Product data sheet 3SK1111-1AB30
SIRIUS SAFETY RELAY STANDARD SERIES DEVICE
RELAY ENABLING CIRCUITS 3 NO CONTACTS + RELAY
SIGNALING CIRCUIT 1 NC CONTACT US = 24 V AC/DC
SCREW TERMINAL
General technical details:
product brand name SIRIUS
product designation safety relays
protection class IP / of the housing IP20
Protection against electrical shock finger-safe
Insulation voltage / rated value V 300
Ambient temperature
• during storage °C -40 … +80
• during operating °C -25 … +60
Air pressure
• according to SN 31205 kPa 90 … 106
Relative humidity
• during operating phase % 10 … 95
Installation altitude / at a height over sea level / maximum m 2,000
Resistance against vibration / according to IEC 60068-2-6 5 ... 500 Hz: 0,75 mm
Impulse voltage resistance / rated value V 4,000
EMC emitted interference IEC 60947-5-1, IEC 61000
Overvoltage class Installation category III
Degree of pollution 3
Number of sensor inputs
3SK1111-1AB30 subject to modifications
Page 1/ 6 01/21/2013 © Copyright Siemens AG 2013
• 1-channel or 2-channel 1
Design of the cascading none
Type of the safety-related wiring / of the inputs single-channel and two-channel
Product feature / transverse contact-secure Yes
safety Integrated Level
• according to IEC 61508 SIL3
Performance Level (PL)
• according to ISO 13849-1 e
Category / according to ISO 13849-1 4
Probability of dangerous failure per hour (PFHD) / with high 1/h 0.17000000000000004E-8
demand rate / according to EN 62061
Average probability of failure on demand (PFDavg) / with low 1/y 0.1E-5
demand rate / according to IEC 61508
T1 value / for proof test interval or service life / according to IEC a 20
61508
Hardware fault tolerance / according to IEC 61508 1
Safety device type / according to IEC 61508-2 Type A
Number of outputs / as contact-affected switching element
• as NC contact / for reporting function / instantaneous switching 1
• as NO contact / for reporting function / instantaneous switching 0
• as NC contact / for reporting function / delayed switching 0
• as NO contact / for reporting function / delayed switching 0
• as NC contact / safety-related / instantaneous switching 0
• as NO contact / safety-related / instantaneous switching 3
• as NC contact / safety-related / delayed switching 0
Number of outputs / as contact-less semiconductor switching
element
• safety-related
• delayed switching 0
• non-delayed 0
• for reporting function
• non-delayed 0
Stop category / according to DIN EN 60204-1 0
General technical details:
Design of the input
• cascading-input/functional switching No
• feedback input Yes
• start input Yes
Design of the electrical connection / jumper socket No
Operating cycles / maximum 1/h 360
3SK1111-1AB30 subject to modifications
Page 2/ 6 01/21/2013 © Copyright Siemens AG 2013
Switching capacity current
• of the NO contacts of the relay outputs
• at DC-13
• at 24 V A 5
• at 115 V A 0.2
• at 230 V A 0.1
• at AC-15
• at 115 V A 4
• at 230 V A 4
• of the NC contacts of the relay outputs
• at DC-13
• at 24 V A 1
• at 115 V A 0.2
• at 230 V A 0.1
• at AC-15
• at 115 V A 1.5
• at 230 V A 1.5
Thermal current / of the contact-affected switching element / A 5
maximum
Mechanical operating cycles as operating time / typical 10,000,000
Cable length / between sensor and electronic evaluation device m 2,000
/ with Cu 1.5 mm² and 150 nF/km / maximum
Make time / with automatic start
• typical ms 200
• for DC / maximum ms 320
• for AC / maximum ms 320
Make time / with automatic start / after mains power cut
• typical ms 200
• maximum ms 320
Make time / with monitored start
• maximum ms 20
• typical ms 15
Backslide delay time / after opening of the safety circuits / ms 10
typical
Backslide delay time / at mains power cut
• typical ms 65
• maximum ms 75
Recovery time / after opening of the safety circuits / typical ms 10
Recovery time / after mains power cut / typical s 0.09
Pulse duration
• of the sensor input / minimum ms 150
3SK1111-1AB30 subject to modifications
Page 3/ 6 01/21/2013 © Copyright Siemens AG 2013
• of the ON pushbutton input / minimum s 0.015
Control circuit:
Type of voltage / of the controlled supply voltage AC/DC
Control supply voltage frequency
• 1 / rated value Hz 50
• 2 / rated value Hz 60
Control supply voltage
• for DC / rated value V 24
• at 50 Hz / with AC / rated value V 24
• at 60 Hz / with AC / rated value V 24
Operating range factor control supply voltage rated value / of
the magnet coil
• at 50 Hz
• for AC 0.85 … 1.1
• at 60 Hz
• for AC 0.85 … 1.1
• for DC 0.85 … 1.2
Active power loss / typical W 2
Installation/mounting/dimensions:
mounting position any
Distance, to be maintained, to earthed part / sidewards mm 5
Distance, to be maintained, to the ranks assembly / sidewards mm 0
Type of mounting screw and snap-on mounting
Width mm 22.5
Height mm 100
Depth mm 121.6
Connections:
Design of the electrical connection screw-type terminals
Product Function:
Product function / parameterizable Sensor floating / sensor non-floating, monitored start /
autostart
Suitability for use / device connector 3ZY12 No
Suitability for interaction / pressing control No
Suitability for use
• safety cut-out switch Yes
• monitoring of floating sensors Yes
• monitoring of non-floating sensors Yes
3SK1111-1AB30 subject to modifications
Page 4/ 6 01/21/2013 © Copyright Siemens AG 2013
• magnetically operated switches monitoring Yes
• safety-related circuits Yes
Certificates/approvals:
Verification of suitability
• TÜV (German technical inspectorate) certificate Yes
• UL-registration Yes
Further information:
Information- and Downloadcenter (Catalogs, Brochures,…)
http://www.siemens.com/industrial-controls/catalogs
Industry Mall (Online ordering system)
http://www.siemens.com/industrial-controls/mall
Cax online generator:
http://www.siemens.com/cax
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
http://support.automation.siemens.com/WW/view/en/3SK1111-1AB30/all
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, ...)
http://www.automation.siemens.com/bilddb/cax_en.aspx?mlfb=3SK1111-1AB30
3SK1111-1AB30 subject to modifications
Page 5/ 6 01/21/2013 © Copyright Siemens AG 2013
last change: Jan 21, 2013
3SK1111-1AB30 subject to modifications
Page 6/ 6 01/21/2013 © Copyright Siemens AG 2013