Earth Fault Relay IM30-B00 Guide

This document summarizes the features of an earth fault relay with three-level earth fault protection and selectable double setting programs. The relay provides time-tagged event recording, programmable output relays, blocking outputs and inputs for coordination, and breaker failure protection. It uses the Modbus communication protocol and is UL/CSA listed. Key features include three-level earth fault protection, selectable 1A or 5A rating, third harmonic filtering, and two remotely selectable setting programs.

Uploaded by

shekooferiahi
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
149 views2 pages

Earth Fault Relay IM30-B00 Guide

This document summarizes the features of an earth fault relay with three-level earth fault protection and selectable double setting programs. The relay provides time-tagged event recording, programmable output relays, blocking outputs and inputs for coordination, and breaker failure protection. It uses the Modbus communication protocol and is UL/CSA listed. Key features include three-level earth fault protection, selectable 1A or 5A rating, third harmonic filtering, and two remotely selectable setting programs.

Uploaded by

shekooferiahi
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

EARTH FAULT RELAY - DUAL SETTING

50N/51N, 51BF, 68
IM30-B00 m Three Earth-Fault levels.
m Selectable double setting program.
Io>

PROG/
I.R.F.
Io>>

B.I.
Io>>> Ch Sett

BRKR. FUNC.
FAIL. DIS.

m Time tagged event recording. IA 500A


m User programmable ouput relays.
N49 -R0 m Blocking Outputs and Blocking Inputs for pilot
wire selectivity coordination.
M-LINE MODE SELECT +

m Breaker Failure protection. RELAY TYPE


IM30-B00
_

m Modbus Communication Protocol. PROG.

m UL / CSA listed.

M
ENTER/RESET

SERIE

Earth fault relay with programmable Time Current Curves suitable for protection of HV & MV,
Transmission and Distribution systems.

Selectable 1 or 5 A rating.

3rd harmonic active filter on the neutral current.

Two complete setting programs remotely selectable via digital input or via serial port

¤ Real Time Measurements = HI - LI


¤ Maximum Demand and Inrush Recording = HI - LI
Programmable Input Quantities
¤ Fn = System frequency : (50 - 60) Hz
¤ HI = Rated primary current of the CTs supplying terminals 29-28(30) : (1 - 9999)A, step 1A
¤ LI = Rated primary current of the CTs supplying terminals 32-31(33) : (1 - 9999)A, step 1A
Connection Diagram

IM30-B00

AUXILIARY
}
SUPPLY
C US LISTED
19CN MS-SCE1693-R0
RINA IND.CONT.EQ. Standard Output

1/2
IM30-B00 M N49-R0'

1 - F50N/51N (1I): First Earth Fault Element


¤ Current setting range : 1I = (0.01 - 2)LI, step 0.01LI
¤ Instantaneous output : £ 0.04s
¤ Definite trip time delay in the mode (D)
(10x[1I] in inverse time operation modes) : t1I = (0.05 - 30)s, step 0.01s
¤ Time current curves F(1I) : Indepedent Definite Time (D), IEC (A / B / C), IEEE (MI / VI / I / EI / SI)

2 - F50N/51N (2I): Second Earth Fault Element


¤ Current setting range : 2I = (0.01 - 2)LI, step 0.01LI
¤ Instantaneous element : £ 0.04s
¤ Independent time delay : t2I = (0.05 - 3)s, step 0.01s

3 - F50N/51N (3I): Third Earth Fault Element


¤ Current setting range : 3I = (0.5 - 10)HI, step 0.1HI
¤ Instantaneous output : £ 0.04s
¤ Independent time delay : t3I = (0.02 - 3)s, step 0.01s

Breaker Failure Element


¤ Trip time delay : tBF = (0.05 - 0.75)s, step 0.01s

2/2