Px3x GettingStarted EN C+
Px3x GettingStarted EN C+
Operating
via HMI and S&R-103
Getting Started
1 Introduction.........................................................................................................3
2 How to Use
The concept of this documentation is to learn step by step, i.e. each exercise requires that the
previous exercise has been carried out successfully.
So please don’t jump! Start at the beginning. The number of pages is 24 only.
3.1 Basics
Oper/
Folder Cyclic measurements
plane 2
Oper/Cycl/
Folder Meas. operating data
plane 3
Oper/Cycl/Data/
Function MAIN
groups
Oper/Cycl/Data/MAIN
Data Date
points 01.01.99 dd.mm.yy
All data points (setting values, signals, measured values, etc.) are selected using the menu tree.
As the user navigates through the menu tree, the first two lines of the LCD display always show
the branch of the menu tree that is active, as selected by the user. The data points are
accessed at the lowest level of a menu tree branch. They are displayed with their plain text
description. The value associated with the selected data point, its meaning, and its unit of
measurement are displayed in the line below.
The desired parameter (e.g. ‘MiCOM Px3x / Parameters / Config.paramters / LOC /
Decimal delimiter’) can be selected by pressing the keys ‘Left’, ‘Right’, ‘Up’ and ‘Down’:
MiCOM Px3x
MiCOM Px3x
Parameters
Par/ Par/
Device ID Config.parameters
Par/Conf/
LOC
Par/Conf/LOC Par/Conf/LOC
Language (tongue) Decimal delimiter
English dot
Note: In the case that the Panel level is displayed please press the ENTER key first in order to
access the menu tree.
Although it is possible to select any data point in the menu tree and read the associated value
by pressing the keys, it is not possible to switch directly to the input mode. This safeguard
prevents unintended changes in the settings. For that prior to any parameter change password
has to be entered.
Changing a parameter (e.g. ‘MiCOM Px3x / Parameters / Config.paramters / LOC /
Decimal delimiter’):
Par/Conf/LOC
Decimal delimiter
Dot
Par/Conf/LOC
Decimal delimiter
Dot
********
Par/Conf/LOC
Decimal delimiter
Dot
Par/Conf/LOC
Decimal delimiter
Comma
Note: Input mode can be left without changing a parameter by pressing the CLEAR key
instead of the ENTER key.
Many problems may occur due to the fact that the setting status of the device is difficult for the
user to see what’s going on. Regarding these problems it’s recommended to intialize a cold
restart in order to put the device in it’s default status.
Prior to initializing a cold restart please ensure that the device is disabled
(‘MiCOM Px3x / Parameters / Functionparamters / Global / MAIN / Protection enabled’):
Par/Func/Glob/MAIN
Protection enabled
No (=off)
Oper/CrtlTest/MAIN
Cold restart
don't execute
Please change the value to ‘execute’ by the procedure described in chapter 3.3:
Oper/CrtlTest/MAIN
Cold restart
execute
********************
**** REBOOT *****
********************
********************
TEST
>>>>>>>>
Note: After a cold restart any special setting has been deleted and all records have been
cleared. All parameters are set to their default value.
After the reboot of the device the ALARM LED is ‘on’ due to a deliberate distortion of the
parameter checksum which initializes the desired cold restart automatically.
Please readout the corresponding entries in the monitoring signal memory
(‘MiCOM Px3x / Operation / Operating data rec. / MT_RC / Mon. signal record.’):
Oper/Rec/MT_RC
Mon. signal record.
For detailed information concerning ALARM LED please refer to chapter 10 ‘Troubleshooting’
of the corresponding manual.
In order to switch off the ALARM LED please clear the monitoring signal memory
(‘MiCOM Px3x / Operation / Control and Testing / MT_RC / Reset recording’):
Oper/CrtlTest/MT_RC
Reset recording
2
Please enter the input mode, change the value to ‘execute’ by the procedure described in
chapter 3.3:
Oper/CrtlTest/MT_RC
Reset recording
2
execute
and press the ENTER key. The number of entries in the monitoring signal memory will be ‘0’
now and the ALARM LED will go ‘off’:
Oper/CrtlTest/MT_RC
Reset recording
0
After the reboot of the device the OUT OF SERVICE LED is ‘on’. In order to switch off the OUT
OF SERVICE LED please enable the device by changing the value of the corresponding
parameter by the procedure described in chapter 0:
Par/Func/Glob/MAIN
Protection enabled
Yes (=on)
Note: Status ‘on’ of OUT OF SERVICE LED may occur due to different reasons. At least one of
the following 3 parameters is not set as follows:
Output relays may not be blocked:
Par/Func/Glob/OUTP
Outp.rel.block USER
No
Par/Func/Glob/MAIN
Protection enabled
Yes (=on)
Par/Func/Glob/MAIN
Trip cmd.block. USER
No
Status ‘on’ of OUT OF SERVICE LED may occur as well since the self-monitoring
function has detected an internal fault of the device. In that case the ALARM LED is ‘on’
too. Please readout the corresponding entries in the monitoring signal memory as
described in chapter 3.5. For detailed information concerning ALARM LED please refer
to chapter 10 ‘Troubleshooting’ of the corresponding manual.
After the reboot of the device the function groups of all main functions (such as IDMT, DIST,
DIFF, …) are disabled.
In order to enable a function group (e.g. ‘DIFF’: ‘Differential Protection’) the desired function
group has to be configured first. Please select the corresponding configuration parameter and
change it accordingly by the procedures described in chapters 3.2 and 3.3
(e.g. ‘MiCOM Px3x / Parameters / Config.paramters / DIFF / Function group DIFF’):
Par/Conf/DIFF
Function group DIFF
With
Having configured the desired function group all related parameters and signals are
displayed. Now enabling of the function group is possible. Please select the corresponding
function parameter and change it accordingly by the procedures described in chapters 3.2 and
3.3 (e.g. ‘MiCOM Px3x / Parameters / Function paramters / General functions / DIFF /
General enable USER’):
Par/Func/Gen/DIFF
General enable USER
Yes
Having enabled the desired function group generally the setting of the active parameter subset
determines whether the corresponding function is actually enabled or not. For the following
example differential protection will be enabled only if parameter subset 1 is actually active
(‘MiCOM Px3x / Parameters / Function paramters / Parameter subset 1 / DIFF /
Enable … ’):
Par/Func/PS1/DIFF Par/Func/PS1/DIFF
Enable PS1 Enable PS2
Yes No
Par/Func/PS1/DIFF Par/Func/PS1/DIFF
Enable PS3 Enable PS4
No No
Note: The parameter subset actually active at a particular time may be determined by
scanning the corresponding logic state signal (‘MiCOM Px3x / Operation / Cyclic
measurements / Log. state signals / PSS / Actual param. subset’).
It’s important to know that the trip signals of the various protection functions are not suitable
for trip command purposes due to their undefined timing.
Note: Never use a trip signal to operate the circuit breaker directly! Always use a trip
command!
For command purposes MiCOM 30 Series devices provide at least 2 trip commands. The
functions to effect a trip can be selected by setting an 'm out of n' parameter independently for
each of them (e.g. ‘MiCOM Px3x / Parameters / Function parameters / Global / MAIN /
Fct.assig.trip cmd.1’):
Par/Func/Glob/MAIN
Fct.assig.trip cmd.1
For example the following 2 trip signals are assigned to trip command 1:
Par/Func/Glob/MAIN Par/Func/Glob/MAIN
Fct.assig.trip cmd.1 Fct.assig.trip cmd.1
#01 DIFF OR #02 MAIN
Trip signal Manual trip signal
Having assigned the trip command the corresponding signal may be assigned to the desired
output relay. We recommend to use output relay 01 on the power supply module which
provides 2 N/O contacts (‘MiCOM Px3x / Parameters / Config. parameters / OUTP / Fct.
assignm. K 2001’):
Par/Conf/OUTP
Fct. assignm. K 2001
MAIN
Gen. trip command 1
Furthermore we recommend to use output relay 08 on the power supply module as watchdog
contact (‘MiCOM Px3x / Parameters / Config. parameters / OUTP / Fct. assignm. K 2008’):
Par/Conf/OUTP Par/Conf/OUTP
Fct. assignm. K 2008 Oper. mode K 2008
MAIN NE updating
Blocked/faulty
This output relay provides a C/O contact. The operation mode (‘MiCOM Px3x / Parameters /
Config. parameters / OUTP / Oper. mode K 2008’) has to be set as ‘NE updating’.
A trip command which has been assigned according to chapter 3.8 may be latched by
appropriate setting. MiCOM 30 Series devices provide individual setting of each of the trip
commands (e.g. ‘MiCOM Px3x / Parameters / Function parameters / Global / MAIN /
Latching trip cmd.1’):
Par/Func/Glob/MAIN
Latching trip cmd.1
Yes
Note: If a trip command is assigned to several output relays latching of the trip command will
be applied automatically to all associated output relays.
In order to release the latching of trip commands please use the corresponding resetting
function (‘MiCOM Px3x / Operation / Control and Testing / MAIN / Rset.latch.trip USER’):
Oper/CrtlTest/MAIN
Rset.latch.trip USER
don't execute
Please enter the input mode, change the value to ‘execute’ by the procedure described in
chapter 3.3:
Oper/CrtlTest/MAIN
Rset.latch.trip USER
execute
and press the ENTER key. Latching of the trip commands will reset provided that the associated
trip signals have reset.
Prior to start communicating with the device please open the dialog box ‘Communication
Settings’ (Communication / Communication Settings...):
In order to check whether communication with the device will work or not please open the
dialog box ‘Identify Device’ (Communication / Identify Device...):
Please ensure that the settings of ‘Baud Rate’, ‘Bay Address’ and ‘Parity’ are equal to the
settings of the device and that further configuration parameters are set as follows:
Par/Conf/PC
Transm.enab.cycl.dat
Without
Please click the button ‘Identify’. Now S&R-103 starts in communicating with the device:
A new default settings file can be created directly by a click on the button ‘Settings File...’:
It may happen that S&R-103 cannot create the default setting file due to the lack of the
corresponding data model:
In that case you can readout (Communication / Read Data Model...) and store the data model
in the preset folder:
Now a new default settings file can be created manually (File / New...):
by selecting the desired combination of device type and SW version (which has to be equal to
the data model version):
The number of inputs and outputs of any MiCOM 30 Series device varies depending on the
ordered optional modules. S&R-103 will display always the maximum if the design version of
the particular device is unknown. Therefore we recommend to readout the design version first
before changing parameters. Assignments to inputs and outputs which are not available will
be avoided.
In order to readout the fitted modules please open the dialog box ‘Design Version’ (Tools /
Design Version…) and click the button ‘Update…’:
Note: In case the particular device is not handy the available inputs and outputs may be set
manually. For this please click the button ‘Definition…’.
In order to readout the settings please highlight the folder ‘Parameters’ in the menu tree and
click the corresponding icon in the toolbar (Communication / Read Value):
For some settings (so-called off-line parameters) it is necessary to disable the protective
function. In order to change off-line parameters via HMI please first set the following
parameter to ‘No’:
Par/Func/Glob/MAIN
Protection enabled
No (=off)
For detailed information please refer to chapter 6.5.3 ‘Change-Enabling Function’ of the
corresponding manual.
5 In case of operating via S&R-103 temporary disabling of the protection function is done
automatically by the operating program.
Par/Func/Glob/PC
Command blocking
No
Par/Func/Glob/PC
Sig./meas.val.block.
No
Please press the CLEAR key in order to trigger LED indicator test and LCD display test. All
LED indicators and LCD display dots should light up. For detailed information please
refer to chapter 6.5.7 ‘Resetting’ of the corresponding manual.