W-1-Day-2-A - Modelling of Wind Farms in Load Flow

The document outlines the modeling of wind farms in load flow studies as part of the USAID Sustainable Energy for Pakistan project. It provides specific data on the required transformers, collector cables, and wind turbine specifications necessary for a 50 MW wind farm. Key parameters include transformer sizes, reactance values, and cable specifications for efficient energy transmission.

Uploaded by

KASHIF
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
194 views4 pages

W-1-Day-2-A - Modelling of Wind Farms in Load Flow

The document outlines the modeling of wind farms in load flow studies as part of the USAID Sustainable Energy for Pakistan project. It provides specific data on the required transformers, collector cables, and wind turbine specifications necessary for a 50 MW wind farm. Key parameters include transformer sizes, reactance values, and cable specifications for efficient energy transmission.

Uploaded by

KASHIF
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

“TRAINING ON ELECTRICAL POWER

SYSTEM STUDIES USING PSS/E”

MODELLING OF WIND FARMS IN LOAD


FLOW BASIC COURSE (WEEK 1 DAY 2-A)

USAID’s SUSTAINABLE ENERGY FOR


PAKISTAN (SEP) PROJECT
Wind Form Layout
Data of Load Flow Case
• Farm Substation
➢ Number of Transformers, their Size and Reactance
➢ For a 50 MW Wind Farm we require: 2 x 40 MVA , 12.5 %
Reactance at own MVA Base
➢ Reactive Power Compensation
• Collector Cables
➢ Number of Collector Groups
➢ kV Level = 20 to 33 kV
➢ Aluminum or Copper, Single Core, directly buried
➢ Line parameters, R, X and B, PU at 100 MVA Base for Aluminum
Cable
Length, kM R+ X+ B+
1 0.025225 0.02458302 2.92954E-05
Data of Load Flow Case
• Wind Turbine Step-Up Transformer data
➢ WTG terminal voltage, LV: 0.6 to 0.69 kV

➢ Reactance of Transformer MV/LV: 6 % = 0.06 PU at own MVA Base

➢ MVA rating to be equal or a bit higher than WTG rated MVA


• Wind Turbine
➢ Rated MW at full speed

➢ Rated MVA and or PF

➢ Reactance = 0.8 PU at own base for GE DFIG WTGs