Site Acceptance Test Report For 11Kv Cable: Project Equipment Client Date Contractor Location Testing Company

This report summarizes the site acceptance test results for a 11kV cable installed at the Qasr Al Jurf Development project. Key details include: 1) Visual, insulation resistance, capacitance and very low frequency hipot tests were performed on a 1620m long 3Cx300mm2 copper cable. 2) All test results including insulation resistance, capacitance and leakage current measurements were found to be within acceptable limits. 3) The cable successfully passed a 13.5kV RMS very low frequency hipot test over 30 minutes with no issues detected.

Uploaded by

Gajendran Sriram
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
601 views3 pages

Site Acceptance Test Report For 11Kv Cable: Project Equipment Client Date Contractor Location Testing Company

This report summarizes the site acceptance test results for a 11kV cable installed at the Qasr Al Jurf Development project. Key details include: 1) Visual, insulation resistance, capacitance and very low frequency hipot tests were performed on a 1620m long 3Cx300mm2 copper cable. 2) All test results including insulation resistance, capacitance and leakage current measurements were found to be within acceptable limits. 3) The cable successfully passed a 13.5kV RMS very low frequency hipot test over 30 minutes with no issues detected.

Uploaded by

Gajendran Sriram
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 3

SITE ACCEPTANCE TEST REPORT FOR 11kV CABLE

QASR AL JURF DEVELOPMENT


PROJECT EQUIPMENT 11kV CABLE
INFRASTRUCTURE-ENABLING WORKS
CLIENT ADDC/IMKAN DATE 02.06.2020
CONTRACTOR ENVICON EMIRATES LOCATION JRP31-JOINT 2
TESTING COMPANY XOLINE PAGE Page 1 of 3

VLF HIGH VOLTAGE TEST REPORT FOR11kV CABLE


1. CABLE PARAMETERS:

CABLE MANUFACTURER ELSEWEDY CABLES


CABLE TYPE / SIZE CU/XLPE/STA/PVC& 3C×300 SQMM
CABLE FROM JRP31-JOINT 2
CABLE TO JRPSWS1/K10 -JOINT 2
APPROXIMATE CABLE LENGTH
1620Mtr
(METERS)

2. VISUAL CHECKS:

Sl. No. Description Remarks


1 Physical Condition of the cable OK
2 Cable Earthing connection checks OK
3 Labels / Markings correctness checks OK
4 Cables installed as per the Approved drawings OK

3. PHASE IDENTIFICATION (CONTINUITY) OF CABLE CORES:

Phases R-phase Y-phase B-phase Remarks

Results OK OK OK OK

4. INSULATION RESISTANCE TEST:


TESTED BY CONTRACTOR WITNESS/APPROVED BY
COMPANY XOLINE ENVICON ADDC
NAME GAJENDRAN K

SIGNATURE

DATE 02.06.2020
SITE ACCEPTANCE TEST REPORT FOR 11kV CABLE
QASR AL JURF DEVELOPMENT
PROJECT EQUIPMENT 11kV CABLE
INFRASTRUCTURE-ENABLING WORKS
CLIENT ADDC/IMKAN DATE 02.06.2020
CONTRACTOR ENVICON EMIRATES LOCATION JRP31-JOINT 2
TESTING COMPANY XOLINE PAGE Page 2 of 3

Ambient Temperature:39.5°C Relative Humidity: 46%

Insulation Resistance Value


Ref. Applied Voltage Duration
Before HV test After HV test
R – (Y+B+E) 59.3 GΩ 25.5 GΩ
Y – (B+R+E) 5000 V DC 60 sec 64.0 GΩ 19.19 GΩ
B – (R+Y+E) 77.2 GΩ 10.37 GΩ

5. CAPACITANCE MEASUREMENT:( Measured by VLF HV test kit )

Phases R-phase Y-phase B-phase Remarks


Capacitance Value
769 769 766 OK
(ηF)

6. VLF TEST:

Ref. Applied Duratio Freq. Leakage Current ( mA)

TESTED BY CONTRACTOR WITNESS/APPROVED BY


COMPANY XOLINE ENVICON ADDC
NAME GAJENDRAN K

SIGNATURE

DATE 02.06.2020
SITE ACCEPTANCE TEST REPORT FOR 11kV CABLE
QASR AL JURF DEVELOPMENT
PROJECT EQUIPMENT 11kV CABLE
INFRASTRUCTURE-ENABLING WORKS
CLIENT ADDC/IMKAN DATE 02.06.2020
CONTRACTOR ENVICON EMIRATES LOCATION JRP31-JOINT 2
TESTING COMPANY XOLINE PAGE Page 3 of 3

Voltage n 1 min 5 min 10 min 15 min 30 min

R-(Y+B+E) 6.53 6.53 6.53 6.53 6.53


13.5
Y-(B+R+E) 30 min 0.1 Hz 6.52 6.52 6.52 6.52 6.52
kV RMS
B-(R+Y+E) 6.50 6.50 6.50 6.50 6.50

7. FORMULA USED:
Applied RMS Voltage = 3U0 / √2kV
Where U0 = 11/√3 = 6.35kV
Applied RMS Voltage =( 3x6.35)/ √2
= 13.5 kV RMS
8. EQUIPMENT DETAILS:

Calibration
Sl.No Instrument Name Make / Model Serial No
Valid
1 IR Tester Megger / MIT515 101574096 18.03.2021

2 HV Test Kit HV Diagnostics / HVA60 GH520416B018 18.08.2020

3 Digital Multimeter Fluke / 87V 32560364 22.02.2021

TESTED BY CONTRACTOR WITNESS/APPROVED BY


COMPANY XOLINE ENVICON ADDC
NAME GAJENDRAN K

SIGNATURE

DATE 02.06.2020