ID 985 LX HG - Hot Gas ENG 4-05
ID 985 LX HG - Hot Gas ENG 4-05
PROGRAMMING MENU
LEDS (See Programming Menu Diagram)
1) Displaying level 1 parameters
Position Associated function Status To access the Programming menu, hold
the “set” button for more than 5 seconds.
If specified, the level 1 access PASSWORD
ECO/ Set point/Reduced set point ON for parameter programming level 2
blinking when reduced set point is entered
will be requested (see parameter “PA1”)
(set point (ON for setting set point) and (if the password is correct) the label
of the first folder will appear. If the pass-
Compressor or relay 1 ON for compressor on; blinking
for protection delay or enabling blocked
word is incorrect, the display will show the
PA1 label again. Use the “UP” and
Defrost ON when defrosting in progress; blinking when activated “DOWN” buttons to scroll through the
manually or by digital input other folders; the folders will only dis-
Alarm ON for active alarm; blinking for silenced alarm play level 1 parameters.
NOTE: at this point level 2 parameters
Fans ON when fan is on are NOT visible even if NOT password-
aux aux ON when auxiliary output is operating protected.
2) Displaying level 2 parameters
o decimal point ON when instrument is on stand-by Go to the “CnF” folder in the
Programming Menu and scroll down the
parameters until you reach the PA2 label. USING THE COPY CARD ADVANCED FUNCTIONS
By pressing and releasing the “set” button The Copy Card is an accessory connected DOOR SWITCH INPUT
you will enter the level 2 parameters and to the TTL serial port used for quick pro- This is a clean contact digital input with
the label of the first folder in the pro- gramming of the unit parameters (upload programmable polarity. The door switch
gramming menu will appear. and download parameter map to one or input functions are controlled by the val-
Level 2 parameters can be protected by a more units of the same type). Operations ues of the following parameters:
second password (see “PA2” parameter in are described below:
the “diS” folder, which is different from Fr-Format (level 2 parameter) Par Description
the PA2 label in the “CnF” folder). If speci- This command can be used to format the dOd Digital input switches off loads
fied, level 2 parameters are not visible to copy card. This operation must be per- dAd D.I. activation delay
OAO Alarm signal delay after dis-
the user. To access the “CnF” folder, users formed when it is used for the first time E nabling the digital input
will have to insert the level 2 access PASS- or used with models that are not compati- (door closed)
WORD. If the correct password is entered, ble. tdO Time out door open. Time out
signalled when D.I is enabled
the label of the first folder in the pro- Warning: When the copy card has been (door open)
gramming menu displays. programmed, all the data entered is can- dOA Forced behaviour from digital input
NOTE: At this point the folders will celled when the “Fr” parameter is used.
PEA Enables forced behaviour from door
only display all the level 2 This operation cannot be undone. switch and/or external alarm
parameters.Therefore level 1 parameters UL-Upload dCO Delay in enabling compressor with
will only be visible if you quit the This operation unloads the programming consensus
dFO Delay in enabling fans with consensus
Programming Menu and repeat procedure parameters from the instrument.
H11 Digital output configurability/polarity 1
1). dL-Download H21...H25 Digital output configurability 1...5
To open the folder, press “set”. The label This operation downloads the program-
of the first visible parameter will appear. ming parameters to the instrument.
To scroll through the other parameters, NOTE:
If activation state forcing is enabled (dOA
use the “UP” and “DOWN” buttons. To • UPLOAD: instrument —> Copy Card
is not 0), the compressor and/or fan out-
change the parameter, press and release • DOWNLOAD: Copy Card —> instr.
puts can be activated when the time set in
“set”, then set the desired value using the These operations can be performed by
parameters dCO and dFO expires.
“UP” and “DOWN” buttons and confirm accessing the folder with the “FPr” label
with the “set” button. Move on to the next and selecting the “UL”, “dL” or “Fr” com- Parameter H11 is used to configure the
parameter. mands. The operation is confirmed when digital input with values between -9 and
PLEASE NOTE: We strongly recommend you press the “set” button. If the opera- +9. Positive and negative values are used
that you switch the device off and on tion is successful, a “y” is displayed where- to select the polarity assigned to the input
again after changing the configuration of as if it is unsuccessful an “n” will be dis- and:
parameters to prevent configuration prob- played. NOTE: the sign “-” indicates that the
lems and/or ongoing timings. Download “from reset” input is activated when the contact is
Connect the copy card with the instrument closed.
PASSWORD OFF. Programming parameters are down- The ‘+’ sign indicates that the input is
Passwords “PA1” and “PA2” allow level 1 loaded when the device is switched on. At activated when the contact is open
and level 2 parameters to be accessed. the end of the lamp test, the following
There are no passwords in the standard messages are displayed for about 5 sec-
configuration. To enable them (value ≠0) onds: LINK (for /CK models only)
and assign them the desired value, access • Label dLY if copy operation is successful The Link function is used to connect up to
the Programming menu in the “diS” folder. • Label DLn if operation fails 8 instruments (1 Master device and 7 slave
If passwords are enabled, they will be PLEASE NOTE: and echo devices). The distance between
requested: • After the parameters have been down- one device and another must be 7 metres
- Use PA1 to open the Programming menu loaded, the device uses the downloaded maximum whereas the maximum distance
(see the “Programming Menu“ section); parameter map settings. between the first and last instrument in the
- Use PA2 in the “Cnf” folder containing network must be approximately 50m.
the level 1 parameters. DISTANCE-MANAGED SYSTEMS PLEASE NOTE: the serial link between the
The Televis remote control systems can be devices is powered.
ACTIVATING MANUAL DEFROST CYCLE connected using the TTL serial port (the Master
To activate the defrost cycle manually, TTL- RS 485 BUS ADAPTER 130 interface Instrument that controls the networks and
press the “UP” button (if configured =1) module must be used). sends commands to the Slaves. The Master
for 5 seconds. To configure the instrument to do this, is selected using parameter L00 (the value 0
If the right defrosting conditions are not you need to access the “Add” folder and defines the Master)
present (the temperature of the evapora- use the “dEA” and “FAA” parameters. Slave
tor probe is higher than the end of defrost Instrument(s) supplied with own controls
temperature, for example) or parameter KEYBOARD LOCKED that also perform(s) commands issued by
OdO≠0, the display will flash three (3) Keyboard operating can be locked by pro- the Master (with parameters L00..L07).
times to indicate that the operation will gramming the “Loc” parameter (see folder Echo
not be performed. with “diS” table). Instrument(s) that only display(s) the values
If the keyboard is locked you can access of the instrument that it is associated with
the Programming Menu by pressing the (it does not therefore have its own I/O
“set” button. The Set point can also be dis- resources but only serves as a repeater).
played. PLEASE NOTE: only one Echo can be con-
nected to the same instrument (Master or
Slave; if it is connected to a Slave, you must
set parameter L04=n).
DEFROST R1=OFF
A B DEFROST R1=ON
On
On
R1 R1
Off
Off
dEt
dEt
ndE
ndE
R2 R2
FdC PdC
FdC PdC
R4 dt R4 dt
Fdt Fdt
R3 R3
Table of faulty probes of alarm does not affect the regulating in pressor, defrost and fan controllers are
progress. deactivated according to the value of the
DISPLAY FAULT Alarms are considered as absolute rLO parameter):
E1 Faulty probe 1 (thermostat control) (default) values or as values related to the
Value Description
E2 Faulty probe 2 (evaporator) Faulty Set point (the distance from the Set point
E3 probe 3 (display) 0 no resources are disabled
itself) and based on the Att parameter. If 1 disables compressor and defrosting
If simultaneous, they will be shown on the display the alarms are relative (Att=1), the para- 2 disables compressor, defrosting and fans
alternately every 2 seconds meter HA1 is set to positive values and
LA1 to negative values.
This alarm condition can be viewed in the This alarm condition can be displayed in
An error condition in probe 1 (thermostat folder “AL” with labels “AH1-AL1”. the “AL” folder using the “EA” label. The
control) causes the following: relay can be silenced; even if the alarm
• E1 code appears on display ALARM WITH THRESHOLD (PROBE 3) icon starts blinking, the controllers remain
• Compressor is activated as indicated by By setting the PbA=3 parameter an alarm locked until the next time the digital input
“Ont” and “Oft” parameters if these are is associated to probe 3. It refers to a spe- is deactivated.
programmed for duty cycle or: The error cific threshold (defined by the SA3 para-
condition for probe 2 (evaporator) causes meter). An over-temperature or an under- OPEN DOOR ALARM
the following: temperature alarm is generated and the If a door is open, the Open Door alarm is
icon is turned on. This alarm condition can signalled in response to a delay defined by
Ont Oft Compressor output
be viewed in the “AL” folder with the the tdO parameter.
0 0 OFF
0 >0 OFF
labels “AH3-AL3”. The alarm is signalled by the flashing alarm
>0 0 ON The alarm is handled as a temperature icon.
>0 >0 dc alarm for probe 3: for delays and back- This alarm condition can be viewed in the
swings, refer to standard alarms “AL” folder with the label “Opd”.
DEFROST ALARM NOTE: Do not set parameter tAo to
• E2 code appears on display If the defrost stops due to a timeout zero when the door is closed since if
• End of defrost due to time-out The error (instead of being stopped by the detection the door is continually opened and
condition for probe 3 (display) causes the of the end defrost temperature), an alarm closed, any alarms would never be sig-
following: is generated and the icon lights up. nalled.
• E3 appears on the display. Other alarms This condition can be viewed in the “AL” LINK ALARM
signals do not appear directly on the dis- folder with the label “Ad2”. If there is a master/slave/echo communi-
play of the device, but can be viewed by Automatic back swinging occurs when the cation failure, the No Link alarm is sig-
selecting the “Machine Status” menu in next defrost starts. nalled. This alarm condition can be viewed
the “AL” folder. The minimum and maxi- By pressing any button during the alarm in the “AL” folder with the label “E7”.
mum temperature alarm refers to the condition, the signal light disappears. In NOTE:
temperature control probe (probe 1) order to cancel the alarm properly, you •The E7 error is signalled after approx. 20
and/or the display probe (probe 3). must wait until the next defrost. seconds in “no link” condition to avoid any
Temperature limits are defined by parame- link disturbance causing communication
ters “HAL” (maximum alarm), “LAL” (mini- EXTERNAL ALARM errors.
mum alarm) and PbA (configuration of The device can also control an external •The E7 error is also signalled for address-
alarm on probe 1,3 or both). alarm, i.e. from a digital input. If the digital ing conflicts when:
MAXIMUM AND MINIMUM TEMPERA- input is enabled, the alarm control is acti- a) the number of Slaves set on the MAS-
TURE ALARM vated by programming and remains TER is different from the actual number of
If an alarm condition occurs and alarm enabled until the next time the digital Slaves on the network
exclusion times are not running (see alarm input is deactivated. When an alarm is set b) 2 or more Slaves have the same
exclusion parameters), the alarm icon off, the alarm icon lights up permanently, address.
lights up permanently and the relay con- a buzzer (if present) and the relay config-
figured as an alarm is activated. This type ured as alarm are activated and the com-
HSE Higher SEt. Maximum possible set point value. LSE..302 50.0 18 1 °C/°F
LSE Lower SEt. Minimum possible set point value. -55.0...HSE -50.0 -22 1 °C/°F
OSP Offset SetPoint. Temperature value to be added algebraically to the set point if reduced -30.0...30.0 0 -10 2 °C/°F
set enabled (Economy function). It can be enabled using a specially configured button.
Cit Compressor min on time. Minimum compressor activation time before disabling. If set at 0...250 0 0 2 min
0 it is not active.
CAt Compressor mAx on time. Maximum compressor activation time before disabling. If set at 0...250 0 0 2 min
0 it is not active.
COMPRESSOR PROTECTIONS (folder with “CP” label)
Ont On time (compressor). Compressor activation time in the event of a faulty probe. If set to 0...250 0 10 1 min
“1” with Oft at “0” the controller is always on whereas if Oft >0 it operates in duty cycle
mode. See Duty Cycle diagram
OFt OFF time (compressor). Compressor in disabled state time in the event of a faulty probe. 0...250 1 5 1 min
If set to “1” with Oft at “0” the controller is always off whereas if Oft >0 it operates in
duty cycle mode. See Duty Cycle diagram
dOn delay (at) On compressor. Delay in activating compressor relay after switch-on of instrument. 0...250 0 0 1 sec
dOF delay (after power) OFF. Delay after switch off; the indicated time must elapse between 0...250 0 0 1 min
switch-off of the compressor relay and the subsequent switch-on.
dbi delay between power-on. Delay between switch-ons; the indicated time must elapse 0...250 0 1 1 min
between two subsequent switch-ons of the compressor.
OdO (!) delay Output (from power) On. Delay time in activating outputs after the start of the 0...250 0 1 1 min
device or after a power failure. 0= not active.
DEFROSTING CONTROLLER (folder with “dEF” label) (6)
dty defrost type. Type of defrost. 0/1/2/3 0 (std. 0 (std. 1 num
0 = electrical defrosting; model) model)
1 = cycle reversing defrosting (hot gas); 3 (/HG 3 (/HG
2 = Free mode defrosting (compressor disabled). model) model)
3 = Hot gas defrost (hot gas)
dit defrost interval time. Period of time between the start of two defrost operations. 0...250 6h 0 1 hours/min/sec
0= function disabled (defrost is NEVER performed) (see dt1)
dt1 defrost time 1. Unit of measurement for defrost times (“dit” parameter). 0/1/2 0 0 2 num
0 = “dit” parameter expressed in hours.
1 = “dit” parameter expressed in minutes.
2 = “dit” parameter expressed in seconds.
dt2 defrost time 2. Unit of measurement for duration of defrosting (“dEt” parameter). 0/1/2 1 1 2 num
0 = “dEt” parameter expressed in hours.
1 = “dEt” parameter expressed in minutes.
2 = “dEt” parameter expressed in seconds.
dCt defrost Counting type. Selection of defrosting time count mode. 0/1/2/3 1 3 1 num
0 = compressor operating hours (DIGIFROST® method); Defrosting active ONLY with (0=df,
compressor on. digifrost
NOTE: compressor time of operation is counted irrespective of evaporator probe (count- 1=rt, real
ing is active if evaporator probe is absent or faulty). The value is ignored if RTC is time, 2=SC,
enabled. stop com-
1 = Real Time - equipment operating hours; defrost counting is always active when the pressor
machine is on and starts at each power-on. 3=RTC)
2 = compressor stop. Every time the compressor stops, a defrost cycle is performed
according to the parameter dtY
3= With RTC. Defrost at times set by dE1…dE8, F1…F8
“dd” (1) dE1…dE8 parameters daily defrost start time 1…8. Range 0…23, 24= off (default) 0...23/0...59 24 24 1 hours/min
“Fd” (1) F1…F8 festive defrost start time 1…8. Range 0…23, 24= off (default) 0...23/0...59 24 24 1 hours/min
The d1…d8, F1…F8 parameters are only visible if dit=0, dCt=3 with clock option present.
They are included in the dd and Fd
dOH defrost Offset folders. Start of defrost delay time from start-up of instrument. 0...59 0 0 1 min
dEt defrost Endurance time. Defrosting time-out; determines maximum duration of defrost- 1...250 30min 25min 1 hours/min/sec
ing. NOTE: Defrost does not stop if a minimum defrost time has been set. See also (see dt2)
ndE
dSt defrost Stop temperature. Defrosting end temperature (determined by evaporator -50.0... 150 8.0 12 1 °C/°F
probe). NOTE: Defrost does not stop if a minimum defrost time has been set. See
also ndE
dPO defrost (at) Power On. Determines if the instrument must start defrost at start-up (if the n/y n n 1 flag
temperature measured by the evaporator allows this) y = Yes, starts defrost at start-up; n
= No, does not start defrost at start-up.
ndE This parameter enables to specify a minimum duration for defrost (unless external alarms 0...250 0 0 1 hours/min/sec
occur (with EAL=1, see) or device stop), even if the temperature measured on the evapo-
rator is above dSt (see). If the parameter is set to 0, the function is disabled.
tcd Time compressor for defrost. Minimum time for compressor ON or OFF before defrost -31...31 0 0 2 min
If >0 (positive value) the compressor remains ACTIVE for tcd minutes; If<0 (negative
value) the compressor remains INACTIVE for tcd minutes; If =0 the parameter is ignored.
Cod Compressor off (before defrost). Time for compressor OFF before defrost cycle. If a 0…60 0 0 2 min
defrost cycle is set within the programmed time for this parameter, the compressor is not
started. If =0 function is stopped.
FAN CONTROLLER (folder with “FAn” label)
FPt Fan Parameter type. Characterizes the “FSt” parameter that can be expressed as an absolute 0/1 0 0 2 flag
temperature value or as a value related to the Set point. 0 = absolute; 1 = relative.
FSt Fan Stop temperature. Fan stop temperature; a value read by the evaporator probe that -50.0..150.0 2.0 8 1 °C/°F
is higher than the set value causes the fans to stop. The value is positive or negative and,
depending on the FPt parameter, could represent the temperature in absolute value or
relative to Set point.
Fod Fan open door open. Used to select the fan stop when door is open and fan re-start n/y n n 2 flag
when door is closed (if they were active). n=fans stop; y=fans unchanged.
FdC Fan delay Compressor off. Fan switch off delay time after compressor stop. In minutes. 0..99 0 1 2 min
0= Function excluded
PdC Compressor start time/start valve suction valve. This parameter enables to set the start 0...250 1 1 1 min
delay of the compressor when the suction solenoid valve is started (provided that the
valve stays on for the whole duration of PdC). If this parameter is set to 0, the function is
disabled.
Fon Fan on (in duty cycle). Fan ON time for duty cycle. 0..99 0 0 1 min
Use of fans in duty cycle mode; valid for FCO = d.c. and H42=1 (probe 2 (evaporator)
present)
FoF Fan oFF (in duty cycle). Fan OFF time for duty cycle. 0..99 0 0 1 min
Use of fans in duty cycle mode; valid for FCO = dc and H42=1 (probe 2 present) (evapo-
rator )).
bPS Fans ON during dt (bypass) time. This parameter can be used to decide if the fans are n/y n n 1 flag
ON (n=No, y=Yes (si)) during the bypass phase (see Hot Gas algorithm).
L03 Refers to Master and Slave. Simultaneous/sequential defrosting. Master: n = simultaneous; n/y n n 2 flag
y = sequential. Slave: n = ignore; y = accept.
L04 Refers to Slave only. Distributed display. n = the Slave displays local values; y = the Slave n/y y n 2 flag
displays Master display
L05 Refers to Master and Slave. Master: n = does not ask Slaves to activate remote functions; n/y n n 2 flag
y = asks Slaves to activate remote functions. Slave: n = ignores activation of remote func-
tions from Master; y = accepts activation of remote functions from Master.
L06 Locks resources (compressors, fans, etc) at the end of defrosting. n=no; y=yes NOTE: n/y y n 2 flag
related to Ldd parameter which has priority over L06 (see)
(FOR /C /CK MODELS ONLY ) DAY/NIGHT CONTROLLER (night and day)
(folder with “nad” label)
E00 Functions enabled during events: 0 = control disabled. 1 = reduced set point; 2 = 0...4 0 0 2 num
reduced set+light; 3 = reduced set+light+aux. 4= instrument off
E01 Hours/minutes of start of event. Sets start time of event. Starting from this time, the 0...23/0...59 0 0 2 hours/min
“NIGHT” mode will be enabled. The duration is determined by EO2.
E02 Duration of event. Sets duration of event (for type of event, see E00) 0…99 0 0 2 hours
E03 Blocking/unblocking daily or holidays defrosting. 0= “work days” defrost sequence 0/1 0 0 2 flag
defined by par. dE1…dE8; 1= “festive/holidays” defrost sequence defined by par. F0…F8;
N.B.: does not affect timed defrosting like Every Day (same defrost sequence for
working days/holidays).
COMMUNICATION (folder with “Add” label)
dEA (!) Device address in family 0...14 0 0 1 num
(4) (values ranging from 0 to 14)
FAA (!) Device family (values ranging from 0 to 14) 0...14 0 0 1 num
(4)
DISPLAY (folder with “diS” label)
LOC (keyboard) LOCK. Keyboard locked. However, you can still access the parameter pro- n/y n n 1 flag
gramming menu and modify parameters including the status of this parameter to allow
keyboard unlocking. y = yes (keyboard locked); n = no.
PA1 PAssword 1. When enabled (value is not 0) it represents the access key to level 1 para- 0...250 0 0 1 num
meters.
PA2*** PAssword 2. When enabled (value is not 0) it represents the access key to level 2 para- 0...255 0 0 2 num
meters.
ndt number display type. Display with decimal point. y = Yes (display with decimal point); n/y y n 1 flag
n = No (only integer numbers).
CA1 CAlibration 1. Calibration 1. Positive or negative temperature value added to the value -12.0...12.0 0 0 1 °C/°F
read by probe 1, based on “CA” parameter settings.
CA2 CAlibration 2. Calibration 2. Positive or negative temperature value added to the value -12.0...12.0 0 0 1 °C/°F
read by probe 2, based on “CA” parameter settings.
CA3 CAlibration 3. Calibration 2. Positive or negative temperature value added to the value -12.0...12.0 0 0 1 °C/°F
read by probe 3, based on “CA” parameter settings.
CA CAlibration Intervention. Offset intervenes on display, thermostat control or both. 0/1/2 2 2 2 num
0 = only modifies the temperature displayed;
1 = adds to the temperature used by controllers, not the temperature displayed that
remains unchanged;
2 = adds to temperature displayed that is also used by controllers.
LdL Low display Label. Minimum value the instrument is able to display. -55.0...302 -50.0 -50 2 °C/°F
HdL High display Label. Maximum value the instrument is able to display. -55.0..302 140.0 140 2 °C/°F
ddL defrost display Lock. Display mode during defrosting. 0/1/2 1 1 1 num
0 = displays the temperature read by the thermostat control probe;
1 = locks the reading on the temperature value read by thermostat control probe when
defrosting starts until the next time the Set point value is reached;
2 = displays the label “deF” during defrosting until the next time the Set point value is
reached (or until Ldd expires).
Ldd Lock defrost disable. Time-out value for unlocking display (dEF label) if reaching the set 0…255 0 60 1 min
point takes too long during defrosting or if the Link (Master-Slave) communication fails
(E7 error)
dro display read-out. Select °C or °F to display temperature read by probe. 0 = °C, 1 = °F. 0/1 0 0 1 flag
N. B: switching from °C to °F DOES NOT modify set points, differentials, etc. (for
example set point=10°C becomes 10°F).
ddd Selection of the value type to be displayed. 0/1/2/3 1 1 2 num
0 = Set point;
1 = probe 1 (thermostat control);
2 = probe 2 (evaporator);
3 = probe 3 (display).
CONFIGURATION (folder with “CnF” label)
H00 (5) (!) Selection of probe type, PTC or NTC. 0 = PTC; 1 = NTC. 0/1 1 1 1 flag
H02 Button activation time if buttons are configured for a second function. 0...15 5 5 2 sec
For the ESC, Up and DOWN buttons configured for a second function (defrost, aux, etc)
the time for quick enabling is set. Aux is an exception and has a set time of 1 second
H06 button/aux input/door switch light active when instrument is off (but powered) n/y y y 2 flag
H08 Stand-by operating mode. 0= only display switched off; 1= display on and controllers 0/1/2 2 2 2 num
locked; 2= display off and controllers locked;
H11 (6) Configuration of digital inputs/polarity. -8…8 0 2 2 num
0 = disabled; 1 = defrosting; 2 = reduced set; 3 = Auxiliary
4 = Door micro 5 = external alarm
*6 = Disables storage of HACCP alarms (*only in HACCP models)
7 = Standby (ON-OFF) 8 = Maintenance request
H12 (6) Configuration of digital inputs/polarity. Same as H11 -8…8 0 0 2 num
(7) WARNING! positive or negative values change polarity
(!) WARNING!
• If one or more parameters marked with (!) are modified, the controller must be switched off after the modification and then switched back on
•PLEASE NOTE: We strongly recommend that you switch the device off and on again after changing the configuration of parameters to prevent configuration problems
and/or ongoing timings.
•folder with “nad” label NIGHT/DAY CONTROL (night and day) FOR /C, /CK MODELS ONLY
•folder with “Lin” label LINK CONTROLLER FOR /CK MODELS ONLY
Ont, OFt parameters programmed for The error condition for probe 1 OUT
Duty Cycle (compressor) causes the follow- On
ing:
• E1 code appears on display
Ont OFt Compressor output • The controller is activated as
Off
0 0 OFF indicated by the “Ont” and
0 >0 OFF “OFt” parameters if pro-
>0 0 ON
>0 >0 D.C.
grammed for the duty cycle
Ont OFt Ont
set
h00
hours
2 sec
set
rtc set '00
minutes
2 sec
set
d00
days
if present
PARAMETERS
press for 5 sec set PA1≠0 set level 1 folders level 2 folders
CP CP
set PA1 value
dEF (+dd+Fd) dEF
FAn FAn
AL AL
Lit -
Lin -
nad -
Add Add
level 2 par set CP CP set level 1 par diS diS
CnF CnF
FPr FPr
Fd
change
level 2 par set Lit Add set level 1 par par value
set
level 1
level 2 par set CnF
level 2
TERMINALS
Wiring Diagram STANDARD CONFIGURATION
ONLY /CK