconnection of current-using equipment is
:;a
impracticable, fhe loca'I switches controlling such lamps and/or equipment should be
open.
:a Where a, cir,cuit contains two-way switching, the two.way switches must be operated one
at a time and further 1nsu'lation resistance tests carried out to ensure that all the circuit
wiring is tested.
:;B
' f Table 10.J..J Minimum values of Insulation resistance
Table 61
Circuit nominal voltage Test voltage Minimum insulation
(V d.c.) resistance (MQ)
SELV and PELV 250 0.5
Up to and induding 500 V with the exception 500 1.0
of SELV and PELY, but induding FELV
Notes:
I Insulation resistance measurements are usually much higher than those of Table I 0.3.3.
2 More stringent requirements are app!icabfe for the wiring of fire alarm systems in buildings; see BS
5839·1.
196
Resistance readings obtained should be not less than the value stated in Table 10.3.3.
On-Site Guide
c The lnstirutionof 8'1gineeringand Technofogy
::g
=a T Figure 10.J.3(11) Insulation resistance test between live conductors of a circuit
:;a
:a
:;B
two-way switches switch on
main protective
bonding conductor
lamps removed
=a
Test between. the live conductors (line and neutral) and the circuit protective conductors
at the distribution board (Figure 10.3.3(iH) illustrates neutral to earth only).
For a circuit containing two-way switching or two-way and intermediate switching, the
switches must be operated one at a time and the drc-Uit subjected to additional insulation
resistance tests.
=9
=9
:;a
==3
On-Site Guide
e The Institutionof EngineeringandTedlnorogy
197
::g
=a T Figure 10.J.3(111) Insulation res;stance test between neutral and earth
:;a
:a
:;B -
two-way switches switchOfl
main protective
bonding conductor
lamps removed
:a Notes:
1 The test may initially be carried out on the complete installation.
l Earthing and bonding connections are in place.
612.3.1 J The earth[ng conductor must connect the main earthing terminal to the means of eanh[ng whilst
=a testing.
Three-phase
Test to earth from all live conductors (induding the neutral) connected together. Where
a low reading is obtained it is necessary to test each conductor separately to earth, after
disconnecting all equipment.
Resistance readings obtained should be not less than the value stated in Table 10.3.3.
=9 v SELV and PELV circuits
612.4., Test between SE'lV and PELV cir,cuits and live parts of other circuits at 500 V d.c.
612.4.2
Test between SELV or PELV conductors at 250 V d.c. and between PELV conductors and
protective conductors •Ofthe PELV cirruit at 250 V d.c.
Resistance readings obtained should be not less than the value stated in Table 10.3.3.
vi FELV circuits
=9 612.4.4 FELV circuits are tested as low voltage cirruits at 500 V d.c.
:;a
==3
On-Site Guide
c The lnstirution of 8'1gineering and Technofogy
198
::g
=a 10.3.4 Polarity
:;a See Figure 10.3.4.
The method of test prior to connecting the supply is the same as test method 1 for
:a checking the continuity of protective conductors which should have already been
carried out (see 10.3.1). For r;ng final circuits a visual check may be required (see 10.3.2
:;B following step 3}.
H. is import�nt to confirm that:
1 overcurrent devices and single-pole controls are in the line conductor,
l except for E14 and E27 lampholders to BS EN 60238, centre contact screw
lampholders have the outer threaded contact connected to the neutral, and
3 socket-outlet and simHar aiccessory polarities are correct.
After connection of the supp'ly, correct polarity must be confirmed using a voltage
indicator or a, test lamp (in eifher case with leads complying with the recommendations
GS 38 of HSE Guidance Note GS 38).
:a ceiling rose
at end of circuit
·l
=a
• -• •••••••• -·
.-·i ; orary llnk
• • •
• • • • • • • • •
- • • • j,e • • •
N
• •l • • •
•
• l JJJJJJJJJ
•
=9 main switch off
circuit-breakers off
test instrument
lamps removed
=9 NQ,tE: The test may be carried out either at l;ighting points or switches.
On-Site Guide 1 9 9
e The Institutionof EngineeringandTedlnorogy
::g
=a A loop impedance tester is connected between the line conductor at the origin of the
installation and the earth electrode with the test link open and a test performed. This
:;a impedance reading is treated as the electrode resistance and is then added to the
resistance of the protectrve conductor for the protected circuits. The test should be
:a carried out before energising the remainder of the instaHation.
Table 41.5 The measured resistance should meet fhe following criteria and those ·Of 10.3.6 but, in
:;B Note 2 any event, should not exceed 200 Q.
411.5.3 For TT systems, the value of the earth electmde resistance RA in ohms multiplied by the
operating a.ment in amperes of the protective device IM should not exceed 50 V.
For example, if RA = 200 Q, then the maximum RCD operating current should not
exceed 250 mA.
REMEMBER TO REPLAC1E THE TEST LINK.
:;a
significantly different, the above procedure should be repeated with test electrode T1
placed further from the electrode under test
==3
:;a
:a
:;B
test tnstrument
electrode
undertest
:a 15•25m 15-25m
1he instrument output current ma,y be a,c. or reversed d.c. to overcome electrolytic
effects. As these types of test instrument employ phase-sensitive detectors (PSD), the
=a
errors associated with stray currents are eliminated. The instrument should be capabte
of checking that the resistance of the temporary spikes used for testing is within the
accuracy limits stated in the instrument specification. This may be achieved by an
indicator provided on the instrument, or the instrument should have a sufficiently high
upper range to enable a discrete test to be performed on the spikes. If the tempora ry
spike resistance is too high, measures to reduce the resistance will be necessary, such as
driving the spikes deeper into the ground.
==3
:;a
==3
On-Site Guide
c The lnstirutionof 8'1gineeringandTechnofogy
1102
10.J.9 Functional testing
612.13 RCDs should be tested as described ,n Section n.
Switchgear, controls, etc., should be functionally tested; that is, operated to check that
they work and are properly mounted and installed.
:a Appx. 4
Table 4Ab
Appendix 4, paragraph 6.4, gives maximum values of voltage drop for both lighting and
other uses and depending upon whether the installation is supplied directly from an LV
distribution system or from a private LV supply.
It should be remembered that voltage drop may exceed the values stated in Appendix
=a 4 in situations, such as motor starting periods and where equipment has a high inrush
current, where such events remain within the limits specified in the relevant product
standard or reasonable recommendation by an equipment manufacturer.
=9
=9
:;a
==3
On-Site Guide 1 1 0 3
e The Institutionof EngineeringandTedlnorogy
::g
=a
:;a
:a
:;B
:a
=a
=9
=9
:;a
==3
On-Site Guide
e T h e Institution o f Engineering and Tedlnorogy
I '°'
::g
=a
:;a Operation of 11
:a
:;B
RC s 1 D
Residual current device (ROD) is the generic term for a device that operates when the
residual current in the circuit reaches a predetermined value. An RCD is a protective
device used to automatically disconnect the electrical supply when an imbalance is
detected between the 'line and neutral conductors. In the case of a single-phase drcuit,
see Figure 11.0, the device monitors the difference in currents between the line and
neutral conductors. In a healthy circuit, where there is no earth fault current or protective
conductor current, t he sum of the currents in the line and neutral conductors is zero. If a
line to earth fau'lt deve'lops, a portion of the line conductor aurrent will not return through
:a the neutral conductor. The device monitors this difference, operates and disconnects
the circuit when the residual current reaches a preset limit, the residual operating current
(ltin).
Trip c o i l
N ■■----_,,/._ _ ..
=9
:;a E
==3
On-Site Guide 1 1 0 5
e The Institutionof Engineeringand Tedlnorogy
::g
=a 612.8 1'1.1 General test procedure
:;a The tests are made on the load side of the RCD, as near as practicab'le to its point of
installation and between the 'line conductor of the protected circuit and the associated
:a drouit protective conductor. The load supplied should be disconnected during tne test.
=a
current of the RCD, the device should open ;n less than 300 ms unless it is
of 'Type S' (or selective) which incorporates an intentional time delay. In this
case, it should trip within a time range from 130 ms to 500 ms.
On-Site Guide 1 1 0 6
c Thelnstirution of 8'1gineeringandTechnofogy
::g
=a 1'1.& Integral test device
:;a 612.13.1 An integral test device is incorporated in each RCD. This device enables the electrical
and mechanica'I parts of the RCD to be verified, by pressing the button marked T' or 1
:a
As each lrive conductor of the RCD is incorporated in the magnetic sensing circuit it is
not necessary to perform the test for poles L2 and L3. However, if there is any doubt as
to the authenticity of the device in question - in terms of a fake or counterfeit device -
the advice would be to repeat the test for poles L2 and L3. It goes without saying that
such important devices, designed to protect 'life and property, should be obtained from
=a trusted sources and made by reputable manufacturers.
If a decision is made to test the RCD on all three lines, there should be Httle on no
discemable difference in operating times as each pole is incorporated in the magnetic
sensing circuit If, for example, the test performed on one pole did not meet rlie required
disconnection time, yet tests on the other two poles were satisfactory, the device should
be considered faulty and rep'laced.
=9
=9
:;a
==3
On-Site Guide
e The Institutionof EngineeringandTedlnorogy
1107
::g
=a
:;a
:a
:;B
:a
=a
=9
=9
:;a
==3
On-Site Guide
e The Institutionof EngineeringandTedlnorogy
1108
::g
=a
:;a
:a
Appendix
Maximum demand
■
:;B
and diversity
311 This appendix provides information on the determination of the maximum demand for
an instaHation and includes the current demand to be assumed for commonly used
equipment. It also includes some notes on the application of allowances for diversity.
The information and values given in this appendix are intended only for guidance be-
cause it is impossible to specify the appropriate allowances for diversity for every type of
:a installation and such allowances caU for special knowledge and experience. The values
given in Table A2 1 therefore, may be increased or decreased as decided by the installa-
tion designer concerned. No guidance is given for blocks of residential dwellings, large
hotels, industrial and large commercial premises; such installations should be assessed
=a on a case-by-case basis.
The current demand of a final circuit is determined by adding the current demands of
all points of utilisation and equipment in the circuit and, where appropriate, making an
allowance for diversity. Typical current demands to be used for this addition are given
in Table Al.
The current demand of an installation cons;sting of a number of final circuits may be
=9 assessed by using the allowanc-es for diversity given in Table A2 which are applied to
the total current demand of all the equipment supplied by the installation. The current
demand of the installation should not be assessed by adding the current demands of
the individual final circuits obtained as outlined above. In Table A2 the allowances are
expressed either as percentages of the current demand or, where followed by the letters
f.L (full load), as percentages of the rated full load current of the current-using equip-
ment. The current demand for any final circuit which is a standard circuit arrangement
complying with Appendix H is the rated current of the overcurrent protective device of
that circuit
=9 An alternative method of assessing the current demand of an installation supplying a
:;a number of final circuits is to add the drversified current demands of the individual circuits
and then apply a1iurther allowance for diversity. In this method the allowances given in
Table A2 should not be used, the values to be chosen being the responsibility of the
==3 installation designer.
On-Site Guide 1 1 0 9
e The Institutionof EngineeringandTedlnorogy
::g Appendix
=a The use of other methods of determining maximum demand is not preduded where
specified by the installation designer. After the design currents for all the circuits have
:;a been determined, enabling the cor:iductor sizes to be chosen, it is necessary to check
that tihe Hmitation on voltage drop is met.
:a
T Table A l Current demand to be assumed for points of utilisation and current-
:;B using equipment
Point of utilisation or current-using Current demand to be nssumed
equipment
Socket-outlets other than 2 A socket-
outlets and other than 13 A socket-
outlets
See note 1
2 A socket-outlets At least 0.5 A
Lighting outlet current equivalent to the connected load,
See note2 with a minimum of 100 W per
lampholder
1 See Appendix H for the design of standard circuits using soc-ket-outfets to BS 1363-2 and BS EN
60309-2 (BS 4343).
2 Final drwits for discharge lighting must be arranged so as to be capable of carrying the total steady
C-Urrem, viz. that of the lamp(s) and any associated controlgear and also their harmonic currents.
Where more exact information is not available, the demand in volt-amperes is taken as the rated
lamp watts multiplied by not less than l.8. This multiplier is based upon the assumption that the
circuit is c-0rrected to a p01Ner factor of not less than 0.85 lagging, and takes into ace.aunt controlgear
losses and harmonic current
=9
:;a
==3
-- )>
T Table Al continued
0
• 10 this context an instantaneous water-heater is considered to be a water-heater of any loading which heats water only while the tap is turned on and therefore uses
electricity interminently.
"ft t It is imporomt to ensure that distribution boards or consumer units are of sufficient rating to take the total load connected to them without the application of any
g·.,. diversity.
2.
1:
ooo
!!I=,,
o..v,
[·
a.f2
-
,2<5:
-< ,,,
.., )>
::g
=a
:;a Appendix •
•
:a
:;B
Maxim,um permissible
measured earth, fault
loop imp,ed'ance
612.9 The tables in this appendix provide maximum permissible measured earth fault loop
411.4.6 impedances (Zs) for compliance with BS 7671 where the standard final circuits of Table
411.4.7 7.1 (i) are used. The values are those that must not be exceeded in the tests carried out
:a 411.4.e under 10.3.6 at an ambient temperature of 10 °c. Table B8 provides correction factors
for other ambient temperatures.
Where fhe cables to be used are to Table 4, 7 or 8 of BS 6004 or Table 3, 5, 6 or 7 of
BS 7211 or are other thermoplastic (PVC) or theirmosetting (low smoke halogen-free -
=a LSHF) cables to these British Standards and the cable loading is such that the maximum
operating temperature is 70 °c, then Tables B l - B 5 give the maximum earth fault loop
impedances for circuits with:
I protective conductors of copper a1nd having from 1 mm 2 to 16 mm 2 cross-
sectional area1
l an overcurrent protective device (I.e. a fuse) to:
- BS 3036 (Table B1)
=9 - BS 88-2.2 a,nd BS 88-6 (Table 82)
- BS 88-2 (Table B3)
- BS 88-3 (Table B4)
- BS 1361 (Table 85).
For eaoh type of fuse, two tables are given:
411.3.2.2 ► where the circuit concerned is a final drcuit not exceeding 32 A and the
maximum disconnection time for compliance with Regulation 411.3.2.2 is
0.4 s for TN systems, and
=9 411.3.2.3 where the circuit concerned is a final circuit exceeding 32 A or a distribution
:;a circuit, and the disconnection time for compliance with Regulation 411.3.2.3
is 5 s for TN systems.
==3 543.1.3 In each table the earth fault loop impedances given correspond to the appropriate
disconnection time from a comparison of the time/current characteristics of the device
concerned and the equation given in Regulation 543.1.3.
:;a Table 86 gwes the maximum measured Zs for circuits protected by circuit-breakers to BS
3871-1 and BS EN 60898 and RCBOs to BS EN 61009.
:a Note: The impedances tabulated in this appendD< are lower than those in Tables 41.2,
4 L 3 and 4 l 4 ·Of BS 7671 as the impedances in th;s appendix are measured values at
:;B an assumed conductor temperature of 10 °c whilst those in BS 7671 are design figures
at the conductor norma'I, operating temperature. The correction factor (divisor) used is
1.24. For smaller section cables the impedance may also be limited by the adiabatic
equation of Regulation 543.1.3. A value of k of 115 from Table 54.3 of BS 7671 is used.
This is suitable for PVC insulated and sheathed cables to Table 4, 7 or 8 of BS 6004 and
for thermosetting (LSHF) insulated and sheathed cabtes to Table 3, 5, 6 or 7 of BS 7211.
The k value is based on both the thermoplastic (PVC) and LSHF cables operating at a
maximum temperature of 70 °C.
The IET Commentary on the Wiring Regulations provides more information.
=a Protective
condudor (mm2)
5 15
Fuse rating (A)
20 30
1.0 7.7 2.1 1.4 NP
c!! 1.5 7.7 2.1 1.4 0.9
:;a NOTE: NP means that the combination of the protective conductor arid the fuse is Not Permitted.
==3
On-SiteGuide 1 1 1 4
e The Institutionof EngineeringandTedlnorogy
::g Appendix Is
=a T Table B2 BS 88-2.2 and BS 88-6 fu.ses. Maximum measured earth fault loop
:;a
impedance (in ohms) at ambient temperature where the overcurrent
protective device is a fuse to BS 88-2.2 or BS 88-6
:a 1.0
15
1.7
2.3
1.2
1.7
0.66
1.1
NP
0.64
NP
NP
NP
NP
NP
NP
NP
NP
2.5 2.3 1.8 1.5 0.93 0.55 0.34 NP NP
NP
=a
4.0 23 1.8 1.5 1.1 0.77 0.50 0.23
6.0 2.3 1.8 l.5 1.1 0.84 0.66 0.36 0.22
10.0 2.3 1.8 1.5 1.1 0.84 0.66 0.46 0.33
16.0 2.3 1.8 l.5 1.1 0.84 0.66 0.46 0.34
NOTE: NP means that the combination of the protective conductor and the fuse is Not Permitted.
=9
=9
:;a
==3
On-Site Guide I 1 1 5
e The Institution of Engineering and Tedlnorogy
::g Appendix Is
=a T Table B J BS 88-2 fuses. Maximum measured earth fault loop impedance
:;a
(in ohms) at ambient temperature where the overcurrent protective
device is a fuse to BS 88-2
=9
:;a
==3
On-Site Guide 1 1 1 6
e The Institution of Engineering and Tedlnorogy
::g Appendix Is
=a T Table B 4 BS 88-3 fuses. Maximum measured earth fault loop impedance
:;a
(in ohms) at ambient temperature where fhe overcurrent protective
device ;s a semi-endosed fuse to BS 88-3
:a 1.5
2.5
2.72
2.72
0.84ad
1.23ad
NP
0.62ad
NP
o.2sad
NP
NP
NP
NP
4.0 2.72 1.32 0.84 0.41acl 0.23ad 0.13acl
=a
6.0 2.72 1.32 0.84 0.58 0.33ad 0.19ad
10 2.72 1.32 0.84 0.58 0.43 0.32
1·6 2.72 1.32 0.84 0.58 0.43 0.32
NOTE 1: NP means that the combination of the protective conductor and the fuse is Not Permitted.
NOTE 2 ad - adiabatic limitation.
=9
=9
:;a
==3
On-Site Guide 1 1 1 7
e The Institutionof Engineeringand Tedlnorogy
::g Appendix Is
=a T Table 8 5 BS 1361 fuses. Maximum measured earth fault loop impedance
:;a
(in ohms) at ambient temperature where the overcurrent protective
device ;s a semi-enclosed fuse to BS 1361
:a 1.0
15
1.7
2.2
0.81
1.2
NP
0.34
NP
NP
NP
NP
NP
NP
2.5 2.3 1.5 0.52 0.21 NP NP
NP
=a
4.0 2.3 1.5 0.69 0.37 0.22
6.0 2.3 1.5 o.n 0.53 0.30 0.15
10 2.3 1.5 0.77 0.56 0.40 0.22
1·6 2.3 1.5 o.n 0.56 0.40 0.29
N.OTE: NP means that the combination of the protective conductor and the fuse is Not Permitted.
=9
=9
:;a
==3
On-Site Guide 1 1 1 8
e The Institutionof Engineering and Tedlnorogy
T Table 8 6 Cirruit-breakers. Maximum measured earth fault loop impedance (in ohms) at ambient temperature where the overrurrent
device is a cirruit-breaker to 85 3871 or 85 EN 60898 or RCBO to 85 EN 61009
9.27 7.75 4.64 3.09 2.90 2.32 1.85 1.55 1.45 1.16 1.03 0.93 0.74 0.46
2 5.3 4.42 2.65 1.77 1.66 1.32 1.06 o.88 0.83 0.66 0.59 0.53 0.42 0.26
B 7.42 6.18 3.71 2.47 2.32 1.85 1.48 1.24 1.16 0.93 0.82 0.74 0.59 0.37
3&C 3.71 3.09 1.85 1.24 1.16 0.93 0.74 0.62 0.58 0.46 0.41 0.37 0.29 0.19
D 1.85 1.55 0.93 0.62 0.58 0.46 0.37 0.31 0.29 0.23 0.21 0.19 0.15 0.09
Regulation 434.5.2 of 85 7671:2008(2011) requires that the protective conductor csa meets the requirements of 85 EN 60898-1, -2 or 85 EN
61009-1, or the minimum quoted by the manufacturer. The sizes given in Table 87 are for energy limiting dass 3, Types 8 and C devices only.
::g Appendix I B
=a T Table B 7 Minimum protective conductor size (mm 2)*
:a Type B Type C
Up to and including 16 A 3 1.0 1.5
:;B Up to and induding 16 A S6 2.5 2.5
over 16 up to and including 32 A S3 1.5 1.5
0ver 16 up to and including 32 A S6 2.5 2.5
40A 53 1.5 1.5
40A S6 2.5 2.5
• For other device types and ratings or higher fault levels, consult manufacture(s data. See
Regulation 434.5.2 and the IET publication Commentary on the IEE Wiring Regulations.
:a Ambient temperature
(°C)
Correction factor (from 10 °C)
(notes 1 and 2)
0 0.96
5 0.98
=a 10 1.00
20 1.04
25 1.06
30 1.08
Notes:
=9 1 The correction factor is given by: {1 + 0..004(ambiem temp- 10)} where 0.004 is the simplified
resistance c-oeffident per "Cat 20 •c given by 8S EN 60228 for both copper and aluminium
c,onductors.
l The factors are different to those ofTab!e 12 because Table B8 corrects from 1o °C and rab,e 12
from 20 °C.
The appropriate ambient correction factor from Table 88 is applied to the earth fault loop
impedances of Tables 81-86 if the ambient temperature is other than 10 °C when the
circuit loop impedances are measured.
=9 For example, if the ambient temperature is 25 °C the measured earth fault loop
impedance of a circuit protected by a 32 A type B circuit-breaker to BS EN 60898 should
:;a not exceed 1.16 x 1.06 = 1.23 Q.
==3
On-Site Guide 1 1 2 0
e The Institutionof EngineeringandTedlnorogy
::g
=a
:;a Appendix
:a
:;B Sel1edion of types of
cable for particular
uses and external
influences
s2 For compl;iance with the requirements of Chapter 52 for the selection and erection of
:a wiring systems in relation to risks of mechanical damage and corrosion, this appendix
lists, in two tables, types of cable for the uses indicated. These tables are not 'intended
to be exhaustive and other limitations may be imposed by the relevant regulations of
BS 7671, in particular, those concerning maximum permissible operating temperatures.
=9
=9
:;a
==3
:a 'fflermoplastic
(PVC) or
For use in conduits, cable
ducting or trunking
lnter:mediate support may be
required on long vertical runs
:;B th.ermosetting
insulated non-
70 °C maximum c-0nductor
temperature for normal wiring
sheathed cable grades induding thermosetting
(BS 7211, BS 7919) types (note 4)
Cables run in PVC conduit should
not operate with a conductor
temperature greater than 70 °C
(note 4)
Flat thennaplastlc For general indoor use in Additional mechanic.al protection
(PVC)or dry or damp locations. May may be necessary where exposed
thenna11111As be embedded in plaster to mechanical stresses
..........._..
lnsulllllld and F or use on exterior surface
walls, boundary walls and
Protedion from direct sunlight may
be necessary. Black sheath colour
:a
(858004) the like is better for a b l e s exposed to
For use as overhead wiring sunlight
between buHdinp May need to be hard drawn (HD)
F or use unde,.round in copper conductors for overhead
wiring (note 6)
=a
conduits or pipes
F or use in building voids or
duds formed in-situ Unsuitable for embedding directly
---
in conaete
Mineral insulated General Ml cables should have overall PVC
(BS EN 60702• 1) covering where exposed to the
weather or risk of corrosion, or
where installed underground, or in
=9 concrete ducts
1hermoplastlc General Additional protection may be
or tllennoNlll111 necessary where exposed to
lnsul . . . mechanical stresses
annourecL Protedion from direct sunlight may
..........
thennopl8ldc
(8554e7,IS1341,
be necessary. Black sheath colour
is better for a b l e s exposed to
sunlight
=9
85 6724, I S 7846) --------------------------
Notes:
:;a 1 The use of cable covers or equivalent medlanical protection is desirable for all underground cables
which might otherwise subsequently be disturbed. Route marker tape should also be installed,
buried Just below ground level. cables should be buried at a sufficient depth.
==3 1 C4bles having thermoplastic (PVC) insulation or sheath should preferably not be used where the
ambient temperature is cons stently below o c or has been within the preceding 24 hours. Whete
0
they are to be installed during a period of low temperature. precautions should be taken to avoid
On-Site Guide
e The Institution of Engineering and Tedlnorogy
1122
::g Appendix le
=a risk of mechanical damage durlng handling, A minimum ambLent temperature of 5 •c is advised in
BS 7540:2005 (series) Electric cables - Guide t o use for cables with orated voltage not exceeding
:;a 450/750 vtor some types .of PVC insulated and sheathed cables.
J cables must be suitable for me maximum amb nt temperature, and must be protected from any
:a
excess heat produced by other equipment. including other cables.
t The,mosening cable types (to BS 721 l or BS 5467) can operate with a conductor temperature of
90 •c. This must be limited to 70 "C where drawn into a conduit, etc., with thermoplastic (PVC)
insulated conductors or connected to erectrical equipment (512.1.5 and 523. l),or where such
:;B cab!es are installed in plastic conduit or trunking.
5 For cables to BS 6004, BS 6007, BS 7211, BS 6346, BS 5467 and BS 6724, further guidance may be
obtained from those staridards. Additional advice is given in BS 7540:2005 (series) Guide t o use of
cables with orated voltage not exceeding 450/750 Vforcables to BS 6004, 8S 6007 and BS 7211.
& cables for O\lerhead wiring between buildings must be ab!e to support their m-vn weight and any
imposed wind or ice/snow 1oading. A catenary support is usual but hard drawn copper types may
be used.
7 BS 5467: Electric cables. Thermosetting insulated, armoured cables for voltages of 600/1000 V
and 1900/3300 v
BS 6004: Electric cables. PVC insulated, non-armoured cables for voltages up to and including
450/750 V for electric power, lighting and internal wiring
BS 6346: Electric cables. PVC insulated, armoured cables for voltages of 600/1000 V and
1900/3300V
BS 6724: Electric cables. Thermosetting ;nsulated, armoured cables for voltages of 600/1000 V
and 1900/3300 V, having low emissioo of smoke and corrosive gases when affected by fire
:a
BS 7.211: Electric cables. Thermosetting insulated, non-,armoured cables for voltages up to and
induding 450/750 V, for electric pO\!Ver, lighting and internal wiring. and having low emission of
smoke and corrosive gases when affected by fire
BS 7846:. Electric cables. 600/1000 V armoured fire-resistant cables having thermosetting
insulation and low emission of smoke and cmosive gases when affected by fire
=a
BS EN 60702-1: Mineral insulated cables and their terminations with a rat(!d voltage not
exceeding 750 V. Gables
:;a
affect other plastics.
Wood preservatives
==3 Thermoplastic (PVC} sheathed cables should be covered to prevent contact with
preservative fluids during application. After the solvent has evaporated (good ventilation
is necessary) the preservative has no effect
On-Site Guide 1 1 2 : S
e The Institution of Engineering and Tedlnorogy
::g Appendix I(
=a C reosote
:;a Creosote should not be applied to thermoplastic (PVQ sheathed cables because it
causes decomposition, solution, swelling and 'loss of pliability.
1124
any exGess heat produced by other equipment. including other cables.
On-Site Guide
e TheInstitutionof Engineeringand Tedlnorogy
::g Appendix le
=a 3 For flexible cords and cab1es to BS 6007, BS 6141 and BS 6500funher guidance may be obtained
from those standards, or from B-S 7540:2005 (series) Guide to use of c-ables with orated voltage
:;a 4
not exceeding 450/750 V.
Where used as connections to equipment, flexible cables shou1d, where possible, be of the
:a
minimum practicable llength t.o minimize dan_ger. The length of the flexible cable must be Sllch that
will permit correct operation of the protective device.
s Where attached to equipment flexible cables should be protected against tension, crushing.
:;B
abrasion, torsion and kinking. particularly at the inlet po;nt to the electrical equipment. At such inlet
points it may be necessary to use a device which ensures that the cal>le is not bent to an internal
radius be'low that given in the appropriate part of Table 4 of BS 6700. Strain relief, damping devices
or cable guards should 110t damage the cable.
& Flexible cables shouk1 not be run under carpets or other floor coverings whete furniture or other
equipment may rest on them or where heat dissipation from the cable will be affected. Flexible
cables should not be placed where there is a risk of damage from traffic passing over them, unless
suitably protected.
7 Flexible cab!es shouk1 not be used in contact with or dose to heated surfaces, especia11y if the
surface approaches the uppe< thermal limh of the cable.
Protection o f exposed metalwork and wiring systems against corrosion
522.3 In damp situations, where metal cable sheaths and armour •Of cables, metal conduit and
522.5 e-onduit fittings, metal ducting and trunking systems, and associated metal fixings, are liabte
to chemical deterioration or electrolytic attack by materials of a structure with which they
On-Site Guide 1 1 2 5
e The Institutionof EngineeringandTedlnorogy
::g
=a
:;a
:a
:;B
:a
=a
=9
=9
:;a
==3
On-Site Guide 1 1 H
e The Institutionof EngineeringandTedlnorogy
::g
=a
:;a Appendix I
:a
:;B Methods of support
for cables, co,nductors
and wiring systems
This appendix describes examples of methods of support for cables, conductors and
522.8 wiring systems which should satisfy the relevant requirements of Chapter 52 of BS
7671. The use of other methods is not precluded where specified by a suitably quaHfied
:a electrical engineer.
cables generally
Items 1 to 8 below are generally applicable to supports on structures whkh are subject
=a
only to vibration of low severity and a low risk of mechanical impact
1 For non-sheathed cabl.es, instaHation in conduit without further fixing of the cables,
precautions being taken against undue compression or other mechanical stressing
of the insulation at the top of any vertical runs exceeding 5 m in length.
2 For cables of any type, installation in ducting or trunking without further fixing of
the cables, vertical runs not exceeding 5 m in length without intermediate support.
3 For sheathed and/or armoured c-ables installed in accessible positions, support by
=9 dips at spacings not exceeding the appropriate value stated in Table Dl.
4 For cables of any type, resting without fixing in horizontal runs of ducts, conduits,
cable ducting or trunking.
s For sheathed and/or armoured cables in horizontal runs which are inaccessible and
unlikely to be disturbed, resting without fixing on part of a building, the surface of
that part being reasonably smooth.
6 For sheathed and-armoured cables in vertica,1 runs which are inaccessible and
unlikety to be disturbed, supported at the top of the run by a dip and a rounded
support of a radius not less than the appropriate value stated in Table D5.
=9 7 For sheathed cables without armour In vertical runs which are inaccessible and
unlikely to be disturbed, supported by the method described in Item 6 above; the
:;a length of run without Intermediate support not exceeding 5 m for a thermosetting
or thermoplastic sheathed cable.
==3 8 For thermosetting or thermoplastic (PVQ sheathed cables, installation in conduit
without further fixing of the cables, any vertical runs belng in conduit of suitable
size and not exceeding 5 m in length.
On-Site Guide 1 1 2 7
e The Institutionof Engineeringand Tedlnorogy
::g Appendix I D
=a Partimlar applications
:;a 721.522.8 9 In caravans, for sheathed cables in inaccessible spaces such a,s ceiling, wall and
floor spaces, support at intervals not exceeding 0.4 m for vertical runs and 0.25 m
Overhead wiring
13 For cables sheathed with thermosetting or thermoplastic material, supported by a
separate catenary wire, either continuously bound up with the cable or attached
thereto at intervals, the inte rvals not exceeding those stated in column 2 of Table D1.
14 Support by a catenary wire incorporated in the cable during manufacture, the
:a spacings between supports not exceeding those stated by the manufacturer and
the minimum height above ground being in accordance with Table 02.
15 For spans without intermediate support (e.g. between buildings) of thermoplastic
(PVC) insulated thermoplastic (PVC) sheathed cable, or thermosetting insulated
cable having an oil-resisting and flame-retardant or HOFR sheath 1 terminal supports
=a so arranged that:
no undue strain is placed upon the conductors or insulation of the cable 1
adequate precautions are taken against any risk of chafing of the cable sheath,
and
the minimum height above ground and the length of such spans are in
accordance with the appropriate values indicated in Table D2.
=9 16 Bare or thermoplastic (PVC) covered conductors of an overhead line for distribution
between a building and a remote point of util ation (e.g. another building)
supported on insulators, the lengths of span and heights above ground having the
appropriate values indica,ted in Table D2 or otherwise installed in accordance with the
E1.ectricity Safety, Quality and Continuity Regulations 2002 (as amended).
17 For spans without intermediate support (e.g. between buikJings) and which are in
situations inaccessible to vehicular traffic, cables installed in heavy gauge steel conduit.
the length of span and height above ground being in accordance with Table 02.
On-Site Guide 1 1 2 8
c The lnstirutionof 8'1gineering and Technofogy
T Table D1 Spacings of supports for cables in accessible positions
•Note:For flatForcables
the spacing of supports for cables having an overall diameter exceeding 40 mm. the manufacturer's recommendations should be observed.
taken as the dimension of the major axis.
0
t The spacings stated for horizontal runs may be applied also to runs at an angle of more than 30• from the venical. For runs at an angle of 30• or less from the
vertical, the vertical spacings are applicable.
"ft
g·.,.
2.
1:
ooo
!!I=,,
o..v,
[·
a.f2
-
,2<5:
-< ,,,
0
::g Appendix lo
=a T Table D2 Maximum lengths of span and minimum heights above ground for
:;a
overhead wiring between buildings, etc.
=a
Thermoplastic (PVC) covered 30 5.8 5.8 3.5
overhead lines on insulators
without intermediate support.
Bare overhead lines on 30 5.8 5.8 5.2
insulators without intennediate
support
Cables sheathed with No limit 5.8 5.8 3.5
=9 thermoplastic (PVC) or
havin,g an oil-res isting and
flame-retardant or HOFR sheath,
supported by a catenary wire.
Aerial cables incorporating a Subject to 5.8 5.8 3.5
catenary wire. Item 14
A bare or insulated overhead
line for distribution between
buildings and structures must
=9 be installed to the standard
required by the Electricity
:;a Safety, Quality and Continuity
Regulations 2002.
"'
==3
Columns is not applicable in agrirultural premises.
t In some special cases, such as where cranes are pre sent, 1t will be necessary to increase the
minimum height of span above ground. It is preferable to use underground cables in such locations.
:a
Rigid metal Rigid insulating Pliable
Nominal diameter
•Ofconduit di (mm) Ho · Vertical Horizontal Vertical Horizontal Vmiral
:;B
2.0
2S<ds40 2.0 2.25 1.75 2.0 0.6 0.8
d>40 2.25 2.5 2.0 2.0 0.8 1.0
Notes:
1 The spacings tabulated allow for maximum fill of cables permitted by the Regulalions and the
thermal limits specified in the re1evam British Standards. They assume that the conduit is not
exposed to other mechanical stress.
2 Supports should be posii;oned within 300 mm of bends or fntings. A flexible conduit should be of
such tength that it does not nee<J to be supported in its run.
3 The inner radius of a conduit bend should be not less than 2.5 times the outside diameter of the
conduit.
=a Cross-sectional area of
trunking, A (mm 2) Horizontal
Metal
Vertical Horizontal
Insulating
Vertical
1
On-Site Guide 1 1 3 1
e The Institution of Engineering and Tedlnorogy
::g Appendix lo
=a T Table D5 Minimum internal radii of bends in cables for fixed wiring
=a *
conduit, ducting or ounking.
Mineral insulated cab,es may be bent to a radius not less than three times the cab,e diameter over
the copper sheath. provided that the bend is not reworked, i.e. straightened and re-bent
=9
=9
:;a
==3
==3 For cables and/or conduits not covered by this appendix, advice on the number of cables
that can be drawn in should be obtained from the manufacturer.
On-Site Guide 1 1 3 3
e The Institutionof EngineeringandTedlnorogy
::g Appendix
=a i Single-core thermoplastic (PVC) insulated cables in straight runs o f
:;a
conduit not exceeding 3 m in len.gth
For each cable it is intended to use, obtain the appropriate factor from Table El.
:a Add the cabte factors together and compare the total with the conduit factors given in
Table E2.
:;B The minimum conduit size is that having a factor equal to or greater than the sum of the
cable factors.
:a 4
6
10
58
88
146
16 202
25 385
=9
:;a
==3
On-Site Guide
e The Institutionof Engineeringand Tedlnorogy
1134
::g Appendix
=a ii Single-core thermoplastic (PVC) insulated cables in strai,ght runs of
:;a
conduit exceeding 3 min. length, or in runs •Ofany length incorporating
bends or sets
:a For each cable it is intended to use, obtain the appropriate factor from Table E3.
Add the cabte factors together and compare the total with the conduit factors given in
:;B Table E4, taking into account the length of run it is inte11ded to use and the number of
bends and sets in that run.
The minimum conduit size is that size having a factor equal to or greater than the sum of
the cable factors. For the larger sizes of conduit, multiplication factors are given relating
them to 32 mm diameter conduit
,.. Table E.J Cable factors for use in conduit in 'long straight runs over 3 m, or runs
of any length incorporating bends
:a or
Stranded
1.5
2.5
4
22
30
43
58
10 105
=a 16
25
145
217
The inner radius of a conduit ber:id should be not less than 2.5 times the outside
diameter of the conduit.
=9
=9
:;a
==3
On-Site Guide 1 1 3 5
e The Institutionof EngineeringandTedlnorogy
T Table E 4 Conduit factors for runs incorporating bends and long straight runs
188 303 543 947 1n 286 514 900 158 256 463 818 130 213 388 692
Covered by
1.5 182 294 528 923 167 270 487 857 143 233 422 750 111 182 333 600
2 Tables 1n 286 514 900 158 256 463 818 130 213 388 692 97 159 292 529
2.5 171 278 500 878 150 244 442 783 120 196 358 643 86 141 260 474
El and E2
3 167 270 487 857 143 233 422 750 111 182 333 600
3.5 179 290 521 911 162 263 475 837 136 222 404 720 103 169 311 563
4 177 286 514 900 158 256 463 818 130 213 388 692 97 159 292 529
4.5 174 282 507 889 154 250 452 800 125 204 373 667 91 149 275 500
5 171 278 500 878 150 244 442 783 120 196 358 643 86 141 260 474
0 6 167 270 487 857 143 233 422 750 111 182 333 600
7 162 263 475 837 136 222 404 720 103 169 311 563
g·.,. 8 158 256 463 818 130 213 388 692 159 292 529
9 154 250 452 800 125 204 373 667 91 149 275 500
1:
ooo
!!I=,,
10 150 244
Additional factors:
442 783 120 196 358 643 86 141 260 474
>
o..v, ► For 38 mm diameter use l .4 x (32 mm factor)
[ ' ► For so mm diameter use 2.6 x (32 mm factor) ::,
c.
a_f;' ► For 63 mm diameter use 4.2 x (32 mm factor)
x·
-
,2<5:
- < t'D
:s: m
::g Appendix
=a iii Single-core thermoplastic (PVC) insulated cables in trunking
:;a For each cable it is intended to use, obtain the appropriate factor from Table ES.
Add the cable factors together and compare the total with the factors for trunking given
:a in Table E6.
The minimum siz.e of trunking is that size having a factor equal to or greater than the sum
:;B of the cab1le factors.
:a
21.2 22.9
10 35.3 36.3
16 47.8 50.3
25 73.9 75.4
=a
Notes:
1 These faetors are for metal trunking and may be optimistic for plastic trunking, where the
cross-sectional area available may be significantly reduced from the nominal by the thickness of the
wall material.
2 The provision of spare space is advisable; however, any circuits added at a later date must take ;nro
account grouping, Regu,ation 523.5.
=9
=9
:;a
==3
:;a Dimensions
of trunking Factor
Dimensions
of trunking Factor
:a (mm xmm)
50x38 767
(mmxmm)
200 X 100 8572
:;B 50x50 1037 200x 150 13001
75 X 25 738 200x 200 17429
75x38 1146 225x38 3474
75x50 1555 225 X 50 4671
75x75 2371 225x75 7167
100 X 25 993 225 X 100 9662
100x38 1542 225 X 150 14652
100 X 50 .2091 225 X 200 19643
100x75 3189 225x225 22138
100 X 100 4252 300 X 38 4648
:a 150x38
150 X 50
2999
3091
300x50
300 x75
6251
9590
150x75 4743 300x 100 12929
=a 150 X 100
150 X 150
6394
9697
300 X 150
300x200
19607
26285
200 X 38 3082 300 X 225 29624
200x50 4145 300x300 394 28
200 X 75 6359
=9 Note: Space factor is 45% with trunking thickness taken into account
On-Site Guide
e The Institutionof EngineeringandTedlnorogy
1138
::g
=a
:;a Appendix
:a
:;B
Current- carrying 1
=a Procedure
Appx 4, 3 I The design current (lb) of the circuit must first be established.
433.1.1 l The overcurrent device rating (I n) is then selected so that In is greater than or
equal to lb
In lb
=9 The tabulated current-carrying capacity of die selected cable (I t) is then given by:
It In
C-iCgCCt
for simultaneously occurring factors.
C is a rating factor to be applied where the installation conditions differ from those for
which values of current-carrying capacity are tabulated in this appendix. The various
rating factors are identified as follows:
=9 Ca for ambient temperature, see Table Fl
Cg for grouping, see Table F3
:;a Ci for thermal insulation, see Table F2 (Note: For cables installed in thermal
insulat;on as described in Tables F4(i), FS{i) and F6, C = 1)
==3
On-Site Guide 1 1 3 9
e The Institutionof EngineeringandTedlnorogy
::g Appendix I f
=a c, for the type of protective device, i.e.:
-
:;a
433.1.101 where the protective device is a semi-enclosed fuse to BS 3036,
Ct=0.725
- for aH other devices Ct = 1.
:a Voltage do p r
:;B 525
Appx 4,6
To cakulate the voltage drop in volts the tabulated value of voltage drop (mV/A/m) has
to be multiplied by the design current of the circuit Clb), the length of run in metres (L),
and divided by 1000 (to convert to vo'lts):
(mV/A/m) X lb X L
voltage drop =
1000
The requirements of BS 7671 are deemed to be satisfied if the voltage drop between
the origin of the installation and a Hghting point does not exceed 3 per cent of the
nominal voltage (6.9 V) and for other current-using equipment or socket-outlets does
not e x c eed 5 per cent (11.5 V single-phase).
Table 481 'Y Table FI Rating factors (Ca) for ambient air temperatures other than 30 °C to be
Insulation
Mineral
=a Ambient 70 °C
temperature thermoplastic
90 °C
thennosetting
lhermoplastic
covered o,r bare
Bare and not
exoosed to
re> and exposed to
touch 70 °C
touch 105 °C
=9 35
40
0.94
0.87
0.96
0.91
0.93
0.85
0.96
0.92
=9
:;a
==3
:a covered by the thermal insulation. Where fixing in such a position is impracticable, the
cross-sectional area of the cable must be increased appropriately.
:;B For a cable installed in thermal insulation as described in Tabl.es F4(i), FS(O and F6 no
correction is required.
N'ote: Reference methods 100, 101 and 102 require the cable to be in contact with the
plasterboard or the joists, see Tables 7.1 (ii) and 7. l (iii) in Section 7.
For a single cable likely to be totally surrounded by thermally insulating material over a
length of more than 0.5 m, the current-carrying capacity should be taken, in the absence
of more precise information, as 0.5 times the current-carrying capacity for that cabte
clipped direct to a surface and open (reference method C).
Where a, cable is totally surrounded by thermal insulation for less than 0.5 m the current-
carrying capacity of the cable should be reduced appropriately depending on the size of
cable, length in insulation and thermal properties of the insu'lation. The derating factors
:a
in Table F2 are appropriate to conductor sizes up to 10 mm 2 in thermal insulation having
a thermal conductivity (A) greater than 0.04 Wm· 1 K· 1 •
=9
=9
:;a
==3
"T1
Notes to Table F3:
"'T1
T Table F4(1) Single-core 70 •c thermoplastic (PVC) or thermosetting (note 1) insulated cables, non-armoured, with or
Table 401A without sheath (copper conductors)
Ambient temperature: 30 •c
Conductor operating temperature: 70 °C
Current-carrying capacity (amperes):
Conductor Reference method A Reference method B Reference method C Reference method F
uos.s- (endosed In (endosed In
sealonal conduit In thermally conduit on a wall or In (In free air or on a perforated cable tny
area lnsullltln1 walL etc.) trunldn1, etc.) (dipped direct) horizontal or vertical)
Spaced by one
3 or4
Touchln1 cable diameter
lcables, cables.
3 or4 3 or4 slnsle- three- 2 cables, 2 cables slnsJe-phase
2 cables, cables, 2 cables, cables, phase 11.c. phase a.c. si I!- 3 cables, 3 cables 11.c. or d.c.. or
slnx!e- three- single- thrre- or d.c. flat ■nd phase ■.c. three- thrre- 3 cables three-
phase phase phase phase flat and tou,chlna or d.c. phase a.c. phase a.c. phase a.c.
a.c. or d.c. a.c. a.c. or d.c. a.c. touchlfll or trefoil flat flat trefoil flat
horizontal vertical
2 3 4 5 6 7 8 !I 10 11 12
()
mm> A A A A A A A A A A A
"ft
I·.,.
g_ 2.5 20 18 24 21 27 25
i"
,.oo
o
4
6
26
34
24
31
32
41
28
36
37
47
33
43 ::r:,,
!oJ' . .:;>
v, 10 46 42 57 50 65 59
ttl
[i%. 16 61 56 76 68 87 79 ::i
c.
a. x·
-
,2i5: 25 80 73 101 89 114 104 131 114 110 146 130
- < /'I)
t "T1
T Table F4(1) continued
Cond11dcM' Reference method A Reference method B Reference method C Reference method F
aoss-- (endosed In (endosed In
sedlonal conduit in therma.lly wndult on a wall or in (In free air or on a perforated c.aible m y
re insulati n g wall, ek.) trunking. etc.) (dipped direct) ho,ri:zont I or vertlc I)
3 or4 Spaced by one
2 c bles. C.llbles. Toudting uble diameter
3 or4 3 or4 sln&fe- three- 2 cables, 2 cables slnsle-ph se
2 aibles, c.ables. 2 c.ables, cables, phase .c. phase .c. slns'e- 3 c.ables, 3 c.ables .c. or d.c. or
slnl'e- three- sln¥1e- three- or d.c. flat and phase a.c. three- three- 3 cables three-
phase phase phase phase flat and touching or d.c. phase &c. phase a.c. phase a.c.
• - ' or d - ' L
C. LC. Of d.c. L
C. touching or trefoil flat flat trefoil flat
horizontal vertical
2 l 4 s 6 7 II 9 10 11 12
mm• A A A A A A A A A A A
35 99 89 125 110 141 129 162 143 137 181 162
50 119 108 151 134 182 1117 19& 174 1117 219 197
70 151 136 192 171 234 214 251 225 216 281 254
95 182 164 232 'll.11 284 261 304 275 264 341 311
The ratings for cables with thermosetting insulation are applicable for cables connected to equipment or accessories designed to operate with cables which run at a
temperature not exceeding 70 •c. Where conductor operating temperatures up to 90 •care acceptable the oment rating is increased - see Table 4E IA of BS 7671.
2 Where the conductor is to be protected by a semi-enclosed fuse to BS 3036, see the introduction to this appendix.
l The current-carrying capacities in columns 2 to 5 are also applicable to flexible cables to BS 6004 Table I (c) and to 90 •c heat-resisting PVC cables to BS 6231
Tables B and 9 where the cables are used in fixed installations.
"'T1
T T a b l e F4(11) Voltage drop (per ampere per metre) at a conductor operating temperature of 70 •c
Table 4 0 I B
2.5 18 18 18 18 15 15 15 15
4 11 11 11 11 9.5 9.5 9.5 9.5
6 7.3 7.3 7.3 7.3 6.4 6.4 6.4 6.4
10 4.4 4.4 4.4 4.4 3.8 3.8 3.8 3.8
16 2.8 2.8 2.8 2.8 2.4 2.4 2.4 2.4
"ft
I·.,.
: , 25 1.75
zt
1.80
zt
1.75
zt
1.80
it
1.55
zt
1.50
zt
1.55
zt
1.55
g_
35 1.25 1.30 1.25 1.30 1.10 1.10 1.10 1.15
i.,.
ooo
50 0.93 1.00 0.95 0.97 0.85 0.82 0.84 0.86
::r:,
70 0.63 0.72 0.66 0.69 o.61 o.57 o.60 0.63
!'oJ . .:;>
v,
95 0.46 0.56 0.50 0.54 0.48 0.43 0.47 0.51
[i%" •
a. c..
x·
-
SJ>i!dngs larger than one cable diameter will result in larger voltage drop.
,2i5:
- < /'I) t The impedance values in Table F4(ii) consist of both the resistive and reactive elements of voltage drop, usually provided sepilrateiy for 25 mm 2 and above
conductor sizes.
I
For more information, see Appendix 4 of BS 7671.
"T1
T Table F5(1) Multicore cables having thermoplastic (PVC) or thermosetting insulation (note 1), non-armoured
Table 402A (copper conductors)
Ambient temperature: 30 •c
Conductor operating temperature: 70 •c
current-carrying capacity (amperes):
Reference method E
Conductor Reference method A Reference method B (In free air or on ■ perforated
cross-sec:tlonal (endosed In conduit In 11 (endosed In conduit Reference method C uble t,ay, etc. homontal or
area therm11lly lnsulatlns wall, etc.) on II wall or In trunklni, etc.) (dipped dlred) vertical}
1 three-aire
1 thi--.:ore 1 three-core 1 thi--.:ore uble•or 1
1two- cable•or 1 1 two- cable• or I I two- cable• or I 1 two- four-<0re
core cable•, four-core core cable•, four-core core cable•, four-core core cable•, ea ble, three-
slnsl�phase uble.three- slnp�phase cable. three- slnpe-phase cable. three- slnpe-ph■se phtie
1.c. or d.c. phase LC. ■.c.. or d.c. ph1se ■.c. 1.c. or cl.c. ph1se 1.c.. ■.c. or d.c. C
I
..
2 3 4 5 6 7 8 g
mm> A A A A A A A A
0
"ft 1.5 14 13 15 19.5 18.5
16.5 17.5 22
g·.,. 2.5 18.5 17.5 23 20 27 24 30 25
4 25 23 30 X1 36 32 40 34
-
2.
1:
6 32 29 38 34 46 41 51 43
10 43 39 52 445 53 57 70 60
ooo 16 57 52 69 62 85 76 94 80 >
-0
!!I=,, -0
o..v,
25 75 90 80 112 H 119 101
[ ' c.
a_f;' 35 92 83 111 99 138 119 148 126
x·
-
,2<5:
- < t'D
"'T1
T Table F5(1) continued
Referenc,e method E
Condudor Referenc,e method A Referen.ce method B (In free air or on II perforated
cross-sectional (endosed In conduit In 11 (endosed In conduit Reference method C cable tray, etc. horizontal or
ere thermally Insulating wall. etc.) on • wall or In tnmldng. etc.) (dipped direct) ...,rtJcal)
1 three-one
1 three-core 1 three-core 1 three-core cable• or 1
1 two- cable•or 1 1 two- cable" or 1 1 two- cable" or I I two- four-<0re
core cable", four-<0re core cable", four-<0re core cable", four-<0re core cable", ea ble. three-
slnsle-phase cable.th.l'ff- single-phase cable. three- single-phase cable. three- sl ngle-ph se phase
LC. or cl.c. phase a.c. a.c.orcl.c. phase a.c. LC. or d.c. phase Le. LC. or cl.c. a.c.
2 3 • 5 6 7 a 9
mm2 A A A A A A A A
50 110 99 133 118 lfi8 144 180 153
70 139 125 168 149 213 184 232 196
95 167 150 201 179 258 223 282 238
"'T1
Appendix
::el Table 4028 T Table FS(il) Voltage drop (per ampere per metre) at a conductor operating
temperature of 70 °C
:a 35
50
1.25
0.93
1.25
0.94
1.10
0.81
70 0.63 0.65 0.57
=a t
95 0.46 0.50 0.43
The impedance values in Table FS(ii) consist of both the resistive and reactive elements of voltage
drop, usually pfovided separately for 25 mm2 and above conductor sizes.
For more information, see Appendix 4 of BS 7671.
=9
=9
:;a
==3
On-Site Guide 1 1 4 9
e The Institution of Engineering and Tedlnorogy
T Table F 6 70 •c thermoplastic (PVC)
insulated and sheathed flat cable with protective conductor (copper conductors)
Table 405 Ambient temperature: 3 0 •c
Conductor operating temperature: 7 0 •c
Current-carrying c.apadty (amperes) and voltage drop (per ampere per metre):
1.5 16 13 16 10 20 14.5 29
2.5 21 17 21 13.5 27 20 18
4 27 22 X1 17.S 37 26 11
6 34 27 35 23.5 47 32 7.3
10 45 36 47 32 64 44 4.4
16 57 46 63 42.5 85 57 2.8
Notes:
• Reference methods 100. 101 and 102 require the cable to be in contact with the plasterboard ceiling. wall()( joist see Tables 7.l(ii) and 7.l(iii) in Section 7.
1 Wherever practicable, a cable is to be fixed in a position such that it will not be covered with thermal insulation.
1 Regulation 523.9, BS 5803-5: Appendix C: Avoidance of overheating of electric cables, Building Regulations Approved Document B and Thermal insulation: avoiding
risks, BR 262, BRE, 2001 refer.
"T1
::g
=a
:;a Appendix
:a
:;B Certification and
reporting
The certificates and forms are used with the kind permission of 8S1.
GI lntrodudion
fundamentally, two types of form are recognised by BS 7671, certificates and reports:
G2 Certification
=a Two types of certificate for new work are recognised by BS 7671:
► Electrical Installation Certificate
► Minor Electrkal Installation Works Certificate.
:;a
the addition of extra load or changes to the original earth fault loop impedance.
G2.J Aaountability
:a Certificates call for those responsible for the elec trical installation or constructlon work to
certify that the requirements of the Regulations have been met. Under no circumstances
:;B should a third party issue a certificate for installation work they have not undertaken.
It is common with larger installations for the design to be carried out by one company,
installation or construction by someone else and the inspection and testing to be
undertaken by some other, e.g. a testing organisation working on behalf of the installer;
this is quite acceptable but the company who carries out the installation must issue the
Electrical Installation Certificate.
GJ Reporting
GJ.1 Electrical Installation Condition Report
The Electrical Installation Condition Report (EICR) is intended to be issued when a
periodic inspection of an electrical installation has been carried out. The EICR does not
:a certify anything and, hence, must not be issued to certify new electrical installation work.
The purpose of the iEICR is to report on the condit;on of an existing electrical insta,llation
and, ultimately, present one of two outcomes:
► SATISFACTORY - the installation is deemed safe for continued use
GJ.2 Observations
=9 Observations to be recorded fall into three categories;
C l - Danger present. Risk of injury. Immediate remedial action required
C2 - Potentially dangerous - urgent remedial action required
C3 - Improvement recommended.
Examples of Cl
Where danger currently exists and an immediate issue of safety is apparent:
► uninsulated live conductors exposed on broken wiring accessory
=9 ► incorrect polarity at socket-outlets, e.g. live/cpc reversal
► item of metalwork that has become live due to a fault.
:;a Examples of C l
Not immediately dangerous but a dangerous condition could occur due to a fault:
==3 ► main equipotential bonding not installed to extraneous-conductive-parts
► RCD (30 mA for additional protection) fails to operate in the required time
On-Site Guide 1 1 5 2
e The Institutionof EngineeringandTedlnorogy
::g Appendix I G
=a ► double-pole fusing (line and neutral)
► no connection to means of earthing at origin
:;a no cpc for lighting circuit having Class I fittings/accessories with exposed-
cond uctive-pa rts.
:a Examples of C3
:a
The inspector is advised to exercise judgement to secure the area and inform the client
immediately, foHowed up in writing, Once permission has been obtained, the danger
should be removed.
On-Site Guide 1 1 5 3
e The Institutionof EngineeringandTedlnorogy
::g Appendix I G
=a Appx6 The introduction to Appendix 6 'Model forms for certification and reporting' of BS
7671 :.2008(2011) is reproduced below.
:;a (i) The Electrical Installation Certificate required by Part 6 should be made out and
:a
work on an e,<,isting installation.
Where design, construction, inspection and testing are the responsibility of one person a
C e rtificate with a single-signature declaration in die form shown below may replace the
multiple signatures section of the model form.
I being the person responsible for the Design, Construdion ., Inspection &
Testing of the electrical installation (as indicated b y my signature below),
particulars ,of w'hich are described above, having exercised reasonable skill
and care when. carrying out the Design, Construdion, Inspection & Testing,
b · CERTIFY
h_ere_y _ _ _ _ _th.at th e s a i___
d w o rk · h' eh
_ f orw_J b· · ·· 'bi e· si t o t h_e
_ _ I h ave_eenrespons1_ ·
(vi) A Minor Works Certificate win indicate the responsibility for design, constrnction,
inspection and testing of the work described on the certificate.
(vii) An Electrical Installation Condition Report will indicate the responsibility for the
inspection and testing of an existing installation within the extent and limitations
specified on the report.
(viii) Schedules of inspection and schedules of test results as required by Part 6
should be issued with the associa,ted Electrical Installation Certificate or Electrical
=9 Installation Condition Report.
(ix) When making out and signing a form on behalf of a company or other business
:;a entity, individuals should state for whom they are acting.
(x) Additional forms may be required as darification, if needed by ordinary persons,
==3 or in expansion, for larger or more complex installations.
(xj) The IET Guidance Note 3 provides further information on inspection and testing
and for periodic inspection, testing and reporting.
On-Site Guide
c Thelnstirution of 8'1gineeringandTechnofogy
1154
::g Appendix I G
=a G4.1 Electrical Installation Certificate
:;a Figures G4.l (i)-(iv) show a typical completed Electrical Installation Ce.rtificate comprising
Forms 1, 3 and 4. It is assumed that the diagrams and documentation required by
:a Regulation 514.9 are availab[e. The installation is for a music shop, which has SELV
lighting, wiring in close proximity to gas pipes, broadband and data cables, and has fire
sealed trunking through to a store room. Regarding Form 4, the continuity test has been
:;B carried out using (R1 + R2) and hence R2 testing is Not AppHcab!e; also, since RCDs 1
and 2 each protect three circuits "ditto" marks have been used on the form. Different
test instruments will show di,fferent displays indicating "out of range", e.g. +299 or >199.
:a
=a
=9
=9
:;a
==3
On-Site Guide 1 1 5 5
e The Institutionof EngineeringandTedlnorogy
Appendix
INSTALLATION ADDRESS
Buzz Music Store
.: . :.......................................... 22.!ah.Dsroa.S.r.rccL ...................................................................... �........ Post Code: �.g9, . 1 . �
Oldtown
DESCRIPTION ANO EXTENT OF THE INSTALLATION TIIC!I boxes as appropriate
New lnstallation 121
Oescriplion ol inslallaUon:
Rewire ,of small commercial premises - music shop
Addition to an
existing lnstalalion □
Extent ol fnslalatlon covered by lhis Certificate:
Complete installation
Alteration to ar1
exiSling instaratiOn □
tUse contlnualion sheel I l'\!!CGSSBM soe conltluatlon sheet No: . A
FO.R DESIGN, CONSTRUCTION, INSPECTION a. TESTING
I b e � the person responsible fllf the design, oonslruction, inspection & testing of the electrical insla!lalion (as irllicated by my
signatu-re below), particulars ol whit!h are described above, having exeJcised reasoo.able skill and care vd1en carrying out lhe design,
construction, lnspecllon & testing hereby CERTIFY lhat the said work for which I have been res ponsible is to the best of my
knowledge and beliel In acconlance with BS 7671 :2008, amended IO ?QJJ•...•• ,(daie} excepl IOf the departures. If any, detalled as
lollows:
Details of deparlures lrom BS 7671 (RegulatiOrtS 120.3 an<l 133.5):
None
e o
: :rE:12 ::;; ; ::
CompanyPCJ,Electrical ........................................................
d
ee
:
•: 0 : : ::
:
;, ; ; ; ............
□
Conductors Protective Device
TN•C
TN•S
a.c. d,c.I.a' □ Nominal vo1tago. U/Uo m ..........no.v
Cha:racteristlcs
1·J)haSe, 2-wite 2•wire D Type S.JJ Lfu
□ 2-phase, 3.-wire □
TN-C-S
TT 1•pl\ase. 3•wlre 3-wlra D Nominal fmquency, f 1'' ............. .S.O. Hz
rr □ other □ L0.9.. kA
3-Pl'laSe, 3-wire □
Pros.l)e(ltive faolt current. lit w Rated
current..............
lOO ,A
,Other sources □ 3-ptme, 4.wJre D External loop imped(U'IQ&, :Z. � ..21. n
of S1Jpply (lo be detailed
on atlached sdhedules) Con&mabon of supply l)Cii¥ity ,,.__ mb y snqu,y. (21 t1J err;ur, aa,y
121 _,..,,,.,,d
Page 1 of .f:
Ear1hing OOJ'lductor; material � P � .............. csa ......... J §.... mm2 Continuity and cormection ve!lfied liZI
Main pwteclive bonding
concJuc!or.i. material � P � L ............ ,c:sa ......... JQ.... mm 2 Continuity and connection verified Ii:!
To iwoming water andfoI gas service ra- To olher elements:�A .............................................................. .
Main Switch orClrcult-br1111ker
es, Type arld No. of poles.��.�.:�!.:�.�?����). C1.men1 rating ....... J:09..A Volt.tg& r�,ng ........ i9. .... V
COMMENTS ON EXilSTING INSTALLATION (in 1h11 case ol an addition at alteration see Section 633):
NIA ....................................................................................................................................................................................................... .
SCHEDULES
The attached Schedules are part of this document and thls Certificate Is vald only when they are attached lo It
...... L . Schedules of Inspections and .....L .. Schedu1es ol TeSI Results are atta.ched.
,c,,x, ...,...,.... o i - - - « i
This safety Ce:rtificate l:ias been inued to confirm that the electrical installation WOl'k to which it relates bas been designed,
00115tl\lcted, inspected and tested in accordaaoe with British Stand:ud 7671 (lhc 1ET Wiring Regulations).
You should hm·e rcce.ived an uorigin;!J'. Ccnific.act and the contractor should h(l\'C retained a duplic.aic. I f you wc,rc the
person ordering the work, bm not the own.er of the in5Ulla.tion. yoo 1hould p:m this C.Crtifieate, or a fu.11 copy of it including
the schedules, immediate I)' to the owner.
The "origrnal" Certificate shoo.Id be retuned in a safe place 3Jld be shown to any penon inspecting or undenaking further
work on the electrical installation in the fulllro. H )O
' U later ncate the property, drls Certificate 'Nill demomtrate to the new
owner that the electrical installation complied v.id:J the requimnen� of British Stand:ud 7671 at the lime lhe Cenificate was
issued. The Construction (Design 1111d M11J1agancol) Regulations require that, f'or a project covered by tho5C Regulations. a
copy of lhis Cenificate. tagctha wid! :;.ehcdulcs, is included in the projt\11 health and s.afcty dO<;Umcmation.
For safety reasons, the electrical insu1ll:u.ion will need to be inspected 111i:!.ppropriate intcM1.l1 by a compc1en1 person. The
m.uimum time interval recommended before I.he next impec:tion is stated on P�c I under• BXT INSPECTJOX·.
This Certificate is intended to be inued only for a new el.eclrical ins1al.lation or for new work usociatcd with 11Daddition or
alteration IO an existing illS!al.lat:ioo. It should not have been is.sued for the inspection of 3JI existing electrical installatioo. An
"Electrical lnstallatioo Condition Repon" 5hould be issued for such an impection.
Page 2 of .4.
Cl] {c)
� of dl!'lgot notlcos rind OCl'!ol watn1ng t!Olloos
Labelw,g ol ptOl:eclMJ dew:as. swlllft!S and IDrminals
NtA) (111) o � � (noro 3)
(Z] (d) ldOlltiricaliorl Of 00f'IC!uc:IOC's
isli:\J (rY) Alaoog CUIOI react, (note 41
C a b l e s and conductors
:Fault protection:
(i) Automatic dh,conl'l&Otlon of supply:
(lJ Seloctoonoloono::UCCO<Sforas�ne-ca,,ry,ng � , y a'ICI
�dW
[ZJ (ZJ Er9Clion melhods
[LI [ZJ Routing ol cables ,n p t � zonos
[ZJ PIOIOllOII of protoctr'ICI bond1!"1g oonduc:lors Cebte, 11'100!1]:IOnllng earthed Bffl'IO!Jf 0t $holllh. 01' n.n
�
� � of suppCornonlary bone ng, QQndl,let(Q w,tlkn an eartried wl."IIIQ system, Cll' OlnerWISe lldoquolclly
rfslAI � Of oaitlanQ Qil'Q(IOiN'l)Cl'U fOC' prolDcled against naJs. saows end lhe
cornbtnod � and rundJonal pulTJOIS(I$ (LI Mellt.onal protlldion � by 30 mA RCO IOt eablos
COl'ICOa!Od in IS (Yltl«O rocr11 rod in pr01Tli$0S no1 unelor
1/\oSupo!'V$bn cd a s 10d « in$tl\ldOd l)Ol'SOl'I)
[l] Cl'IOooo and S4'lling of pmoc!IVO a.-.cl mon.lO!"ll'lg (Z] Presenco 01frro berTiors. suia'!lle seals and protocoon
against lllOnnal oftocts
C!ovioos (for tau� 111'1d/oro..orcvrronl protoctoon}
(II) ,Non-conducting tocatlon: (nole 5) General
Bii! AbsMoo 01protective concM:lors PtOSOnCO and OOl'f{lel IOalliOn o f � deviCos lot
-I.Chg-
(110 Earth•free local equipotentJaJI bo!'lding: (no106) ISOlalieln ancl SWitd\tng
� P r ( J s - 01(laah.froe IQcal oqu,pol(lnllal AdlHlU!ICY ol !ll0COSS ro !IDd othoI oqu,pmonl
bonc:bg Pani.culal protGclNO measures for spoc:ial rnstallal,ons and
(Iv) Electrical sei:,aratlon: (ncto 7} IO(;aUons
isiJl Ptov,ao<:J for c,no item of cu�-us,rrg � ol s ngre-cx,lo dov'ieoJ IOI p,ot.o,;t,on 0t
OQ!llil)'TlOl'lt $WilCh ng ,n no QOnduc:lots on!)'
� PrtMded flX more than one !tom of curont- Cotrecl oonnection 01acc:es:sones: and �
lJ'Sfng equtpmonl
"- 01·ullC:Ol"'l'O'lagO p,ococtwo Clcrrcos
Acldtuonal protection: SeloCllal ol oq1.apmonl and proledl� memuimi
[Z) Pmsonco of ros.\du:al C<ATent r:fev,COS{5) apptopna1e ro extornal lnfluor>00s
� P� Of ,supploriionlary bonditrg· (:(Jndudot$ $dod,o;\ ol approprta!O krndional sw-lOl'ling dCIV>OOS
4-Jan-2-012
NOTES:
to indlcate an ins,peclioc, h3s been carried out and the result Is sa�sfacto,y
NIA to indicate th.111 1h11lnspoc:tion is not applicable to a particular item
An 8f11ry must be rnade in IMIIY box.
1. SELV AA GXtr.1-<IOw VOllllgO syswmWhtdl is Oloctricallf
scpatalOd from Ea11n at1e1from othor s)'Sloms. Tho
- Non<oncluaiog IOeal!Otll •not •l)plicablo rn domOSllc promisos
arid toQuiMg spoei p,oeauliOI\$ (soo Rogu!alloo 418.1)
parfiCul8r roquiNIWll'lts or lbo Rogv'aiJol\$ must tio e. EaM<f-oo IOc:al oq..,;polOl'll!al 1Jood1r,g •l'IOI IOll)li(;ablo In
r:IIOCkod (SOOSOCl.«I 414) Clomoslic p,omi:SOS, orly I.ISOd III Spacial C!tCumst.lncos (sao
2. Molllocl of basrc l)(Ol.odion •wiu illCluOo mtaWtOmom ol Ragu'aliOn 41&2)
41Stano8$ woo,'O - � 7. Eloo\lleal SO!)alabon hvo Socliot1 0 3 a!'ld Rogula1#! 418.3)
J. Ol:liStadDs •only OC!Gp1)Jd 11'1s;,oe,a' OICUtrl$Ul'ICO$ ($CIO
Rogulal!on!s 417.1 encl 417.2)
1158
4. Ptaor,g oYI ol road! •0i\Jy adop(OCI in Spocrlll Page .3 of .A
«c:um$taRcos, (-Rog�bot"IS-417.1 al'ld 417.3)
On-Site Guide
c The lnstirution of 8'1gineering and Technofogy
T Figure G4.1(1v) Generic schedule of test results - Electrical Installation Certificate - page 4
el-
Z H I DB (0) .9.JJ . ..........................
, .............. lnuation res_stari<:e Ser No 11 ---
,.. at 08 (kA) .J..9.2 . ....... .................. Earth ta.-t loop lmpecance s.,. r<o. 116Ji47S
Corrac:t supply powtty con!lnned fil, ............................. .................. RCO ......... !kr,,No.. 116lll475 .......
-
··--·····-·····-··-·-····-··· Earth
-
. ... resislana, 1'!"··-···-- ·--·····-··-·-·····-··--·····-·····-·
Ph&M uoutnet conffrmtd.......,. • • - I l l m..
I Tntrnults
Tested by:
N•. . (Coplt.ls) C L I V E J E N K I N
C,..J.iJ.e.j.-- -- ·· ••
I
Ringinal Co,auy RCO
Si9nahn •••.• 011, .!l.-:J1UJ,:i0.LL c..o.ilccnilluity (OJ Retil:at<o z. Re,r,w
-
(R,•R,l (0) (oontnJe on a sep;wa1e sheet ii
Clrwldmlls (0) <rib (MO)
,__ (ms)
- Owra,m,nt deYa Conduc1Drdelai$
---1 i--
- -- -
lj1 ,.i i
I I
g fl il i II ! ij
- /;
. .•
E
z f
'E
a Cirrul llescrqux1
i
.f
. :. t J
!!!. UJ
8l I!!.
;,- I! <U ::,!<'
e. .l.: t
::,
" ..
.?
<Il <Ill J"
.
' ' .,
,;;
' I c n n
1 Ring - sockets shop area 60898 B 32 6 C 2.5 1.5 0.6 0.6 0.97 038 NJA
.2'.11
; :,-.wi 0.57 56 142 RCD I
-
s'76 6 +t29
2 IRadial - Water heater 60898 B 16 6 C 2.5 1.5 NIA NIA NIA 0 2 0.4L.:_ RCDI
-.- -
11
. - •-2.5
60898 C 1.5 NIA NIA NIA 029
.
i-:---,
3 Radial - Burglar alarm +• rt-299o.49 • RCDI
4 Ra&al • : t i « h b WCICOllllll!tt Mid t . c k ou898 B 16 6 C 2.5 1.5 NIA NIA NIA 0.59 NIAJ+""'"'"""I { 0.78 48 19.9 RCD2
Fire al.um _ 60898 B 16 6 C 2.5 1.5 NIA NIA NIA 033 NIA +iwr_:,,,,. 0.53 • RCD2
R_adial
6 Lights - internal, cxtcmal sign 60898 B 6 6 C 1.s-· J.O NIA N/A NM. 0.51 . 299{0.71 • -.- RCD-2
171span:
Spare
'Whlnhnnnoap.n-t1amgl'Nlma.itlhis..,.isal!ohe(R1•fb)dN<mit
"'-
NOTE: One schedule of test results will be issued for every consumer unit or distribution board Page .4. of .4.
Ill C')
::g Appendix IG
=a G4.2 Electrical Installation Certificate - Completion
:;a Notes:
:a
1. The Electrical Installation Certificate is to be used only for the initial certification of a
new Installation or for an addition or alteration to an existing installation where new
drcuits have been introduced.
:;B It is not to be used for a Periodic Inspection, for which an Electric-al Inspection
Condition Report form should be used.
For an addition or alteration which does not extend to the intiroduct'ion of new
drouits, a Minor Electrical lnstaHation Works Certificate may be used.
The o riginal8 Certificate is to be given to the person ordering the work CRegulation
11
This safety Certificate has been issued to confirm that the electrical installation work to
which it relates has been designed, constructed, inspected and tested in accordance
with British Standard 7671 (the IET Wiring Regulations).
You shoul.d have rece ived an ''original" Certificate and the contractor should have
retained a duplicate. If you were the person ordering the work, but not the owner of the
=9 installation, you should pass this Certifica.te, or a full copy of it induding the schedules,
immediately to the owner.
:;a The original" Certificate should be retained in a safe place and be shown to any person
11
inspecting or undertaking further work on the electrical installation in the future. If you
==3 later vacate the property, this Certificate wil'I demonstrate to the new owner that the
electrical installation complied with the requirements of British Standard 7671 at the
On-Site Guide
e T h e Institution o f Engineering and Tedlnorogy
I ''°
::g Appendix I G
=a time the Certificate was issued. The Construction (Design and Management) Regulations
require that, for a project covered by those Regulations, a copy of this Certificate, together
:;a with schedules, is included in the project health and safety documentation.
:a For safety reasons, the electrica'I installation will need to be inspected at appropriate
intervals by a oompetent person. The maximum time interval recommended before the
next inspection is stated on Page 1 under "NEXT INSPECTION".
:;B This Certificate is intended to be issued only for a new electrical installation or for new
work associated with an addition or alteration to an existing installation. It should not
have been issued for the inspection of an existing electrical installation. An NElectrical
Installation Condition Report" should be issued for such an inspection.
=a The following tests., where relevant, must be carried out in. the given sequence
(see also 10.2.):
:a Each conductor of the ring fina'I circuit must be tested for continuity, ,including
spurs. An exception is permitted where the cpc is formed by, e.,g. metallic conduit
or trunking and is not in the form of a ring. N/A can be recorded here but continuity
:;B of the cpc wiU be confirrned in either column 13 or 14.
2 Insulation resistance
All voltage sensitive devices to be disconnected or test between live conductors
(line and neutral) connected together and earth.
The insulation resistance between live conductors (Une-to-Hne and line-to-neutral
for three-phase installations and line-to-neutral for single-phase installat;ons) is
inserted in column 15 and between Hve conductors and earth in column 16.
The minimum insulation resistance values are given in Table 10.3.3 of this Guide.
3 Polarity - by c.ontinuity method
A satisfactory polarity test may be indicated by a tick in column 17. Only in a
:a
Schedule of Test Results associated with an Electrical Installation Condition Report
is it acceptable to record incorrect polarity.
B - Installation energised
=a
4 Polarity ·of supply
The polarity of the supply at the distr·ibution board should be confirmed and
indlcated by ticking the box o n the Schedule of Test Results.
5 Earth fault loop impedance l s
This may be determined either by direct measurement at the furthest point of a live
circuit or by adding {R1 + R i ) of column 13 to Ze- Ze is determined by measurement
at the origin of the installation.
=9 Z s = Ze + (R1 + Ri)
Zs should not exceed the va'lues given in Appendix B.
6 Fundional testing
The operation of RCDs (including RCBOs) is tested by simulating a fault condition,
independent of any test facitity in the device; see Section 11.
When testing an RCD at lo.n, record the operating time in column 19.
Where RCDs rated at 30 mA or less are used to provi,de additional protection, the
=9 devices are also to be tested at 5I.6.n and the operating time recorded in column
20.
:;a Effectiveness of the test button must be confirmed and the result recorded in
:a
=a
=9
=9
:;a
==3
On-Site Guide 1 1 6 3
e The Institutionof EngineeringandTedlnorogy
Appendix
T Figure G4.5 Minor Electrical 'lnstaUation Works Certificate - page l of 1
2. Localloo!Adct,ess 1 L a t r i g g Rise, O l d t o w n
P•ost Code A:C30 2 B N
3. Date mrnor works completed 4-Jan-2012
3. ProiecilYe device lor lhe modilled circuit Type .llS..EN. 6lQ09..'IYm. C Ratlng .......... i. A
Com.rneru on existslg instdation, lndlJdJng adeqLJaey ol earttw,g and bondhg arrangementS (see Regutatlon 132.16):
E a r t h leakage c i r c u i t • b r e a k e r ( E L C B ) w e d i n u t i l i t y a r t a o n older p a r t o f the i.n.)1.aJJation;
client advised t h a t E L C B m a y n o t p r o v i d e adequate protection and t o have periodic inspection
carried o u t o n installation.
E a r t h i n g and bonding arrangements generally satisfaclory.
PART 4:0eclaratlon
Wle CERTIFY lllal tl'I& $aid WOrks dO riot impair ttie sa!ety ol ll'le e:itislwig insta!lati011, t!'lat ttie said works have bee11
designoo, ocms1ructed. i n � e d and tested in acxoidance wilh 8S 7671 :2008 (IET W1rillg RegulatiOns). amended to
2011 ........ {date) and lhat the said works, to the best of my/our knov.tedge aod beief. at the lime ol myfour inspection,
oomolied wih BS 7671 exoecl as detaied in Part 1 above.
Page 1 of 1
c The lnstirution
On-Site Guide
of 8'1gineering and Technofogy
1164
::g Appendix IG
=a G4.6 Minor Elecbical Installation Works Certificate -
Scope of application
:;a
Notes:
:a 1. The Minor Works Certificate is intended to be used for additions and alterations
to an installation that do not extend to the provision of a new circuit. Examples
:;B indude the addition of socket-oudets or lighting points to an existing circuit, the
relocation of a light switch etc (see G2.2).
2. This Certificate may also be used for the replacement of equipment such as
accessories or luminaires, but not for the repiacement of distribution boards or
similar items. Appropriate inspection and testing, however, should always be carried
out irrespective of the extent of the work undertaken.
G4.7 Minor Electrical Installation Works Certificate -
Guidanee for redpients
(to be appended t.o the Certificate)
This Certificate has been issued to confirm that the electrical installation work to which it
relates has been designed, constructed, inspected and tested in accordance with British
=a Certificate should have been received for each existing circuit on which minor works
have been carried out. This Certificate is not appropriate if you requested the contractor
to undertake more extensive installation work, for which you should have received an
!Electrical Installation Certificate.
The Certificate should be retained in a safe place and be shown to any person inspecting
or undertaking further work on the electrical installation in the future. If you later vacate
the property, this Certificate will demonstrate to the new owner that the minor electrical
=9 installation work carried out complied with the requirements of British Standard 7671 at
the time the Certificate was issued.
=9
:;a
==3
On-Site Guide 1 1 6 5
e The Institutionof EngineeringandTedlnorogy
::g Appendix IG
=a G4..8 Notes on completion of the .Minor Electrical
Installation Works Certificate
:;a
:a T Table G4.8 Description of the area,s to be completed
Description of minor works Information t o record
:;B 1,l The work to which the certificate applies must be so
described that the work can be readily identified.
4 No departures are to be expected except in most
unusual drcumstances. See Regulations 120.3 and
133.5.
Part 2 - Installation details --
2 lhe method of fault protection must be dearly
identified e.g. automatic disconnection of supply
(ADS).
comments on existing The installer responsible for the new work should
installation record on the Minor Electrical Installation Works
Certificate any defects found, so far as is reasonably
:a practicable, in the existing installation. The defects
recorded should not affect the safety of the
installation work to which the oertfficate applies.
Part J - Essential tests lhe relevant provisions of Part 6 (Inspection and
Testing) of as 7671 must be applied in full to all
=a minor works. For example, where a socket-outlet is
added to an existing drcuit it is necessary to:
i) establish that the earth socket-tube of the socket-
outlet is connected to the main earthing terminal
ii) measure the insulation resistance of the drcuit
that has been added to and establish that it
complies with Table 61 of as 7671
=9 iii) measure the earth fault loop impedance
to establish that the maximum permitted
disconnection time is not exceeded
iv) check that the polarity of the socket-outlet is
correct
v) (If the work is protected by an RCD) verify the
effectiveness of the RCD.
Part 4 - Declaration
=9 Raplatlon 651 A 1he Certificate must be made out and signed
:;a
by a competent person in respect of the design,
construction, inspection and testing of the work.
==3
On-Site Guide
e The Institutionof EngineeringandTedlnorogy
1166
::g Appendix I G
=a T Table G4.8 continued
:a However, this Guide will only consider the Electrical Installation Condition Report for
Domestic and similar installations with up to 100 A supply. For installations with a supply
greater than 100 A, see 11ET Guidance Note 3.
For domestic and similar installations with up to l 0 0 A supply, the inspector will be
=a required to complete a minimum of five pages of information for an EICR.
An Electrical Installation Condition Report (:Form 6) is to be issued for all
inspected installations.
Figures G4.9 (i)-(v) show a typical completed Electrical Installation Condition Report
comprising Forms 6, 7 and 4. The insta\lat'ion is some 20 years old and has no RCD
fitted.
=9
=9
:;a
==3
On-Site Guide 1 1 6 7
e The Institutionof EngineeringandTedlnorogy
Appendix
T Figure G4.9(1) Electrical Installation Condition Report- page 1
::• =
SECTJON D. EXTEHT AND UHTATIOHS OF INSPECTION�DTESTIHG
Exfel1I d Ille e!edlical ilst.alatim covered� ll1is report
Visual i n ¥ c l i o n . t o disuibuto.s tlqwpment and electric mcter�inspcction and test o f consumer unit and
..fimiJ..!;.ii.t . -·ir·----illn-;;i=·----J""fniteC:fU"·,,.......__,.-----···
�d .
lirllt.l�ll$ i'l(l):jing the rea:scns � Reg1'a,O,, 63'.21 ...P ....��.!!!�.·--··tv..��;P.,�!..... -.!L._. __�!t!?.�_1¥.!1_�.P.!__._._._.
--·--·-·-·-···--·-·-·-··-····-·-·····----·-··---·-·······-···-·····allPllanqt:a,. __._._...... __.__._.... ___._.... _____.... ____ .......___ .... .
-- ---
ihe Jea$:!IIS(se& page no.•____) - ����--·······---···-·--·--··--·-·-·-·----·-·-·----·-·-·-----·-·-·
.. -·-·-·-..... ..,-,-·--·--·-·-··--------·-·------
The inspectian 1111dtemg detailed In lhb repart and a � r r y i n g sdiedUles 11.1w been carried ou\ In acaxdance wi:11 SS 7671: 200B (JET
Wiring � U o n s ) as amended 10 .i(U l . ............................ -·
I. mJ1d be oo'.ed ihal � c:o11tealied'IWNn Mki1Q n l cmliirs, lndef ffocn. in roof spaces. and generaly "'tti'n lhe labric or tile buiklrg or
in:lergroold.J!.rte not beM1 tJspee'Jld mess s p e d � agreedbe!',,-, ihe e l m and � _ p r i o r co lhe fnspecilon.
SECTION E. SUMMARY OF TliECONDfTIO.N OF TllEUISTAl.LA�N
General oondiioo cl tie in.stalalbrl f11 !ec111$at etedlica1 Mlety) . b l e d�.8�.�x��!l.!}.!'}_�!'!.L.���.i� condition
..Q.[lh.<=�im.t�UQnj5.g�ra.]Jy_,gwd,Lid.tlm.ugh_s.Q,m��lgJl_�.J2f.Y.t'..w..ru1.d.tw:,... _ _ _ _ _ •.•.•- - ..-·-··
- • • - • • • • • - • • - - • • • • • • • - - • • • • • u • - - • • - • u • - - - • • " • - - - - • • • • • • • - - • u .. • • • - - • - - - - • - . , • - - - - - - • - - - - • • • - • • - - • • • - • • - - - - -
O\reral asse.ssmernd. Ille ilmla:ion in lams of i::. stilatiiy for m r w d use
SM+ef+\GTeRlf-,UNISATISFA CTORY'· (Oelele as 11pjl!Qpria:e)
'An u n � imessment i'dicl:es 1hat dlln aide Cl ard'or n:us code C2 oondaiDns ha'o'e been id�Jed.
SECTJON F. RECOMMENDATIONS
Where lhe overal assessmen.tof he suilabli:y of 1fle in�llalial for allUIUed use above is st.aled a UNSATISFACTORY, Ifwe recomme(KJ !hat
anyoi:lseMltion5 dassife:las 'Dallger,creseo!"(oodeC1)0l'Pole�dangerous·(oode C2) are llct.ed upon as a malterof wgency.
kl'.ellga:lon," ' � delay is reoarnmendedbr obseMllioos lden!oed as 'flxihef� teql.'ffd'.
Obserr.tlons classiled as 1inproi"'1111ld� t d t l d ' (code C3) sooud be gilien me c:onsldera�on.
&AJied btler,eressaiyrenedaaalO!!_belng laken, l l'Ml!ECX)lllllelldlhatll'e!_ll$131a!lonis l\rthef.llsPeded ancltestedbyJan.�20.t:i._.(da!e
SECTION G.. DECLAAAT10N
Wi1, being thl persOll(1) rnponslble for till Inspection and tnlfng ol the elecu:Jcirl ln�l11lon ( u Indicated by my/our llgnaturu
bllow)i. partlallar1 ol-..Nlch are described above, having enn:lsed iusonable 111111 a n d � WhNI cllT)'fng aut the l n � n and
tes11ng, hereby decla.l't lhll the lnfol'fflltlon In !his report, lncfud ng the obseM1lons 111.dthe ltlached schedules, provides ai 1CC1.1rat1
nsessment ol lhe condldon of the eltetrical lnstallldon takln Into aoco11n1 the staled exlem and llmlJat!ons In section D oClhhl re
Page 1 of .5.
TN.C
Earthing
O
Nu mber and Type of l.lve
a!.C.liiia cLc. 0
Nature of S11Pply Parameters
_ 1 r n 1 9 m ts -t--- ---=. - Cond u d o r s - - = ----+-- - - - - - - - - ..,.....- -----<> - -- - ....--..,..,..,.------ - --t
NomlnalYO!age,U/U-.'J _____ , A - V
I
SUpply F'rotedlft Otvlce
8S(ENJH:S W l . -•--·
TN-S O 1-phase, 2•'1\ft il° 2-wtre O Nomna1 tequency. f'I -·-----·-.!:i9_ Hz. T n_ _ _ _
__. . .
TTTN.C-S " 1-pllase, l - m □□· 3-w.ireDo PIOspedwe !all\ oimo1. l f l ___ JA_ M.
0 2 pl'8se. 3"llire · Otl'ler ·
E.t.emal bop - - Ze.,, ....Q 1 -n Raled culrelll _____JML.A
I
IT O 3 phase. 3-wtre D No'.e: ( 1) by enQJily
3ohase 4-wire O (2) byerqiiryorbyme.awemenl
Con."rma!icn ol < 1 1 n t ' f v Mll>IL'V VJ
(as
_Other 5JlllJlteS ol '1.l!l)ly delded on $Ched1Je) 0
SECTION J; PART IC\11:..ARS OF INSTAI..LAllON REFERRED TO IN fflE REPORT
Mtant of earttilng OeUita of 1n,1a1Iat1on Ea:M EledrOdt (t<hilre-e, )
·Oislrib1.1l01'$ Tni,e ··- N IA ·-·-·-·-···--·-·-·----·-·-·-·· ..·-·-·-·-·· .·-·-·-·-·-··-·-·-·-·-··--·-·-···-·· ......._.___...._._.__........
ln$ 11$)n LC!CabOn N!.A...-·-·-·----·-·-·-·-·····-·-··-----·-··-·-· .· - - · - · - · ..· - - - - - - · · · - - ...- - . - - ......._. ___ .__
-
d9c:#0<1e D I Re!is'.ance m Earth ..... . N I A O
Main Protl'Cfl'n Conductors
11.a1er1a1 Capper,_ .. _..___. csa _,_ .. _ _ 1.6_._r,n2
,Mail pl'OiedMl t u d 1 g
aird'r:JC!Ors
MafWI Coppet...•·-··--·--- e a _......- ...10"·-
To inmmin<l w.m- serriee u f Tortnrrim """'service u Toincollinaohervice 0 I Tos s:eet
I
C<itine;oll)n,
n
veri.'ied f;6
-
Mtln Switch I SwitcM'use I Circuit,Bru I RCO
I.Oc:ation go.-•--·-·-·--- .......- ......... I C1.111'8ntrat:9 ---··.. --·-·-:·--·- A ' !! RCD mli11 .-witell
---·--·--·-·-·-···--·-·-·---···-·---·--···-·-.. Fuse I d bng or &eng ·23o
A Ra:ed t:eSi:11.ral Q.ltl9tlt (l y ,) ...... _..N/A.mA
SS(EN) .BS..548.6___ ,__ . __ ·-·--· ......- I Vobge ra- ng ·-··--.. -·-·-···-------·-· v R$:ed Cm$ <lef.r, - ..·-·· . ·--···-·-··----·---'/jj_A . 111' $
Nod"""- ' 2__........ ____.. . . . .... . Meastnd cpemrg time{al , , ··-···--·--J L . 111' $
SECTION K. OBScRVATlONS
Refe,mg ID 11:!e schelfl.lles al lnspedicn am leSI resuts. Mid st.tJjied to tie illtali:Jns Sfleci5ell al the E.dMI M d dlnsp&dion
and llt.s6n,Q Secti:111
,No rernedl!lil acib1 b reqlired
D
OOSE.R\IAnot,{S) FURTHER
INVESTIGATION
REQU;Rm
('(ES I NOi
I . DaffiaJ:r lo ea.hk ror !Jlonr.cimill LClr.No.7} In lo1'11.aind:uclon •1'.lhll!._arclni, ttldcnl 1 ._ .... CL... -.. ._. _No..... _.._.
4. No.lddltiurlil prutectiol'I by RCI> rur t ulprncnt u"l'CI ouUIOGN--·-··-....····-----· . · - - - .. . -....._C3_ ....,_._ _,___.N.11.........--,
------·- ---·-·-·-----·-•·----·-"--------
.:.!'.St'.!!!!!!l .P.!llttt!Jcm
..
forJa_'!.,!l!!-)·.!11!!£ffi'WlliIn b a l l u , I J ! ! ! ! ' ; _ _ _ _ _ _ _ _ _ _ ·--·· C J ... - - · · - j l ____ _
Ole of t,e lollow.ng codes, as appo te, ha:5 been allocated lo e.adll a lhe dl5eM!ions l13de abow to idea to lte per5011(5) responstle
be mtallation 1he decree al IMtlentY lor remed"ml action. -
...9!- Pd.e112t,, erws • uruerit remedial IICti0l1-
C3- rec:ommended
Paae 2 of.$.
'"°' -
Note: This form is suitable for many types of smaller installation not exclusively domestic.
I
DESCRIPTION li1'lon .
NO CI.C2nC?O'Jdtd"'11sfl>tio
.ri s.ctiDfl II ofrtit Cc:VICtliotlRflllCl'(I ('( (JIH)
-
3.1 Presence allCI a:nditJ:111ol dis1ribtt.t:r"searthn;i arran.i-,eni (542.1.2.1; 542.1.2.2) Nn
3.2 Presence aRdcmdiliori al eal!h eCectnx1ec:xmecli:lrl 'M1e!e app(albie (542.1.2.3) A No_
3T PtfMslon di earthing I bomdlng labets al a i appropriate loca s (514.13} ./ Nn
3.4 c«i:imalon 01 emfhm s i z e 1542.3; 543.1. U J Mn
3.5 Aa:es$1lil!v m l COfdtion cl earlmo
3.6 OJn."mlaQOll 01 nain
3.7 Condilion ar.i lit)'
al MET (54J..J2)
bOll(jng Wlductor es (544.1)
of main pi'O(die bOll®'IO (543.3..?; 544.1.2} I
./
NO
-
3.8 A.ccffl,til!y am c:onlt'..ion,rJ all pro:adve boll,ing COM9Ctions [543.3.2} No
4.0 C<lNSUMER UNn(S) I OISTRIBUTION BOARD(SI
4.1 Ade"acy of workilg space/ il'Xe$Sibc.'Y ID consumer Lni I dis!Jillnon board --(132.12; 513.1)
' -
J N"
4 . 2 Sewity iii: misi (t34.1.11 I No
&-
4.3 Cond on O en;josu-e/:Sl in term,,ol IP r3ling el"C{416t) N"
4.4 Condr!ion or e,v:jowe(s) in ol etc ( 6.Sl Nn
4.5 Endosuffl l'llll dama,gecl(cfelma'llld so as 10 tnpair sa'ety (621.2r■)} N2-
4.6 Presence or i m i "1ked S'Mth (as retJJll"lld by S.!7. U ) II '"5-
4.7 Opera!lan al mail S'Mi:11 (flnciional chedc) (612.13
-1/ LNo
4 . 8 - Manual operation ol a m . i t Gld ROils kl prove diso:medi0n (612.1 J.21
4.9 Correa idri"'ICiS!ion d CWJil de:aJs s1d ?"olective de'li0es (514.8.1: 514.9.1)
./
I./ """'
Mn
4.10 Presence ot RC-0 (IUSl".erly le$! nooce at OI near o:nsi,mer l.l'lil I disiibwon bOeflJ (514. 12.2) lr No
4.11 Ptesenoe or noMiandatd (mb:ed) cable CCIOU' wan.ng,
dirnbc.rti)n bOanHS.1,.1 I
- notice, at 01 nell' Cl)l'l$llmer l.l'lhl No
4.12 Ptesenoe or a l w¥l'IIIQ t'ICi6::>eet 0t n e a r uni/ tio(Wd (514.15) N / A NO
4.13 Ptesence of ctherfl!tpnd I l l (plWe soecitt1{Seo:lcn 51 ) tNtA No
4.i4 Exama'Jon o f deYicJ,e(s)and base(s): cxmcttniund rating{noslgns di No
unac:ceir.able theonal darnMe At!'h! or f421.1.31
4.15 SilWJ&.poiepmc:tlvedM:!!IS lnlinll ClOl'ltlleloronl-/(132.14.1:530.3.2) I NO
4.t6 agaml medmlcal damage Y<he,re cables efller COO!!llmet unit I dlsillJutlan board
!522.8.1 • 522.8.11) No
4.17 agailst electronagnrJc 11,ects \ilfflll cables en:er CORSlffllif uli.: I ds!ribu'..1011board 'I No
endosures 1521.5.11
4.18 RCO(s) provided for lault protection-lrd!des RCBOs (411.4.9: 41 tS.2: 531.2) Lj No
4.19 RCO(s) prottided for illt:l::ional p!UeCiiion • lncbles RCBOs {411.3.3; 415.1) tG No
,.,,,...,,
HOI
ITEMI _,,, -
(I.JM lllllMI abcMt. lt!Hl,MIII
Fwt!N,
I
DESCRIPTIOH
111' s«to, I( rl "'°
c1.ane:to«11111 10bt (YorNJ
llloMJ
5.0 FIHAl CIRCUITS
5.1 ldll!n::iflCffllll ol mndu:i:M (514.3.1) No
52 Cablm O'lffecil't" suppollil!d 11:roogh!M 1helr M (522-8.5} o
5.3 Coodtion ol llldB!loo at tve pa,ts (416.1)
- Nco-walhedcables by endowre in Olll1duJ. ell ornriffQ (521.10.1)
- i l°i
=-
1N/A
No
No -
• To i1cule 1he i/1',eoritv0/ COIW and l'IQ sv..';ems (rnet,91;; and plast;;) i"rj/A No
5.5 Adequacy ol c:ab1es for ll)i'l9 eapacify Mt! rega«i lcr the type and d
, 0
SI$ ISectiOci 523\
5.6 Cx,rdinaxo betNeen and overload devic:eS (•33.1; 533.2.11 No
5.7 Ad ol pro' (le',1(l$$: Mie ¥a:I wrren: for '3,jt (4, , .3) I NO
5.8 Presence m act«iuacy o1 circut p,otec'.ive concM:.Ors (411.S..1.1: 543..1) No
5.9 w..tng S)Om(s) llflprqxlate lcr 1h11type aid M'J.Jre ol ltie lnsralb!lon and eXlt:mal ir6lences
(Sl!C!ion 522) C1 • 0
5.10 Concealed cat.s installed rn prMalbed m m (see Sedlcxl D..&!Mt and li'IWaCillns)
1.5226.1011 l 0
5.11 Calcul!ld cables lncolpora'.r,g e:riit!d am,ur or shealti, « M 'NMil Ul1hed \lfring syslarn.
or Olherllise poled8d • i n s t meenaml dl e rrom nails,
D. & m d 11M hl'atM<I IS22.6.101; 522.6.100)
and the a (see Section r3 I 'o
5.12 PrcMs/on ot dib:Jnal p-olt!dion by RCD ndl exceeding 30 mA:
• foraUsockel-ou ets o!rdlg 20 Acrlnss provided f a 11Se llyordnary pm,onsudes:san
e:uiection Is oemil'td 1411.3.31 'C3 I 0
• for S!.Wf to motiile ent not ,e:x.OM!fftg 32 A raang for 1 $ aMoots (411..3.S.) M No
• lor cables oanreu:I In wab a ,DRll!w: (522.6.101; 52'2..6.1031 '.\ No
1-
13 Pwvisi0n of r.re lmMn, sea!J1g arrqiemea!s aoo lhemllll e1lecc (Sedion 527)
- ..No _
14 Santi I aitJ!es segega'.ed/sepanr'.edfrorn Band I cables(528.1) :"olo
5.15 segegB'.ed I separated mn c:orimuricetiol cabling (2 6.2)
5
No
5.16 cac. SBCnOll'..ed/ sepattled ftctn Cl!I ww:ies (S'28.3) ./ '1n
5.17 Ternm,Scn ol cabAl!s at e n - lniicate er.em ol Sfflping In Section O ol l!'le ffl110rl
{Sectit:>n 5261
• :sc.itldty ma4e ani, l.t'4er no e $ll'eitl [ 6l ,( i'iO
• No !,age lnwlation of a, o:rdJctor ..tsil:te OU'.slde 1516.8) NO
>-
I Comedians of tve mndllC!m adequa.ltty endosecl (521i.5) No
7 Acleq1111 conneded at polll ol emry ID endM!le (glnb, bushes etc.) (522.U} No -
5.18 Cood!ion ot accessories inclJdiJg, IIDdl.et-olA!eb:. S'M'.d1es and jainl baxes (621 l ( i ) ) ./ Nn
5.19 &litatililY ol a for ex!emal intueoces 1512..2) No_
--=====··=··::··;:···:::·-:::::::::::===::·:·--:::
---·-=·::·
=====·::··::--·
Zs al DB (0} .....QJ.6 ------- ----- . - · - - - - - - - - - - - - - - · - · - ..... - ·-·.. .,-, •=-� ... .
I,, al DB (kA} ••• 1.4 . _....... _... __ --·---·--· .......... --------·-- .-................ _.........._ ....... ---................. Earti lil\At l o o p � �::":!!... ............................................ .
=::i;.-,
CanMtsupplypolarityconfirmed Ii"] ---------------------- RCD ........ 546 3·71?
. ::.
3_ _ _ _ _ _ _
� H<jlltn<e =finned (when aocroorlalal liil• Eaifl electroOe resistn»
•
1- -
- - - - - - - - - - - - T71st n, s ul!s� - � - - - - - - - - - - i
CLIVE JENKIN I
Slgnl!!Jra ... _. [, ,J ..-..... Datt 4-.J.an-2012....... drail� � ,::=.. f Z.
RCO
(cor«itue on a separate sheet r necessaiy)
Circul c1ta111 ;
(O) I (R•: > M
I OJ o. (Cl)
I (ms}
1-----------+--'°""?Jl"'Jlde',ioe---1..Conducw_de!ais,_. l..._� - - -+-- - - 'l- - - - '- -+-- - '- � - +- +-- - - - - - - - - ---1
CitCscl Desctipl,)n
,,
I Ring - sockets downstairs BS 3871 I 3 0 2 C 2.S I .S 0.48 0.48 0.79 10.31 N I A + & . +299 0.48 NIAN/A NIA
2 Ring . sockets upstairs �s mitt 'l;;-, 3:;;;-n
0 2- t -"c,;-,2�.5r t -'1.7S1u' ."33; t0' .'33
"; t0' .:;:-:tO
5 4 ' .:-::t-
22 N :-:/7IA
:: t+:-:; ,,,, ..:-:;
,,;;;;;!' ,._ � - -:--t.o, ."38;t;N
2;;#: " '/"rA-t,N:;;/;A.-t,N:c/;A.- t -- - - - - - - - - -1
3 Ring - kitchen and utility �� .,..,, I 30 2 C 2.5 I - ' 0.7 0.7 I.IS 0.4() NIA+,,,, -o-2� 0.62 NIAN/A NIA
fsz f
4 Lights - upstairs BS 3871 I 5 2 C 1.0 1.0 �'I.IA NIA NIA13.07 NIA +zY,;+29', 3.2A N/A,N/A NIA
3.96N/r�� l A N /A - - - - - - -
.,., " ' " ".,.,- , +
5Ughu-downswsandutili1y�S3871 I C - 1 . 0 ; 1.0 l''-IAN/AIN7Ar3.8 N / A f � 9 ' . / - - --i
6 Lights - garage �� 3871 I 5 2 C 1.0 1 1.0 N/A NIA N/Aj0.36 NIA + 2 � 2 � 0.S2 NIAN/A NIA
7 Shower (8 kW) �S ;is71 I I 40 2 C 6.0 I 2.S NIA N/A NIA'0.15 NJA;+2'N/"291 0.31 N/AINIA N/A
8 - L ,_ - ---L- . - - • .- -+--+-+-�---------l
NOTE: One schedule of test results will be issued for every consumer unit or distribution board Page .S. of .5.
C')
::g
=a
:;a Appendix
:a
:;B Standard circuit
arrangements for
household and similar
inst,allations
Hl lntrodudion
:a This appendix g;ves advice on standard circ-uit arrangements for household and similar
premises. The circuits provide guidance on the requirements of Chapter 43 for overload
protection and Section 537 of BS 7671 for isolation and switching. Reference must also
=a
be made to Section 7 and Table 7.1 (i) for cable csa, length and installation reference
method.
It is the responsibility of the designer and installer when adopting these circuit
arrangements to take the appropriate measures to comply with the requirements of
other chapters or sections which are relevan , such as Chapter 41 'Protection against
electric shock', Chapter 54 'Earthing arrangements and protective conductors' and
Chapter 52 'Selection and erection of wiring systems'.
=9 Circuit arrangements other than those detailed in this appendix are not precluded when
specified by a competent person, in accordance with the general requirements of
Regulation 314.3.
=a A2.
A3
Radial
Radial
30 or32
20 2.5 1.5 50
• See Section 7 and Table 7.l (i) for the minimum csa for particular installation reference methods. It
is permitted to reduoe the values of conductor cross-sectional area for fused spt1rs.
Where two or more ring final circuits are installed, the socket-outlets and permanently
connected equipment to be served should be reasonably distributed among the circuits,
=9
H2.2 Circuit protedion
Table H2.1 is applicable for circuits protected by:
► fuses to BS 3036, 85 1361 and BS 88, and
circuit-breakers:
- Types 8 and C to BS EN 6 0 8 9 8 or BS EN 61009-1
- BS EN 60947-2
- Types l,. 2 and 3 to BS 387i1.
=9
:;a
==3
:a carrying capacity for the partirular method of installation, after applying appropriate
rating factors from Appendix F, see Table 1.·1 (i).The as..installed current-carrying capacity
(IJ so cakulated must be not less than:
:;B 20 A for ring circuit A 1
► 30 A or 32 A for radial cirruit A2 (i.e. the rating of the overcurrent protective
device)
20 A for radia'I circuit A3 (i.e. the rating of the overcurrent protective device).
The conductor size for a fused spur is determined from the total current demand served
by that spur, which is limited to a maximum of 13 A.
Where a fused spur serves socket-outlets the minimum conductor size is:
► 1.5 mm 2 for cables with thermosetting or them,oplastic (PVC) insulated
cables, copper conductors
1 mm2 for mineral insulated cables, copper conductors.
:a The conductor size for circ,uits protected by BS 3036 fuses is determined by applying the
0.725 factor of Regulation 433.1.1 m,that is the rurrent-carrying capacity must be at least
27 A for circuits Al and A3, 41 A for circuit A2.
H2.4 Spun
=a The total number of fused spurs is unlimited but the number of non-fused spurs should
not exceed the total number of socket-out'lets and items of sta,tionary equipment
connected directly in the circuit.
In an A 1 ring final circuit and an A2. radial circuit of Table H2. l a non-fused spur should
feed only one s;ngle or one twin or multiple socket-outlet or one item of permanently
connected equipment. Such a spur should be connected to the circuit at the terminals
=9 of a socket-outlet or junction box or at the origin of the circuit in the distribution board.
A fused spur should be connected to the circuit through a fused connection unit, the
rating of the fuse in the unit not exceeding that of the cable forming the spur and, in any
event, not exceeding 13 A.
:;a
is not required if the circuit-breaker is to be used as a switch.
==3
On-Site Guide 1 1 7 5
e The Institutionof EngineeringandTedlnorogy
::g Appendix
=a HJ Radial final circuits using 16 A socket-
:;a outl,ets complying with B5 EN 60309•.2 (B5
434])
:a HJ. I General
:;B Where a radial circuit feeds equipment the maximum demand of which, having allQV!led
for diversity, is known or estimated not to exceed the rating of the overourrent protective
device and in any event does not exceed 20 A, the number of socket-outlets is unlimited.
=9 The rating of the circuit is determined by the assessment of the current demand of the
cooking appliance(s), and cooker control unit socket-outlet if any, in accordance with
Table A 1 of Appendix A. A 30 or 32 A circuit is usuaHy appropriate for household or similar
cookers of rating up to, 15 kW.
A circuit of rating exceeding 15 A but not exceeding 50 A may supply two or more
cooking appliances where these are installed in one room. The control switch or cooker
control unit should be placed within 2 m of the appliance, but not direcdy above it.
Where two stationary cooking appliances are installed in one room, one switch may be
used to control both appliances provided that neither appliance is more than 2 m from
=9 the switch. Attention is drawn to the need to provide selective (discriminative) operation
of protecti,ve devices as stated in Regulation 536.2.
:;a
==3
On-Site Guide 1 1 7 6
e The Institutionof EngineeringandTedlnorogy
::g Appendix IH
=a HS Water and space heating
:;a Water heaters fitted to storage vessels in excess of 15 litres capacity, or permanently
connected heating appliances forming part of a comprehensive space heating instal'lation,
:a should be suppHed by their own separate circuit.
Immersion heaters should be supplied through a switched cord-outlet connection unit
:;B complying with BS 1363-4.
=9
entry door two-way
phone bell switch
maximum
1200mm
-- .. ·- -- minimum
=9 450mmf
:;a
tv aerial telepnone socket·
socket socket outlet
==3
On-Site Guide 1 1 7 7
e The Institutionof EngineeringandTedlnorogy
::g Appendix I H
=a H7 Number of socket-outlets
:;a 553.1.7 Sufficient socket-oudets are required to be installed so that all equipment likely to be used
can be supplied from a reasonably accessible socket-outlet, taking account of the length
:a of flexible cab'le normally fitted to portable appliances and lumina;res. Table H7 provides
guidance on the number of socket-outlets that are likely to meet this requirement.
:;B In Scotland, mandatory standard 4.6 requires that every building must be designed and
constrncted in such a way that electric lighting points and socket-outlets are prov ided
to ensure the health,. safety and convenience of occupants and visitors. The Building
Standards Division of the Scottish Government make recommendations for the number
of socket-outlets that should be installed in a domestic premises in section 4.6.4 of the
domestic technica'I handbook as follows:
kitchen - 6 (at least 3 above worktop height)
► other habitable rooms - 4
► plus at least 4 more throughout the property including at least one per
circulation area per storey.
The socket-oudets may be either single or double.
=9 Conservato ry 3 4 5
Hallway 1 2 3
:;a Loft 1 2 3
Location co ntaining a note 5
==3 bath or sho wer
On-Site Guide 1 1 7 8
c The lnstirutionof 8'1gineering and Technofogy
::g Appendix I H
=a Notes to Table H7:
:;a
I KffCHEN - If a socket-outlet is provided in tl,e cooker control unit, this should not be
induded in the 6 rec-0mmended in the table above.
Appliances built into kitcnen furniture (integrated appliances) should be connected
:a to a1 socket-outlet or switch fused connection unit that is accessible when the
appliance is in place and in normal use. Alternatively, where an appliance is supplied
:;B from a socket outlet or a connection unit. this should be controlled by an accessible
double-pole switch or switched fused connection unit.
It is recommende.d tha,t waH mounted socket outlets above a work surface are
spaced at not more than 1 m intervals along the surface.
2 GARAGE - The number of socket outlets specified allows for the use of a battery
charger, tools, portable light and garden appliances.
J BEDROOM - It is envisaged that this room will be used in different ways in different
households. It may be used simply as a child's bedroom requiring socket-outlets
for table lamps, an electric blanket and an electric heater only; or it may serve as a
teenager's bedroom and living room combined, where friends are entertained. In
this case, socket-outlets may be needed for computers (printers, sc-anners, speakers,
etc.), games consoles, MP3/4 players, mobite phone chargers, DVD players, digital
receivers, home entertainment systems (amplifier, CD player), haird r y er, televis;on
:a 4
and radio, in addition to lamps, an electric blanket and electric heater.
HOME ENTERTAINMENT - In addition to the number of socket-outlets shown in the
tab1le it is recommended that at least two further double socket-outlets are installed
in home entertainment areas.
=a
5 LOCATIONS CONTAINING A BATH O R SHOWER - Except for SELV socketwoutlets
complying with Section 414 and shaver supply units complying with BS EN 61558-
2 5, socket ou ets are prohibited within a distance of 3 m horizontally from the
boundary of zone l.
6 BEDSITTING ROOM - Rooms specifically designed or envisaged to be used as
student bedsitting rooms should be provided with additional socket outlets which
may be needed since persons using these rooms wiU often introduce other portable
=9 appliances in addition to items already mentioned in Note 3. In such situations a
lack of sufficient socket-outlets is an additional danger and therefore the minimum
number of twin out1ets should be increased to four.
=9
:;a
==3
On-Site Guide 1 1 7 9
e The Institutionof Engineeringand Tedlnorogy
::g
=a
:;a
:a
:;B
:a
=a
=9
=9
:;a
==3
On-Site Guide
e The Institutionof EngineeringandTedlnorogy
1180
::g
=a
:;a Appendix
:a
:;B Resistanc:e of copper
and aluminium
conductors
434.S.2 To check compliance with Regulation 434.5.2 and/or Regulation 543.1.3, i.e. to
543.1.3 evaluate the equation 52 = 12.t/k2, it is nec-essary to establish the impedances of the
cirouit conductors to determine the fault current I and hence the protective device
:a disconnection time t.
Fault current I = Uo/Zs
where:
=9 Ze is that part of the earth fault loop impedance external to the circuit concerned
R1 is the resistance of the Hne conductor from the origin of the circuit to the
point of utilization
R2 is the resistance of the protective conductor from the origin of the circuit to
the point of utilization.
Similady, in order to design circuits for compHance with BS 7671 limiting values of earth
fault loop impedance given in Tab'les 41.2 to 41 A, it is necessary to establish the relevant
impedances of the circuit conductors concerned at their operating temperature.
=9 Table 11 gives values of (R, + R v per metre for various combinations of conductors up to
and induding 35 mm 2 cross-sectional area. It also gives values of resistance (milliohms)
:;a per metre for each si�e of conductor. These values are at 20 °C.
==3
:;a
aluminium conductors at 20 °C
:a
4 2.5 12.02
4 4 9.22
6 3.08
6 2.5 10.49
6 4 7.69
6 6 6.16
10 1.83
10 4 6.44
10 6 4.91
10 10 3.66
16 1.15 1.91
=9 16
16
6
10
4.23
2.98
16 16 2.30 3.82
25 0.727 1.20
25 10 2.557
25 16 1.f177
25 25 1.454 2.40
35 0.524 0.87
35 16 l.674 2.78
35 25 1.251 2.07
35 35 1.048 1.74
:;a 50
50 25
0.387
1.114
0.64
1.84
==3 50
50
35
50
0.911
0.774
1.51
1.28
OnaSite Guide
e The Institution of Engineering and Tedlnorogy
1182
::g Appendix I 1
=a T Table 12 Ambient temperature multipliers to Table 11
:a
5 0.94
10 0.96
:;B 15
20
0.98
1.00
� 25 1.02
"' The correction factor is given by {1, + 0.004(ambient temp - 20 •c)}
� where 0.004 is the simplified resistance c-0efficient per 0c at 20 °c given by BS EN 60228 for
copper and aluminium conductors.
�
Verification
� For verification purposes the designer will need to give the values of the line and circuit
protective conductor resistances at fhe ambient temperature expected during the tests.
� This may be different from the reference temperature of 20 °C used for Table 11. The
rating factors in Table 12 may be applied to the values to take account of the ambient
:a temperarure (for test purposes only).
�
Multipli:ers for mnductor operating temperature
Table 13 gives the multipHers to be applied to the values given in Table 11 for the purpose
=a of calculating he resistance at maximum operating temperature of the line conductors
and/or circuit protective condu.ctors in order to determine compliance with, as applicable,
Table 41.2 the earth fault loop impedance of Table 41.2, 41.3 or 41.4 of BS 7671.
� Table 41.3
Table 41.4 Where it is known that the actual operating temperature under normal load is less than
� the maximum permissible value for the type of cable insulation concerned (as given in
the tables of current-carrying capacity) the multipliers given in Table 13 may be reduced
=9 accordingly.
=9
:;a
==3
�
On-Site Guide 1 1 8 3
�
e The Institutionof EngineeringandTedlnorogy
::g Appendix
=a T Table IS Multipliers to be applied to Table 11 to calculate conductor resistance at
maximum operating temperature (note 3) for standard devices (note 4)
:;a Conductor Conductor insuhrtion
:a installation
:;B
Not incorporated in a 1.04 1.04 1.04
cable and not bunched
�
(note 1)
Incorporated in a cable 1.20 1.28 1.28
�
or bunched (note 2)
� Notes:
Table 54.2 1 See Table 54.2 of BS 7671, which applies where the protective conductor is not incorpOl"ared or
lab le 54.3 bunched with cables, or for bare protecnve conductors in contact with cable covering.
� 2 See Table 54.3 of BS 7671, which applies where the protective conductor is a core in a cable or is
bunched with cables.
� J The multipliers given in Table 13 for both copper and aluminium conductors are based on a
simplification of the formula given in BS EN 60228, namely that the resistance-temperature
:a 4
coefficient is 0.004 per •cat 20 •c.
Standard devices are those described in Appendix 3 of B5 7671 (fuses to B5 1361, B5 88, B5 3036,
circuit-breakers to BS EN 60898 types B, C, and D) and BS 3871-1.
�
=a
�
=9
�
=9
:;a
==3
�
�
On-Site Guide
c The lnstirution of 8'1gineering and Technofogy
1184
::g
=a
:;a Appendix
:a
:;B Sel1edion of devices
for isolation and
switching
Table 53.-1!1 Y Table JI Summary of the functions provided by devices for isolation and
switching
:a
Device Standard Isolations Emergency Functional
switchingu switdling-5
Switching device BS EN 50428 No No Yes
BS EN 60669-1 No Yes Yes
BS EN 60669-2-1 No No Yes
=a BS
BS
EN 60669-2-2
EN 60669-2-3
No
No
Yes
Yes
Yes
Yes
BS EN 60669-2-4 Yes Yes Yes
BS EN 60947-3 Yes 1 Yes Yes
BS EN 60947-5-1 No Yes Yes
Contactor as EN 60947-4-1 Yes 1 Yes Yes
as EN 61095 No No Yes
=9 Circuit-breaker BS EN 60898 Yes Yes Yes
BS EN 60947-2 Yes 1 Yes Yes
BS EN 61009-1 Yes Yes Yes
RCD as EN 60947-2 Yes 1 Yes Yes
as EN 61008-1 Yes Yes Yes
as EN 61009-1 Yes Yes Yes
Isolating switch BS EN 60669-2-4 Yes Yes Yes
BS EN 60947-3 Yes Yes Yes
=9 Plug and socket-
outlet ( 32 A)
as EN 60309
IEC 6 0 8 8 4
Yes
Yes
No
No
Yes
Yes
:;a PIUg and socket-
IEC 6 0 9 0 6
BS EN 60309
Yes
Yes
No
No
Yes
No
outlet (> 32 A)
==3
On-Site Guide 1 1 8 5
e TheInstitution of EngineeringandTedlnorogy
::g Appendix
=a T Table JI continued
=a outlet
SWitched fused 85 1363-4 Yesl Yes Yes
connection unit
Unswitched fused BS 1363-4 Yes3 No No
connection unit (removal of
fuse link)
Yes No No
=9
Fuse 85 1362
Cooker c-ontrol unit BS 4177 Yes Yes Yes
switch
Notes:
I function provided if the device is suitable and marked with the symbol for isolation (see BS E
60617 identity number S00288). _ / -
537.4.2.5 2 The means of operation shall be readily aocessib!e at places whe re a danger might occur and, where
approprlate, at any additional remote pos;tion from which that danger can be removed.
J Device Is suitable fOI" oo-load isolation, Le. disconnection whilst carrying load current.
=9 537.2.2.1 4 In an illStallation forming part of a TT or IT system, isolation requires disconnection of all the live
conductors.
:;a
s 'Yes' indicates function provided; 'No' indicates function not provided.
==3
On-Site Guide
e The Institution of Engineering and Tedlnorogy
1186
::g
=a
:;a Appendix
:a
:;B Identification of
conductors
Kl Introduction
The requirements of BS 7671 were harmonized with the technical intent of CENELEC
Standard HD 384.5.514: Jdentifimtion, including 514.3: Jdentificmion of conductors (now
withdrawn).
=9
:;a
==3
On-Site Guide 1 1 8 7
e The Institutionof EngineeringandTedlnorogy
::g Appendix I K
=a Table 51
514.3.1
T Table K l Identification of conductors (Harmonized)
:a
Protective conductors
Functional earthing conductor
a.c. power drmlt 1
Green-and-Yellow
Crea m I
:;B Line of single-phase drcuit
Neutral of single- or three-phase drcuit
L
N
Brown
Blue
Line 1 of three-phase a.c. drcuit L1 Brown
Line 2 of three-phase a.c. drcuit L2 Black
Line 3 of three-phase a.c. drcuit ------
L3 Cirey
Two-wire unearthed d.c. power circuit
Positive of twe=wire circuit L+ Brown
Negative of two-wir,e circuit _ _ _ _ _ L- Grey
Two-wlre wthecl d.c. power drmlt
Positive (of negative earthed) drcuit L+ Brown
Negative (of negative earthed) drcuit2 M Blue
Positive (of positive earthed) drcuit2 M Blue
Negative (of positive earthed) drcuit L- Cirey
:a Three-wire d.c. power drcuit
Outer positive of two-wire circuit derived
from three-wire system L+ Brown
Outer negative of two-wire circuit derived
from three-wire system L- Grey
=a Positive of three-wire circuit
Mid-wire of three-wire circuit2.3
L+
M
Brown
Blue
Negative of three-wire circuit _ _ _ _ L- Grey
Conlrol drmlts, EUf and o l har applkalions
Line conductor L Brown, Black, Red,
Oran ge, Yellow,
Violet. Cirey, Vllhite,
=9 Neutral or mid-wire4 N or M
Pink or Turquoise
Blue
Notes:
1 Power circuits include lighting circuits.
l M identifies either the mid-wire of a three-wire d,c. circuit, or the earthed conductor of a two-wire
earthed d.c. circuit.
J Only the middle wire of three-wire circuits may be earthed.
• An earthed PELV conductor is blue.
=9
:;a
==3
On-Site Guide
c The lnstirution of 8'1gineering and Technofogy
1188
::g Appendix
=a IU Addition or alteration t o an existing
:;a installation
:a K2.1 Single-phase
An addition or alteration made to a single-phase installation need not be marked at the
:;B interface provided that:
the old cables are correctly identified by the colours red for line and black for
neutral, and
ii the new cabtes are correctly identified by the colours brown for line and blue
for neutral.
=a
Table 7A ,.- Table K2 Example of conductor marking at the interface for additions and
a'lterations to an a.c. installation identified with the old cable colours
On-Site Guide 1 1 8 9
e TheInstitution of EngineeringandTedlnorogy
::g Appendix I K
=a K4 Intermediate and two-way switch wires in a
:;a new installation or an addition or alteration
to an existing installation
:a Where a three-core cable w(th cores coloured brown, black and grey is used as a switch
wire, aU three conductors being line conductors, the black and grey conductors should
:;B be marked brown or Lat their terminations.
:;a Four-core
F"ive-core
Red, Yellow, Blue, Black
Red, Yenow, Blue, Black,
Brown, Black, Grey, Blue
Brown, Black. Grey, Blue,
==3 Green-and-Yellow Green-and-Yellow
On-Site Guide I
c The lnstirutionof 8'1gineeringand Technofogy
''°
::g Appendix I K
=a Table 7D T Table K6(HI) 'Flexible cable to BS 6500
=a Table 7E Y Table K 7 Examp'le o f conductor marking at the interface for additions and
alterations to a d.c. installation identified with the old cable colours
Function Old c::ondudor New conductor
------ ------
Colour Marking Marking Colour
Two-wire unearthed d.c. power circuit
=9 Positive of two-wire circuit
Negative of two-wir,e circuit
Red
Black
L+
L-
L+
L-
Brown
Grey
Two-wire wthecl cLc. pcM11r clraalt
Positive (of negative earthed) drcuit Red L+ L+
Negative (of negative earthed) drcuit Black M M Blue
Positive (of positive earthed) drcuit Black M M Blue
Negative (of positive earthed) drcuit Blue L- L- Grey
Three-wire d.c. power drcuit
Outer positive of two-wire circuit derived
=9 from three-wire system
Outer negative of two-wire circuit derived
Red L+ L+ Brown
:a
=a
=9
=9
:;a
==3
On-Site Guide
e The Institutionof EngineeringandTedlnorogy
1192
::g
=a
:;a
:a
:;B
A
Additional protection
inspection 9.2.2viHd
labelling 6.1
provision by RCD 3.4.1.1
supplementary bonding 4.7
testing 11.5
Alphanumeric identification of
Table K 1
:a
conductors
Alternative supplies, warning notice 6. 14
Automatic disconnection (ADS) 3.4. l;
3.5; 9.2.2c
=a B
Bands I and 11,segregation 7.4. 1
Basic. protection 3.4.1.1
Bath/shower 8
cubide not in bathroom 8.2
general 3.6. l iii; 3.6.3; 7.2.5iii; 8;
Table 3.4.3
=9 summary of requirements 8.1;
Tabte 8.1
underfloor heating 8.3.1
zone diagrams Figs 8.1 (i)-(iii)
Bending radii of cables Table 0 5
Bonding 4
BS 1363 socket-outlets AppxH
Building logbook Forevvord
Building Regu'lations 1.2
=9
:;a
C
Cable
commun1cations 7.4.2
==3 floors and ceilin_gs
grouping
7.3.1
7.2.1
in thermal insulation Table 7. 1(iii)
On-Site Guide 1 1 9 3
e The Institutionof EngineeringandTedlnorogy
::g
=a
:;a
:a
:;B
=a
Charge retention, warning
tabel 6.2
Circuit protective conductors 10.3. l ;
AppxB
continuity test 10.3. l i
Circuit-breakers
application Table 7.2.7(10
short-circuit capacity Table 7.2.7 )
=9 Class I and dass II equipment 2.4.1
Appx K
Colours, cable oore
Communica,tions cables 7.4.2
Competent persons Preface;
Foreword
Conductor cross sed1onal
area Table 7.1 (Ii)
Conduit
capacities Appx E
=9 supports
Consumer unit
Table 0 3
2.25; 3.3
:;a split
with RCBOs
Figs 3.6.3 )/(ii)/
(iv)/(v)
Fig 3.6.3(iii)
==3 Controlgear
Cooker circuit
2.2.5; 6.3
AppxH
Corrosion of ea ble AppxC
On-Site Guide 1 1 9 3 a
e The Institutionof EngineeringandTedlnorogy
::g I Index
:a Devices, selection. of
isolation and switching AppxJ
:;B protective 7.2.7
Diagrams 6.11
Disconnection times 3.5; 7. lviii; 7.2.7i v;
AppxB
Distribution board 3.1; 6.15
Distributor (definition) 1.1
Diversity AppxA
E
Earth electrode 4.9; 4.1 O
testing W.3.5; Fig 10.3.5.2
Earth fault loop impedance 1.1 iv; 13iv;
3.6. 1i; 7.2.5; 7.2.6;
:;a
External cables and
telecommunicatio11S Table 7.4.20)
==3 F
Fault current
prospective 1.3iii; 7.2.7
On-Site Guide
e The Institutionof EngineeringandTedlnorogy
1194
::g I Index
=a protection 3.3
:;a
Fault protection 3.4.1.2
FELV 10.3.3vi; Table 10.3.3
Final. circuits 7
:a standard
Fire safety requirements
7.2; Appx H
1.2.1
,G
Garages 1.1a
Gas ;nstallations 2.3; 4.3; 4.4 ; 7.4.3
H
Height of overhead wiring Table D2
=a Height of switches, socket--0utlets AppxH
High protective conductor current
earthing 7.5
labelling at D8 Fig 6.15
HSE Guidance Note GS 38 10.1
=9 Identification of conductors
Immersed equipment
Appx K
Table 3.4.3
Immersion heaters AppxH
Induction loops (hearing) 7.4.4
lnfomiation 1.3
lnittal testing 10
Inspection and testing 9
checklists 9.2.2; 9.3.1
label for periodic Fig 6.10
=9 report
schedules
AppxG
AppxG
:;a lnstaHation
considerations
diagram
7.3
6.11
==3 method
Ins ulation resistance
7.1
93. l ; 10.3.3
1194a
minimum values Table 10.3.3
On-Site Guide
e The Institutionof EngineeringandTedlnorogy
::g I Index
:a M
Manual, operation and
maintenanc,e Foreword
Maximum demand AppxA
=a Mechanical maintenance,
switching for 5.2
Meter 2.2.2
Meter tails 2.2.3
Mineral insulated cable Table C l
Minor Works Certificate AppxG
N
=9 Nomina'I, voltage 1.1 ii; 6.4
Non-sheathed cables 3.4.1.1
Non-standard colours 6.13
Notices 6
0
Off-peak supplies 1. l a
Ohmmeter 10.3.1
Outbuildings 1. l a
=9 Overhead lines/wiring
Overload protection
3.7.2.1; Appx D
3.2
:;a Overvoltages
p
3.7.2
==3 Part P
PELV
1.2.1
3.4.3; 7.3. 1v; 7.3.2vi; 9.2.2;
10.3.3v; Table 10.3.3
On-Site Guide 1 1 9 5
e The Institutionof EngineeringandTedlnorogy
::g I Index
:;a
Phase sequenoe check 10.3.8
Photovoltaic systems 6.16
Plastic services 4.5; 4.8
:a Polarity testing
Portable generators
9.3.1; 10.2; 10.3.4
2.4
R
Radial circuits Table 7.1 (,); Appx H
testing 10.3.1
Rated short.,cirruit capacities Table 72.70)
RCBOs 3.6.3c; 7.2.6
RCDs 2.2.5; 3.6; 7.2.4;
9.2.2d
diagram of operation Fig 11.0
integral test device 11.6
:a labelling
rnultipole
6.12
11.7
om;ssion of 3.6.2; 7.2.5
requirements 7.2.5
testing 11
=a Reports
Residual rurrent devices
Appx G
see RCDs
Resistance of conductors Appx I
Ring circuits Table 7.1 (i); Appx H
spurs 7.2.2; H2.4
testing 10.3.2
=9 s
Sdiedu!es 9.1; Appx G
Scope Preface; 1. 1
Se,lection
ea bles Appx C
devices for isolation etc. Appx .I
S5tV 3.4.3; 73. lv; 7.3.2vi;
9.2.2; 10.3.3v;
Table 10.3.3
On-Site Guide 1 1 9 5 a
e The Institutionof EngineeringandTedlnorogy
::g I Index
=a Socket-outlets - contd
protection by RCD 3.6.lii
:;a SPDs
decision flow chart
3.7
Fig 3.7.2.2
:a conductor critical length
connection methods
3.7.5
3.7.6
selection 3.7.4; Fig 3.7.4
:;B types 3.7.3
Split consumer unit Figs 3.6.3(1)/(ii)/
(iv)/(v)
Spurs 7.2.2; H2.4
Standard circuits Appx H
Stud walls Tables 7.1 (TI), 7.1 (ilQ, F6
Supplementary equipotential
bonding 4.6-4.8; Table 4.6
Supplier (definition) 1.1
Supply
frequency 1.li
nominal voltage 1.1 ii
Support, methods of Appx D
see SPDs
:a
Surge protective devices
Surges
lightning 3.7.1; 3.7.2
switching 3.7.1
Switch g e ar 5.1.2; 6.3
=a Switching 5
T
Tails (consumer) 2.2.3; Figs 2. 1(i)-(iii)
Telecommunications 'lines 3.7.1
Testing 9
instruments 10.1
procedures 10.3
=9 results schedule Appx G
sequence 10.2
checklist 9.3.1
Thermal insulation Table 7.1 (ii ; Appx F
Thermoplastics/thermosetting,
applications Table C l
TN system
conduit it1StaHations 3.6.3a
=9
:;a
==3
On-Site Guide
e The Institutionof EngineeringandTedlnorogy
1196
::g I Index
=a disconnection times
TN-S system
3.5.2
u
Underfloor heating 8.3
V
Ventilation 1.2.1
=a Voltage drop
calculation AppxF
general 7.1; 7.2.3;
Table 7. l (1) note 1
inspection 9.2.2
verification 10.3.10
=9 w
Walls and partitions 7.3.2
Water heaters AppxH
z
Zones
bathrooms 8.1
cables in walls 7.3.2v; 9.2.2
=9
:;a
==3
On-Site Guide 1 1 9 6 a
e The Institutionof EngineeringandTedlnorogy
1 n Wiring Regulatlons and associated publlcatlons
The IET prepares regulations for the safety of electrical installations, the IET Wiring Regulations
(BS 7671: Requirements for Electrical Installations), which are the standard for the UK and
many other countries. The IET also offers guidance around SS 7671 in the form of the
Gl.Jidance Notes series and the E\ectrician1s Guides as well as running training courses and
a technical helpline. The Wiring Regulations and guidance are now also available as e-books
through Wiring Regulations Digital (see overleaf).
IET Members receive discounts across IET publications 1 courses and e-book packages.
continues overleaf ►
::g
=a Electrician's Cuide to Fire Detection and
Alarm Systems
:;a Order book PVi/R05130 Paperback 2010
ISBN: 978-1-84919-130-2 £2'2
:a For more information and to buy the
tET Wiring R.egulations and associated
:;B guidance, visit www�theiet.org/electrical
:;a
Visit www.theiet.or:g/courses�pub f•or
information and to book a course. To
discuss your training requirements,
==3 particularly for on-site groups, please
contact one •Ofour advisors on 01438
767289.
IEr Order Form
How to order Detai Is
B Y PHONE: I N,J,nf' I
+44 (0)1438 767328
I
I
I Jotll ,
B Y FAX:
[ Colnpani I Oil tu�on
44 (0)1438 767375
IBY P O S T : [ Address
I
I
T h e lnsbtulion o f
Engineering Cour'l;ry,
I
I Poslo.-oe
a n d Technology, Fa>
I Tel:
PO Box 96,
I Em.1 I
I
Stevenage
SGl 2SD, UK I Meml>Prshp Ng (tf lns:tttu.!00 member):
ONLINE:
w,vw.the,el.org/electrical Ordering i·nformati on
80011 No. P r i " (_£)
IIIF'Oll,._TIOII StCV!llrt
l'I a, nrt ,i,1 ,oor <,;im
i br
.m..... TI 1E1 V :tie � al w u i
� Qet.li5 and � e a , : ,
l f l f � , ; o ..,-, W � Y 111d n n:(
p m ; � einad lrar{.)CtOffi
Payment methods
O CDUn' 0 !f"I
T
GUAR.Ulffl0 ltli;K Of IEllJlllle
0
"1 " ' ! i d )'OIi • �" ' ' "
□ □□□□□OJ □□m□
IJuc, . l l • " ' . ; C r o l l , '011 'A ;;() d l r , Oydllolllt •"" ,ltM: . . � - t . l [ - , . . 1 , , l l - . : ,
lor a Ii.I refund Plaase lllCluoo a COp\'
.:0:0
□ □ □
11,a--CJ<f,
O A U PlGTCC'IDt:
G
□rn□
n,.
□□□□ □□□□
, n m l t r I ,I ,ou prowide � h i ¥.-. M,:•�., """'= r.,,..., l:sutl'll
I T ,. be I t Id la t.1'111,re � � , t c
1'0.J ,,,t priOdut:ti and , c o tl\ll v.-.i ,c, £, ,r,Orb, CW�"ltCok
' rnc,ct �llf � Thi$ ;my tnCldc "
llO
l"
Q
l' J
I €to• I
::g
=a Membership
PacSsionate about your career? Beoome an IET Member and benefit from a range of benefits
from the industry experts. As co-publishers of the IET Wiring Regulations, we can assist you in
:;a demonstrating your te-chnical professional oornpetence and support you with all your training and
career development needs.
:a The Institution of Engineering and Technology is the professional home for Hfe for engineers and
technicians. With over 150,000 members in 127 countries, the IET is the largest professional body
:;B of engineers in Europe.
Joining the IET and having acces"S to tailored products and services will become invaluable for your
career and can be your first step towards professional qualifications.
You can take advantage •of...
■ a 35% disc<Junt on BS 7671 :2008(2011) the IET Wiring Regulations, associated guidance
publications and Wiring Regulations Digital
■ career support services to assist throughout your profess[onal development
■ dedicated training courses, seminars and events covering a wide range of subjects and
skills
■ an array of specialist online communities
■ professional development events covering a wide range of topics from essential business
skills to time management, health and safety, life skills and many more
■
:a
access to over 100 Local networks around the world
■ live lET.tv event footage
■ instant on-line access to over 70,000 books, 3,000 periodic.als and full-text collections
of electronic artides through the Virtual library, wherever you are in the world.
=a
Join online today: www.theiet.org/join or contact our membership and customer service
centre on +44 (0)1438 765678.
Dedicated Website
Everything that you need from the IET is now in one place. Ensure that you are up·to date with BS
7671, find guidance and book training courses by visiting our dedicated website for the electrical
industry.
Catch up with the latest forum discussions, download the Wiring Regulations forms (as listed in BS
=9 7671) and read articles from the IET's free Wiring Matters magazine.
The IETWiring Regula,tions BS 7671:2008(2011) and all associated guidance publications can be
bought directly from the site. You can even pre-order titles that have not yet been published at
discounted prices.
www theiet.org/electrical
----
-=- - -
=9
:;a
==3
Updates
Fifth edition (incorporating Amendment No 1 to BS 7671 :2008) September 2011
Version 5.0le 21/10/2011
The following changes have be,en made:
I. A number of links were "landing" slightly misaligned - they have b e e ncorrected.
2. The Index has been converted from two columns into a single column m order to make
the electronic use easier, all links have been remade.
3. Previous contents entry "Tables & Figs", which was a combined list, has been divided
into two lists - "Table of figures., and "Table of tables", at the req uest of users.
The Hst below is provided to help trainers and those who wish to update earlier printed
versions of the book:
1. Page 83, Fig 8. l(i), Plan view, partition added at end of bath
2. Page 144, Table F4(i), Column 4 Row 4 mm2, value changed from "2" to "32"
3.. Page 196, Stud Walls, changed to "Tables 7. l(ii), 7.2(iii), F6"