Unisab III Settings 1.03 en PDF

This document contains settings for a Unisab III compressor control system. It lists various functions and their associated parameter settings, organized into sections for compressor control, sequencing, configuration including calibration, drive system, oil system, communication protocols, auxiliary outputs, digital inputs, plant settings, timers, and refrigerant property tables. The settings are tailored for a specific compressor installation, including the customer, end user, shop and equipment identifiers.

Uploaded by

Radwan AL Troug
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
406 views4 pages

Unisab III Settings 1.03 en PDF

This document contains settings for a Unisab III compressor control system. It lists various functions and their associated parameter settings, organized into sections for compressor control, sequencing, configuration including calibration, drive system, oil system, communication protocols, auxiliary outputs, digital inputs, plant settings, timers, and refrigerant property tables. The settings are tailored for a specific compressor installation, including the customer, end user, shop and equipment identifiers.

Uploaded by

Radwan AL Troug
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

Date: __________ Init.

: __________

Settings for Unisab III 1.03


Customer:

End user:

Compressor shop no.:

Local compr. no. :

ROC no.:

Order no.:

Plant type:

Compressor type:

Software version/date:

Set up >Compr. Control Set up >Sequencing


No Function Setting No Function Setting
1 Mode 1 Start no
2 Control On 2 System no
3 Capacity controller 3 System controller
4 Auto Start
5 Auto Stop Set up > Multisab
6 Cold Store 1 Parallel offset
7 Climate Compensation
8 Multisab master

Setup> Configuration>Calibrate

>Press transducer >Process out Temp. >Position >Motor Freq


Suction Adjust Process out Adj Cap. Pos Motor Freq
Discharge Adjust Cap. Zero Ad Frq. Zero Adj
Oil Adjust Cap. 100 Adj Freq. 100 Adj
Diff./Imed Adjust Vi Position
Oil. Adjust Vi. Zero Adj
Eco Adjust Vi. 100 Adj

Page 1/4
Settings for Unisab III 1.03
Setup>Configuration
>Drive >Oil system >Communication
No. Function Setting No. Function Setting No. Function Setting
1 Motor range Amp 1 Oil pump 1 Compressor
2 Motor range KW 2 Full Flow Pump 2 Baud rate
3 Motor nom kW 3 Oil Cooling 3 Profibus
4 Display 4 Oil controller 4 Profi. node no.
5 Motor input signal 5 Water Cooling 5 Profi. baud rate
6 Rotatune 6 Oil Rectifier 6 GSD file no.
7 Motor rpm min. 7 Sep.Vel.Ref
8 Motor rpm max. 8 Sep.Vel.CR

>Compressor block
No. Function Setting >Measuring
1 Compressor Type No. Function Setting
2 Swept Volume 1 Press./Temp.
3 Volume Ratio 2 Pressure range
4 Vi Low Range 3 Low Suct. Press
5 Vi Mode % 4 Capacity signal
6 Mech. Zero
7 Manual Zero >Aux output >Dig. In Via Profibus
8 Booster No. Function Setting No. Function
9 Economizer 1 Activate when 1 Dig. Input 1
10 Eco Low Cap. 2 Signal Low 2 Dig. Input 2
11 Neutral zone 3 Signal High 3 Dig. Input 3
12 Eco High Suction 4 Dig. Input 4
13 Unloading >External (user 1) input 5 Dig. Input 5
14 Unload assist 1 Function 6 Dig. Input 6
15 Cap.decr.assist rate 2 4 mA 7 Dig. Input 7
16 Volume dead band 3 20 mA 8 Dig. Input 8
9 Dig. Input 9
>Plant 10 Dig. Input 10
No. Function Setting 11 Dig. Input 11
1 Refrigerant 12 Dig. Input 12
2 Compressor Setup>Session 13 Dig. input 13
3 Start 1 Language 14 Dig. Input 14
4 System
Common
5
Evap/Cond
6 HP on Two Stage
7 High Limit >Factory reset
8 Take Over No. Function Setting
9 COP Active 1 Factory reset
10 Chiller
11 Flow factor
12 Liquid subcool

Setup>Configuration>R000
Temp °C/R Press Bar Temp °C/R Press Bar Temp °C/R Press Bar
-90 -30 30
-85 -25 35
-80 -20 40
-75 -15 45
-70 -10 50
-65 -05 55
-60 00 60
-55 05 65
-50 10 70
-45 15 75
-40 20 80
-35 25

Page 2/4
Settings for Unisab III 1.03
Setup>Timers>Timers Setup (1)

No. Function Setting No. Function Setting No. Function Setting


Oil Pressure Low
45/300/25
(*S)
01 Start-Start Delay 13 25 Oil Rect. Start
Oil Pressure Low
60
(*R)
Filter diff high (*S) 300
02 Stop-Start Delay 14 26 Oil Rect. Pause
Oil press high (*R) 20
03 Start Delay 15 Oil Temp Low 300 27 Oil Rect. Disable
16 300
04 Stop Delay Oil Temp High 28 Start HP
0
300
05 Suction Ramp 17 Superheat Low 29 No Chiller 10
15
Slide Max (*S) 18
06 Superheat High 300 30 Cap. Negative (*S)
Delay Up (*R)
Pre lubrication 10/60/0/6/
Disch Press
07 (*S) 50/0 19 300 31 Start Unload (*S)
O/load
Delay Down (*R)
Oil Flow 600/90/60/
08 (*S) 120/600/0 20 Current Overload 300 32 Low suct. press
Transfer max (*R)
Oil Flow Delay
50/0/20/10
(*S)
09 21 Motor Start 33 Lub Pressure (*S) 145
Take Over Delay
300
(*R)
No Oil Flow 10/2/6/120
(*S) /30 22 PMS Feedback
10 34 Vi pause (*S) 60
Interm Press Low
20
(*R)
Lub time/flow F.F. Pump Oil Log Shutdown
60/300 35 60
(*S) Start(*S) (*S)
11
Filter Diff High 23 Oil Cool On
300 36 Low Oil Flow (*S) 180
(*R) (*R)
Diff press OK (*S) 60 Oil Pump Start(*S) 37 Oil Cir. Alm (*S) 600
12 24 Oil Cir. Shutdown
Total unload (*R) Oil Return (*R) 38 900
(*S)
39 SSSTV delay

Setup>Timers>P Band Factor Setup>Timers>Transfer Setup>Timers>Take Over


(1) (1) (1)
Delay Up (*R) Factor Down (*R) Factor Up (*R)
Delay Down (*R) Zone (*R) Factor Start (*R)
Start Delay Zone (*R)
Stop Delay

Setup>Service>Maintenance

Estimated compressor main service


Hour counter
Time to next main service C
Time to next part service B
Time to next part service A

Page 3/4
Settings for Unisab III 1.03
Control values>

Alarm-/Shutdown Limits & High High Low Low SP SP NZ PB T. T. MIN RUN


Regulator Settings (1) Shut Alarm Alarm Shut No. 1 No. 2 Integ. Diff. PULS TIME
down down
Suction>Suction pressure
[ºC/R]

Suction>Suction superheat

Discharge>Disch. pressure
[ºC/R]

Discharge>Disch.
Temperature

Discharge>Disch. Superheat

Oil>Oil pressure

Oil>Oil filter pressure


(*S)

Oil>Oil temperature

Oil>Oil separator temperature


(*S)

Motor>Motor current

Motor>Motor Power

Capacity>Capacity
(*S)

Capacity>Vi Position
(*S)

Process temp>Process out


temp

User> User input 1

Intermediate>Interm. pres.
[ºC/R] (*R)

Intermediate>Interm.
temperature (*R)

Notes:

(*S) = Screw, (*R) = Reciprocating

(1) The value(s) will be changed to factory settings by a “Factory reset”.