MIILLE APPLIED
RESEARCH CO., INC.
STANDARD
CABLE ASSEMBLIES
Revised 01/24/2003
PRODUCTS
APPLICATION NOTE
STANDARD MARC CABLE ASSEMBLIES
1995-2003 MIILLE APPLIED RESEARCH CO., INC.
HOUSTON, TEXAS U.S.A.
APPLICATION NOTE #1 PAGE 1
STANDARD MARC CABLE ASSEMBLIES
STANDARD MARC CABLE ASSEMBLIES
MARC stocks a large number of standard cable assemblies for use
with our PLC communication modules. This Application Note
describes the standard MARC cable assemblies that are available for
use with Allen-Bradley PLC equipment. The communication modules
can be connected in many ways depending upon the applicaition.
The exact connection depends primarily on two things; the hardware
characteristics (pin numbers and connector type) and the specific
protocol emulation that is to be accomplished. The cables are
different because in some cases it may not be necessary to
implement all of the RS-232 modem handshake signals that are
available in each of the connectors or special connections are
required because of protocol emulation requirements. The following
pages detail each of the standard MARC cable assemblies along with
a list of the most common use for each. Note that the MARC part
number for a cable assembly includes the final cable length (in
inches) as the last two digits of the part number. All cables are
available in any length as a special order. The cable lengths which
are normally stocked are listed at the top of each page.
MIILLE APPLIED RESEARCH CO., INC.
HOUSTON, TEXAS U.S.A. 800/729-0818
PAGE 2 APPLICATION NOTE #1
STANDARD MARC CABLE ASSEMBLIES
1995-2003 MIILLE APPLIED RESEARCH CO., INC.
HOUSTON, TEXAS U.S.A.
APPLICATION NOTE #1 PAGE 3
STANDARD MARC CABLE ASSEMBLIES
127-052-12
THIS CABLE IS USED FOR:
MARC Comm-Troller to Allen-Bradley 1785-KE
MARC Comm-Troller to Allen-Bradley 1771-KG
MARC Comm-Master to Allen-Bradley 1785-KE
MARC Comm-Master to Allen-Bradley 1771-KG
MARC 166-010 Dial Up Modem to Comm-Troller or Comm-Master
MARC Allen-
Comm-Troller Bradley
Comm-Master 1785-KE or
166-010
TXD 2 2 TXD
RXD 3 3 RXD
RTS 4 4 RTS
CTS 5 5 CTS
GND 7 7 GND
ENA 13 13 ENA
DSR 6 6 DSR
DCD 8 8 DCD
DTR 11 11 DTR
DE-15P DE-15P
MARC Cable Ass'y #127-052-XX
MIILLE APPLIED RESEARCH CO., INC.
HOUSTON, TEXAS U.S.A. 800/729-0818
PAGE 4 APPLICATION NOTE #1
STANDARD MARC CABLE ASSEMBLIES
127-053-96
THIS CABLE IS USED FOR:
MARC Comm-Troller to Allen-Bradley 1770-KF2
MARC Comm-Troller to Allen-Bradley 1770-KF3
MARC Comm-Master to Allen-Bradley 1770-KF2
MARC Comm-Master to Allen-Bradley 1770-KF3
MARC Allen-
Comm-Troller Bradley
or 1770-KF2 or
Comm-Master
TXD 2 2 TXD
RXD 3 3 RXD
RTS 4 4 RTS
CTS 5 5 CTS
GND 7 7 GND
ENA 13 13 ENA
DSR 6 6 DSR
DCD 8 8 DCD
DTR 11 20 DTR
DE-15P DB-25S
MARC Cable Ass'y #127-053-XX
1995-2003 MIILLE APPLIED RESEARCH CO., INC.
HOUSTON, TEXAS U.S.A.
APPLICATION NOTE #1 PAGE 5
STANDARD MARC CABLE ASSEMBLIES
127-054-12
THIS CABLE IS USED FOR:
MARC Comm-Troller to MARC 137-001 FSK Modem
MARC Comm-Master to MARC 137-001 FSK Modem
MARC MARC 137-001
Comm-Troller
or FSK Modem
Comm-Master
TXD 2 2 TD
RXD 3 3 RD
RTS 4 7 RTS
CTS 5 8 CTS
GND 7 5 GND
DCD 8 1 DCD
DTR 11 4 DTR
9 RI
DE-15P DE-15P
MARC Cable Ass'y #127-054-XX
MIILLE APPLIED RESEARCH CO., INC.
HOUSTON, TEXAS U.S.A. 800/729-0818
PAGE 6 APPLICATION NOTE #1
STANDARD MARC CABLE ASSEMBLIES
127-055-12
THIS CABLE IS USED FOR:
MARC Comm-Troller to MARC 137-002 FSK Modem with Radio
Transmitter Controls
MARC Comm-Troller to MARC 148-001 Dual FSK Modem
MARC Comm-Master to MARC 137-002 FSK Modem with Radio
Transmitter Controls
MARC Comm-Master to MARC 148-001 Dual FSK Modem
MARC 137-002
MARC FSK Modem or
Comm-Troller
or 148-001 Dual
Comm-Master FSK modem
TXD 2 2 TD
RXD 3 3 RD
RTS 4 4 RTS
CTS 5 5 CTS
DSR 6 6 DSR
GND 7 7 GND
DCD 8 8 DCD
DTR 11 11 DTR
DE-15P DE-15P
MARC Cable Ass'y #127-055-XX
1995-2003 MIILLE APPLIED RESEARCH CO., INC.
HOUSTON, TEXAS U.S.A.
APPLICATION NOTE #1 PAGE 7
STANDARD MARC CABLE ASSEMBLIES
127-056-12
THIS CABLE IS USED FOR:
MARC FSK Modem to Allen-Bradley 1771-KGM
MARC FSK Modem to Allen-Bradley 1785-KE
MARC
Allen-Bradley
1771-KGM or 137-001-0
1785-KE FSK
Modem
TXD 2 2 TXD
RXD 3 3 RXD
RTS 4 7 RTS
CTS 5 8 CTS
DSR 6 6 N/C
GND 7 5 GND
DCD 8 1 DCD
DTR 11 4 DTR
ENA 13 9 RI
DE-15P DE-15P
MARC Cable Ass'y #127-056-XX
MIILLE APPLIED RESEARCH CO., INC.
HOUSTON, TEXAS U.S.A. 800/729-0818
PAGE 8 APPLICATION NOTE #1
STANDARD MARC CABLE ASSEMBLIES
127-058-12
THIS CABLE IS USED FOR:
MARC Dual FSK Modem to Allen-Bradley 1771-KGM
MARC Dual FSK Modem to Allen-Bradley 1785-KE
MARC FSK Modem with Radio Control to Allen-Bradley 1771-KGM
MARC FSK Modem with Radio Control to Allen-Bradley 1785-KE
MARC
Allen-Bradley 137-002-0 FSK Modem
1771-KGM or
1785-KE or 148-001-0 Dual FSK
Modem
TXD 2 2 TXD
RXD 3 3 RXD
RTS 4 4 RTS
CTS 5 5 CTS
DSR 6 6 N/C
GND 7 7 GND
DCD 8 8 DCD
DTR 11 11 DTR
ENA 13
DE-15P DE-15P
MARC Cable Ass'y #127-058-XX
1995-2003 MIILLE APPLIED RESEARCH CO., INC.
HOUSTON, TEXAS U.S.A.
APPLICATION NOTE #1 PAGE 9
STANDARD MARC CABLE ASSEMBLIES
127-060-96
THIS CABLE IS USED FOR:
MARC Comm-Troller to other Modems
MARC Comm-Master to other Modems
Typical
MARC connections to
Comm-Troller modems from other
or
Comm-Master manufacturers
TXD 2 2 TXD
RXD 3 3 RXD
RTS 4 4 RTS
CTS 5 5 CTS
DSR 6 6 DSR
GND 7 7 GND
DCD 8 8 DCD
DTR 11 11 DTR
DE-15P DB-25P
MARC Cable Ass'y #127-060-XX
MIILLE APPLIED RESEARCH CO., INC.
HOUSTON, TEXAS U.S.A. 800/729-0818
PAGE 10 APPLICATION NOTE #1
STANDARD MARC CABLE ASSEMBLIES
166-004-96
THIS CABLE IS USED FOR:
MARC Comm-Master to Allen-Bradley RTU 5/1000 (direct connect)
MARC Comm-Master to Allen-Bradley RTU 5/2000 (direct connect)
MARC
Comm-Master Allen-Bradley
RTU (direct connect)
TXD 2 2 RXD
RXD 3 3 TXD
RTS 4 4 DCD
GND 7 7 GND
CTS 5 19 RTS
DE-15P DB-25P
MARC Cable Ass'y #166-004-XX
1995-2003 MIILLE APPLIED RESEARCH CO., INC.
HOUSTON, TEXAS U.S.A.
APPLICATION NOTE #1 PAGE
STANDARD MARC CABLE ASSEMBLIES 11
127-063-12
THIS CABLE IS USED FOR:
MARC Comm-Master to PLC 5 Channel 0
MARC Comm-Troller to PLC 5 Channel 0
Allen-Bradley
MARC
Comm-Troller, PLC 5 Channel 0
Comm-Master
TXD 2 3 RXD
RXD 3 2 TXD
RTS 4 4 RTS
CTS 5 5 CTS
GND 7 7 GND
NC 13 13 NC
DSR 6 6 DSR
DCD 8 8 DCD
DTR 11 20 DTR
DE-15P DB-25P
MARC Cable Ass'y #127-063-XX
MIILLE APPLIED RESEARCH CO., INC.
HOUSTON, TEXAS U.S.A. 800/729-0818
PAGE 12 APPLICATION NOTE #1
STANDARD MARC CABLE ASSEMBLIES
127-064-12
THIS CABLE IS USED FOR:
MARC RFSK Modems to PLC5 Channel 0
MARC Allen-Bradley
RFSK Modem PLC5 Channel 0
TD 2 2 TXD
RD 3 3 RXD
RTS 4 4 RTS
CTS 5 5 CTS
DSR 6 6 DSR
GND 7 7 GND
DCD 8 8 DCD
DTR 11 20 DTR
DE-15P DB-25P
MARC Cable Ass'y #127-064-XX
1995-2003 MIILLE APPLIED RESEARCH CO., INC.
HOUSTON, TEXAS U.S.A.
APPLICATION NOTE #1 PAGE
STANDARD MARC CABLE ASSEMBLIES 13
127-067-12
THIS CABLE IS USED FOR:
PLC5/ Channel 0 to 137-001 FSK Modem
PLC 5 MARC
Channel 0 137-001-0
FSK Modem
TXD 2 2 TXD
RXD 3 3 RXD
RTS 4 7 RTS
CTS 5 8 CTS
GND 7 5 GND
DCD 8 1 DCD
DTR 20 4 DTR
DSR 6 9 RI
DB25-P DE-15P
MARC Cable Ass'y #127-067-XX
MIILLE APPLIED RESEARCH CO., INC.
HOUSTON, TEXAS U.S.A. 800/729-0818
PAGE 14 APPLICATION NOTE #1
STANDARD MARC CABLE ASSEMBLIES
127-069-12
THIS CABLE IS USED FOR:
FSK Modem to SLC 503
166-101 SLC 503
PORT CHAN. 0
1
NC 1 1 DCD
RD 2 2 RXD
TD 3 3 TXD
DTR 4 4 DTR
GND 5 5 GND
DCD 6 6 DSR
RTS 7 7 RTS
CTS 8 8 CTS
NC 9 9 NC
DE-9S DE-9S
MARC Cable Ass'y #127-069-XX
1995-2003 MIILLE APPLIED RESEARCH CO., INC.
HOUSTON, TEXAS U.S.A.
APPLICATION NOTE #1 PAGE
STANDARD MARC CABLE ASSEMBLIES 15
127-070-12
THIS CABLE IS USED FOR:
OMNII-COMM Modem to 1747-KE
MARC Omnii-Comm Allen-Bradley
166-101 Port P1 1747-KE
NC 1 1 NC
RD 2 2 RXD
TD 3 3 TXD
DTR 4 4 DTR
GND 5 5 GND
DCD 6 6 DSR
RTS 7 7 RTS
CTS 8 8 CTS
NC 9 9 NC
DE-9S DE-9S
MARC Cable Ass'y #127-070-XX
MIILLE APPLIED RESEARCH CO., INC.
HOUSTON, TEXAS U.S.A. 800/729-0818
PAGE 16 APPLICATION NOTE #1
STANDARD MARC CABLE ASSEMBLIES
127-071-12
THIS CABLE IS USED FOR:
MARC ONMII-COMM TO PLC-503 or 1747-KE
MARC OMNII-COMM Allen-Bradley
P2 SLC 503
NC 1 1 NC
RXD 2 3 TXD
TXD 3 2 RXD
DTR 4 4 DTR
GND 5 5 GND
DCD 6 6 DSR
RTS 7 7 RTS
CTS 8 8 CTS
NC 9 9 NC
DE-9S DE-9S
MARC Cable Ass'y #127-071-XX
1995-2003 MIILLE APPLIED RESEARCH CO., INC.
HOUSTON, TEXAS U.S.A.
APPLICATION NOTE #1 PAGE
STANDARD MARC CABLE ASSEMBLIES 17
127-073-12
THIS CABLE IS USED FOR:
MARC ONMII-COMM TO PLC-5 Channel 0
MARC OMNII-COMM Allen-Bradley
(all RS232 ports) PLC 5 Channel 0
NC 1
RXD 2 2 TXD
TXD 3 3 RXD
DTR 4 4 RTS
GND 5 5 CTS
DCD 6 6 DSR
RTS 7 7 GND
CTS 8 8 DCD
NC 9 20 DTR
DE-9S DB-25-P
MARC Cable Ass'y #127-073-XX
MIILLE APPLIED RESEARCH CO., INC.
HOUSTON, TEXAS U.S.A. 800/729-0818
PAGE 18 APPLICATION NOTE #1
STANDARD MARC CABLE ASSEMBLIES
127-074-12
THIS CABLE IS USED FOR:
MARC ONMII-COMM TO 1785-KE
MARC OMNII-COMM Allen-Bradley
(all RS232 ports) 1785-KE
NC 1 1 NC
RXD 2 2 TXD
TXD 3 3 RXD
DTR 4 4 RTS
GND 5 5 CTS
DCD 6 6 DSR
RTS 7 8 DCD
CTS 8 11 DTR
NC 9 7 GND
13 ENA
DE-9S
DE-15P
MARC Cable Ass'y #127-074-XX
1995-2003 MIILLE APPLIED RESEARCH CO., INC.
HOUSTON, TEXAS U.S.A.
APPLICATION NOTE #1 PAGE
STANDARD MARC CABLE ASSEMBLIES 19
127-077-12
THIS CABLE IS USED FOR:
MARC 166-100 Dial-up Modem to SLC 503
166-100 SLC 503
PORT CHAN. 0
1
NC 1 1 DCD
RD 2 2 RXD
TD 3 3 TXD
DTR 4 4 DTR
GND 5 5 GND
DCD 6 6 DSR
RTS 7 7 RTS
CTS 8 8 CTS
NC 9 9 NC
DE-9S DE-9S
MARC Cable Ass'y #127-077-XX
MIILLE APPLIED RESEARCH CO., INC.
HOUSTON, TEXAS U.S.A. 800/729-0818
PAGE 20 APPLICATION NOTE #1
STANDARD MARC CABLE ASSEMBLIES
127-078-12
THIS CABLE IS USED FOR:
MARC 166-010 Dial-up Modem to PLC 5 Channel 0
Note: Revision 2 or greater only.
Allen-Bradley
MARC
166-010 PLC 5 Channel 0
TXD 2 2 RXD
RXD 3 3 TXD
RTS 4 4 RTS
CTS 5 5 CTS
GND 7 7 GND
NC 13 13 NC
DSR 6 6 DSR
DCD 8 8 DCD
DTR 11 20 DTR
DE-15P DB-25P
MARC Cable Ass'y #127-078-XX
1995-2003 MIILLE APPLIED RESEARCH CO., INC.
HOUSTON, TEXAS U.S.A.
APPLICATION NOTE #1 PAGE
STANDARD MARC CABLE ASSEMBLIES 21
127-079-12
THIS CABLE IS USED FOR:
MARC 166-010 Dial Up Modem to 1785-KE and 1771-KG
MARC Allen-
166-010 Bradley
1785-KE or
TXD 2 2 TXD
RXD 3 3 RXD
RTS 4 4 RTS
CTS 5 5 CTS
GND 7 7 GND
ENA 13 13 ENA
DSR 6 6 DSR
DCD 8 8 DCD
DTR 11 11 DTR
DE-15P DE-15P
MARC Cable Ass'y #127-079-XX
MIILLE APPLIED RESEARCH CO., INC.
HOUSTON, TEXAS U.S.A. 800/729-0818
PAGE 22 APPLICATION NOTE #1
STANDARD MARC CABLE ASSEMBLIES
127-XXX-XX
Comm-Master or Comm-Troller RS422 Connections (typical)
DE-15P RS 422 DEVICE
TX+ 9 RX+
TX- 10 RX-
RX+ 13 TX+
RX- 12 TX-
GND 7 GND
RTS 4
CTS 5
Comm-Master or Comm-Troller RS485 Connections (typical)
RS-485 Device
TX+ 9 TR+ NORMALLY HIGH
TX- 10 TR- NORMALLY LOW
RX+ 13
RX- 12
GND 7 GND
RTS 4
CTS 5
DE-15P
1995-2003 MIILLE APPLIED RESEARCH CO., INC.
HOUSTON, TEXAS U.S.A.
APPLICATION NOTE #1 PAGE
STANDARD MARC CABLE ASSEMBLIES 23
RS-422 NULL MODEM CABLE
for Comm-Troller or Comm-Master (Typical)
TX+ 9 9 TX+
TX- 10 10 TX-
RX+ 13 13 RX+
RX- 12 12 RX-
RTS 4 4 RTS
CTS 5 5 CTS
DE-15P DE-15P
MIILLE APPLIED RESEARCH CO., INC.
HOUSTON, TEXAS U.S.A. 800/729-0818
PAGE 24 APPLICATION NOTE #1
STANDARD MARC CABLE ASSEMBLIES
127-076-72
6
5 Y R+
4 G T+
3 R T-
2 B R-
1
modular connector 6’
VIRGINIA
PLASTICS
020.002.260
MARC Cable Ass’y #127-076-72
1995-2003 MIILLE APPLIED RESEARCH CO., INC.
HOUSTON, TEXAS U.S.A.
APPLICATION NOTE #1 PAGE
STANDARD MARC CABLE ASSEMBLIES 25
NOTES
MIILLE APPLIED RESEARCH CO., INC.
HOUSTON, TEXAS U.S.A. 800/729-0818
PAGE 26 APPLICATION NOTE #1
STANDARD MARC CABLE ASSEMBLIES
CONTACT OUR SALES OFFICE AT THE NUMBER BELOW TO
GET ADDITIONAL INFORMATION ON OUR
PLC COMMUNICATIONS PRODUCTS
LEASED LINE MODEMS
FOR PLC 5 AND SLC 500
DIAL UP MODEMS
FOR PLC 5 AND SLC 500
COMM-MASTER
PLC 5 POLLING MASTER CARD
COMM-TROLLER
PLC 5 PROTOCOL CONVERTER
OMNII-COMM
UNIVERSAL COMMUNICATIONS CONTROLLER
FOR PLC5 AND SLC 500
MIILLE APPLIED RESEARCH CO., INC.
P.O. BOX 87634
HOUSTON, TEXAS 77287
U.S.A.
VOICE 800/729-0818
OR
FAX 713/472-0318
http://www.miille.com
1995-2003 MIILLE APPLIED RESEARCH CO., INC.
HOUSTON, TEXAS U.S.A.