624 Influence of Shunt Capacitor Banks On Circuit Breaker Fault Interruption Duties
624 Influence of Shunt Capacitor Banks On Circuit Breaker Fault Interruption Duties
Working Group
A3.26
June 2015
INFLUENCE OF SHUNT CAPACITOR BANKS ON
CIRCUIT BREAKER FAULT INTERRUPTION DUTIES
Working Group
A3.26
June 2015
Members
R. Alexander (US), A. Bosma (SE, convenor), R. Campos (BR), A. Canhôto (PT), L. Collete (US),
C. Creusot (FR), Y. Filion (CA), J. Hu (CA), S. Huang (CN), A. Kalyuzhny (IL), J. Mantilla (CH),
M. McVey (US), S. de Azevedo Morais (BR), J. Nelson (US), F. Richter (DE), H. Rörvall (SE),
R.P.P Smeets (NL, guest), B. Sunga (CA), C. Watier (FR), L. Violleau (FR), D. Yoshida (JP)
Copyright © 2015
“Ownership of a CIGRE publication, whether in paper form or on electronic support only infers right
of use for personal purposes. Are prohibited, except if explicitly agreed by CIGRE, total or partial
reproduction of the publication for use other than personal and transfer to a third party; hence circu-
lation on any intranet or other company network is forbidden”.
Disclaimer notice
“CIGRE gives no warranty or assurance about the contents of this publication, nor does it accept
any responsibility, as to the accuracy or exhaustiveness of the information. All implied warranties
and conditions are excluded to the maximum extent permitted by law”.
ISBN: 978-2-85873-327-9
Influence of shunt capacitor banks on circuit breaker fault interrupting duties
Abbreviations
CB Circuit Breaker
L 90 Short-line fault 90 %
RLC Circuit consisting of a resistance (R), inductance (L) and capacitance (C)
SW Switching device
WG Working Group
Page 2
Influence of shunt capacitor banks on circuit breaker fault interrupting duties
CONTENTS
1 Introduction ................................................................................................................. 7
1.1 General .............................................................................................................. 7
1.2 Capacitor bank configuration ................................................................................ 7
1.3 Fault interruption near a capacitor bank ................................................................ 7
2 Capacitor bank switching ............................................................................................. 9
2.1 General .............................................................................................................. 9
2.2 Energisation of capacitor banks ........................................................................... 9
2.2.1 General ....................................................................................................... 9
2.2.2 Single capacitor bank ................................................................................. 10
2.2.3 Back-to-back capacitor bank ....................................................................... 11
2.3 De-energisation of capacitor banks .................................................................... 13
2.3.1 General ..................................................................................................... 13
2.3.2 Capacitive current ...................................................................................... 14
2.3.3 Recovery voltage ....................................................................................... 14
2.3.4 Considerations for transient inrush (outrush) currents .................................. 17
3 Influence of shunt capacitor banks on line circuit breaker TRVs and potential
effect on fault interrupting times ................................................................................. 18
3.1 Introduction ....................................................................................................... 18
3.2 Analytical study ................................................................................................. 19
3.2.1 General ..................................................................................................... 19
3.2.2 Analytical study of the maximum TRVpeak................................................... 19
3.2.3 Parallel RLC circuit ..................................................................................... 29
3.2.4 EMTP simulations ...................................................................................... 38
3.3 Influence on fault interrupting times .................................................................... 50
4 Influence of outrush currents on line circuit breakers during fault switching
sequences ................................................................................................................. 51
5 Influence of capacitor bank configuration, component topology and fault type on
fault interruption by both line and capacitor bank circuit breakers ................................. 52
5.1 Capacitor bank configuration .............................................................................. 52
5.2 Capacitor bank switching device ........................................................................ 52
5.2.1 TRVs ......................................................................................................... 52
5.2.2 Mitigation means ........................................................................................ 56
5.3 Transmission line circuit breaker ........................................................................ 56
6 Circuit breakers of different types and their applicable characteristics .......................... 56
6.1 General ............................................................................................................ 56
6.2 Oil circuit breakers ............................................................................................ 56
6.3 Air-blast circuit breakers .................................................................................... 56
6.4 Vacuum circuit breakers .................................................................................... 57
6.5 SF 6 circuit breakers .......................................................................................... 57
7 Mitigation of the effects of the interruption of short-circuit currents in the presence
of a capacitor bank .................................................................................................... 57
7.1 Mitigation at the capacitor bank .......................................................................... 57
7.1.1 Installation of damping reactors .................................................................. 57
7.1.2 Fixed or switched resistor in parallel with a reactor ...................................... 58
Page 3
Influence of shunt capacitor banks on circuit breaker fault interrupting duties
Figure 1 – Transmission line circuit breaker interrupting a fault near a capacitor bank ............ 8
Figure 2 – Alternative location of damping reactor L 1 in Figure 1 .......................................... 8
Figure 3 - Parallel capacitor banks .................................................................................... 12
Figure 4 – Single-phase equivalent circuit for capacitive current interruption ........................ 14
Figure 5 – Voltage and current shapes at capacitive current interruption ............................. 15
Figure 6 – Voltage and current wave shapes in the case of a restrike .................................. 16
Figure 7 – Voltage build-up by successive restrikes ............................................................ 17
Figure 8 – Single-phase representation of Figure 1 ............................................................ 20
Figure 9 – TRV waveforms after clearing of the first pole during a terminal fault in a
170 kV substation ............................................................................................................. 25
Figure 10 – Maximum TRV peak versus k pp ....................................................................... 26
Figure 11 – Maximum TRV peak versus the equivalent inductance Lc ................................. 27
Figure 12 – Maximum TRV peak versus the reactive power of the capacitor bank ................ 28
Figure 13 – Influence of the neutral earthing of the capacitor bank on the maximum
TRV peak ......................................................................................................................... 28
Figure 14 – Basic circuit for TRV calculation ...................................................................... 30
Figure 15 – Generalized damping curves ........................................................................... 30
Figure 16 – Base TRVs for T100, T60, T30 and T10 ........................................................... 32
Figure 17 – Base TRV for T100 and TRVs with additional capacitance ................................ 32
Figure 18 – Base TRV for T60 and TRVs with additional capacitance .................................. 33
Figure 19 – Base TRV for T30 and TRVs with additional capacitance .................................. 33
Figure 20 – Base TRV for T10 and TRVs with additional capacitance .................................. 34
Figure 21 – Base TRVs and TRVs with added capacitance of 1 F ...................................... 35
Page 4
Influence of shunt capacitor banks on circuit breaker fault interrupting duties
Figure 22 – Hydro-Québec EMTP study: TRVs without added shunt capacitor banks ............ 36
Figure 23 – Hydro-Québec EMTP study: TRV without shunt capacitance (blue trace)
and with added shunt capacitance (red trace) .................................................................... 37
Figure 24 – Comparison of Hydro-Québec EMTP and parallel RLC circuit TRV
calculations ...................................................................................................................... 37
Figure 25 – Circuit diagram used for 72,5 kV simulation ...................................................... 38
Figure 26 - Trace of the recovery voltage (left) and outrush current (right)
corresponding to the case of a non-effectively earthed source and a capacitor bank
with isolated neutral .......................................................................................................... 40
Figure 27 - Trace of the recovery voltage (left) and outrush current (right)
corresponding to the case of an effectively earthed neutral source and a capacitor
bank with solidly earthed neutral ....................................................................................... 41
Figure 28 - Trace of the recovery voltage (left) and outrush current (right)
corresponding to the case of a non-effectively earthed source and a capacitor bank
with isolated neutral .......................................................................................................... 42
Figure 29 - Trace of the recovery voltage (left) and outrush current (right)
corresponding to the case of an effectively earthed neutral source and a capacitor
bank with solidly earthed neutral ....................................................................................... 43
Figure 30 – Circuit diagram used for 245 kV simulations ..................................................... 43
Figure 31 – Comparison of transient recovery voltage with no capacitor bank, with
capacitor bank and no damping reactor, and with capacitor bank and damping reactor ......... 44
Figure 32 - Trace of the current interrupted by the circuit breaker for the case with a
capacitor bank without damping reactor ............................................................................. 46
Figure 33 - Trace of the transient recovery voltage across the circuit breaker for the
case with a capacitor bank without damping reactor ........................................................... 46
Figure 34 - Trace of the current interrupted by the circuit breaker for the case with a
capacitor bank and a 1000 H damping reactor .................................................................. 47
Figure 35 - Trace of the transient recovery voltage across the circuit breaker for the
case with a capacitor bank and a 1000 H damping reactor ................................................ 47
Figure 36 – Circuit diagram used for 362 kV simulations ..................................................... 48
Figure 37 – Two capacitor banks with isolated neutral – Restrike on phase B followed
by a restrike on phase A ................................................................................................... 49
Figure 38 – Inrush current versus instant of fault initiation on first phase to close ................. 51
Figure 39 – Short-circuits resulting in high-frequency TRVs ................................................ 52
Figure 40 - Field test measurements on 0,23 mH damping reactor in a 120 kV
installation ........................................................................................................................ 53
Figure 41 – 40 kA three-phase asymmetrical fault at 120 kV – Currents and TRVs ............... 54
Figure 42 – Initial TRV of the fault case described in Figure 41 ........................................... 55
Figure 43 – Solution with a damping resistor ...................................................................... 58
Figure 44 – Solution with a switched resistor ...................................................................... 58
Figure 45 – Solution with a MOV in parallel to the damping reactor ..................................... 58
Figure 46 – Solution with a MOV in parallel with the damping reactor .................................. 59
Figure C.1 – Comparison of It integral for different currents .............................................. 68
Figure C.2 – Difference between inrush current frequencies ............................................... 68
Figure D.1 – Switching of a capacitor bank bank-to-back to underground cables .................. 71
Figure D.2 – Waveforms of the total inrush current and the inrush current through the
voltage source .................................................................................................................. 72
Page 5
Influence of shunt capacitor banks on circuit breaker fault interrupting duties
Figure D.3- Single-phase circuit for analysis of the capacitive inrush current ....................... 73
Figure D.5 -Circuit for analytical study of the inrush current due to initial traveling
waves in the alongside cables ........................................................................................... 75
Figure D.7 - Inrush current waveform obtained in EMTP simulation ..................................... 79
Figure D.8 - Inrush current peak versus the number of underground cables ......................... 80
Figure D.9 – Curves of the inrush current peak versus equivalent inductance L ................... 81
Figure D.11 – Curves of I peak versus equivalent inductance L at different values of l c ......... 82
Figure D.12 – Curves of I peak versus the length of the shortest cable ................................. 82
Page 6
Influence of shunt capacitor banks on circuit breaker fault interrupting duties
1 Introduction
1.1 General
Shunt capacitor banks are being applied worldwide in substations in ever increasing numbers.
At voltage ratings up to and including 52 kV capacitor banks are either fixed or switched. At
voltage ratings of 75,5 kV up to and above each individual bank is typically switched with its
own switching device and may incorporate either active (controlled switching, pre-insertion
impedance) and/or passive (series reactors) means to limit the effects of inrush and/or outrush
currents.
NOTE Harmonic filters consist of a capacitor bank with a series reactor. Their behaviour will be similar.
From the perspective of line circuit breakers during fault interruption, the banks represent a
large source side capacitance and also a source of outrush currents, both of which may
influence the fault interrupting time. If a capacitor bank incorporates series current limiting
reactors between the capacitor bank circuit breaker and the capacitor bank, the circuit breaker
will be exposed to significant fast transient recovery voltages (TRVs) for faults between the
reactor and the capacitor bank. Exposure to fast TRVs applies to all circuit breakers installed
immediately in series with the reactor.
Against this background Study Committee A3 established Working Group (WG) A3.26. The
tasks assigned to the WG were as follows:
– To study the influence of shunt capacitor banks on line circuit breaker TRVs and potential
effect on fault interrupting times;
– To study the influence of outrush currents on line circuit breakers during fault interruption
sequences;
– To study the influence of capacitor bank configuration, component topology and fault type
on fault interruption by both line and capacitor bank circuit breakers;
– To study the influence of the presence of a series reactor in the vicinity of the circuit breaker;
– To investigate which potential remedies that may be applied by users to mitigate or avoid
the above influences;
– To make recommendations (as applicable) as to how the applications need to be addressed
in the standards.
The analysis considers circuit breakers of the different types (oil, air-blast vacuum and SF 6 )
and their applicable characteristics.
This document is the complete and final report from the working group.
Some capacitor bank installations are fitted with series reactors (so-called damping reactors)
to limit the inrush/outrush current. Annex A provides some more details about series reactors
in general.
Page 7
Influence of shunt capacitor banks on circuit breaker fault interrupting duties
SW1 C1
L1
Us L'
Ls
CB
Transmission line
is
Key
Us Source voltage L' Busbar inductance
Figure 1 – Transmission line circuit breaker interrupting a fault near a capacitor bank
The capacitor bank (C 1 ) reduces the rate-of-rise of recovery voltage (RRRV), making it easier
for the transmission line circuit breaker (CB) to interrupt. Additionally, the capacitor bank will
increase the amplitude factor, i.e. will increase the TRV peak. When the ITRV is negligible, the
circuit breaker CB may be successful in interrupting with a shorter minimum arcing time than
obtained during the type tests (i.e. a small contact gap). As the recovery voltage increases
across the gap, a dielectric re-ignition may occur and the capacitor bank will discharge into the
fault through the circuit breaker CB. The amplitude of the discharge current depends on the
instantaneous voltage of the capacitor bank at the time of re-ignition and the frequency of the
discharge current is determined by the capacitance C 1 of capacitor bank C 1 and the inductance
(L 1 + L') between the capacitor bank and the fault location.
NOTE 1 If the ITRV is not negligible, the minimum arcing time will be similar to that obtained during the type tests
and the case described above may not occur.
NOTE 2 The influence of the stray capacitance is neglected since its capacitance is small compared to the
capacitance of the capacitor bank.
Page 8
Influence of shunt capacitor banks on circuit breaker fault interrupting duties
The high frequency discharge current is superimposed on the fault current, which creates
additional current zeros if the high frequency current amplitude exceeds the momentary
amplitude of short-circuit current from the source. Depending on the type of circuit breaker (oil,
air-blast, vacuum or SF 6 ), this high frequency current may be interrupted causing high
overvoltages.
A similar situation may occur, when circuit breaker CB closes into a fault (e.g. a reclosing
operation). The capacitor bank discharges into the fault and depending on the magnitude of the
inductance between the capacitor bank and the fault location (i.e. L 1 + L'), the discharge current
can reach high peak values and frequencies. Especially when the damping reactor L 1 is not
installed, the inrush current parameters can exceed those given in Table 9 of IEC 62271-100
[1] and Tables 4, 8 and 14 of IEEE C37.06 [2].
Publications [3] and [4] address among others the energisation, de-energisation and application
considerations of shunt capacitor banks mainly under normal switching conditions (i.e. without
faults present). The case where a line circuit breaker switches a fault on the line in the presence
of a capacitor bank is briefly addressed, but a detailed analysis of the influence on the circuit
breaker TRV or the effects of the contribution of the capacitor bank to the fault current is not
provided.
Other cases that are not addressed by [3] and [4] are switching of a single capacitor bank and
back-to-back to parallel cables and switching of parallel cables. Those cases are addressed in
Annex D.
To understand the phenomena associated with the switching of fault currents in the presence
of capacitor banks the theory of inrush and outrush current is provided.
- inrush currents;
- overvoltages caused by the system response to the voltage dip when energising capacitor
banks (see 2.2.2);
Since the use of capacitor banks for compensation purposes is increasing, it is common that
more than one capacitor bank is connected to the same bus. This has no influence on the
conditions at interruption of the capacitive current. The current at closing, however, is affected
to a high degree. Two different situations may occur:
a) The capacitor bank is energised from a bus that does not have other capacitor banks
energised. This is called single capacitor bank switching.
b) The capacitor bank is energised from a bus that has other capacitor banks energised. This
is called back-to-back capacitor bank switching.
The conditions for single and back-to-back capacitor bank switching are given in 2.2.2 and
2.2.3. Even energised capacitor banks in nearby substations may contribute to the inrush
current such that a back-to-back situation occurs.
Back-to-back capacitor bank switching may give rise to inrush currents of very high amplitude
and frequency and they sometimes have to be limited in order not to be harmful to the switching
device, the capacitor banks and/or the network. The magnitude and frequency of this inrush
current is a function of the following:
Page 9
Influence of shunt capacitor banks on circuit breaker fault interrupting duties
The transient inrush current to a single bank is less than the available short-circuit current at
the capacitor bank terminals. It rarely exceeds 20 times the rated current of the capacitor bank
at a frequency that approaches 1 kHz. Since a switching device must meet the making current
requirements of the system, transient inrush current is not a limiting factor in single capacitor
bank applications. A rule of thumb used as a criteria for determining the maximum size of a
capacitor bank is that it should not result in a steady state voltage variation more than 3 % of
the system voltage: i.e. the size of the capacitor bank in Mvar/short-circuit power in MVA should
be less than 3 %.
When capacitor banks are switched back-to-back, that is, when one bank is switched while
another bank is connected to the same bus, transient currents of prospective high magnitude
and with a high natural frequency may flow between the banks on closing of the switching
device. The effects are similar to that of a re-ignition or a restrike on opening. This oscillatory
current is limited only by the impedance of the capacitor bank and the circuit between the
energised bank or banks and the switched bank. This transient current usually decays to zero
in a fraction of a cycle of the system frequency. In the case of back-to-back switching, the
component supplied by the source is at a lower frequency and so small it may be neglected.
The case of energising a single capacitor bank is equal to energisation of C 1 in Figure 1 when
there is no fault present on the transmission line. The circuit consists then of the source
inductance L s , the busbar inductance L' and the inductance of damping reactor L 1 in series with
the capacitor bank C 1 . The inductance of L' + L 1 can be disregarded here, since L s >> L' + L1 .
In this case, the peak of the inrush current (I i peak ) and inrush current frequency (f i ) are limited
by the inductance of the source impedance L s .
C1
ii Î i sin it Û s sin it (1)
Ls L' L1
and
1
fi (2)
2 ( Ls L' L1)C1
where
Page 10
Influence of shunt capacitor banks on circuit breaker fault interrupting duties
i = 2f i angular inrush frequency in rad/s, where f i is the inrush current frequency, in
Hz
with L s >> L' + L 1 , equations (1) and (2) transfer to:
C1
ii Û s sin it (3)
Ls
1
fi (4)
2 LsC1
The maximum inrush current peak is obtained when switching the capacitor bank at the peak
of the supply voltage.
C1
I i max U s 2 (5)
Ls
Us
With I sc and I1 sU sC1 , equations (4) and (5) transform to
s Ls
I i max 2 I sc I1 (6)
and
I sc
fi f s (7)
I1
where
fs power frequency, in Hz
I sc short-circuit current of the source, in A (r.m.s.)
I1 current through the capacitor bank C 1 , in A (r.m.s.)
Ii max maximum peak of the inrush current, in A
In the three-phase case the same equations may be applied. The voltage U s is then the rated
phase-to-earth voltage U r / 3 .
The derivation of the inrush current using the series RLC circuit is given in Annex B.
In back-to-back application the inrush current seen by a single bank will be increased when
other capacitor banks are already connected to the same bus. Some considerations regarding
the limits of inrush/outrush currents are given in Annex C.
The single-phase equivalent of a circuit where two capacitor banks are connected to a busbar
is shown in Figure 3. L' represents the busbar inductance and L 1 and L 2 represent the additional
Page 11
Influence of shunt capacitor banks on circuit breaker fault interrupting duties
damping inductance (if used). The inductance L s of the supply network will be several orders of
magnitude higher than L', L 1 or L 2 .
Key
Us Source voltage SW 1 , SW 2 Capacitor bank switching device
L' Busbar inductance L1, L2 Damping reactor, also including the bus
inductance between the banks
is Short-circuit current CB Transmission line circuit breaker
Ceq
I i max U s 2 (8)
Leq
1
fi (9)
2 LeqCeq
with
C1C 2
C eq (10)
C1 C 2
and
Page 12
Influence of shunt capacitor banks on circuit breaker fault interrupting duties
Leq L1 L2 (11)
I i max and f i can reach extreme values since the magnitude of L eq can be arbitrarily small (i.e.
when no damping reactors are installed).
Inserting Equations (10) and (11) in Equations (8) and (9) gives the following equations for the
maximum inrush current peak and frequency:
I 1I 2 U s I 1I 2
I i max U s 2 2 (12)
U s s Leq ( I1 I 2 ) s Leq ( I1 I 2 )
1 U s ( I1 I 2 ) 1 2f sU s ( I1 I 2 )
fi (13)
2 Leq I1I 2 2 Leq I1I 2
In a three-phase case the same equations may be applied. The voltage Us is then the rated
phase-to-earth voltage U r / 3 .
n 1 C
ii peak U s 2 (14)
n L
and
1
fi (15)
2 LC
In a three-phase case the same equations may be applied. The voltage Us is then the rated
phase-to-earth voltage U r / 3 .
In case the inrush current amplitude and frequency need to be limited, this can be done by
insertion of additional series inductance in the circuit, or by using pre-insertion resistors.
Another possibility is to use controlled switching.
Page 13
Influence of shunt capacitor banks on circuit breaker fault interrupting duties
Key
Us Source voltage (r.m.s.) u cb Voltage across the circuit breaker (r.m.s.)
sC1 U s C U
ic s 1 s (16)
2
1 LsC1 s2
1
i2
with
1
i 2f i , where f i is the inrush current frequency in Hz (see also 2.2.2).
LsC1
Page 14
Influence of shunt capacitor banks on circuit breaker fault interrupting duties
u, i
us
t
ucb
uL
t
ic
Key
ic Capacitive current
After interruption of the current, the supply side voltage u s will be more or less unaffected. There
is only a minor decrease in amplitude, associated with the removal of the capacitive load. The
transition to the new amplitude value is associated with a slight oscillation, the frequency of
which is determined by L s and C s .
The interruption of the current leaves a trapped charge u L on the capacitor bank. The voltage
u L will therefore remain constant at the value it had at current zero (namely the peak value of
the supply voltage).
Together with the low current amplitude to be interrupted, the low initial rate-of-rise of the
recovery voltage makes it relatively easy for the circuit breaker to interrupt. Some circuit
breakers may interrupt even if the current zero occurs immediately after contact separation.
Half a cycle after current zero, the recovery voltage increases to an amplitude of twice the peak
value of the supply voltage. Consequently, a rated frequency of 60 Hz is more severe than
50 Hz. The circuit breaker may then not be able to withstand the high value of the recovery
voltage across a relatively small contact gap. Dielectric breakdown may occur between the
contacts and the current is re-established between the contacts.
Figure 6 shows current and voltage wave shapes in a case where voltage breakdown occurs
relatively close to the recovery voltage peak. The load side voltage will swing up to a voltage
that ideally (without damping present) reaches three times the supply voltage peak u p . The
oscillation frequency of the current and voltage after the breakdown is determined by L s and C 1
(assuming C 1 >> C s ). The circuit breaker may easily interrupt the oscillatory current at one of
its current zeros, with the result that the voltage across the capacitor may attain a new constant
value, perhaps higher than before. Further breakdowns associated with even higher
overvoltages across the load may then occur (Figure 7).
Page 15
Influence of shunt capacitor banks on circuit breaker fault interrupting duties
Key
up Peak of the source voltage
ic Capacitive current
Page 16
Influence of shunt capacitor banks on circuit breaker fault interrupting duties
Key
1 p.u. is the peak value of the phase-to-earth voltage
Voltage breakdowns at capacitive current interruption are divided into re-ignitions and restrikes.
Re-ignitions and restrikes are defined in IEC 62271-100 [1] and IEEE C37.100 [5].
The definitions of re-ignition and restrike are valid only when the recovery voltage has a
1-cosine waveshape based on the power frequency of the network.
Restrikes will lead to overvoltages across the capacitive load (maximum 3 p.u. for a single
restrike, where 1 p.u. is the peak value of the phase-to-earth voltage) while re-ignitions will not
produce any overvoltages (theoretically maximum 1 p.u.). Re-ignitions are acceptable but may
cause power quality problems.
Page 17
Influence of shunt capacitor banks on circuit breaker fault interrupting duties
Another effective measure to reduce transient inrush currents is to add inductance in the circuit
between the capacitor banks.
Consider the situation given in Figure 1 or Figure 3. Depending on the position of the circuit
breaker (open or closed) the following situations associated with outrush current may occur:
3 Influence of shunt capacitor banks on line circuit breaker TRVs and potential
effect on fault interrupting times
3.1 Introduction
The phenomena occurring during interruption of a short-circuit near a capacitor bank are given
in 1.3.
Janssen and van der Sluis [6, 7] studied these phenomena in a 170 kV grid and tests were
conducted to establish the behavior of different circuit breaker types (air-blast, oil and SF 6 )
when exposed to high frequency current zeros. The authors concluded that damping of the high
frequency current (i.e. reducing the number of current zeros) in combination with a circuit
breaker that does not clear in any of the high frequency current zeros will avoid the occurrence
of high overvoltages. In the case described a damping resistor was inserted in series with the
capacitor bank in combination with an SF 6 puffer type circuit breaker.
Other means than series resistors can be used to mitigate the effects of the presence of the
capacitor bank. These means are presented in detail in Chapter 7 and are summarized here.
– Addition of series reactors in the circuit of the capacitor bank. This is illustrated by the
inductances L 1 and L 2 in Figure 3;
– Sabot et al [8] present a damping circuit for shunt capacitor bank switching consisting of a
damping reactor with a parallel Metal Oxide Varistor (MOV) in series with a resistor;
Page 18
Influence of shunt capacitor banks on circuit breaker fault interrupting duties
– Mysore et al [9] present a damping circuit consisting of a series reactor with a parallel
capacitor;
– J. Sawada and G. Polovick [10] of British Columbia Hydro (Canada) propose a damping
circuit consisting of a series reactor having a parallel capacitor and surge arrester on the
low voltage side (neutral) of the capacitor bank;
– Martin et al [11] analyzed a filtered capacitor bank, where a filter is inserted in series with
the capacitor bank. By a proper choice of the components the high frequency component
can be eliminated;
– Controlled fault interruption [12]. This method can be used to avoid breaking with short
arcing times.
3.2 Analytical study
3.2.1 General
To analyse the phenomena associated with the interruption of a fault near a capacitor bank (i.e.
TRV and outrush current waveforms), several methods can be used. Some of these methods
are:
In order to evaluate the TRV peak, a closed form solution is derived to evaluate the TRV
waveform after the clearing of the first pole during a three-phase terminal fault near a capacitor
bank.
Page 19
Influence of shunt capacitor banks on circuit breaker fault interrupting duties
Key
us (t) Source voltage Lc Inductance between the capacitor bank and
the fault location
Ls Source side inductance Rc Resistance representing the losses
between the capacitor bank and the fault
location
Rs Resistance representing the losses in the C1 Capacitor bank
source circuit
CB Circuit breaker ic(t) Capacitive current
u TRV ( t ) TRV across the circuit breaker u c( t) Voltage across the capacitor bank
In Figure 8 L c is the inductance between the capacitor bank and the fault location. For the
analysis of a terminal fault the inductance between the capacitor bank and fault location is given
by Lc L1 L' , where L 1 and L' are the inductances (in H) of L 1 and L' given in Figure 1.
us ûs cost (17)
The peak of the source voltage û s , the source side inductance L s and the resistance R s in the
single-phase circuit for the TRV calculation after clearing of the first pole is given by:
2 X
ûs kppU r , Ls kpp 1 , R s = k pp R 1, (18)
3
where
For effectively earthed neutral systems k pp = 1,0 - 1,3 and for non-effectively earthed neutral
systems k pp = 1,5.
Page 20
Influence of shunt capacitor banks on circuit breaker fault interrupting duties
For a capacitor bank with earthed neutral the values of C 1 , Lc and R c are given by:
C 1 = C ph , L c = L ph , R c = R ph (19)
For a capacitor bank with isolated neutral the values of C 1 , L c and R c are given by:
In Equations (19) and (20) C ph is the capacitance of a capacitor bank phase, L ph and R ph are
the phase inductance and phase resistance of the circuit between the capacitor bank and the
fault location, respectively.
The TRV across the circuit breaker after clearing of the first pole can be determined using
Equation (21).
c 2 2 2 2
uTRV (t ) ucp cos(t ) c 2 0 Ucpe 0t cos(0t ) (21)
c 2 c
With
1 1
c , 0 (22)
Lc C1 ( Ls Lc )C1
2 0 2
U cp kppUr (23)
3 ( 0 2 2 )
Rs Rc
0 (24)
2( Ls Lc )
Note that c is the natural angular frequency of the capacitor bank discharge current into the
short-circuit. 0 is the natural frequency of the capacitor bank inrush current, Ucp is the peak
voltage across the capacitor bank phase after clearing of the first pole and 0 is the damping
factor of the circuit in Figure 8.
The TRV reaches its maximum peak u TRVmax at a time t peak given by:
tpeak ( Ls Lc )C (25)
0
2 2 2 2
uTRV max kppU c peak c 0 c cos( ) (26)
c 2 c 2 0
In Equation (26) U c peak is the peak of the phase-to-earth voltage across the capacitor bank
under normal conditions,
2 02
U c peak U r (27)
3 02 2
Page 21
Influence of shunt capacitor banks on circuit breaker fault interrupting duties
To analyse the parameters that influence the maximum peak value of the TRV waveform,
Equation (26) is simplified by expanding cos( ) into a MacLaurin series using the first two
0
terms.
Lc ( )2
uTRV max kppU c peak 2 ) (28)
Lc Ls 2 0 2
As can be seen in Equation (28), the maximum TRV peak depends on the following parameters:
U CPmax k ppU cpeak 1 cos( ) (29)
0
Expanding cos( ) into a MacLaurin series and limiting the expansion to the first two terms,
0
the following equation is obtained:
( ) 2
U CPmax k ppU cpeak 2 - (30)
2 0 2
The capacitor bank discharge current peak I out can be calculated using the following Equation
(31):
C
I out U (31)
CPmax
Lc
The derived expressions for the maximum TRV peak u TRV max , the time instant t peak , the outrush
current peak I out and the outrush current frequency f out are summarised in Table 2.
Page 22
Influence of shunt capacitor banks on circuit breaker fault interrupting duties
u TRVmax (kV)
kppU r
2 0 2
2 -
Lc
2
3 02 2 Ls Lc 2 0 2
t peak (s) L s L c C
f out (Hz) 1
2 Lc C
NOTE I out is calculated under the assumption that a re-ignition occurs at t peak
X1
The short-circuit inductance Ls k pp , where X 1 is the positive sequence short-circuit
reactance.
Parameters L c and C depend on the earthing of the capacitor bank neutral, see Table 3.
Page 23
Influence of shunt capacitor banks on circuit breaker fault interrupting duties
Table 3 – Expressions for L c and C in relation to the earthing of the capacitor bank
neutral
Equations (26) and (27) enable to perform a parametric study of the maximum TRV peak as a
function of k pp , L c , Q c and the neutral earthing of the capacitor bank.
The developed equations have been used for analysis of the TRV in a 170 kV, 50 Hz system.
The system is presented by the following data:
– U r = 170 kV;
– I sc = 50 kA;
– DC time constant = 45 ms;
– k pp = 1,0, on other substations of the utility k pp varies between 1,0 and 1,3.
The capacitor bank with Q c = 222,9 Mvar at U r = 170 kV is connected to the substation busbar
through a damping reactor of 1,2 mH. The reactor resistance is determined under the
assumption that its qualify factor is 14,1. The capacitor units are Y connected with solidly
earthed neutral.
The values of the system presented here give the following single-phase values:
– Source: U peak = 138,8 kV, L s = 6,25 mH, R s = 0,139 (see equations (18));
– Capacitor bank: C 1 = 24,56 µF, L c 0 1,2 mH, R c = 0,027 (see equations (19)).
The parameters for the calculation of u TRV (t) are
a) A 170 kV circuit breaker with the following TRV data: u 1 = 135 kV, t 1 = 68 µs, u c = 253 kV,
t 3 = 272 µs (based on k pp = 1,3);
b) A 245 kV circuit breaker with the following TRV data: u 1 = 195 kV, t 1 = 98 µs, u c = 364 kV,
t 3 = 392 µs (based on k pp = 1,3).
Page 24
Influence of shunt capacitor banks on circuit breaker fault interrupting duties
To validate the developed equations, the TRV waveform given by Equation (21) was compared
to the waveform obtained using EMTP for the three-phase model in Figure 1. The TRV
waveforms are shown in Figure 9 together with the TRV envelope of a 170 kV circuit breaker.
250
TRV voltage [kVpeak]
200
150
100
50
50
100
0 1 2 3 4 5
time [ms]
Figure 9 – TRV waveforms after clearing of the first pole during a terminal fault in a 170
kV substation
Figure 9 shows that the analytical waveform (the solid curve) is in good agreement with the
EMTP waveform (the dotted curve). The analytical waveform practically coincides with the
EMTP waveform near the maximum TRV peak. That very good agreement justifies using the
derived analytical equations for evaluation of the maximum TRV peak. Figure 9 shows that the
maximum TRV peak u TRVmax is very close to the TRV peak value u c of the TRV envelope for a
170 kV circuit breaker. For higher values of k pp , u c will be proportionally higher and this
increased TRV peak may cause a restrike during the clearing of a three-phase terminal fault.
The curves of u TRVmax resulting from clearing of the three-phase terminal fault in the presence
of a 222,9 Mvar capacitor bank versus the first pole-to-clear factor k pp are shown in Figure 10.
The curves are calculated for the following values of the equivalent inductance L c : L c = 1,2 mH
and L c = 10 mH. Both values are selected taking into account possible resonance phenomena
as well as power quality aspects.
Page 25
Influence of shunt capacitor banks on circuit breaker fault interrupting duties
300
200
100
1 1.05 1.1 1.15 1.2 1.25 1.3
Dashed green line: TRV peak value u c for 170 kV and k pp = 1,3
Dashed black line: TRV peak value u c for for 245 kV and k pp = 1,3
Figure 10 shows that the maximum TRV u TRVmax is proportional to k pp . The increase of
u TRVmax with k pp may require a 245 kV circuit breaker in 170 kV substations where capacitor
banks are installed. It is evident that application of a 10 mH damping reactor instead of 1,2
mH may significantly reduce the maximum TRV peak.
The curves of u TRVmax versus the equivalent inductance Lc are shown in Figure 11. The curves
are calculated for the following values of the first pole-to-clear factor: k pp = 1 and k pp = 1,3.
Page 26
Influence of shunt capacitor banks on circuit breaker fault interrupting duties
200
100
2 4 6 8 10
Figure 11 shows that an increase of L c results in significant reduction of the maximum TRV
peak. It is assumed that L c includes a stray inductance of 0,1 mH and the inductance of the
damping reactor. If the damping reactor is not installed, the maximum TRV peak exceeds the
TRV peak value for the envelope of a 170 kV circuit breaker even if k pp =1.
Applying a damping reactor of 10 mH reduces the TRV peak significantly. For example, for a
170 kV power system with k pp =1,3, the maximum TRV peak decreases from 348 kV to 230 kV
making it possible to apply a 170 kV circuit breaker.
The curves of u TRVmax versus reactive power of the capacitor bank Q c are shown in Figure 12.
The curves are calculated under assumption that k pp = 1 for the following values of the
equivalent inductance: Lc = 1,2 mH and L c = 10 mH.
Page 27
Influence of shunt capacitor banks on circuit breaker fault interrupting duties
250
190
160
50 100 150 200 250
Figure 12 – Maximum TRV peak versus the reactive power of the capacitor bank
Figure 12 shows that an increase of the reactive power of the capacitor bank results in an
insignificant reduction of the maximum TRV peak. For example, for L c =1,2 mH, a change of Qc
from 50 Mvar to 250 Mvar results in decrease of u TRVmax from 253 kVpeak to 223 kVpeak.
The influence of the neutral earthing of the capacitor bank on the maximum TRV peak is
illustrated in Figure 13.
310
TRV peak [kVpeak]
270
230
190
150
1 1.05 1.1 1.15 1.2 1.25 1.3
Figure 13 – Influence of the neutral earthing of the capacitor bank on the maximum TRV
peak
Page 28
Influence of shunt capacitor banks on circuit breaker fault interrupting duties
Figure 13 shows that using capacitor banks with isolated neutrals (ungrounded – Y-connected
banks) results in insignificant reduction (3 – 7 %) of the maximum TRV peak.
When L c << L s , the equations given in Table 3 can be simplified. The result is given in Table 4.
The equations given in Table 4 are used to compare the values obtained using EMPT
simulations with those obtained using the analytical analysis
I out 2C 4 2C 2C 4 2C
2k pp U r kpp U r 2kpp U r kpp U r
(kApeak) 3000 L1 3 3000 L1 3000 L1 3 3000L1
f out 1 1 1 1 1 1 1 1
(kHz) 2 103 L1C 2 103 L1C 2 103 L1C 2 103 L1C
NOTE The calculation of I out assumes that the re-ignition occurs at the peak of the TRV.
Where
k pp is the first pole-to-clear factor – 1,3 for effectively earthed neutral source and 1,5 for
non-effectively earthed neutral source (p.u.)
U r is the system voltage (kV r.m.s.)
L s is the short-circuit reactance (mH)
L 1 is the reactance between the capacitor bank and the line (mH)
C is the capacitance of the capacitor bank (µF)
In case of a single-phase fault with the capacitor bank connected, the results are as follows:
1 1
fout
2 103 L1C
These simplifications are meant to provide a first approximation of the phenomena that occur
close to or at the TRV peak.
Page 29
Influence of shunt capacitor banks on circuit breaker fault interrupting duties
TRVs can be calculated using the circuit shown in Figure 14 [13]. R, L and C elements of the
actual circuit can be reduced to form an equivalent parallel oscillating circuit with C sh being the
additional capacitance due to the presence of a shunt capacitor bank. The TRV for the basic
RLC case is first calculated and then various values of C sh can be added to determine their
effect on the TRVs.
The TRV is calculated using the current injection method described in [14]. The resulting
solution has three possible outcomes depending upon whether the circuit is over-damped,
critically damped or under-damped. Generalized damping curves can be derived as shown in
Figure 15 [15].
The parameter used in the curves is R/R cd where R cd is the value of R which results in critical
damping, i.e. R/R cd = 1. The three cases can be summarized as follows:
Page 30
Influence of shunt capacitor banks on circuit breaker fault interrupting duties
The time axis is generic where one unit is the angular period of the underdamped oscillation
given by LC .
L
Rcd 0,5 (32)
C
It is clear from Equation (32) that any increase in the value of C will increase the value of R/R cd .
The effect is therefore twofold:
Rated Test- First Amplitude First Time TRV Time Time Voltage Time Rate-
voltage duty pole- factor reference peak delay of-
to- voltage value rise
clear
factor
t 2 or u1/t1
Ur k pp k af u1 t1 uc td u' t'
t3 uc/t2
The TRVs for T100 and T60 are four-parameter over-damped exponential functions with the
first part being local and the second part due to the return of the reflected travelling wave [13].
Only the first part of these TRVs is considered in this analysis. The TRVs for T30 and T10 are
two-parameter underdamped oscillatory functions.
Figure 16 shows the base TRV cases with no added capacitance and Figure 17 through Figure
21 show the base TRV cases and the cases with the above noted capacitance values,
respectively. For the T100, T60 and T30 cases, 1 p.u. equals 260 kV while for the T10 1 p.u.
equals 300 kV.
Page 31
Influence of shunt capacitor banks on circuit breaker fault interrupting duties
1,6
TRV (p.u.)
1,4
0,2
0
0 200 400 600 800 1000
Time (µs)
Figure 17 – Base TRV for T100 and TRVs with additional capacitance
Page 32
Influence of shunt capacitor banks on circuit breaker fault interrupting duties
Figure 18 – Base TRV for T60 and TRVs with additional capacitance
Figure 19 – Base TRV for T30 and TRVs with additional capacitance
Page 33
Influence of shunt capacitor banks on circuit breaker fault interrupting duties
Figure 20 – Base TRV for T10 and TRVs with additional capacitance
The effect of the added capacitance is obvious. The lower values of C sh represent situations
where added capacitance might be required to provide TRV control.
NOTE The upper limit of added capacitance of 5 µF is a practical limit for TRV/surge capacitors.
For T30 and T10, the TRV values approach high amplitude factors quite rapidly with
increasing C sh values; additionally, the oscillations will ring for some cycles of the power
frequency voltage.
Figure 21 shows the migration of the base family of TRVs with the addition of a 1 μF capacitor.
The blue curves are without added capacitance and show the TRVs for T10 to T100 from left to
right. The red curves are with the additional capacitance and show the TRVs for T100 to T10
again read left to right.
Page 34
Influence of shunt capacitor banks on circuit breaker fault interrupting duties
In general, the actual existing TRVs in any substation will not be known. However, the TRV
capability of the existing circuit breakers is known and can be used as the base TRV. For
example, if the circuit breakers are rated at 50 kA, and the actual fault level is 40 kA, the base
“T80 TRV” is extrapolated from the T100 and T60 values and used to determine the base circuit.
The effect of added capacitance is then determined as discussed above.
The question now is: how accurate is an RLC calculation as compared to using a transients
program such as EMTP. Hydro-Québec carried out an EMTP study for a 735/315 kV substation
to determine the effect of adding two 315 kV, 384 Mvar shunt capacitor banks, the three-phase
to earth fault level being 42,4 kA rms. The calculated TRVs without added shunt capacitor banks
are shown in Figure 22.
Page 35
Influence of shunt capacitor banks on circuit breaker fault interrupting duties
80
60
40
20
-20
-40
-60
-80
0 4 8 12 16 20 24 28 32 36 40
Time (ms)
2
1,5
0,5
-0,5
-1
-1,5
-2
0 4 8 12 16 20 24 28 32 36 40
Time (ms)
Figure 22 – Hydro-Québec EMTP study: TRVs without added shunt capacitor banks
Expressed in IEC terms, the characteristics of the first-pole-to-clear two parameter TRV values
are: u c = 1,82 p.u., k af = 1,4 and u c /t 3 = 2,2 kV/s. The TRV is underdamped. With the two
added shunt capacitor banks, the TRV characteristics become: u c = 2,23 p.u., k af = 1,72 and
u c /t 3 = 0,5 kV/s. The two TRVs are shown in comparison in Figure 23 for the first-pole-to-clear.
The effect of the added capacitance is as expected and the longer term ringing noted above is
evident.
The TRV as modified by the presence of the capacitor banks can be compared to the TRV for
out-of-phase switching given in IEC 62271-100. The two-parameter values for the out-of-phase
TRV are: u c = 1,91 p.u. and u c /t 3 = 1,54 kV/µs. The peak of the modified TRV is more severe
than that for out-of-phase switching, whereas the rate-of-rise of the modified TRV is much lower
than that for out-of-phase.
Using the EMTP calculated TRV values with no added shunt capacitor banks, a basic RLC
circuit can be calculated as for the 245 kV circuit breaker case discussed above. The effect of
the added capacitance is then readily determined as shown in Figure 24. The RLC calculation
compares well with the EMTP calculation but exhibiting less damping.
Page 36
Influence of shunt capacitor banks on circuit breaker fault interrupting duties
Figure 23 – Hydro-Québec EMTP study: TRV without shunt capacitance (blue trace) and
with added shunt capacitance (red trace)
From Figure 24 the conclusion can be drawn that the parallel RLC analysis is more conservative
than that of an EMTP calculation.
Page 37
Influence of shunt capacitor banks on circuit breaker fault interrupting duties
The results of the EMTP simulations were compared to the analytical result obtained using the
equations given in Table 4.
The circuit consists of two sources, the short-circuit current is set at 31,5 kA when both sources
are connected.
The capacitor bank is a 17,9 Mvar capacitor bank (capacitance 10 µF) connected via a damping
reactor of 100 µH.
Page 38
Table 6 – Results of analysis for 72,5 kV, non-effectively earthed neutral source, full short-circuit
Table 7 – Results of analysis for 72,5 kV, effectively earthed neutral source, full short-circuit
Page 39
From the results given in Table 6 and Table 7 the following conclusions can be drawn:
– The outrush current peak and frequency from EMTP simulations are in line with the analytic
values as well as the TRV peak value.
– An isolated neutral capacitor bank allows to reduce the amplitude of the outrush current.
– Simulation of a restrike at the peak of the TRV, will give the outrush current and the TRV
that the circuit breaker has to withstand if the circuit breaker clears at the first high frequency
current zero.
Figure 26 shows an example of a re-ignition at the TRV peak on the green phase. The case
considered is a non-effectively earthed source and a capacitor bank with isolated neutral. The
results are as follows:
– An outrush current of 37,5 kA peak with a frequency of 4,95 kHz occurs. This current is
cleared at the first high frequency current zero;
– The result is that an even higher voltage peak (300 kV peak instead of the original 170 kV peak )
appears between the circuit breaker terminals.
Figure 27 shows an example of a re-ignition at the TRV peak on the blue phase. The case
considered is an effectively earthed source and a solidly earthed capacitor bank. The results
are as follows:
– An outrush current of 48,4 kA peak with a frequency of 4,95 kHz occurs. This current is
cleared at the first high frequency current zero;
– The result is that an even higher voltage peak (appears between the circuit breaker
terminals, in that case 263 kVpeak compared to the original 170 kV peak .
Figure 26 - Trace of the recovery voltage (left) and outrush current (right)
corresponding to the case of a non-effectively earthed source and a capacitor bank with
isolated neutral
Page 40
Influence of shunt capacitor banks on circuit breaker fault interrupting duties
Figure 27 - Trace of the recovery voltage (left) and outrush current (right)
corresponding to the case of an effectively earthed neutral source and a capacitor bank
with solidly earthed neutral
Table 8 – EMTP simulation results for 72,5 kV, single-phase fault, non-effectively
earthed neutral source
Page 41
Influence of shunt capacitor banks on circuit breaker fault interrupting duties
Table 9 – Results of analysis for 72,5 kV, single-phase fault, effectively earthed neutral
source
From the results given here the following the conclusions can be drawn that the amplitude of
the outrush current is strongly reduced when the capacitor bank has an isolated neutral.
Figure 28 shows an example of restrike at the TRV peak on the blue phase. The case
considered is a non-effectively earthed source and a capacitor bank with isolated neutral. The
results are as follows:
– An aperiodic outrush current of 6,1 kA peak appears, the current is cleared only after the next
power frequency current zero.
Figure 29 shows an example of restrike at the TRV peak on the blue phase. The case
considered is an effectively earthed source and a capacitor bank with solidly earthed neutral.
The results are as follows:
– An outrush current of 37,4 kA peak at a frequency of 4,95 kHz appears. The current is cleared
at the first high frequency current zero;
– The result is that an even a higher voltage (204 kV peak compared to the original 114 kV peak )
appears between the circuit breaker terminals.
Figure 28 - Trace of the recovery voltage (left) and outrush current (right)
corresponding to the case of a non-effectively earthed source and a capacitor bank with
isolated neutral
Page 42
Influence of shunt capacitor banks on circuit breaker fault interrupting duties
Figure 29 - Trace of the recovery voltage (left) and outrush current (right)
corresponding to the case of an effectively earthed neutral source and a capacitor bank
with solidly earthed neutral
3.2.4.2 245 kV
3.2.4.2.1 General
EMTP simulations have been performed considering a single-phase-to-earth fault.
The EMTP model for the simulations is given in Figure 30. The circuit consists of a combination
of two short-circuit equivalent circuits (i.e., transformer and transmission line circuit) to obtain
63 kA short-circuit current and a transient recovery voltage response representative of the T100
short-circuit test-duty for 245 kV, 63 kA rated circuit breaker with a first pole-to-clear factor of
1,3. The shunt capacitor bank used for the simulations is 100 Mvar (5,014 F at 230 kV).
Short-Circuit Equivalent
Circuit Breaker
Transformer Circuit ~60% Contribution Interrupting Fault.
from Transformers
Damping
Short-Circuit Equivalent Reactor
Transmission Line Circuit
Shunt
Capacitor Bank
Page 43
Influence of shunt capacitor banks on circuit breaker fault interrupting duties
– Single-phase to earth fault with a 5,014 F capacitor bank and 1000 H damping reactor.
Figure 31 shows a comparison of the three simulated cases.
As shown in Figure 31, the addition of the shunt capacitor bank significantly reduces the rate-
of-rise of the TRV, especially in the first few µs. However, if a damping reactor is used with the
capacitor bank, the initial rate-of-rise of the TRV is fairly consistent to the case with no capacitor
bank.
If a restrike occurs at the peak of the TRV an outrush current will flow through the circuit breaker
interrupting the fault current. To quantify the outrush currents for the case with a restrike at the
peak of the TRV, the following cases are simulated:
Page 44
Influence of shunt capacitor banks on circuit breaker fault interrupting duties
Table 10 - Simulation results for 245 kV circuit breaker with a single-phase to earth fault
I sc kA (rms) 63 63 63 63
uc kV 364 337 384 365
t2 µs 392 341 594 657
RRRV kV/µs 2,0 2,0 0,7 1,2
Outrush current peak I out kA - - 206,0 31,5
Outrush current frequency f out kHz - - 16,0 2,2
a 10 µH included to represent buswork
The presence of a capacitor bank results in an outrush current component added to the current
through the circuit breaker interrupting the fault. The outrush current may potentially result in
high frequency current zeros that the circuit breaker could interrupt before the next power
frequency current zero. To illustrate this concept a simulation is performed with a restrike at the
peak of the TRV with the circuit breaker interrupting at a high frequency current zero.
Figure 32 shows a plot of the current through the circuit breaker interrupting the fault with a
single capacitor bank without damping reactor. Figure 33 shows a plot of the transient recovery
voltage for the same case.
Damping reactors are often used to reduce the peak and frequency of inrush and outrush
currents from shunt capacitor banks especially where back-to-back switching may occur.
However, because of the lower frequency from the damping reactor the circuit breaker may be
able to interrupt the high frequency current more easily. Figure 34 shows a plot of the current
through the circuit breaker interrupting the fault with a single capacitor bank and a 1000 H
damping reactor. Figure 35 shows a plot of the transient recovery voltage for the same case.
Page 45
Influence of shunt capacitor banks on circuit breaker fault interrupting duties
Figure 32 - Trace of the current interrupted by the circuit breaker for the case with a
capacitor bank without damping reactor
Figure 33 - Trace of the transient recovery voltage across the circuit breaker for the
case with a capacitor bank without damping reactor
Page 46
Influence of shunt capacitor banks on circuit breaker fault interrupting duties
Figure 34 - Trace of the current interrupted by the circuit breaker for the case with a
capacitor bank and a 1000 H damping reactor
Figure 35 - Trace of the transient recovery voltage across the circuit breaker for the
case with a capacitor bank and a 1000 H damping reactor
3.2.4.3 362 kV
3.2.4.3.1 General
EMTP simulations were performed considering a 3-phase-to-earth fault and a single-phase-to-
earth fault. The simplified network is a typical 362 kV substation represented by a Thévenin
equivalent source. The substation has 4 overhead lines at 362 kV with a total load of 450 MW.
The substation has two shunt capacitor banks of 457 Mvar each. The capacitor banks are either
with solidly earthed neutral or isolated neutral.
Page 47
Influence of shunt capacitor banks on circuit breaker fault interrupting duties
0.5
overhead lines 248.90/_-4.9
+
R1
GND
PI
LF
3063 +
150MW
PI 30MVAR
3062 +
248.98/_-4.8
362_KV_Source
+ PI 248.73/_-5.0 LF
+
+ 150MW
30MVAR
PI
+
LF
150MW
CB_CAP1 30MVAR
+
+
1mH
C3
+
SW1
3484uS
+ +VM
GND
Bus_Bar
CB_CAP2
+
+
+
1mH C4
3484uS
GND
shunt capacitor banks
The capacitance value of the banks is 9,24 μF. The capacitor banks are connected via a
damping reactor of 1 mH.
Page 48
Influence of shunt capacitor banks on circuit breaker fault interrupting duties
Figure 37 – Two capacitor banks with isolated neutral – Restrike on phase B followed
by a restrike on phase A
Page 49
Influence of shunt capacitor banks on circuit breaker fault interrupting duties
The effect of adding two large shunt capacitor banks (2 457 Mvar) in the substation is twofold:
– The RRRV is greatly reduced (< 0,6 kV/µs for test-duty T100s);
– The peak value of the TRV is increased by roughly 50 %.
In the case of capacitor banks with isolated neutral, a restrike of the circuit breaker during
interruption of a T100s would not cause a high frequency outrush current. For the case of a
capacitor bank with solidly earthed neutral, a restrike during interruption of a single-phase or
multi-phase fault will automatically expose the circuit breaker to high frequency outrush
currents.
Page 50
Influence of shunt capacitor banks on circuit breaker fault interrupting duties
c) When the making occurs at voltage zero, the contribution from the system will be fault
current only. The current will be fully asymmetrical;
d) When the making occurs at voltage peak, the contribution of the fault current at the time the
outrush current reaches its first peak can be neglected and the most significant contribution
from the system will be the outrush current peak;
e) When the circuit breaker closes at a point-on-wave between those described in a) and b)
the contribution will be an outrush current superimposed on the fault current. The circuit
breaker needs to be able close into this combination of outrush and fault current.
Cases a), b) and c) are illustrated in Figure 38. The values of the first current peak are given in
Table 13.
300
Voltage (kV)
200
100
0
-100
-200
-300
0 4 8 12 16 20 24 28 32
Time (ms)
150
Current (kA)
100
50
0
-50
-100
-150
0 4 8 12 16 20 24 28 32
Time (ms)
Key
Red arrow Initiation of short-circuit at voltage peak
Green arrow Initiation of short-circuit at voltage zero
Blue arrow Initiation of short-circuit at 45
Figure 38 – Inrush current versus instant of fault initiation on first phase to close
Page 51
Influence of shunt capacitor banks on circuit breaker fault interrupting duties
45 28
Only dry-type reactors are used in these applications today. Such reactors have a low
inductance value and low stray capacitance values in the order of a few hundred pF. The TRVs
are fast rising with significant amplitudes.
The severity of the TRV is illustrated in the next example. A field test measurement has been
performed on a 120 kV, 96 Mvar capacitor bank with a 0,23 mH damping reactor in a substation
owned and operated by Hydro-Québec, Canada.
Page 52
Influence of shunt capacitor banks on circuit breaker fault interrupting duties
This case can be illustrated by considering an EMTP simulation done on a 66 kV, 50 Mvar
isolated neutral shunt capacitor bank with a 0,4 mH damping reactor. The TRV for a three-
phase earthed fault between the reactor and the capacitor bank is shown in Figure 41. The
effect of the reactor is very evident as is further shown in Figure 42.
Page 53
Influence of shunt capacitor banks on circuit breaker fault interrupting duties
Page 54
Influence of shunt capacitor banks on circuit breaker fault interrupting duties
Voltage (kV) 24
20
16
tT
12
u0
4
uL*
0
tdL
-4
tL
-8
-12
0 1 2 3 4 5
time (µs)
Figure 41Table 14 compares the line side TRV of a 90 % short-line fault with the values of initial
TRV illustrated in Figure 42.
Table 14 - Comparison of initial TRV values between SLF L90 and a fault involving
damping reactor for 145 kV, 40 kA breaker – HQ case
TRV parameters IEC L 90 40 kA 145 kV HQ case 120 kV, 40 kA, shunt capacitor
t d (µs) 2 0 (no delay)
t dL (µs) 0 0,23
Page 55
Influence of shunt capacitor banks on circuit breaker fault interrupting duties
Table 14 shows that the initial TRV of the reactor limited fault is more severe than the
prospective TRV of short-line fault test-duty L 90 . Mitigation means are required to lower the
initial TRV of the reactor limited fault, alternatively a circuit breaker with higher rated short-
circuit current may be used.
There are several means to reduce the TRVs associated with a reactor limited fault. Some of
these mitigation means are described in 7.1.1.
The results presented in Table 15 also apply to the case of a fault in the 72,5 kV system
described in 3.2.4.1 under same conditions, i.e. effectively earthed neutral source and single-
phase and three-phase to earth fault.
An oil circuit breaker will interrupt in one of the high frequency current zeroes. This will increase
the risk for high overvoltages.
Page 56
Influence of shunt capacitor banks on circuit breaker fault interrupting duties
Janssen and van der Sluis also noted that when the current peak and voltage were reduced to
50 %, the air-blast circuit breaker was capable of interrupting in one of the high frequency
current zeroes, causing an overvoltage of 3,9 p.u.
When the circuit breaker closes into a fault, the high frequency discharge current may cause
welding spots that change the smoothness of the contact surface. This changes the
restrike/re-ignition probability on the following breaking operation.
This phenomenon is recognised in Table 4 of IEEE C37.06, which contains inrush current data
for some vacuum circuit breakers. These inrush current data are generally lower than required
for other technologies (i.e. SF 6 circuit breakers).
The capability to interrupt in any of the high-frequency current zeroes is low for the modern
puffer circuit breakers and even lower for self-blast (or arc assisted) circuit breakers. This also
means that the risk for overvoltages is low.
Page 57
Influence of shunt capacitor banks on circuit breaker fault interrupting duties
The values used in combination with the puffer circuit breaker used in Figure 43 were: C = 14,4
µF, L add = 600 µH and R d = 15 .
Page 58
Influence of shunt capacitor banks on circuit breaker fault interrupting duties
In the solution presented by Mysore [9] the damping reactor has a surge capacitor and MOV in
parallel as illustrated in Figure 45. Application of a capacitor in parallel with a MOV will reduce
outrush current and TRV frequency.
In the solution used by Hydro-Québec the damping reactor is installed in the neutral of the
capacitor bank. A properly dimensioned MOV is installed in parallel with the damping reactor.
Using a MOV only will limit the outrush current.
The protective level of the MOV is selected in such a way that the residual voltage across the
breaking chamber does not exceed the tested values of TRV peak for terminal fault interruption.
The critical point regarding the selection of the proper MOV is the energy consumption of the
MOV. The MOV has to handle the energy that is stored in the capacitor bank. The highest
energy consumption will occur in the rare case of a re-ignition.
The case when MOVs are used for circuit breakers consisting of several series connected
breaking chambers deserves some extra attention. The worst case is that only one MOV has to
handle the whole energy consumption. The reasons are the unequal voltage distribution and
the mechanical time spread between the breaking chambers units during opening and closing
operation.
For the selection of the MOV in parallel with the breaking chamber the network parameters at
the point of application are important.
The load influences the energy consumption of the MOV. The ratio between network impedance
and load affect the transient overvoltage at re-ignition or restrike.
Page 59
Influence of shunt capacitor banks on circuit breaker fault interrupting duties
0,5 cycle of power frequency. The controller will cause additional delay in the time from impulse
to current extinction. The system has to be suited to accept this additional delay.
8 Recommendations
8.1 General
Analysis and laboratory tests have shown that a major influence of a shunt capacitor bank in a
substation is to modify the TRV for any circuit breaker clearing a fault when the capacitor bank
is on the source side of the circuit breaker. The modified TRV can theoretically result in high
re-ignition outrush currents and in some cases severe overvoltages.
Putting this in context of service experience, worldwide, the overall service experience of circuit
breakers spans over millions of circuit breaker years. Many circuit breaker are operating or
have operated in the vicinity of shunt capacitor banks with no known problems due to the
presence of the shunt capacitor. There have been some failures due to the presence of
“damping reactors” (associated with fast rising TRVs), but none known to be due to the “re-
ignition outrush” described in this brochure, or the modified TRV which the capacitor bank
causes.
Lacking any hard evidence pointing to the capacitor banks as a reason for circuit breaker failure
when clearing short-circuits, the working group does not suggest any mitigation for the re-
ignition outrush current or the modified TRV from capacitor banks.
The working group does not see a need to update/change the existing circuit breaker standards.
– Possible simulations to see the effect of the installation of the additional capacitor bank(s);
– Additional capacitor bank(s) affect the existing circuit breaker(s) because of back-to-back
capacitor bank switching. The suitability of the existing circuit breakers for this application
needs to be checked (e.g. replacing oil circuit breaker for SF 6 );
– There may be a need to replace circuit breakers that interrupt a fault in the substation where
the capacitor banks are on the source side of the circuit breaker. This will depend on the
capability of the circuit breaker. For example, the line circuit breaker may have a capability
exceeding the standard ratings;
– Space requirements for additional mitigation means (reactors, MOVs, etc.) based on the
results of the simulations;
– Circuit breaker design and characteristics need to be considered (i.e. capability of
interrupting in any of the high frequency current zeroes);
– Space requirements of a possible change of circuit breakers that interrupt a fault in the
substation where the capacitor banks are on the source side of the circuit breaker to a higher
voltage rating;
– If surge arresters are used, their location is important: the can be installed between circuit
breaker and reactor or between reactor and capacitor bank. The latter case will give rise to
TRVs with high frequency in case of failure of the surge arrester;
Page 60
Influence of shunt capacitor banks on circuit breaker fault interrupting duties
– Outrush current should be considered when capacitor banks are used without damping
reactors. An example is the use of controlled closing. Controlled closing will only affect
inrush current, outrush is not limited.
8.3 New installation
In a new installation that is going to include capacitor bank(s), the following may be analysed:
– Simulations that will result in the proper choice of circuit breaker(s) and mitigation means;
– Future expansion of the substation needs to be considered.
8.4 Simulations
The simulations that should be done should provide information about how the TRV waveshape
is modified by the presence of the capacitor bank for first, second and third pole-to-clear.
Furthermore, the simulation should provide information about the effect of the installation of a
capacitor bank including already installed reactors to see if there is a potential problem. Worst
case analysis with maximum outrush current (re-ignition at the peak of the modified TRV) should
be checked. Simulation should take account of the TRV capability of the circuit breaker.
Such tests would show the re-ignition behaviour as well as the capability of the circuit breaker
to interrupt at any of the high frequency current zeroes in case of a re-ignition. Such tests
depend to a high degree on the substation layout and a standard set of tests cannot be given.
8.7 Testing
Due to the large variety of the different installations no common values can be determined for
TRV waveshape and the high frequency current following a re-ignition. Therefore no specific
test requirements are provided.
The phenomena described depend to a high degree on the capability of the circuit breaker to
withstand the modified TRV peak and/or the capability to interrupt in any of the high frequency
current zeroes.
Withstanding a modified TRV can be checked in a laboratory and will show if additional
mitigation means are required. The TRV waveshape will be a two parameter TRV with a peak
of maximum 2 p.u. The frequency of the TRV depends on the circuit components (capacitance
of the capacitor bank, inductance of the busbar including damping reactor, grounding conditions
of the capacitor bank and source, etc.).
To verify the behaviour of the circuit breaker when interrupting the high frequency current
following a re-ignition, the circuit breaker should interrupt a short-circuit with a modified TRV
and when the circuit breaker re-ignites, the circuit should provide the correct high frequency
current. In other words: the verification is done in a circuit that reflects the actual situation in
that specific substation.
9 References
[1] IEC 62271-100: High-voltage switchgear and controlgear – part 100: Alternating current
circuit breakers
Page 61
Influence of shunt capacitor banks on circuit breaker fault interrupting duties
[2] IEEE C37.06: IEEE Standard for AC High-Voltage Circuit Breakers Rated on a
Symmetrical Current Basis – Preferred Ratings and Required Capabilities for Voltages
Above 1000 V
[4] IEEE C37.012: IEEE Guide for the Application of Capacitance Current Switching for AC
High-Voltage Circuit Breakers Above 1000 V
[6] L. van der Sluis and A.L-J. Janssen: Clearing faults near shunt capacitor banks, paper 90
WM 188-3 PWRD, PES Winter meeting 1990, IEEE Transactions on Power Delivery, Vol.
5, No. 3, July 1990
[7] A.L.J. Janssen and L. van der Sluis: Controlling the transient currents and overvoltages
after interruption of a fault near shunt capacitor banks, paper 13-13, CIGRE 1988 session,
Paris
[8] A. Sabot et al, “A unique multipurpose damping circuit for shunt capacitor bank switching”,
IEEE transactions on Power Delivery, Vol 8, No. 3, July 1993, pp. 1173 - 1183
[9] Pratap G. Mysore, Bruce A. Mork and Himanshu J. Bahirat: Improved Application of Surge
Capacitors for TRV Reduction When Clearing Capacitor Bank Faults, IEEE transactions
on power delivery, Vol. 25, No. 4, October 2010
[11] F. Martin and E. Joncquel, “Circuit breaker tripping near capacitor banks”, CIGRE paper
A3-203, 2006 session in Paris
[12] R. Thomas: Three Phase Controlled Fault Interruption Using High Voltage SF 6 Circuit
Breakers, thesis Chalmers University of Technology, Gothenburg, Sweden, ISBN 987-91-
7291-976-1
[13] IEEE C37.011, Application Guide for Transient Recovery Voltage for AC High-Voltage
Circuit Breakers
[14] E.W. Boehne, “The Determination of Circuit Recovery Rates”, AIEE Transactions, Volume
54, May 1935
[15] A. Greenwood, “Electrical Transients in Power Systems” (Book), John Wiley & Sons, 1971
[16] ANSI C37.06.1, Guide for High-Voltage Circuit Breakers Rated on Symmetrical Current
Basis Designated “Definite Purpose for Fast Transient Recovery Voltage Rise Times”
[18] D.F. Peelo, “Current Interruption Transients Calculation”. John Wiley & Sons Ltd., 2014
[21] F. Faria da Silva, Claus L. Bak and M. Lind Hansen: Back-to-back energization of a 60
kV cable network – Inrush current phenomenon. Proceedings of the Power and Energy
Society General Meeting 2010. (pp. 1-6) IEEE Press. 10.1109/PES.2010.5589314
Page 62
Influence of shunt capacitor banks on circuit breaker fault interrupting duties
Annex A
The size of series reactors in mH or depends on the rated voltage and the application. There
is no defined range for the three types of reactors mentioned here.
Reactor connected in series with shunt capacitors used for the following purposes:
Reactor connected in series in a power system to limit the current under system fault conditions.
Current limiting reactors may create similar fast TRVs as damping reactors.
Power flow control reactors match the impedance of different parts of an electrical system. Also
such reactors may create fast TRVs.
Page 63
Influence of shunt capacitor banks on circuit breaker fault interrupting duties
Annex B
With reference to Figure 4, L s , R and C form a series RLC circuit. Applying a voltage u to such
a circuit, the inrush current i i can be calculated in general as follows:
dii q
u Ri Ls
dt C
Differentiating and treating u as a step voltage, i.e. switching in at the instant of the voltage
peak:
d2ii R dii 1
ii 0 (B.1)
2 Ls dt LC
dt
Equation (B.1) is a second order linear homogenous differential equation with three possible
solutions depending on the degree of damping in the circuit. Taking = R/2L s and 0 1 Ls C ,
the three solutions are:
1. Overdamped 2 > 0 2
u
i(t ) e αt sinh α 2 ω0 2 t (B.2)
2
Ls α ω02
2. Critically damped 2 = 0 2
u αt
i( t ) te (B.3)
Ls
3. Underdamped 0 2 > 2
u
i(t ) e t sin 0 2 2 t (B.4)
2
Ls 0 2
Ls
Rcd 2 (B.5)
C
In most cases, the inrush current oscillation is underdamped and Equation (B.4) is of most
interest. If closing resistors are applied to limit the inrush current, then Equation (B.3) or (B.5)
may be applicable.
Page 64
Influence of shunt capacitor banks on circuit breaker fault interrupting duties
Annex C
Higher voltage and small back-to-back capacitor banks will naturally result in inrush frequencies
considerably higher than 4 250 Hz. This does not seem to be a problem as long as the peak
currents are kept below 25 kA (and a damping factor of about 0,85). Higher peak current may
be allowable if the circuit is highly damped or the duration of the inrush is very short.
The dissipated energy in the circuit breaker closing arc and not just peak current is the main
contributor to contact wear. A short current burst much higher than 25 kA can be withstood
without increasing contact wear as long as the integrated I t, during the closing arc time, is
less than the tested value.
Table C.1 contains some suggested inrush current limits for the different circuit breaker types.
Page 65
Influence of shunt capacitor banks on circuit breaker fault interrupting duties
In a capacitive discharge, there is a certain amount of energy available. Only a small portion of
that energy is causing contact erosion. The losses in the circuit in which the discharge takes
place are:
When the frequency is raised from the power frequency to higher values, the skin effect
becomes more and more dominant. The higher the frequency, the higher the ohmic losses in
the circuit. Therefore, higher frequencies would mean more damping and possibly lower contact
erosion. This effect may be overcompensated by the fact that a high frequency discharge will
occur during the time of the closing arc, while a low frequency discharge will partially occur
while the contacts are fully closed.
For an SF 6 circuit breaker subject to a direct discharge, most of the energy is dissipated in the
circuit resistance external to the circuit breaker arc.
Table C.2 lists the estimated apportionment of capacitive discharge energy for the tested SF 6
circuit breaker.
Table C.2 – Distribution of capacitive discharge energy for an SF6 circuit breaker
Page 66
Influence of shunt capacitor banks on circuit breaker fault interrupting duties
In the case of a real substation application, the external circuit resistance would be significantly
higher than a direct discharge test. In the 2 – 5 kHz range, the energy available for contact
erosion would be less than 1 % of the total dissipated capacitor energy.
Controlled closing or properly sized closing resistors can reduce the contact erosion energy by
a factor of 5 or more. Detailed transient studies are needed to determine the precise impact of
closing transient mitigation.
Page 67
Influence of shunt capacitor banks on circuit breaker fault interrupting duties
150
100
current (kA)
50
-50
0 1 2 3 4 5 6 7 8 9 10
4
10
3
int(I.t) (kA.s)
10
2
10
1
10
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
time (ms)
Figure C.2 shows the difference between the It integral of the rated back-to-back capacitor
bank making current with two different frequencies: the rated frequency of 4 250 Hz and
42 500 Hz
150
100
current (kA)
50
0
20 kApeak, 42500 Hz
-50
0 1 2 3 4 5 6 7 8 9 10
3
10 20 kApeak, 42 500 Hz
int(I.t) (kA.s)
2
10 20 kApeak, 4 250 Hz
Page 68
Influence of shunt capacitor banks on circuit breaker fault interrupting duties
It should be noted that while the IEC capacitor standard has a limitation on capacitor transient
current of 100 times the “rated” power frequency current, for the same duty, IEEE std 18 has a
limitation of 800 times the “rated” power frequency current for frequent operation and 1500
times ‘rated’ for rare events like outrush.
C.3 Recommendation
It is difficult to develop a generic recommendation on inrush capabilities even for non-oil circuit
breakers as each design will have differing geometries, contact sizes, pre-arcing times, etc. A
key factor is the accumulated current time product (I t) during the pre-arcing time over many
operations. The manufacturer should determine an appropriate I t limit (contact erosion limit)
which will not reduce the performance of the circuit breaker. Lacking inrush current data for
contact erosion, based on good experience and industry acceptance, a peak current limitation
in the standards of 25 kA, for inrush on SF 6 breakers is sufficient. A test frequency of about 5
kHz (somewhere between 2,5 and 10 kHz) is reasonable, as it will cause significant contact
erosion. But for SF 6 , and vacuum circuit breakers, there is no upper (or lower) limit for applied
circuit natural frequencies in service. Keeping inrush current magnitude the same, higher
frequencies might be expected to cause somewhat more contact erosion, since more of the
discharge occurs during the closing arcing time. This is a contact wear issue which is quite
different than a destructive shockwave issue.
Vacuum circuit breakers have concerns on contact welding during inrush events that may lead
to stress enhancement, and micro particle creation. Both of these can lead to increased
probability of restrike. These concerns require lower arcing energy limitations in order to keep
restrike probabilities from increasing. It has been found that a typical vacuum circuit breaker
can meet capacitance current switching class C2 if inrush current is kept below about 7 kA, and
class C1 if inrush is kept below 20 kA. This is based on typical CuCr contact materials, and
typical pre-arcing times. Different materials, contact structures and closing speeds will give
differing results. As with SF 6 , higher frequencies alone are not much concern.
Page 69
Influence of shunt capacitor banks on circuit breaker fault interrupting duties
Annex D
According to the general theory of capacitive current switching, the peak value I peak of the
inrush current of single capacitor bank i L (t) is limited by the characteristic impedance formed
by the source inductance L S and the capacitance of the capacitor bank C [3, 4]:
V0
Ipeak (D.1)
Ls / C
di V0
(D.2)
dt Ls
In Equations (D.1) and (D.2) V 0 is the peak value of the steady-state voltage on the substation
busbar after energising the bank [3, 4]:
2
V0 Vm (D.3)
2 2
In Equation (D.3)
The values of I peak and di / dt, as follows from Equations (D.1) and (D.2), are limited by the
source inductance L s . It is assumed that for the real-world systems, the inrush current of an
isolated neutral capacitor bank does not pose any problem neither to the capacitor switching
device nor to the capacitor bank.
The replacement of overhead lines with cables requires taking an additional component of the
capacitive inrush current into consideration. This component results from the traveling waves
in the alongside cables (see Figure D.1) [20].
Page 70
Influence of shunt capacitor banks on circuit breaker fault interrupting duties
V (t,0)
i( t ) Iin (t,0) iL (t )
I in (t,0) in
Zc
Key
Vm peak value of the voltage source i(t) inrush current of the capacitor bank
angular frequency of the voltage source propagation velocity of the traveling waves
along the cables
SW capacitor bank switching device, switching the V in ( t , 0) waveform of the initial voltage surge at the
bank at time instant t 0 source voltage end of a cable
C capacitance of the capacitor bank I in ( t , 0) waveform of the initial voltage surge at the
source voltage end of a cable
Zc surge impedance of an underground cable
After the instant t 0 , when the capacitor circuit breaker closes, energising the capacitor bank,
the voltage at the substation busbar collapses in a few microseconds. The rapid change of the
busbar voltage initiates the voltage surges V in (t, 0) traveling down the cables connected to the
same busbar (see Figure D.1).
These voltage surges generate current surges I in (t, 0) in the cables. Since the amplitudes of
the current traveling waves I in (t, 0) are limited by small surge impedance of the cables Z c , they
Page 71
Influence of shunt capacitor banks on circuit breaker fault interrupting duties
can reach significant values. This component of the inrush current is a sum of the current
traveling waves (see Figure D.1). The more cables are connected alongside the capacitor bank,
the higher the value of inrush current that should be expected.
The total inrush current i(t) can be determined as the sum of the current traveling waves in the
cables I in (t, 0) superimposed on the "inrush current of isolated neutral capacitor bank" i L (t).
Waveforms of the total inrush current i(t) and its component i L (t) flowing in the L s C circuit are
shown in Figure D.2. It can be seen that the inrush current due to the traveling waves in the
alongside cables is significantly higher than "the inrush current of isolated neutral capacitor
bank".
The inrush current due to traveling waves attains its peak value in few microseconds, when the
inrush component i L (t) is negligibly small. Due to attenuation of the traveling waves in the
cables, the current component resulting from the traveling waves significantly decays in 0,1-0,3
ms. When "the inrush current of isolated neutral capacitor bank" reaches its peak value, the
inrush component due to the traveling waves may be ignored.
Figure D.2 – Waveforms of the total inrush current and the inrush current through the
voltage source
The single-phase circuit shown in Figure D.3 can be used for analysis of the capacitor bank
inrush current. The inductance L s and resistance Rs represent the short-circuit impedance of
the voltage source, C is the capacitance of the switched utility capacitor bank, L is the equivalent
inductance between the capacitor bank and the substation busbars, Z cw is the equivalent surge
impedance of n underground cable, Z lw represents some equivalent surge impedance at the
termination of the cable at the remote end.
Page 72
Influence of shunt capacitor banks on circuit breaker fault interrupting duties
Figure D.3- Single-phase circuit for analysis of the capacitive inrush current
The maximum inrush current takes place if the SW closes the circuit at the time instant t = 0,
when waveform of the voltage source reaches its peak value V m .
The peak value of the inrush current due to the traveling waves occurs at the time instant, when
the "the inrush current of isolated neutral capacitor bank" is still very small. "The inrush current
of isolated neutral capacitor bank" attains its peak value, when the traveling waves in the
alongside cables have already attenuated (see Figure D.2). This is why we can determine each
component of the inrush current regardless from the other component using the equivalent
circuits shown in Figure D.4.
Ls Rs cable
Zcw
Zlw
L L
-V0 C C -Vm
a) b)
Figure D.4 -Circuits for analytical study of the inrush current. (a) Inrush current through
the voltage source. (b) Inrush current due to the traveling waves in the alongside cables
The component of the capacitive inrush current i L ( t ), generally referred to as the "inrush current
of isolated neutral capacitor bank", can be determined from the circuit in Figure 4a. The current
waveform is [18].
Page 73
Influence of shunt capacitor banks on circuit breaker fault interrupting duties
Rs
t
2( Ls L )
iL (t ) I peak e sin t (D.5)
If the inductance L is negligibly small in comparison to the inductance L s , the peak inrush current
I peak and its frequency β are obtained using Equation (D.1) and Equation (D.4) accordingly.
The component of the capacitive inrush current i w ( t ) that appears due to traveling waves in the
alongside cables can be determined from the circuit in Figure D.4.b.
Consider a general case, when n underground cables have different lengths. In this study, the
cable length is understood as a distance between the substation busbar and some junction
(terminal) that causes the reflection of the wave traveling along the cable. Assume that all the
cables have the same specific parameters. In that case, the equivalent cable surge impedance
Z cw is determined as follows
Zc 1 L0
Z cw (D.6)
n n C0
L0
where Z c
C0
Z c in Equation (D.6) is a cable surge impedance determined by the cable specific inductance
L 0 and capacitance C 0 .
The cable specific parameters seen by the traveling waves are similar to the parameters for
oscillatory transients with frequencies lying in the range of 20-100 kHz. Taking into account that
L 0 does not change greatly in that range, its value can be selected corresponding to the
frequency of 40 kHz.
The capacitor bank energisation results in appearance of the current waves traveling along the
cables with propagation velocity .
1
(D.7)
L0C0
The waves reflect at the terminations on the opposite ends of the cables. Since the cables have
different lengths, the reflected waves arrive to the capacitor bank busbar at different time
instances. The reflected waves reduce the inrush current. This is why the inrush current reaches
its maximum value until the reflected waves arrive at the substation busbar.
The capacitive inrush current i w ( t ) produced by the initial current waves in n alongside cables
can be derived from the circuit in Figure D.5. The circuit is obtained from Figure D.4b, while the
cable termination impedance Z lw is short-circuited.
Page 74
Influence of shunt capacitor banks on circuit breaker fault interrupting duties
Figure D.5 -Circuit for analytical study of the inrush current due to initial traveling
waves in the alongside cables
where
p 1 = - + , p 2 = - - D.9)
The expression of the inrush current waveform depends on the relationship between the
equivalent cable surge impedance Z cw and the characteristic impedance Z w of the circuit formed
by the capacitor bank inductance L and capacitance C:
L
Zw (D.11)
C
A value of the characteristic impedance Z w depends mainly on the size of inductance L. The
equivalent inductance L includes the inherent inductance of the capacitor bank, the inductance
of the connections between the bank and the substation busbar as well as the inductance of a
damping (current limiting) reactor. If the damping reactor is not installed, L includes only a stray
inductance that varies from 5 to 15 μH [3, 4]. Application of the damping reactor may increase
the inductance to hundreds/thousands of μH.
For real-world capacitor banks, if the damping reactor is not installed, the following relationship
takes place:
Z cw ≥ 2Z w (D.12)
Under condition (D.12), the capacitive inrush current i w (t) can be derived from Equations (D.8)
– (D.10) and expressed similar to Equation (D.5) [18]
For real-world capacitor banks with damping reactor installed alongside underground cables,
the relationship between impedances Z w and Z cw is
Page 75
Influence of shunt capacitor banks on circuit breaker fault interrupting duties
Z cw < 2Z w (D.14)
Under the condition given in Equation (D.14), the inrush current derived from Equations (D.8)
– (D.10), becomes oscillatory. Its waveform can be given by [18]
The time instant t m , when the inrush current waveform i W (t) reaches its peak value, can be
determined from the condition
diw (t )
0 (D.16)
dt
1
tm ln (D.17)
2
Substitution of Equation (D.17) into Equation (D.13) enables obtaining the peak value I peak of
current waveform i w (t) [18]
2I
Ipeak (D.18)
2
2
2 2
The inrush current reaches its peak value I peak at the time instant t = t m determined by Equation
(D.17). Since the waves travel along the cables with the propagation velocity v given by
Equation (D.7), the cables should be long enough so that at the time instant t = t m , no reflected
waves arrive at the capacitor bank termination.
Define the minimal length of cable l min as the shortest cable length among n cables that makes
it possible for the inrush current to reach its peak value I peak determined from Equation (D.18)
before the reflected wave in that shortest cable arrives at the substation busbar. The value of
l min is given by [18]
1 1 tm
lmin tm (D.19)
2 2 L0C0
If among n cables, length of the shortest cable l c is smaller than l min the inrush current attains
its peak value at the time instant t c , when the reflected wave in the shortest cable arrives at the
substation busbar:
2lc
tc (D.20)
The inrush current peak I peak is determined by substitution of t c into Equation (D.13)
The inrush current peak depends on the inductance L. If the value of L tends to zero, the
expression of I peak is as follows:
Page 76
Influence of shunt capacitor banks on circuit breaker fault interrupting duties
V
I peak n m (D.22)
Zc
For that limiting case, the peak inrush current is proportional to the product of the number of
underground cables n and the system voltage peak V m and inversely proportional to the cable
surge impedance Z c .
For a circuit where, due to application of the damping reactor with high value of L, the
characteristic impedance Z w obtained by Equation (D.11) is significantly larger than the
equivalent surge impedance of n cables Z cw (see Equation (D.6)), the inrush current peak is
limited only by the characteristic impedance Z w :
V
Ipeak m (D.23)
Zw
The rate of change of the inrush current can be obtained by differentiation of i W (t) (see Equation
(D.13)). The maximum rate of change is achieved at the time instant t = 0; its value is given by
[3, 4]
di Vm
(D.24)
dt L
The maximum rate of change of the inrush current (as it follows from Equation (D.24)) is limited
only by the equivalent inductance L. If L only includes the stray inductance, (damping reactor
is not applied) the value of di / dt can be extremely high.
The capacitive inrush current i W (t) that occurs due to the traveling waves is not oscillatory in
the usual frequency related sense, but the initial slope of its waveform can be used to determine
an equivalent frequency f eq , which can be compared with the rated inrush current frequency
defined in the circuit breaker standards [3, 4]:
di
dt 1 2 2
f eq 2 2
(D.25)
2I max 2
Some particular case, when n underground cables connected alongside the capacitor bank have
equal length, was considered in [18]. The equations for the capacitive inrush current due to
superposition of the initial current wave and three reflected current waves were derived.
According to the study performed in [18], the maximum value of the inrush current is always
achieved at the first peak of the current waveform due to the initial current waves in the
alongside cables. Its value is close to the inrush current peak I peak determined by Equation
(D.18), if the shortest cable is longer than l min (see Equation (D.19)). The following crest values
of the current waveform are smaller than the first peak because of the attenuation of the
traveling waves.
Page 77
Influence of shunt capacitor banks on circuit breaker fault interrupting duties
The utility is represented by the step-down transformer fed from an infinite busbar. The system
source strength at the utility busbar is 250 MVA, maximum system voltage – 24 kV, fundamental
frequency – 50 Hz. The study deals with switching 9 Mvar and 5 Mvar capacitor banks. The
capacitors are connected into Y or double Y with isolated neutral (see Figure D.6).
In order to verify the phenomenon of the capacitor bank switching back-to-back to underground
cables, field tests of switching the 9 Mvar, 24 kV capacitor bank were conducted. The tested
capacitor bank is installed at the secondary side of 45 MVA, 161/24 kV transformer alongside
eight underground cables used for power delivery to the loads in the distribution network.
Lengths of the underground cables vary from 1 km to 9 km. In addition to the 8 cables used for
power delivery, the outgoing cables also include two short cable sections (each one is shorter
than 30 m) connecting the earthing transformer and the auxiliary need transformer to the
busbar. The peak inrush current values measured during the tests attained 7,1-7,2 kA. The
measured values of di/dt reached 3300 kA/ms [18]. The above values significantly exceeded
the corresponding parameters of the "inrush current of isolated neutral capacitor bank" given
by Equation (D.1) and Equation (D.2): I peak = 1,6 kA, di / dt = 2,67 kA/ms.
The results of the field tests were compared with the simulations done using the
Electromagnetic Transient Program (EMTP). The waveform of the maximum phase inrush
current obtained in the simulations is shown in Figure D.7.
In the phase, where the voltage waveform of the voltage source reaches its peak value at the
instant of the CB closing, the inrush current peak is 6,4 kA, while its maximum rate of rise is
3600 kA/ms. These values are in good agreement with the results of the field tests. The inrush
current component that can be ascribed to the traveling waves significantly decays in 100-200
microseconds. After the wave attenuation, the waveform is close to the waveform of the "inrush
current of the isolated neutral capacitor bank" described by the general theory of capacitive
switching [3, 4].
Page 78
Influence of shunt capacitor banks on circuit breaker fault interrupting duties
The peak inrush current I peak and di / dt of i w (t) are determined using the above Equations. For
the considered network
Capacitor bank: C = 49,736 F; L = 5,2 H; Z w = 0,323 (see Equation (D.11)).
Underground cables: specific inductance at 40 kHz L 0 = 127,9 H/km; C 0 = 0,2506 F/km; for
8 cables Z cw = 2,824 (see Equation (D.6)); = 1,76610 5 km/sec (see Equation (D.7)).
Parameters for calculation of Ipeak : I = 6,915 kA; = 2,71510 5 ; = 2,64310 5 (see Equation
(D.10)); minimal length of cable l min = 0,72 km (see Equation (D.19)).
Capacitive inrush current i w (t) due to traveling waves in the alongside cables: I peak = 6,4 kA
(see Equation D.18); di / dt = 3654 kA/ms (see Equation (D.24)).
These values are in good agreement with the results of the field tests as well as with the results
of EMTP simulations.
The inrush current due to capacitor bank switching back-to-back to underground cables
depends on number n of underground cables, equivalent inductance L between the capacitor
bank and the substation busbar as well as on the length l c of the shortest cable.
The curves of I peak resulting from switching 5 Mvar and 9 Mvar capacitor banks versus n are
presented in Figure D.8. The curves are calculated for the following values of the equivalent
Page 79
Influence of shunt capacitor banks on circuit breaker fault interrupting duties
inductance between the capacitor bank and the substation busbar: L = 5H, L = 100 H and
L = 1000H.
Figure D.8 shows that if L = 5H (L includes only a stray inductance), the I peak is proportional
to n. The change of n from 2 to 12 results in the increase of Ipeak from 1,7 kA to 9 kA. The curve
corresponding to switching 9 Mvar capacitor bank (the solid curve) practically coincides with
the curve for switching 5 Mvar capacitor bank (the dotted curve). The independence of the
inrush current peak on the capacitance of the switched capacitor bank proves that the inrush
current is a sum of traveling waves in the alongside cables, which is proportional only to the
number of cables, as it follows from Equation (D.22)).
0
2 4 6 8 10 12
Figure D.8 - Inrush current peak versus the number of underground cables
Adding damping reactor in series with the capacitor bank reduces the dependence of the inrush
current peak on the number of cables. It is evident that if L = 1000 H (L includes a big current–
limiting reactor), the I peak is practically independent of n. In that case, the I peak is limited
primarily by the characteristic impedance Z w formed by L and the capacitance C of the switched
capacitor bank (see Equation (D.23)).
Applying a damping reactor to the capacitor bank results in reduction of the inrush current due
to the following reasons:
a) Enlargement of the equivalent inductance L reduces the inrush current peak I peak given by
Equation (D.18)) that is achieved at time instant t = t m (see Equation (D.17)). The curves of
I peak versus L corresponding to switching 5 - and 9 -Mvar capacitor banks back-to back to
eight underground cables are presented in Figure D.9.
Page 80
Influence of shunt capacitor banks on circuit breaker fault interrupting duties
Ipeak versus L
7
3
0 50 100 150 200 250
Figure D.9 – Curves of the inrush current peak versus equivalent inductance L
10
10
88
66
44
22
00
00 50
50 100
100 150
150 200
200 250
250
Equivalent bank inductance (µH)
Equivalent bank inductance [microhenry]
Figure D.10 – Curves of the minimal length of cable for the capacitor banks switched
back-to-back to eight cables
The increase of l min in relation to L shown in Figure D.10 can be explained by the drastic
reduction of the rate of change of the inrush current due to adding the damping reactor.
The inrush current due to switching the capacitor bank with damping reactor may reach its peak
value I peak given by Equation (D.18) only if the minimal length of cable l min exceeds a number
of km. For example, the inrush current due to switching the 9 - Mvar capacitor bank with
damping reactor of 100 μH back-to-back to 8 underground cables may reach its peak value only
Page 81
Influence of shunt capacitor banks on circuit breaker fault interrupting duties
if l min exceeds 6 km (see Figure D.10). For a typical substation, the average cable length
between the substation busbar and some junction, where the traveling wave is reflected, is
smaller than 5 km. This is why the inrush current of the capacitor bank with damping reactor
generally cannot reach its peak value given by Equation (D.18).
Since the required length of l min exceeds the existing lengths of the underground cables, the
inrush current peak should be calculated as a function of a length of a shortest cable l c given
by Equation (D.21). The curves of I peak versus L corresponding to switching 9 Mvar capacitor
bank back-to back to 8 underground cables at different lengths of the shortest cable l c are
presented in Figure D.11.
Ipeak versus L
7
Inrush current peak [kA, peak]
0
0 50 100 150 200 250
Figure D.11 shows that applying a damping reactor of 100-250 H to 24 kV capacitor bank
significantly reduces the inrush current peak, if the length of a shortest cable does not exceed
2 km.
The inrush current peak versus the length of a shortest cable l c for switching 9 Mvar capacitor
bank alongside eight cables is shown in Figure D.12.
0
0 0.4 0.8 1.2 1.6 2
Figure D.12 – Curves of I peak versus the length of the shortest cable
Page 82
Influence of shunt capacitor banks on circuit breaker fault interrupting duties
Figure D.12 shows that switching capacitor bank without damping reactor (L = 5 μH) back-to-
back to underground cables results in significant inrush currents even at short lengths of the
cables. Applying a damping reactor significantly reduces the inrush currents due to the traveling
waves in the alongside cables.
The study was done on a 66 kV system, where a cable was energised while other cables were
connected to the bus. In a worst case analysis the inrush current peak was in the order of 1750
A and the frequency in the order of 5 kHz. The authors concluded that the i max peak f inrush of
85 10 6 AHz is not exceeded and that a circuit breaker specified in accordance with IEC 62271-
100 would fulfil the requirements.
_____________
Page 83