SSVT–350 Station Service VT 69000 Volt
Outdoor 69kV, 350kV BIL, Power Winding, Single & Dual Ratios (w/ Tertiary)
Oil-Filled, Wound Type, Control Power/Metering/Relaying March 2008
application
The SSVT-350 outdoor station service voltage transformer is
rated for use on 69,000 volt systems with 350kV BIL. The unit
is a station service voltage transformer with power and can be
supplied with metering rated secondary winding(s). It provides
a convenient and cost effective means of serving small power
and/or metering requirements directly from a transmission line.
Standard 125/250V nominal power winding designs are available
with thermal ratings of 10, 25, 50, 100 kVA and higher. Primary
voltage measurement ratios are available from 300:1 to 600:1 for
use on 69,000 volt systems, at 60 Hertz (Hz). This oil-filled sta-
tion service voltage transformer will provide control power and
can provide high accuracy for metering or relay applications.
mechanical description
The tank and expansion chambers are steel plate, pressure and
vacuum tight and hermetically sealed at the factory to prevent
breathing and oil contamination. Expansion chambers allow for
the expansion/contraction of oil for temperature and load fluctua-
tions. Tank components are washed and coated with anticorro-
sive iron phosphate and then finished with ANSI 70 Gray baked-
on electrostatic polyester powder. The primary bushing is ANSI
70 Gray, high strength porcelain with a high degree of stability for
transportation and seismic withstand. The primary terminal is a
stainless steel, NEMA 4-hole pad. The secondary station service
power terminals are 1”-14 externally mounted studs housed in an
ANSI 4X low voltage terminal box separate from metering with a
removable plate and 6” x 20” opening in the bottom for conduit
entry. They are offered with high conductivity, tin plated alumi- mounting
num, 2-hole set screw connectors suitable for 1/0 to 750MCM The SSVT is designed for mounting on substations structures in
conductors terminals. The neutral, tank ground connector ac- an upright position with four mounting holes in the base.
cepts 1/0 to 750 MCM conductors. The secondary metering ter-
minals are ¼”-20 copper studs with associated hardware located testing
inside a removable terminal box with three (3) 1 ½” NPT conduit The unit is individually tested per the IEEE C57.13 standard, in-
hubs. The ground terminal is a stainless steel NEMA 2-hole pad. cluding applied and induced voltage, accuracy and polarity. Addi-
The unit is fitted with a 5kV H0 Bushing, pressure relief valve, oil tional tests include dissipation and partial discharge tests. Partial
level gauge, ¾” oil fill plug, and ¾” drain valve. discharge testing is performed to guarantee the unit is free of
partial discharge through 135% of the nominal system voltage.
accuracy performance
The SSVT-350 will operate with nominal 125/250V control power options
output and if specified, a 0.15 Class metering accuracy for bur- The SSVT is available with an Extra Creep Bushing, Polymer
dens of 0, W, X, M, Y, Z and ZZ (0.3 ZZ for 10kVA size power Bushing, Stainless Steel Tank and/or Dome, one or two second-
units). The transformer is accurate from 90% to 110% of rated ary metering windings, one or two CTs, de-energized taps and/or
primary voltage. Unique to the SSVT design is the ability to pow- -50°C oil. Other secondary terminal connectors include Clamp
er motor loads of up to 10% of the transformer kVA rating and Type for up to 1000MCM or NEMA 4-hole Pads. Contact factory
metering/relaying simultaneously. for other needs.
ORDERING INFO FOR SSVT-350
kVA Primary Secondary Volts Catalog Number Metering
Rating Voltage Power° Metering w/o Metering w/ Metering* Accuracy/Burden
10 40250 125/250 115/67.08 J97N323010A J97M323010A 0.3 0,W,X,Y,Z,ZZ
25 40250 125/250 115/67.08 J99N323025B J99M323025B 0.15 0,W,X,Y,Z,ZZ
50 40250 125/250 115/67.08 J99N323050B J99M323050B 0.15 0,W,X,Y,Z,ZZ
100 40250 125/250 115/67.08 J99N328100B J99M328100B 0.15 0,W,X,Y,Z,ZZ
*For two metering secondaries, change M to D in catalog no.
°Nominal output. Actual rated output is supplied on unit nameplate.
- Overvoltage Ratings: 1.1x cont., 1.73x 1 min.
11
Dry type: 3022 NC 43 North • Pinetops, NC 27864 • Phone: +1 252 827-3212 • www.abb.com/mediumvoltage
Oil type: 101 Kuhlman Blvd • Versailles, Kentucky 40383 • Phone: +1 859 879-2999 • www.abb.com/highvoltage
69000 Volt SSVT–350 Station Service VT
March 2008
NOTE: OUTLINES ARE FOR REFERENCE ONLY. CONTACT FACTORY FOR ACTUAL DESIGN DRAWINGS.
12
Dry type: 3022 NC 43 North • Pinetops, NC 27864 • Phone: +1 252 827-3212 • www.abb.com/mediumvoltage
Oil type: 101 Kuhlman Blvd • Versailles, Kentucky 40383 • Phone: +1 859 879-2999 • www.abb.com/highvoltage