Sealed lead-acid battery
Model: EP 7,2 - 12 EP Series
EP type batteries are made in AGM technology and are constructed by plates, separators, safety
valves and a container. Since the electrolyte is held by a glass-mat separator and plates, the
batteries can be used in any chosen position without the risk of leakage. EP type batteries have a
pressure relief valves that allows safe dispersal of any excess pressure inside the cell (VRLA). Due
to advantages as sealed construction, maintenance free, low internal resistance and long term
storage, EP batteries are the base of the emergency power supplying.
TECHNICAL DATA APPLICATIONS
Nominal voltage 12 V uninterruptible power supplies solar powered systems
Nominal capacity 7,2 Ah / C20 (UPS) medical equipment
Cell per unit 6 emergency lighting systems mobile and portable equipment –
telecommunication PABX cycle use
Technology AGM
cash registers and fiscal printers measuring devices
6~9 years @ 20oC* fire and security systems
Design life o
5 years @ 25 C
height 98,0 mm
Dimensions length 151,0 mm DIMENSIONS
width 65,0 mm
Weight ~2,54 kg mm(inch)
20h 0,360A @1,75V/cell 7,20 Ah
Capacity 10h 0,684A @1,75V/cell 6,84 Ah
43±1 (1.69±0.04)
o
@ 25 C 5h 1,220A @1,75V/cell 6,10 Ah
1h 4,720A @1,60V/cell 4,72 Ah
o o
Ambient nominal charge 0 C ~ 40 C
temperature discharge o
-20 C ~ 50 C
o
range
storage o
-20 C ~ 40 C
o
Internal resistance @ fully charge battery £25 mW 151±1.5 (5.95±0.06) 65±1.5 (2.56±0.06)
13,5V to 13,8V 13.5±1 (0.53±0.04) 7.5±1 (0.29±0.04)
standby use o
Charging voltage (-18 mV/ C)
o
@ 20 C 14,4 V to 15,0V
98±2 (3.86±0.08)
93±1.5 (3.66±0.06)
cycle use o
(-24 mV/ C)
recommended 0,72 A
Charging current
maximum 2,16 A
Maximum discharge current (for 5 sec) 108,0 A
Capacity retention after 1 month 97 %
o
during storage @ 20 C after 6 months 80 %
(self discharge) after 12 months 63 %
standard ABS UL 94-HB
Container material
optional ABS UL 94-V0**
Terminal faston F1,F2 T1,T2
TERMINALS
Terminal hardware initial torque - mm(inch)
T1 3.2(0.126)
T2 3.4(0.134)
*) - According to Eurobat (General Purpose group) **) - Flame-retardant
4.75(0.187)
6.35(0.25)
NO TRANSPORT RESTRICTED
Not restricted for air, surface and water transport. Classified as non-
0.8(0.031)
0.8(0.031)
hazardous material (IATA/ICAO Special Provision A67, DOT-CFR Title 49 6.35(0.25) 7.85(0.309)
parts 171-189, IMDG amendment 27)
DISCHARGE CHARACTERISTICS
o o
• Constant current (Current [A], 25[ C] / 77[ F]) Discharge time
F.V.
V/cell 5 min 10 min 15 min 30 min 50 min 1hr 2hr 4hr 6hr 8hr 10hr
1,80 23,50 16,90 13,40 7,740 5,110 4,400 2,400 1,410 1,040 0,812 0,674
1,75 27,60 18,30 14,00 8,040 5,270 4,540 2,460 1,430 1,060 0,824 0,684
1,70 29,40 18,90 14,40 8,220 5,380 4,620 2,490 1,440 1,060 0,829 0,687
1,65 30,07 19,40 14,70 8,340 5,440 4,670 2,520 1,450 1,070 0,831 0,689
1,60 31,70 19,80 15,00 8,420 5,500 4,720 2,540 1,460 1,070 0,832 0,689
1,50 32,93 20,14 15,30 8,500 5,545 4,757 2,554 1,460 1,066 0,830 0,688
o o
• Constant power (Power [W/cell], 25[ C] / 77[ F]) Discharge time
F.V.
V/cell 5 min 10 min 15 min 30 min 50 min 1hr 2hr 4hr 6hr 8hr 10hr
1,80 43,3 31,9 25,6 15,2 10,1 8,7 4,8 2,8 2,1 1,6 1,3
1,75 50,2 34,7 26,8 15,8 10,4 9,0 4,9 2,9 2,1 1,7 1,4
1,70 53,3 35,8 27,6 16,2 10,7 9,2 5,0 2,9 2,1 1,7 1,4
1,65 55,8 36,7 28,2 16,4 10,8 9,3 5,0 2,9 2,1 1,7 1,4
1,60 57,7 37,5 28,8 16,6 10,9 9,4 5,1 2,9 2,1 1,7 1,4
1,50 59,7 38,3 29,4 16,8 11,0 9,5 5,2 3,0 2,2 1,7 1,4
F.V. - Final voltage
www.europower.eu EP
EP 7,2 - 12
Battery life characteristics of standby use Battery life characteristics of cycle use
10
8 Temperature:
o o
25[ C] / 77[ F]
Charging voltage: 120
6 2.275 V/cell
5
4 100
Retention Capacity [%]
Life Expectancy [year]
3
80
2
60
100[%] 80[%] 50[%] 30[%]
Depth of discharge D.O.D D.O.D D.O.D
40
1
20
0.5 0
o
20 30 40 50 [ C] 0 200 400 600 800 1000 1200
o
68 86 104 122 [ F]
Numbers of cycles
Battery Temperature
Battery discharge characteristics Battery self discharge characteristics
100
13.0
Temperature:
o o
25[ C] / 77[ F]
12.0
80
Capacity Retention Ratio [%]
11.0 o o
5[ C]/41[ F]
Terminal Voltage [V]
1.22[A] 0.68[A] 0.36[A]
10.0 1.8[A]
60
4.32[A]
9.0
40[oC]/104[oF] 30[oC]/86[oF] 20[oC]/68[oF]
8.0
40
21.6[A] 14.4[A] 7.2[A]
7.0
1 2 3 5 10 20 30 60 2 3 5 10 20 30
0 2 4 6 8 10 12 14 16 18 20
[min] [hr] Storage time [months]
Discharge time
Battery charging characteristics for the standby use Battery charging characteristics for the cycle use
0.21 15.0 140 0.21 15.0 Charge voltage
140
0.18 14.0 Charge voltage 120 0.18 14.0 120
lume
Charge vo
lume
0.15 13.0 Charge vo 100 0.15 13.0 100
Charge current [CxA]
Charge current [CxA]
Charge volume [%]
Charge voltage [V]
Charge volume [%]
Charge voltage [V]
0.12 12.0 80 0.12 12.0 80
Discharge Discharge
100% (0.05C[A] x 20[h]) 100% (0.05C[A] x 20[h])
0.09 11.0 50% (0.05C[A] x 10[h]) 60 0.09 11.0 50% (0.05C[A] x 10[h]) 60
Charging Charging
constant voltage: 2.275[V/cell] constant voltage: 2.45[V/cell]
constant current: 0.1C[A] constant current: 0.1C[A]
0.06 10.0 40 0.06 10.0 Temperature: 20[oC](68[oF])
40
Temperature: 20[oC](68[oF])
0.03 20 0.03 20
Charge current Charge current
0 0 0 0 0 0
0 5 10 15 20 25 0 5 10 15 20 25
Charge time [hr] Charge time [hr]
Battery discharge current and final discharge voltage
Discharge
current
[A]
1.44 > I 1.44 £ I < 3.6 3.6 £ I < 7.2 7.2 £ I
Final discharge
voltage 1.75 1.70 1.55 1.30 Pb
[V/cell]
*) C - Capacity
Date of issue: 24.06.2006; change number: 6; date of change: 24.09.2014
www.europower.eu EP