Basic Requirements for Equipment
Selection
● Voltage
● Current
● Service Conditions
● Accessibility
● Loss Of service continuity
● Degrees of Protection
● Internal Arc
MV Network design – chapt. 05 Oct 2008
1
Standard
The main changes in the new IEC 62271-200 standard
● The standard IEC 62271-200:
● replaces the former IEC 60298
● Has been published in december 2003
● The standard IEC 62271-200 specifies requirements:
● for factory-assembled metal-enclosed switchgear and controlgear
● for alternating current of rated voltages above 1kV and up to 52kV
● for indoor or outdoor installation
● for services frequencies up to and including 60Hz
● AIS - GIS - OIS
● P < 300kPa (3 bar)
● The standard partially includes the requirements of the IEC 60694 “common
clauses for high voltage switchgear and controlgear”
● It adds specific requirements for metal-enclosed switchgear
MV Network design – chapt. 05 Oct 2008
2
MV Network design – chapt. 05 Oct 2008
3
MV Network design – chapt. 05 Oct 2008
4
MV Network design – chapt. 05 Oct 2008
5
MV Network design – chapt. 05 Oct 2008
6
MV Network design – chapt. 05 Oct 2008
7
MV Network design – chapt. 05 Oct 2008
8
MV Network design – chapt. 05 Oct 2008
9
MV Network design – chapt. 05 Oct 2008
10
Partitioning & Nature of barrier
The nature of the partitioning class
Switchgear classification with regard to the nature of the barrier
Features
between live parts and opened accessible compartment.
Metal shutters and partitions between
live parts and open compartment
PM (metal-enclosed condition maintained).
Insulation - covered discontinuity in
the
PI metal partitions / shutters between live
parts and open compartment.
MV Network design – chapt. 05 Oct 2008
11
MV Network design – chapt. 05 Oct 2008
12
Service continuity
Loss of Service LSC 2A
Continuity Maintainability of one
• Safe access to functional unit
Class (LSC) compartment allowing normal
Several levels • With power flow in
• Architecture based on service of the
of service busbar and the other
“safe compartment remaining units of
continuity units
access” the switchboard
during • MV Cables must be (busbar in a
maintenance earthed separate
compartment)
LSC 2B
• Safe access to compartment Maintainability of defined
• With power flow in busbar parts with no need of cable
and the other units disconnection (separate
• MV Cable in separate cable compartment)
compartment
• Cable of unit under
maintenance can remain LSC 1
energised • Metal enclosed not
of LSC2 class
MV Network design – chapt. 05 Oct 2008
13
SM6
PIX
MV Network design – chapt. 05 Oct 2008
14
Metal-enclosed, factory built equipment
DIFFERENT ENCLOSURE TYPE
IEC 60298
metal clad
compartment
Block type
LSC 2B LSC 2A LSC 1
MV Network design – chapt. 05 Oct 2008
15
IEC / AS
62271-200 Loss of Service Continuity
LSC 1 LSC 2A LSC 2B
Switchgear categories with regard to Features
the loss of service continuity when
opening accessible compartments
LSC1 Other functional units or some of
them shall be disconnected
Other functional units can be
LSC2A
energized
LSC2
Other functional units and all cable
LSC2B
compartments can be energized
SM6
Schneider Electric - UGLPresentation_23-09-14.pptx 16
Make-up/Architecture of MV Switchboard (LSC-2B )
Schneider Electric - UGLPresentation_23-09-14.pptx 17
Schneider Electric - UGLPresentation_23-09-14.pptx 18
Schneider Electric - UGLPresentation_23-09-14.pptx 19
Ensuring hi-safety with an optimized architecture
PI & LSC2A
CB Mechanism
SM6 has 3 SM6has 2
compartments cabinets
1.Busbar 1. LV
2.Switch (LBS) 2. Mechanism
3.Cable or CB connection SF6 CB
Cable Connection
● Thanks to isolated (PI)
compartments ●Thanks to LSC2A
●No risk to access live parts ●No need to cut-off
while realizing any operation in energy of switchboard
one of compartment SF6 CB cubicle
while realizing any
(ex: cable or CB) operation in one of
compartments or cabinets
Switch cubicle (ex: cable or CB)
Schneider Electric - UGLPresentation_23-09-14.pptx 20
MV Network design – chapt. 05 Oct 2008
21
MV Network design – chapt. 05 Oct 2008
22
MV Network design – chapt. 05 Oct 2008
23
Origins of an internal faults
● Tools forgotten after maintenance
● Very corrosive atmosphere
● Forced inter-locks
● Overvoltages due to lightning
● Faulty protection system operation
● Faulty component
Schneider Electric - UGLPresentation_23-09-14.pptx 24
Equipment requirements for
internal arcing
● Must resist mechanical and thermal stresses
● Must protect the operator against any risk
resulting from the devastating effects of
possible internal arcing
● The cubicle design allows for arcing effects to
be contained (internal suppression,
mechanical and thermal stress):
● choice of non-flammable materials
● channelling of hot gases
Schneider Electric - UGLPresentation_23-09-14.pptx 25
IEC / AS
62271-200 Safety
Internal Arc Classification
IAC A
A-FLR
A-FL
A-F
5 criterias
1: correctly secure doors and covers do not open
2: no fragmentation of the enclosure occurs within the time specified for
the test
3: arcing does not cause holes in the accessible sides up to a height of
2m
4: indicators do not ignite due to the effect of the hot gases
5: the enclosure remains connected to its earthing point
MV Network design – chapt. 05 Oct 2008
26
MV Network design – chapt. 05 Oct 2008
27
Internal arc fault & classification
Types of accessibility
Metal-enclosed switchgear and controlgear, except pole mounted:
Accessibility Type A Restricted to authorized personnel only.
Accessibility Type B Unrestricted accessibility, including
that of the general public.
According the accessibilities F: for Front side
A and B type, the following L: for Lateral side
code shall be used: R: for Rear side
Pole-mounted metal-enclosed switchgear and controlgear:
Accessibility Type C Accessibility restricted by installation
out of reach.
Schneider Electric - Power BU - E&S - 02/2009 28
MV Network design – chapt. 05 Oct 2008
29
MV Network design – chapt. 05 Oct 2008
30
MV Network design – chapt. 05 Oct 2008
31
MV Network design – chapt. 05 Oct 2008
32
Internal arc tested equipment
Successful test
Schneider Electric - UGLPresentation_23-09-14.pptx 33
Sample Classification/ SM6-36
Power
IEC 62271-200 Standard Compliancy
According to the IEC62271-200, design and function definition for SM6-36
Compartmented Factory-Built Cubicles
Circuit
Compartment List Busbar
Breaker
Design Fixed Removable
Accessibility With an
Locks
instrument
Partition Isolation material
Classification :
5 cubicle compartments:
1 – Switching component
◼ LSC2A
2 – Busbars ◼ PI
3 – Connection and switching
component ◼ 3 sides A FL 16kA 1s
4 – Operating mechanism (Internal arc withstand IAC classification)
5 – LV compartment
Power BU - MVP Dept - 19/03/2008
Sample Classification/ RM6-24Kv
Power
IEC 62271-200 Standard Compliancy
According to the IEC62271-200, design and function definition for RM6-24
◼ Maintenance-free, for all compartments except fuses
Classification :
◼ LSC2A
◼ PM
◼ 4 sides AFLR up to 20kA 1s
(Internal arc withstand IAC classification)
Power BU - MVP Dept - 19/03/2008
TYPICAL TYPE TEST
REQUIREMENTS
Type test:
Specified requirements according to IEC 62271-200
1. Dielectric withstand tests
2. Temperature rise tests
3. Measurement of the resistance of the main circuit
4. Short-time withstand current and peak withstand current tests
5. Short-circuit making and breaking tests
6. Capacitive current switching tests
7. Mechanical operation tests
8. Circuit breaker endurance tests
9. Verification of degree of protection
10. Tests on auxiliary and control
circuits
11. Electromagnetic compatibility
tests
12. Internal arc tests
Schneider Electric - UGLPresentation_23-09-14.pptx 36
Connected MV Switchgear by Application
Energy Buildings, industry, MMM, O&G
Primary substation (> 20 MVA) GIS AIS Heavy industry primary substation (> 20 MVA) AIS
36kV 24kV 24kV 17.5kV
36kV 24kV 17.5kV 36kV
A1 A2
F400 /
Heavy Industry MCset DNF7 PIX-Rof
CBGS WS GMA PIX PIX-Rof 10-50MVA, busbar < 3150A, draw out
Busbar > 2000A
LSC2B-PM Petrochemical, automotive, steel & cement plants, paper mills LSC2B-PM
Large switching substation (< 4 MVA) Large MV consumers site (5-10 MVA)
AIS Consumer site (1-5 MVA) AIS
24kV 17.5kV 24kV +36kV
A3 A4
Infra & Industry SM6
630-1250A, fixed, pilot protections
PIX PIX-Rof 630A-1250A, fixed, pilot protections LSC2A-PI
hospitals, universities, regional airports, food & beverage factories,….
LSC2B-PM
MV/LV substations (< 2 MVA) 24kV GIS 36kV
AIS
24kV GIS 36kV 24kV +36kV
A5 A6
RM6 FLUSARC
RM6 Outdoor RM6 FLUSARC SM6
630A ring main unit - kiosks or buildings 630A, kiosks or buildings
LSC2A-PM Shopping center, light manufacturing, retail or industrial park,…. LSC2A-PI
Residential Commercial
Typical SLD in Commercial & Industrial Building Application
Mid-size building (CIB-2) Large building (CIB3)
SM6
Trihal
ATS
Prisma
+Masterpact MTZ
or Okken (CIB 3)
Incomings: 1250A max RM6 / Flusarc
ATS Outgoing: 630A
BC Imprego Majority of Circuit Breakers
Limited switch functions