Solaredge Extended Power Three Phase Inverters: Se12.5K - Se27.6K
Solaredge Extended Power Three Phase Inverters: Se12.5K - Se27.6K
12-20
USA - CANADA - GERMANY - ITALY - FRANCE - JAPAN - CHINA - AUSTRALIA - THE NETHERLANDS - UK - ISRAEL - TURKEY - SOUTH AFRICA - BULGARIA www.solaredge.com
SolarEdge Extended Power Three Phase
Inverters SE12.5K - SE27.6K
SE12.5K SE15K SE16K SE17K SE25K SE27.6K
OUTPUT
Rated AC Power Output 12500 15000 16000 17000 25000 (1) 27600 VA
Maximum AC Power Output 12500 15000 16000 17000 25000 (1) 27600 VA
AC Output Voltage - Line to Line /
380 / 220 ; 400 / 230 Vac
Line to Neutral (Nominal)
AC Output Voltage -
184 - 264.5 Vac
Line to Neutral Range
AC Frequency 50/60 ± 5 Hz
Maximum Continuous Output
20 23 25.5 26 38 40 A
Current (per Phase)
Grids Supported - Three Phase 3 / N / PE (WYE with Neutral) V
Utility Monitoring, Islanding Protection, Configurable Power Factor,
Yes
Country Configurable Thresholds
INPUT
Maximum DC Power (Module STC) 16850 20250 21600 22950 33750 37250 W
Transformer-less, Ungrounded Yes
Maximum Input Voltage 900 Vdc
Nominal DC Input Voltage 750 Vdc
Maximum Input Current 21 22 23 23 37 40 Adc
Reverse-Polarity Protection Yes
Ground-Fault Isolation Detection 700kΩ Sensitivity 350kΩ Sensitivity(2)
Maximum Inverter Efficiency 98 98.3 %
European Weighted Efficiency 97.7 97.6 97.7 97.7 98 98 %
Nighttime Power Consumption < 2.5 <4 W
ADDITIONAL FEATURES
Supported Communication
RS485, Ethernet, Zigbee (optional), Wi-Fi (optional), Built-in GSM (optional)
Interfaces(3)
Smart Energy Management Export Limitation, Home Energy Management
DC SAFETY UNIT (OPTIONAL)
2-pole Disconnection N/A 1000V / 40A
DC Surge Protection N/A Type II, field replaceable
DC Fuses on Plus & Minus N/A Optional, 20A
Compliance N/A UTE-C15-712-1
STANDARD COMPLIANCE
Safety IEC-62103 (EN50178), IEC-62109, AS3100
Grid Connection Standards(4) VDE-AR-N-4105, G59/3, AS-4777,EN 50438 , CEI-021,VDE 0126-1-1, CEI-016(5), BDEW
Emissions IEC61000-6-2, IEC61000-6-3 , IEC61000-3-11, IEC61000-3-12
RoHS Yes
INSTALLATION SPECIFICATIONS
18-25mm / Solid wire
AC Output Gland Diameter / Wire
15-21mm / Solid wire 2.5-16 mm2, Stranded wire 2.5-10 mm2 2.5-16 mm2, Stranded wire
Cross Section
2.5-10 mm2
DC Input 2 MC4 pairs 3 MC4 pairs
Gland diameter 5 - 10 mm
DC Input with Safety Unit N/A
Wire cross section 0.5 - 13.5 mm2
Dimensions (HxWxD) 540 x 315 x 260 mm
Dimensions with Safety Unit (HxWxD) N/A 775 x 315 x 260 mm
Weight 33.2 45 kg
Weight with Safety Unit N/A 48 kg
Operating Temperature Range -20 - +60(6) (M40 version -40 - +60) ˚C
Cooling Fan (user replaceable)
Noise < 50 < 55 dBA
Protection Rating IP65 - Outdoor and Indoor
Bracket Mounted (Bracket Provided)
(1)
24.99kVA in the UK
(2)
Where permitted by local regulations
(3)
Refer to Datasheets -> Communications category in Downloads page for specifications of optional communication options: http://www.solaredge.com/groups/support/downloads
(4)
For all standards refer to Certifications category in Downloads page: http://www.solaredge.com/groups/support/downloads
(5)
Models SE25K and SE27.6K only
(6)
For power de-rating information refer to: https://www.solaredge.com/sites/default/files/se-temperature-derating-note.pdf
© SolarEdge Technologies, Inc. All rights reserved. SOLAREDGE, the SolarEdge logo, OPTIMIZED BY SOLAREDGE
are trademarks or registered trademarks of SolarEdge Technologies, Inc. All other trademarks mentioned herein
are trademarks of their respective owners. Date: 11/2017. V.01. Subject to change without notice.