0% found this document useful (0 votes)
93 views

MJB 355 MB 4: 4 Poles 50 Hz-1500 Min / 60 Hz-1800 Min

This document provides specifications for a three-phase synchronous generator with the following key details: - It is a 50/60 Hz, 380-480V generator with an output of 800kVA at 0.8 power factor. - The generator has 4 poles, Class H insulation, and is rated for continuous duty operation at an ambient temperature of 40°C. - Additional technical details are provided on efficiency, reactances, time constants, mechanical characteristics, standards, and typical efficiency curves.

Uploaded by

Rafael Lopez
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
93 views

MJB 355 MB 4: 4 Poles 50 Hz-1500 Min / 60 Hz-1800 Min

This document provides specifications for a three-phase synchronous generator with the following key details: - It is a 50/60 Hz, 380-480V generator with an output of 800kVA at 0.8 power factor. - The generator has 4 poles, Class H insulation, and is rated for continuous duty operation at an ambient temperature of 40°C. - Additional technical details are provided on efficiency, reactances, time constants, mechanical characteristics, standards, and typical efficiency curves.

Uploaded by

Rafael Lopez
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

THREE-PHASE SYNCHRONOUS GENERATOR

MJB 355 MB 4
4 POLES
-1 -1
CONTINUOUS DUTY 50 Hz-1500 min / 60 Hz-1800 min
AMBIENT TEMPERATURE 40°C WINDING DATA
TEMPERATURE RISE H Winding code 17
INSULATION CLASS H Number of leads 6
POWER FACTOR 0,8 Winding pitch 2/3

FREQUENCY Hz 50 60
VOLTAGE Star V 380 400 415 416 440 460 480
Delta 220 230 240 240 254 265 277
kVA 800 800 800 880 920 950 960
RATING
kW 640 640 640 704 736 760 768
4/4 94,9 95,0 95,1 95,2 95,2 95,2 95,3
EFFICIENCY (%) @ 0,8 p.f. 3/4 95,4 95,5 95,6 95,5 95,6 95,6 95,7
2/4 95,7 95,6 95,6 95,6 95,7 95,8 95,8
4/4 96,0 96,1 96,1 96,2 96,2 96,2 96,3
EFFICIENCY (%) @ 1,0 p.f. 3/4 96,4 96,4 96,5 96,4 96,5 96,6 96,6
2/4 96,6 96,6 96,6 96,5 96,6 96,7 96,7
SHORT CIRCUIT RATIO 0,38 0,42 0,45 0,34 0,37 0,39 0,42
REACTANCES (%)
Direct axis synchronous xd 285 255 240 310 290 275 255
Quadrature axis synchronous xq 155 140 130 170 155 150 140
Direct axis transient x'd 23,0 20,8 19,3 25,4 23,7 22,4 20,8
Direct axis subtransient x"d 11,0 9,9 9,2 12,1 11,3 10,7 9,9
Quadrature axis subtransient x"q 13,6 12,3 11,4 15,0 14,0 13,3 12,3
Negative sequence x2 12,3 11,1 10,3 13,5 12,7 12,0 11,1
Zero sequence x0 3,1 2,8 2,6 3,4 3,2 3,0 2,8

TIME CONSTANTS [s]


Open circuit (T'do) 2,2 Subtransient (T''d) 0,016
Transient (T'd) 0,18 Armature (Ta) 0,026

MECHANICAL CHARACTERISTICS
D-end bearing/Lubrication 6322 C3 / With grease nipple
N-end bearing/Lubrication 6317 2Z C3 / Prelubricated
Weight (IM B34) [kg] 2050
2
Inertia (J) (IM B34) [kgm ] 13,12
Overspeed [min-1] 2250
Method of cooling IC 01
Cooling air required [m3/s] @ 50/60 Hz 0,93 / 1,12
Degree of protection IP 23
Type of construction available B2 - SAE / IM B34
Direction of rotation CW

OTHER DATA
Phase resistance mΩ @ 20 °C - Star series 3,1
Overloads 10% for 1 hour
3-phase short circuit current >= 300% (3 In)
Voltage regulation accuracy +/- 0,5% (in steady state condition, speed
from -2% to +5%, p.f. from 0,8 to 1)
Radio interference EN 55011 Class B Group 1
Wave form THF <2%
Total harmonic content <2% (at no load)

STANDARDS
IEC 60034-1; CEI 2-3; BS 4999-5000; VDE 0530; NF 51-100,111; OVE M-10, NEMA MG 1.22.

Data and Technical Specification are subject to change in order to update or improve the products, without prior notice

SIN.DT.025.7 1/4
THREE-PHASE SYNCHRONOUS GENERATOR

MJB 355 MB 4
-1
Typical efficiency curves 50 Hz - 1500 min

380 V 98
Efficiency [%]

96 1,0 p.f.

0,8 p.f.
94

92
0 0,25 0,5 0,75 1 1,25
Load [p.u.]

400 V 98
Efficiency [%]

96 1,0 p.f.

0,8 p.f.
94

92
0 0,25 0,5 0,75 1 1,25
Load [p.u.]

415 V
98
Efficiency [%]

96 1,0 p.f.

0,8 p.f.

94

92
0 0,25 0,5 0,75 1 1,25
Load [p.u.]

Data and Technical Specification are subject to change in order to update or improve the products, without prior notice

SIN.DT.025.7 2/4
THREE-PHASE SYNCHRONOUS GENERATOR

MJB 355 MB 4
-1
Typical efficiency curves 60 Hz - 1800 min

416 V 98
Efficiency [%]

1,0 p.f.
96

0,8 p.f.
94

92
0 0,25 0,5 0,75 1 1,25
Load [p.u.]

440 V 98
Efficiency [%]

1,0 p.f.
96
0,8 p.f.
94

92
0 0,25 0,5 0,75 1 1,25
Load [p.u.]

460 V
98
Efficiency [%]

1,0 p.f.
96
0,8 p.f.
94

92
0 0,25 0,5 0,75 1 1,25
Load [p.u.]

480 V 98
Efficiency [%]

1,0 p.f.
96
0,8 p.f.
94

92
0 0,25 0,5 0,75 1 1,25
Load [p.u.]

Data and Technical Specification are subject to change in order to update or improve the products, without prior notice

SIN.DT.025.7 3/4
THREE-PHASE SYNCHRONOUS GENERATOR

MJB 355 MB 4

Locked rotor motor starting curves (*)


-1
50 Hz - 1500 min
40

30
Voltage Dip (%)

380 V
400 V
20 415 V

10

0
0 500 1000 1500 2000 2500
∆P [kVA]

-1
60 Hz - 1800 min
50

40

416 V
Voltage Dip (%)

30
440 V
460 V
480 V
20

10

0
0 500 1000 1500 2000 2500
∆P [kVA]

∆ P = Pn x (Is / In) / (cosϕn x ηn)

(*): A coefficient of 0,85 must be applied to the voltage dip if the load has a power factor equal or greater than 0,8.

Data and Technical Specification are subject to change in order to update or improve the products, without prior notice

SIN.DT.025.7 4/4