0% found this document useful (0 votes)
642 views

IDM+ Techinical Information

The document provides technical specifications for the IDM+ device in a table format organized by category and parameter. It lists specifications for the processor, operating system, data storage, power supply, analog and digital inputs, alarm notifications, time synchronization, mechanical dimensions, communication ports, environmental tolerances, and EMC compliance standards. The device has 9 configurable analog channels, a 32-bit 400MHz processor, and measures voltage, current, power quality parameters, and temperature.

Uploaded by

Doan Anh Tuan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
642 views

IDM+ Techinical Information

The document provides technical specifications for the IDM+ device in a table format organized by category and parameter. It lists specifications for the processor, operating system, data storage, power supply, analog and digital inputs, alarm notifications, time synchronization, mechanical dimensions, communication ports, environmental tolerances, and EMC compliance standards. The device has 9 configurable analog channels, a 32-bit 400MHz processor, and measures voltage, current, power quality parameters, and temperature.

Uploaded by

Doan Anh Tuan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 8

Appendix A – Technical Specifications

Appendix A
Technical Specifications

158 www.qualitrolcorp.com
Appendix A – Technical Specifications

Appendix A – Technical Specifications


The following table lists the technical specifications for the IDM+ device.
Category Parameters Specifications
General Processor 32 bit, 400 MHz processor
9 configurable analog channels for IDM+ 3U device ,
9/18/27/36 configurable analog channels for IDM+ 6U
device.
Sampling rate 25.6 kHz at 50 Hz, 30.72 kHz at 60 Hz
Bandwidth 25 to 4600 Hz ± 0.5 dB
Operating System Monta Vista Linux with real time extensions
Status Indicators 9 LEDs (Healthy, Communication, clock sync, battery,
trigger, alarm and sensors (status))
Quality System Developed, designed, and manufactured according to
DN ISO 9001:2000.
Calibration Solid state design, no user adjustments.
Calibration check must be performed once in 5 years.
Data Storage Compact Flash for record storage 4 GB standard (8
GB/16 GB optional)
On-board Flash for firmware – 64 MB
A RAM based temporary file system is used to avoid
excessive Flash use avoiding Flash wear. The IDM+
firmware is designed to optimize the write operations
for every memory block.
Power Supply Input Range Type 1: 90 – 264 VAC (88-300 VDC), 47 –63 Hz
Type 2: 36 – 72 VDC
Maximum Load 40 VA for 3U IDM+ device and
80 VA for 6U IDM+ device
Typical Load
For 6U Device
110 VA (With UPS)
112 VA (With UPS)
Auxiliary Output DC output 12 VDC at 750 mA

159 www.qualitrolcorp.com
Appendix A – Technical Specifications

Category Parameters Specifications


Analog Inputs - Input Range Nominal (full scale) in VAC:
Voltage AC 63.5 (140)
120 (270)
240 (480)
440 (800)
Safety Rating 300 V CAT III, 150 V CAT IV
Maximum Overload 1000 VAC continuous
Input Option 1: Impedance: > 2.5 MΩ (at 63.5 V) ,> 2 MΩ (at 120 V) , >
TX_AFE 1 MΩ (at 240 V), > 0.1 MΩ (at 440 V)
16-bit resolution for voltage
Input Option 2: Impedance: > 4MΩ
HIA-AFE 24-bit resolution for voltage/current channels:
Accuracy ≤ 0.1°

Optional for The transient voltage (up to 6 kV) is detected by the TR


HIA-AFE: module with a bandwidth of 2.5 kHz to 5 MHz.
Fast Transient Sampling rates (user configurable):
Recording 20 MHz, 10 MHz, 5 MHz, 2.5 MHz, 1.25 MHz
12-bit resolution

Analog Inputs - Input Range Full scale in VDC: 12, 120, 240, 480
Voltage DC
(optional Safety Rating 300 V CAT III, 150 V CAT IV
instead of AC)
Maximum Overload 500 VDC continuous
Input Impedance >= 420 KΩ - (TX-AFE and HIA-AFE)

Analog Inputs – Input Range Nominal (full scale) in AAC: 1 (10), 2 (20), 5 (50), 10
Current (100)
Maximum Overload 200 A for 1 second, 40 A continuous
Input Impedance < 0.02 Ω
20-bit resolution for current
(To achieve a 20-bit resolution on a current channel,
two 16-bit A/D converters are used with different gain
factors to provide an effective 20-bit resolution.)
. Digital Inputs 32 (isolated into groups of 8)
Voltage range independent from 24/48 to 250 VDC

160 www.qualitrolcorp.com
Appendix A – Technical Specifications

Category Parameters Specifications


Alarm Notification 4 form A/B relay outputs (configurable - normally closed
or normally open at factory)
Relay 1 indicates system Healthy.
Relay 2, 3 are user configurable for PQ parameters.
Relay 4 is user configurable for either temperature
under/over temperature threshold.
Resistive load: 250 VAC 5 A, 110 VDC 0.5 A, 48 VDC
1.0 A
Options Time GPS (accuracy ± 300 ns between time masters)
Synchronization IRIG-B modulated and level shift (accuracy ± 2 ms
between time masters)
Time slave (synchronized through 1 PPS)
Mechanical Dimensions H x W x D: 132.5 mm 487 mm x 362.2 mm for IDM+ 3U
device
H x W x D: 265.8 mm 487 mm x 362.2 mm for IDM+ 6U
device
Weight 15 kg without battery and 15.5 kg with battery for IDM+
3U device
23 kg without any external battery and 4 kg with two
external batteries for IDM+ 6U device
Housing/Mounting Metal 19” rack mounted cabinet

Communication Ports Four Serial (of these, three are RS232 ports with male
DB-9 connectors, and one is RS485 with 1*5 pin
connector.)
Internal PSTN (V.90) modem (optional on RS232-2)
Two 100 Mb Ethernet ports with RJ45 connectors
Optional Fiber optic Ethernet (on rear port)
Differential (RS485 levels) for 1 PPS for time
synchronization
Fiber optic 1 PPS output (master)/input (slave)
Protocols TCP/IP, Modbus, IEC 60870-5, IEC 61850, GSM,
GPRS

Standard IEC 61000-4-30 Class A


Compliance IEC 61000-4-7 harmonics and inter-harmonics
IEC 61000-4-15 flicker
CBEMA, ITIC
IEEE 1159, IEEE 519

161 www.qualitrolcorp.com
Appendix A – Technical Specifications

Category Parameters Specifications


Environmental Temperature Operating: -5°C to 50°C (23°F to 122°F)
Cold start is not possible below 0°C (32°F)
Storage: -30°C to +70°C (-22°F to +158°F)
Humidity 0 to 95% non-condensing
Enclosure IP 40 according to IEC 60529

Others RoHS compliant

EMC Standards

Standards References/Test criteria


IEC 60255-22-6 / IEC 61000-4-6 Tested to IEC 61000-4-6, Tested for 10 V, 150 kHz –
Conducted Susceptibility (CS) 80 MHz
Tested on Power-line, RS232 -1, Ethernet port 1,
Analog inputs (V & I), Digital Inputs, and Relay Outputs.
Passed with : Criteria A

IEC 60255-22-4 / IEC 61000-4-4 & Tested to IEC 61000-4-4, Tested for : 4 kV,
ANSI C37.90.1.2002 Electrical fast 5KHz/100KHz/2.5KHz
transient burst test Tested on Power-line, RS232-1, Ethernet port 1, Analog
inputs (V & I), Digital Inputs, Relay outputs.
Passed with : Criteria A

IEC 60255-22-3 / IEC 61000-4-3 Tested to IEC 61000-4-3, Tested for 10 V/m, 80 MHz –
Radiated Susceptibility (RS) 1000 MHz
Tested on Complete Device
Passed with : Criteria A
EN 55011 Conducted Emission (CE) Tested to CISPR-11 Tested for 79 dB (µV) quasi-peak
and 66 dB (µV) average at 0.15 MHz to 0.5 MHz
73 dB (µV) quasi-peak and 60 dB (µV) average at 0.50
MHz to 5 MHz
73 dB (µV) quasi-peak and 60 dB (µV) average at 0.50
MHz to 30 MHz
Tested on : Complete Device
Passed & the Emission levels are within the Specified
limits of CISPR 11

162 www.qualitrolcorp.com
Appendix A – Technical Specifications

Standards References/Test criteria


EN 55011 Radiated Emission (CE) Tested to CISPR-11 Tested for 40 dB (µV/m) quasi-
peak from 30 MHz to 230 MHz
at 10 m (32.8 ft)
47 dB (µV/m) quasi-peak from 230 MHz to 1000 MHz at
10 m (32.8 ft)
Tested on : Complete Device
Passed & the Emission levels are within the Specified
limits of CISPR 11
IEC 61000-4-8 Power frequency Tested to IEC 61000-4-8 ,Tested for 30 A/m, x, y, z
magnetic field test axis
Tested on : Complete Device
Passed with : Criteria A
IEC 60255-22-1 / IEC 61000-4-12 & Tested to IEC 61000-4-12 ,Tested for 2.5 kV Common
ANSI C37.90.1.2002 Damped Mode, 1 kV Differential Mode, 1MHz
oscillatory wave disturbance tests Tested on : Power-line, Digital, Analog inputs( V ),
Relay
Passed with : Criteria A
IEC 61000-4-12 Ring wave test Tested to IEC 61000-4-12, Tested for Level 3,+/- 2 kV
Common Mode, 1 kV Differential Mode, 100 KHz
Tested on Power-line, Digital, Analog inputs (V), Relay
Passed with : Criteria A
IEC 61000-4-5 Surge test Tested to IEC 61000-4-5 ,Tested for Class 4, I/O 4 KV
Common Mode, 2 KV Differential Mode
Tested on Power-line, Digital, Analog inputs (V), Relay
Passed with : Criteria A

ENV 50204 Immunity to EMI from Tested to ENV 50204, Tested for level 3, 10 V/m, @900
digital radio telephones MHz +/- 5 MHz, @1890 MHz +/- 10 MHz keyed at
frequency 200 Hz +/- 1%, 50% duty cycle [2.5 ms ON
2.5 ms OFF].
Tested on Complete Device
Passed with : Criteria A
IEC 60255-5 Clause 6 Dielectric test Tested to 2.5 kV for 1 minute, Tested for 2.5 kV for
ANSI IEEE C37.90 – 1989 SWC Power-port, Analog inputs (V & I), Digital inputs, Relay,
dielectric tests and 1 kV for isolated communication ports (RS232 &
RS485).
No flashover or breakdown occurred.

163 www.qualitrolcorp.com
Appendix A – Technical Specifications

Standards References/Test criteria


IEC 60255-5 Clause 7 Insulation test Tested to applied 500 VDC with respect to Earth.
Tested on Power port, Analog inputs (V & I), Digital
inputs & Relay.
The impedance was greater than 100Mohms.

IEC 60255-5 Clause 8 Impulse voltage Tested to +/-5 kV, 0.5 J.


test Tested on: Power-line, digital, Analog inputs (V & I) &
Relay.
No flashover or breakdown occurred.
IEC 61000-4-11 Supply Voltage Dips Tested to Dips-Class-3,Interruptions-Class-3
and Interruptions Tested on Power-port.
Passed with : Dips - Criteria A
Interruptions - Criteria B
IEC 60255-22-2 / IEC 61000-4-2 Tested to IEC 61000-4-2,Tested for : 8 kV contact, 15
Electro static discharge tests kV air
Tested on Enclosure, all accessible I/O lines and ports.
Passed with : Criteria A
IEC 60255-6/EN60255-6 Supply Tested for PSU Tested for DC range 80 VDC to
voltage limit test 300VDC

IEC 60068-2-1/EN60068-2-1 Cold Tested for Cold Storage -45˚C (49˚F) for 96 hours
tests Cold Operating: -5˚C (23˚F) for 16 hours
Tested on Complete Device
IEC 60068-2-6 Vibration tests Tested for 2g Acceleration, Frequency is 10- 150 HZ, 20
sweep cycles in each of three mutually perpendicular
planes (x, y, and z).
Tested on Complete Device
IEC 60068-2 Cyclic Temperature Test Tested for Cyclic Temperature test for 5 cycles. Each
cycle has 3 hours for 70 degrees & 3 hours for -5
degree in Power off Condition
Tested on Complete Device

164 www.qualitrolcorp.com
Appendix A – Technical Specifications

IEC 61000-4-30 Class A


The following table summarizes the IDM+ accuracy and range specification of IEC 61000-4-
30 Class A parameters. The IDM+ is specified for Udin = 230V, 50/60 Hz.
Parameter Accuracy Measuring Accuracy
Specified over Range
Range
Frequency 42.5 Hz ~ 57.5 42.5 Hz ~ 57.5 +/- 0.01 Hz of injected
Hz, Hz,
51 Hz ~ 69 Hz 51 Hz ~ 69 Hz
Voltage RMS 10%~150% of 10%~200% Udin +/- 0.1% of Udin
Udin.
Flicker short term 0.2~10.0 Pst 0~20 Pst 5% of Measured Value / applied
(10 min)-Pst input
Supply Voltage Dips N/A N/A ±0.2% of Udin.
and Swells
Voltage interruptions N/A N/A ±0.2% of Udin.

Voltage Unbalance 1 – 5% 0 – 100% If unbalance is in the range 1 to


5% = +/-0.15%

Harmonics (up to 10% to 200% of 200% of Class 3 Um >= 1% Unom Æ 5% of Um


50th order) Class 3 IEC of IEC 61000-2- Um < 1% Unom Æ .05% Unom
61000-2-4 4 ( Max allowed THD = 20% )
Interharmonics (up to 10% to 200% of 200% of Class 3 Um >= 1% Unom Æ 5% of Um
50th order) Class 3 IEC of IEC 61000-2-4 Um < 1% Unom Æ0.05% Unom
61000-2-4 ( Max allowed THD = 20% )

Signaling Voltages 0% to 15% of 0% ~ 15% Udin 1% and 3% of UdinÆ ±0.15% of


Udin [below 3 Udin
kHz] 3% and 15% of UdinÆ ±5 % of
the measured value

Supply Voltage Under 10% ~ 150% of N/A +/- 0.1% of Udin


and Over deviation Udin.

Note Udin = Nominal voltage


Um = Measured Voltage
Unom = Nominal voltage

165 www.qualitrolcorp.com