Design Calculation Sheet: Booster Pumps

This document provides design calculations for booster pumps for a building's town houses. It calculates the required total flow rates and head pressures for two sets of town houses, labeled THC&THE and THA&THB&THG. For each set, it determines the static head, residual pressure, pipe friction losses, and total head required. It selects suitable pumps from a manufacturer's catalog with a head capacity of 12 meters to meet the calculated head requirements. It also calculates the number and size of storage tanks needed based on the pump flow rates and operating parameters.

Uploaded by

Islam Soliman
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
1K views2 pages

Design Calculation Sheet: Booster Pumps

This document provides design calculations for booster pumps for a building's town houses. It calculates the required total flow rates and head pressures for two sets of town houses, labeled THC&THE and THA&THB&THG. For each set, it determines the static head, residual pressure, pipe friction losses, and total head required. It selects suitable pumps from a manufacturer's catalog with a head capacity of 12 meters to meet the calculated head requirements. It also calculates the number and size of storage tanks needed based on the pump flow rates and operating parameters.

Uploaded by

Islam Soliman
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 2

Design calculation sheet

Project no.: Date: Sheet No.: 1 of 1 Computed by:


Subject: Booster pumps Checked by:
Building: Town Houses Approved by:
Total F.U for THC&THE 41 F.U. = 27.46 G.P.M.
THD&THH&THJ = 1.73 l/s
FlowTOTAL = 1.73 l/s

Head Required : Static Head -1 m


:Residual 1.00 Bars = 10.2 m
:Friction:Length of Pipe: 7 m Roof
10 m (3rd)
1 m (Vertical)
18 m TOTAL
hfriction= 18 × 1.5 × 5% = 1.35 m

hTOTAL = 10.55 m
Taking h = 12 m
Taking Pump with head = 12 m
1 operating pumps 1 standby
Select from Grundfos catalugue a Pump having Model Num:CHN 4-30
motor power: 0.75KW

Total F.U for THA 41 F.U. = 18.85 G.P.M.


THB&THF&THG = 1.19 l/s
FlowTOTAL = 1.19 l/s

Head Required : Static Head -1 m


:Residual 1.00 Bars = 10.2 m
:Friction:Length of Pipe: 7 m Roof
10 m (3rd)
1 m (Vertical)
18 m TOTAL
hfriction= 18 × 1.5 × 5% = 1.35 m

hTOTAL = 10.55 m
Taking h = 12 m
Taking Pump with head = 12 m
1 operating pumps 1 standby
Select from Grundfos catalugue a Pump having Model Num:CHIU 4-20
motor power: 0.5KW

PRC-EN-04 (F1) REV 1


Number of vessels needed = 1 vessels THA
THB&THD&THG

Total tank volume


V=16.5(Q/Zmax).[(Pu.Pi)/(∆P.Pc)]

Where V:Tank volume in liters


Q: flow of the pump in l/min
Z: maxImum acceptable Number of pump start per hour
Pu: absolute pressure at which the pumps stops in Bars
Pi: absolute pressure at which the pumps starts in Bars
∆P:Pu-Pi
Pc= Pi-0.5 (initial air charge absolute pressure Pressure)

having Q= 71.4 l/min


Z= 50 times
Pu= 2.37 bars
Pi= 1.785 bars
∆P= 0.585 bars
Pc= 1.285 bars

71.40 2.37 × 1.785


V = 16.5× × = 133
50 0.585 × 1.285

V/vessel= 150.00