0% found this document useful (0 votes)
63 views1 page

Alte Documente

The document is a declaration of performance for a rectangular fire damper product. It provides the product's unique identification code, intended use as a fire damper for partitions, and manufacturer information. It also lists the product's fire resistance performance ratings for different wall and floor types and sealing methods.

Uploaded by

Sergiu Alupoae
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
63 views1 page

Alte Documente

The document is a declaration of performance for a rectangular fire damper product. It provides the product's unique identification code, intended use as a fire damper for partitions, and manufacturer information. It also lists the product's fire resistance performance ratings for different wall and floor types and sealing methods.

Uploaded by

Sergiu Alupoae
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Declaration of performance CE_DoP_Rf-t_C3_EN I-05/2018

Declaration of performance
CE_DoP_Rf-t_C3_EN
I-05/2018

1. Unique identification code of the product-type: CU-LT


2. Intended use/es: Rectangular fire damper to be used in conjunction with partitions to maintain fire compartments in heating, ventilating and air conditioning installations.
3. Manufacturer: Rf-Technologies NV, Lange Ambachtstraat 40, B-9860 Oosterzele
4. System/s of AVCP: System 1
5. Harmonised standard / European Assessment Document; notified body / European Technical Assessment, Technical Assessment EN 15650:2010, BCCA with identification number 0749; BCCA-0749-CPR-BC1-606-0464-15650.05-0464; BCCA-0749-CPR-BC1-606-0464-15650.15-2517
Body, notified body; certificate of constancy of performance:
6. Declared performance according to EN 15650:2010 (Fire resistance according to EN 1366-2 and classifications according to EN 13501-3)
Essential characteristics Performance
Range Wall type Wall Sealing Installation Classification
200x100 mm ≤ CU-LT ≤ 800x600 mm Rigid wall Aerated concrete ≥ 100 mm Mortar 1 EI 90 (ve i n o) S - (500 Pa)
Gypsum 1 EI 120 (ve i n o) S - (500 Pa)
Stone wool + coating ≥ 140 kg/m³ + coated casing 1 EI 120 (ve i n o) S - (300 Pa)
Stone wool + coating ≥ 140 kg/m³ 1 EI 90 (ve i n o) S - (300 Pa)
Galvanised duct + stone wool + coating ≥ 150 kg/m³ 1x60 mm + IFW installation kit 2 EI 60 (ve i n o) S - (300 Pa)
Galvanised duct + stone wool + coating ≥ 140 kg/m³ 1x80 mm + IFW installation kit 2 EI 90 (ve i n o) S - (300 Pa)
Galvanised duct + stone wool + coating ≥ 140 kg/m³ 2x50 mm + IFW installation kit 2 EI 90 (ve i n o) S - (300 Pa)
Galvanised duct + GEOFLAM® F 45 mm + mortar 2 EI 120 (ve i n o) S - (500 Pa)
Galvanised duct + GEOFLAM® Light 35 mm + mortar 2 EI 120 (ve i n o) S - (500 Pa)
Flexible wall Metal studs gypsum plasterboard Type A (EN 520) ≥ 100 mm IFW installation kit 3 EI 60 (ve i n o) S - (500 Pa)
Gypsum 1 EI 60 (ve i n o) S - (500 Pa)
Stone wool + coating ≥ 140 kg/m³ 1 EI 60 (ve i n o) S - (300 Pa)
Galvanised duct + stone wool + coating ≥ 150 kg/m³ 1x60 mm + IFW installation kit 2 EI 60 (ve i n o) S - (300 Pa)
Metal studs gypsum plasterboard Type F (EN 520) ≥ 100 mm IFW installation kit 3 EI 90 (ve i n o) S - (500 Pa)

Harmonised standard
Gypsum 1 EI 90 (ve i n o) S - (500 Pa)

EN 15650:2010
Stone wool + coating ≥ 140 kg/m³ + coated casing 1 EI 120 (ve i n o) S - (300 Pa)
Stone wool + coating ≥ 140 kg/m³ 1 EI 90 (ve i n o) S - (300 Pa)
Galvanised duct + stone wool + coating ≥ 140 kg/m³ 2x50 mm + IFW installation kit 2 EI 90 (ve i n o) S - (300 Pa)
Rigid floor Reinforced concrete ≥ 110 mm Mortar 1 EI 90 (ho i n o) S - (500 Pa)
Reinforced concrete ≥ 150 mm Gypsum 1 EI 120 (ho i n o) S - (500 Pa)
Aerated concrete ≥ 150 mm Gypsum 1 EI 120 (ho i n o) S - (500 Pa)
Stone wool + coating ≥ 140 kg/m³ + coated casing 1 EI 120 (ho i n o) S - (300 Pa)
Stone wool + coating ≥ 140 kg/m³ 1 EI 90 (ho i n o) S - (300 Pa)
200x100 mm ≤ CU-LT + GDA ≤ 800x600 mm Flexible wall Metal studs gypsum plasterboard Type F (EN 520) ≥ 100 mm GDA + stone wool ≥ 40 kg/m³ 4 EI 120 (ve i n o) S - (300 Pa)
1 Type of installation: built-in ≥ 25 mm 2 Type of installation: remote ≥ 25 mm 3 Type of installation: 4 Type of installation:
0/90/180/270°. Minimal ≥ 50 mm
from the wall, 0/180°. Mini- ≥ 50 mm
built-in 0/90/180/270° built-in 0/180°
distances authorised. ≥ 50 mm mal distances authorised. ≥ 50 mm

Essential characteristics Performance


Nominal activation conditions/sensitivity: Pass
Response delay (response time): closure time Pass
MFUSP - 50 cycles; MMAG - 300 cycles;
Operational reliability: cycling
B(L)F(T) ; BFL(T) ; ONE ; UNIQ - 10000 cycles
Durability of response delay: Pass
Durability of operational reliability: Pass
Protection against corrosion according to EN 60068-2-52: Pass
Damper casing leakage according to EN 1751: ≥ class C
The performance of the product identified above is in conformity with the set of declared performance/s. This declaration of Signed for and on behalf of the manufacturer by:
performance is issued, in accordance with Regulation (EU) No 305/2011, under the sole responsibility of the manufacturer identi- Frank Verlinden, Product Manager
fied above.