Product data sheet 3SK1111-1AB30

SIRIUS SAFETY RELAY STANDARD SERIES DEVICE


RELAY ENABLING CIRCUITS 3 NO CONTACTS + RELAY
SIGNALING CIRCUIT 1 NC CONTACT US = 24 V AC/DC
SCREW TERMINAL

General technical details:


product brand name SIRIUS

product designation safety relays

protection class IP / of the housing IP20

Protection against electrical shock finger-safe

Insulation voltage / rated value V 300

Ambient temperature

• during storage °C -40 … +80

• during operating °C -25 … +60

Air pressure

• according to SN 31205 kPa 90 … 106

Relative humidity

• during operating phase % 10 … 95

Installation altitude / at a height over sea level / maximum m 2,000

Resistance against vibration / according to IEC 60068-2-6 5 ... 500 Hz: 0,75 mm

Impulse voltage resistance / rated value V 4,000

EMC emitted interference IEC 60947-5-1, IEC 61000

Overvoltage class Installation category III

Degree of pollution 3

Number of sensor inputs

3SK1111-1AB30 subject to modifications


Page 1/ 6 01/21/2013 © Copyright Siemens AG 2013
• 1-channel or 2-channel 1

Design of the cascading none

Type of the safety-related wiring / of the inputs single-channel and two-channel

Product feature / transverse contact-secure Yes

safety Integrated Level

• according to IEC 61508 SIL3

Performance Level (PL)

• according to ISO 13849-1 e

Category / according to ISO 13849-1 4

Probability of dangerous failure per hour (PFHD) / with high 1/h 0.17000000000000004E-8
demand rate / according to EN 62061

Average probability of failure on demand (PFDavg) / with low 1/y 0.1E-5


demand rate / according to IEC 61508

T1 value / for proof test interval or service life / according to IEC a 20


61508

Hardware fault tolerance / according to IEC 61508 1

Safety device type / according to IEC 61508-2 Type A

Number of outputs / as contact-affected switching element

• as NC contact / for reporting function / instantaneous switching 1

• as NO contact / for reporting function / instantaneous switching 0

• as NC contact / for reporting function / delayed switching 0

• as NO contact / for reporting function / delayed switching 0

• as NC contact / safety-related / instantaneous switching 0

• as NO contact / safety-related / instantaneous switching 3

• as NC contact / safety-related / delayed switching 0

Number of outputs / as contact-less semiconductor switching


element

• safety-related

• delayed switching 0

• non-delayed 0

• for reporting function

• non-delayed 0

Stop category / according to DIN EN 60204-1 0

General technical details:


Design of the input

• cascading-input/functional switching No

• feedback input Yes

• start input Yes

Design of the electrical connection / jumper socket No

Operating cycles / maximum 1/h 360

3SK1111-1AB30 subject to modifications


Page 2/ 6 01/21/2013 © Copyright Siemens AG 2013
Switching capacity current

• of the NO contacts of the relay outputs

• at DC-13

• at 24 V A 5

• at 115 V A 0.2

• at 230 V A 0.1

• at AC-15

• at 115 V A 4

• at 230 V A 4

• of the NC contacts of the relay outputs

• at DC-13

• at 24 V A 1

• at 115 V A 0.2

• at 230 V A 0.1

• at AC-15

• at 115 V A 1.5

• at 230 V A 1.5

Thermal current / of the contact-affected switching element / A 5


maximum

Mechanical operating cycles as operating time / typical 10,000,000

Cable length / between sensor and electronic evaluation device m 2,000


/ with Cu 1.5 mm² and 150 nF/km / maximum

Make time / with automatic start

• typical ms 200

• for DC / maximum ms 320

• for AC / maximum ms 320

Make time / with automatic start / after mains power cut

• typical ms 200

• maximum ms 320

Make time / with monitored start

• maximum ms 20

• typical ms 15

Backslide delay time / after opening of the safety circuits / ms 10


typical

Backslide delay time / at mains power cut

• typical ms 65

• maximum ms 75

Recovery time / after opening of the safety circuits / typical ms 10

Recovery time / after mains power cut / typical s 0.09

Pulse duration

• of the sensor input / minimum ms 150

3SK1111-1AB30 subject to modifications


Page 3/ 6 01/21/2013 © Copyright Siemens AG 2013
• of the ON pushbutton input / minimum s 0.015

Control circuit:
Type of voltage / of the controlled supply voltage AC/DC

Control supply voltage frequency

• 1 / rated value Hz 50

• 2 / rated value Hz 60

Control supply voltage

• for DC / rated value V 24

• at 50 Hz / with AC / rated value V 24

• at 60 Hz / with AC / rated value V 24

Operating range factor control supply voltage rated value / of


the magnet coil

• at 50 Hz

• for AC 0.85 … 1.1

• at 60 Hz

• for AC 0.85 … 1.1

• for DC 0.85 … 1.2

Active power loss / typical W 2

Installation/mounting/dimensions:
mounting position any

Distance, to be maintained, to earthed part / sidewards mm 5

Distance, to be maintained, to the ranks assembly / sidewards mm 0

Type of mounting screw and snap-on mounting

Width mm 22.5

Height mm 100

Depth mm 121.6

Connections:
Design of the electrical connection screw-type terminals

Product Function:
Product function / parameterizable Sensor floating / sensor non-floating, monitored start /
autostart

Suitability for use / device connector 3ZY12 No

Suitability for interaction / pressing control No

Suitability for use

• safety cut-out switch Yes

• monitoring of floating sensors Yes

• monitoring of non-floating sensors Yes

3SK1111-1AB30 subject to modifications


Page 4/ 6 01/21/2013 © Copyright Siemens AG 2013
• magnetically operated switches monitoring Yes

• safety-related circuits Yes

Certificates/approvals:
Verification of suitability

• TÜV (German technical inspectorate) certificate Yes

• UL-registration Yes

Further information:
Information- and Downloadcenter (Catalogs, Brochures,…)
http://www.siemens.com/industrial-controls/catalogs

Industry Mall (Online ordering system)


http://www.siemens.com/industrial-controls/mall

Cax online generator:


http://www.siemens.com/cax

Service&Support (Manuals, Certificates, Characteristics, FAQs,...)


http://support.automation.siemens.com/WW/view/en/3SK1111-1AB30/all

Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, ...)
http://www.automation.siemens.com/bilddb/cax_en.aspx?mlfb=3SK1111-1AB30

3SK1111-1AB30 subject to modifications


Page 5/ 6 01/21/2013 © Copyright Siemens AG 2013
last change: Jan 21, 2013

3SK1111-1AB30 subject to modifications


Page 6/ 6 01/21/2013 © Copyright Siemens AG 2013

You might also like