Switched Rack Power Distribution Unit (AP8958EU3)

Overview and Specifications


Übersicht und technische Daten

Información general y especificaciones

Présentation et caractéristiques techniques

Panoramica e specifiche

Visão geral e especificações

Przegląd i specyfikacja

Описание и характеристики

Genel Bakış ve Teknik Özellikler

Menu
Main

Sc ro ll

Se le ct
L ink - Rx/ Tx

Temp/ Humid ity


10 0
1 0/
In

Out
Seria l Port

USB

pdu0485a
Overview

The APC by Schneider Electric Switched Rack Power Distribution Unit (PDU) distributes power to
devices in the rack. It has a sensor that measures the current that it and its attached devices use. It can be
monitored through Web, Telnet, SNMP, SSH, or InfraStruXure® Central interfaces.

Outlets. The Rack PDU has seven (7) IEC-320-C13 and one (1) IEC-320-C19 locking outlets . A
green LED for each outlet turns on when the outlet is energized. (The locking feature is compatible with
APC locking input cords and APC locking jumper cords.)

Display interface. The liquid crystal display (LCD)  and input buttons  allow you to monitor
current, power, and voltage measurements of the Rack PDU. Local communication can be established
through the serial port , and remote communication through the network port . The USB  and
CAN  ports enable data transfer for future expansion options. The environmental sensor port  allows
for monitoring of the temperature and humidity of the room or enclosure.

Power cord. A detachable 3.0-m (10-ft), 16 A, 3-pin C19-to-IEC-309 power cord  is provided. The
Rack PDU has one (1) IEC-320-C20 inlet .

Toolless mounting. The Rack PDU has two toolless mounting pegs  for 0 U mounting capability in
a rack or enclosure.
Menu
Main

Scroll

Select

Main
Menu

Scroll

Select
Link - Rx /Tx

Temp/Humidity
Link - Rx/Tx

100
10/
In

Out
Temp/Humidity

Serial Port

USB
100
10/
In

Out
Serial Port

USB

pdu0486a

2 Switched Rack PDU—Overview and Specifications


Specifications

Electrical

Acceptable input voltage 100–240 VAC +6%, -10%

Maximum input current (phase) 16 A UL (derated)


16 A VDE
20 A PSE

Input frequency 50/60 Hz

Input connection IEC-320-C20

Detachable 16 A, 3-pin C19-to-IEC-309 power cord


provided

Input power 3.3 kVA UL


3.7 kVA VDE
4.0 kVA PSE

Output voltage 100–240 VAC

Maximum output current (outlet) IEC-320-C13: 12 A; IEC-320-C19: 16 A UL (derated)


IEC-320-C13: 10 A; IEC-320-C19: 16 A VDE
IEC-320-C13: 15 A; IEC-320-C19: 20 A PSE

Maximum output current (phase) 16 A UL (derated)


16 A VDE
20 A PSE

Output connections Seven (7) IEC-320-C13; one (1) IEC-320-C19

Physical

Dimensions (H x W x D) 99.1 x 5.6 x 4.6 cm (39.0 x 2.2 x 1.8 in)


(depth does not include toolless pegs)

Power cord length 3.0 m (10 ft)

Shipping dimensions (H x W x D) 112.4 x 16.5 x 11.4 cm (44.3 x 6.5 x 4.5 in)

Weight/shipping weight 3.9 kg (8.7 lb) / 5.5 kg (12.1 lb)

Environmental

Maximum elevation (above MSL)


Operating/Storage 0–3 000 m (0–10,000 ft) / 0–15 000 m (0–50,000 ft)

Temperature
Operating/Storage –5 to 45°C (23 to 115°F) / –25 to 65°C (–13 to 149°F)

Humidity
Operating/Storage 5–95% RH, non-condensing

Compliance

EMC verification FCC Part 15 Class A, ICES-003 Class A, VCCI-A,


EN 55022 Class A, EN 55024, EN 61000-3-2, EN 61000-3-3

Safety verification UL, VDE, PSE

Customer support and warranty information is available at the APC Web site, www.apc.com. 990-3445
12/2009
© 2009 APC by Schneider Electric. All trademarks are owned by Schneider Electric Industries
S.A.S., American Power Conversion Corporation, or their affiliated companies.
Schaltbare Ausgangsverteilung (PDU) für
Rack-Einbau (AP8958EU3)

Übersicht und technische Daten

Me nu
Main

Sc ro ll

Select
Link - Rx/ Tx

Temp/ Humidity
10 0
10/
In

O ut
Se rial Port

USB

pdu0485a
Übersicht

Die schaltbare Ausgangsverteilung (PDU) für Rack-Einbau von APC by Schneider Electric verteilt
Strom an die Geräte im Rack. Sie verfügt über einen Sensor, der den eigenen Stromverbrauch und den
der angeschlossenen Geräte misst. Sie kann über Web-, Telnet-, SNMP-, SSH- oder InfraStruXure®
Central-Schnittstellen überwacht werden.

Stromausgänge. Die Rack PDU verfügt über acht verriegelbare Ausgänge, sieben vom Typ
IEC-320-C13 und eine vom Typ IEC-320-C19 . Sobald der Ausgang bestromt wird, leuchtet die
dazugehörige grüne LED ein. (Die Verriegelung passt mechanisch zu verriegelbaren
Eingangsstromkabeln und Überbrückungskabeln von APC.)

Display. Mithilfe des LCD-Displays  und der dazugehörigen Eingabetasten  können


Stromaufnahme, Leistung und Spannung der Rack PDU überwacht werden. Der Datenaustausch mit
lokalen Systemen ist über den seriellen Anschluss  möglich, für den Datenaustausch mit externen
Systemen steht ein Netzwerkanschluss  zur Verfügung. Anschlüsse für USB  und CAN 
ermöglichen den Datenaustausch mit nachträglich installierten Erweiterungsoptionen. Über den
Umgebungssensoranschluss  können die Temperatur und Feuchtigkeit im Aufstellraum oder
Systemschrank überwacht werden.

Netzkabel. Ein abziehbares Netzkabel von 3,0 m Länge, 16 A, 3-polig, Typ C19-an-IEC-309  wird
mitgeliefert. Die Rack PDU verfügt über einen Stromeingang vom Typ IEC-320-C20 .

Montage ohne Werkzeug. Die Rack PDU verfügt über zwei Montagestifte für den werkzeuglosen
Einbau  in ein Rack oder einen Systemschrank mit 0 HE.
Men u
Main

Scroll

Select

Main
Menu

Scro ll

Sele ct
Link - Rx /Tx

Temp/Humidity
Link - Rx/Tx

1 00
10/
In

Ou t
Te mp/Humidity

Ser ial Por t

USB
10 0
10 /
In

Out
Serial Port

USB

pdu0486a

Schaltbare Ausgangsverteilung (PDU) für Rack-Einbau – Übersicht und technische Daten 5


Technische Daten

Elektrik

Zulässige Eingangsspannung 100 - 240 V~ +6%, -10%

Maximaler Eingangsstrom (Phase) 16 A UL (unterbelastet)


16 A VDE
20 A PSE

Eingangsfrequenz 50/60 Hz

Eingangsanschluss IEC-320-C20

Abziehbares Netzkabel, 16 A, 3-polig, Typ C19-an-IEC-309 im


Lieferumfang enthalten

Eingangsstrom 3,3 kVA UL


3,7 kVA VDE
4,0 kVA PSE

Ausgangsspannung 100 - 240 V~

Maximaler Ausgangsstrom (je Stromausgang) IEC-320-C13: 12 A; IEC-320-C19: 16 A UL (unterbelastet)


IEC-320-C13: 10 A; IEC-320-C19: 16 A VDE
IEC-320-C13: 15 A; IEC-320-C19: 20 A PSE

Maximaler Ausgangsstrom (Phase) 16 A UL (unterbelastet)


16 A VDE
20 A PSE

Ausgangsanschlüsse Sieben vom Typ IEC-320-C13; einer vom Typ IEC-320-C19

Maße und Gewichte

Abmessungen (H x B x T) 99,1 x 5,6 x 4,6 cm (39,0 x 2,2 x 1,8 in)


(Tiefe ohne Montagestifte für werkzeuglosen Einbau)

Länge des Netzkabels 3,0 m (10 ft)

Versandabmessungen (H x B x T) 112,4 x 16,5 x 11,4 cm (44,3 x 6,5 x 11,43 cm)

Gewicht/Versandgewicht 3,9 kg / 5,5 kg

Umgebungsbedingungen

Maximale Höhe (über dem Meeresspiegel)


Betrieb/Lagerung 0–3 000 m (0 - 10.000 ft) / 0 - 15 000 m (0 - 50.000 ft)

Temperatur
Betrieb/Lagerung –5 bis 45 °C (23 bis 115 °F) / –25 bis 65 °C (–13 bis 149 °F)

Luftfeuchtigkeit
Betrieb/Lagerung 5–95% RH, nichtkondensierend

Konformität

EMC FCC Teil 15 Klasse A, ICES-003 Klasse A, VCCI-A,


EN 55022 Klasse A, EN 55024, EN 61000-3-2, EN 61000-3-3

Sicherheitsprüfung UL, VDE, PSE

Bei Fragen an den Kundendienst oder zur Abwicklung möglicher Garantiefälle informieren Sie 990-3445
sich bitte auf der Website von APC unter www.apc.com. 12/2009

© 2009 APC Schneider Electric. Alle Marken sind Eigentum von Schneider Electric Industries
S.A.S., der American Power Conversion Corporation oder ihnen angegliederter Unternehmen.
Unidad de distribución de alimentación conmutada de
rack (AP8958EU3)

Información general y especificaciones

Me nu
Main

Sc ro ll

Select
Link - Rx/ Tx

Temp/ Humidity
10 0
10/
In

O ut
Se rial Port

USB

pdu0485a
Información general

La Unidad de distribución de alimentación (PDU) conmutada de rack de APC by Schneider Electric


distribuye la alimentación a los dispositivos del rack. Dispone de un sensor que mide la corriente usada
por ella misma y por los dispositivos conectados a ella. Esta se puede supervisar a través de una interfaz
Web, Telnet, SNMP, SSH o de InfraStruXure® Central.

Tomas de corriente. La PDU de rack cuenta con siete (7) tomas de corriente bloqueables
IEC-320-C13 y una (1) IEC-320-C19 . Cada toma de corriente tiene un LED verde que se enciende
cuando se activa. (La característica de bloqueo es compatible con los cables de entrada bloqueables
APC y los cables de puente bloqueables APC.)

Interfaz de pantalla. La pantalla de cristal líquido (LCD)  y los botones de entrada  le permiten
supervisar las medidas de corriente, potencia y tensión de la PDU de rack. La comunicación local se
puede establecer a través del puerto serie , y la comunicación remota a través del puerto de red . Los
puertos USB  y CAN  posibilitan la transferencia de datos para futuras opciones de expansión. El
puerto de sensor ambiental  permite la supervisión de la temperatura y la humedad de la sala o
armario.

Cable de alimentación. Se proporciona un cable de alimentación desconectable C19 a IEC-309 de


3 clavijas y 16 A de 3 metros (10 pies) . La PDU de rack tiene una (1) entrada IEC-320-C20 .

Montaje sin herramientas. La PDU de rack tiene dos clavijas de montaje sin herramientas  que
permiten un montaje de 0 U en un rack o un armario.
Men u
Ma in

Scroll

Select

Main
Menu

Scroll

Select
Link - Rx /Tx

Temp /Humidity
100
Link - Rx/Tx

10 /
In

Out
Te mp/Hu midity

Ser ial Por t

USB
10 0
1 0/
In

Ou t
Seri al Port

USB

pdu0486a

8 PDU (Unidad de distribución de alimentación) conmutada de rack—


Información general y especificaciones
Especificaciones

Eléctricas

Tensión de entrada aceptable 100–240 VCA +6%, -10%

Corriente de entrada máxima (fase) 16 A UL (limitada)


16 A VDE
20 A PSE

Frecuencia de entrada 50/60 Hz

Conexión de entrada IEC-320-C20

Se proporciona un cable de alimentación desconectable C19 a


IEC-309 de 16 A y 3 clavijas

Potencia de entrada 3,3 kVA UL


3,7 kVA VDE
4,0 kVA PSE

Tensión de salida 100–240 VCA

Corriente de salida máxima (enchufe) IEC-320-C13: 12 A; IEC-320-C19: 16 A UL (limitada)


IEC-320-C13: 10 A; IEC-320-C19: 16 A VDE
IEC-320-C13: 15 A; IEC-320-C19: 20 A PSE

Corriente de salida máxima (fase) 16 A UL (limitada)


16 A VDE
20 A PSE

Conexiones de salida Siete (7) IEC-320-C13; una (1) IEC-320-C19

Físicas

Dimensiones (Alto x Ancho x Fondo) 99,1 x 5,6 x 4,6 cm (39,0 x 2,2 x 1,8 pulg.)
(el fondo no incluye las clavijas de montaje sin
herramientas)

Longitud del cable de alimentación 3,0 m (10 pies)

Dimensiones de salida de fábrica


(Alto x Ancho x Fondo) 112,4 x 16,5 x 11,4 cm (44,3 x 6,5 x 4,5 pulg.)

Peso/Peso de salida de fábrica 3,9 kg (8,7 lb) / 5,5 kg (12,1 lb)

Ambientales

Altura máxima (sobre el nivel del mar)


Funcionamiento/almacenamiento 0–3 000 m (0–10.000 pies) / 0–15 000 m (0–50.000 pies)

Temperatura
Funcionamiento/almacenamiento –5 a 45 °C (23 a 115 °F) / –25 a 65 °C (–13 a 149 °F)

Humedad
Funcionamiento/almacenamiento 5–95% RH sin condensación

Cumplimiento

Verificación de EMC Normas de la FCC Parte 15 Clase A, ICES-003 Clase A, VCCI-A,


EN 55022 Clase A, EN 55024, EN 61000-3-2, EN 61000-3-3

Verificación de seguridad UL, VDE, PSE

La información sobre asistencia al cliente y garantía está disponible en el sitio Web de APC, www.apc.com. 990-3445
12/2009
© 2009 APC by Schneider Electric. Todas las marcas comerciales son propiedad de Schneider Electric Industries
S.A.S., de American Power Conversion Corporation o de sus empresas asociadas.
Unité de distribution de l'alimentation à monter en rack
avec système de commutation (AP8958EU3)

Présentation et caractéristiques techniques

Me nu
Main

Sc ro ll

Select
Link - Rx/ Tx

Temp/ Humidity
10 0
10/
In

O ut
Se rial Port

USB

pdu0485a
Présentation

L'unité de distribution de l'alimentation (PDU) à monter en rack avec système de commutation d'APC by
Schneider Electric distribue l'alimentation aux dispositifs du rack. Elle est munie d'un capteur mesurant
le courant utilisé par la PDU et les dispositifs reliés. Elle peut être contrôlée par l'intermédiaire
d'interfaces Web, Telnet, SNMP, SSH ou InfraStruXure® Central.

Prises. La PDU à monter en rack est dotée de sept (7) prises à verrouillage CEI-320-C13 et d'une (1)
prise à verrouillage CEI-320-C19  Pour chaque prise, un voyant vert s'allume lorsque la prise est
activée (la fonction de verrouillage est compatible avec les cordons d'entrée à verrouillage d'APC et les
cordons d'alimentation à verrouillage d'APC).

Interface d'affichage. L'affichage à cristaux liquides (LCD)  et les boutons d'entrée  permettent de
contrôler les mesures d'intensité, de puissance et de tension de la PDU en rack. La communication locale
peut être établie par l'intermédiaire du port série , la communication à distance par l'intermédiaire du
port réseau . Les ports USB  et CAN  permettent de transférer des données pour des options
d'extension futures. Le port du capteur environnemental  permet de contrôler la température et
l'humidité de la salle ou de l'armoire.

Cordon d'alimentation. Un cordon d'alimentation C19/CEI-309 amovible de 3 m, 16 A, à


3 broches  est fourni. La PDU en rack comprend une (1) entrée CEI-320-C20 .

Montage sans outil. La PDU en rack comprend deux chevilles de montage sans outil  pour une
option de montage 0 U dans un rack ou une armoire.
Menu
Main

Scroll

S elect

Main
Menu

Scroll

Select
Link - Rx /Tx

Temp/Humidity
Link - Rx/Tx

100
10/
In

Out
Temp/Humidity

Ser ial Port

USB
100
10/
In

Out
Serial Port

USB

pdu0486a

PDU à monter en rack avec système de commutation — 11


Présentation et caractéristiques techniques
Caractéristiques techniques

Circuit électrique

Tension d'entrée admissible 100-240 V c.a. +6 %, -10 %

Intensité maximale en entrée (phase) 16 A UL (déclassé)


16 A VDE
20 A PSE

Fréquence d'entrée 50/60 Hz

Connexion d'entrée CEI-320-C20

Cordon d'alimentation C19/CEI-309 amovible de 16 A à


3 broches fourni

Puissance d'entrée 3,3 kVA UL


3,7 kVA VDE
4,0 kVA PSE

Tension de sortie 100 -240 V c.a.

Intensité maximale en sortie (prise) CEI-320-C13 : 12 A ; CEI-320-C19 : 16 A UL (déclassé)


CEI-320-C13 : 10 A ; CEI-320-C19 : 16 A VDE
CEI-320-C13 : 15 A ; CEI-320-C19 : 20 A PSE

Intensité maximale en sortie (phase) 16 A UL (déclassé)


16 A VDE
20 A PSE

Connexions de sortie Sept (7) CEI-320-C13 ; une (1) CEI-320-C19

Caractéristiques physiques

Dimensions (H x l x P) 99,1 x 5,6 x 4,6 cm


(la profondeur ne tient pas compte des chevilles sans
outil)

Longueur du cordon d'alimentation 3,0 m

Dimensions à l'expédition (H x l x P) 112,4 x 16,5 x 11,4 cm

Poids / Poids à l'expédition 3,9 kg / 5,5 kg

Caractéristiques environnementales

Altitude maximale (au-dessus du niveau de la mer)


Fonctionnement / Stockage 0–3000 m / 0 à 15 000 m

Température
Fonctionnement / Stockage –5 à 45°C (23 à 115°F) / –25 à 65°C (–13 à 149°F)

Humidité
Fonctionnement / Stockage 5–95% HR, sans condensation

Conformité

Compatibilité électromagnétique FCC, section 15, classe A, ICES-003 classe A, VCCI classe A
EN 55022 classe A, EN 55024, EN 61000-3-2, EN 61000-3-3

Normes de sécurité UL, VDE, PSE

Pour obtenir des informations sur l'assistance et la garantie, les clients peuvent consulter le site 990-3445
Web d'APC à l'adresse www.apc.com. 12/2009

© 2009 APC by Schneider Electric. Toutes les marques déposées sont la propriété de Schneider
Electric Industries S.A.S., American Power Conversion Corporation ou de leurs filiales.
Unità di distribuzione dell'alimentazione con
montaggio a rack alternato (AP8958EU3)

Panoramica e specifiche

Me nu
Main

Sc ro ll

Select
Link - Rx/ Tx

Temp/ Humidity
10 0
10/
In

O ut
Se rial Port

USB

pdu0485a
Panoramica

L’unità di distribuzione dell'alimentazione in rack alternato APC by Schneider Electric distribuisce


l’alimentazione ai dispositivi nel rack. Dispone di un sensore che misura la corrente utilizzata sia
dall’unità che dai dispositivi collegati. Può essere monitorata tramite interfacce web, Telnet, SNMP,
SSH o InfraStruXure® Central.

Uscite. La PDU in rack dispone di 7 uscite IEC-320-C13 e 1 uscita di fissaggio IEC-320-C19 .


Quando un'uscita viene alimentata, si accende il rispettivo LED verde. (La funzione di fissaggio è
compatibile con i cavi di ingresso di fissaggio APC e con i cavi di accoppiamento di fissaggio APC.)

Interfaccia del display. Il display LCD  e i pulsanti di ingresso  consentono di monitorare le


misurazioni di corrente, potenza e tensione della PDU in rack. È possibile stabilire la comunicazione a
livello locale tramite la porta seriale  e la comunicazione remota tramite la porta di rete . Le porte
USB  e CAN  consentono il trasferimento di dati per opzioni di espansione future. La porta del
sensore ambientale  consente di eseguire il monitoraggio di temperatura e umidità della stanza o
dell’armadietto.

Cavo di alimentazione. Un cavo di alimentazione rimovibile da 3 m (10 piedi), 16 A, da C19 a


IEC-309 a 3 pin  è in dotazione. La PDU in rack dispone di 1 ingresso IEC-320-C20 .

Installazione senza utensili. La PDU in rack dispone di due pioli di sostegno che non richiedono
l’uso di strumenti  per funzionalità di installazione 0 U in un rack o in un armadietto.
Men u
Main

Scroll

Select

Main
Menu

Scroll

Sele ct
Lin k - Rx /Tx

Temp/Hu midity
1 00
Link - Rx/Tx

10/
In

Ou t
Temp/Humidity

Ser ial Por t

USB
100
1 0/
In

Out
Seri al Port

USB

pdu0486a

14 PDU con montaggio a rack alternato - Panoramica e specifiche


Specifiche

Caratteristiche elettriche

Tensione in ingresso accettabile 100–240 V c.a. +6%, -10%

Corrente massima in ingresso (fase) 16 A UL (a potenza ridotta)


16 A VDE
20 A PSE

Frequenza in ingresso 50/60 Hz

Collegamento in ingresso IEC-320-C20

Cavo di alimentazione rimovibile a 16 A, da C19 a IEC-309 a 3 pin


in dotazione

Potenza in ingresso 3,3 kVA UL


3,7 kVA VDE
4 kVA PSE

Tensione di uscita 100–240 V c.a.

Massimo carico di corrente in uscita (uscita) IEC-320-C13: 12 A; IEC-320-C19: 16 A UL (a potenza ridotta)


IEC-320-C13: 10 A; IEC-320-C19: 16 A VDE
IEC-320-C13: 15 A; IEC-320-C19: 20 A PSE

Massimo carico di corrente in uscita (fase) 16 A UL (a potenza ridotta)


16 A VDE
20 A PSE

Collegamenti in uscita 7 uscite IEC-320-C13; 1 uscita IEC-320-C19

Caratteristiche fisiche

Dimensioni (A x L x P) 99,1 x 5,6 x 4,6 cm (39,0 x 2,2 x 1,8 pollici)


(la profondità non comprende i pioli)

Lunghezza del cavo di alimentazione 3 m (10 piedi)

Dimensioni con imballaggio (A x L x P) 112,4 x 16,5 x 11,4 cm (44,3 x 6,5 x 4,5 pollici)

Peso/peso con imballaggio 3,9 kg (8,7 libbre) / 5,5 kg (12,1 libbre)

Caratteristiche ambientali

Altezza massima (SLM)


Di esercizio/Di stoccaggio 0–3.000 m (0–10.000 piedi) / 0–15.000 m (0–50.000 piedi)

Temperatura
Di esercizio/Di stoccaggio Da –5 a 45 °C (da 23 a 115 °F) / da –25 a 65 °C (da –13 a 149 °F)

Umidità
Di esercizio/Di stoccaggio 5–95% umidità relativa senza condensa

Conformità

Verifiche EMC FCC parte 15 Classe A, ICES-003 Classe A, VCCI-A,


EN 55022 Classe A, EN 55024, EN 61000-3-2, EN 61000-3-3

Verifiche di sicurezza UL, VDE, PSE

Le informazioni sull’assistenza clienti e sulla garanzia sono consultabili sul sito web di APC 990-3445
all’indirizzo www.apc.com. 12/2009

© 2009 APC by Schneider Electric. Tutti i marchi commerciali sono di proprietà di Electric
Industries S.A.S., American Power Conversion Corporation o di aziende affiliate.
Unidade de distribuição de energia para rack
comutada (AP8958EU3)

Visão geral e especificações

Me nu
Main

Sc ro ll

Select
Link - Rx/ Tx

Temp/ Humidity
10 0
10/
In

O ut
Se rial Port

USB

pdu0485a
Visão geral

A unidade de distribuição de energia (PDU) para rack comutada da APC by Schneider Electric distribui
energia para dispositivos no rack. Possui um sensor que mede a corrente usada por ela e por seus
dispositivos conectados. Pode ser monitorada através das interfaces Web, Telnet, SNMP, SSH ou
InfraStruXure® Central.

Tomadas. A PDU para rack possui 7 (sete) tomadas com trava IEC-320-C13 e 1 (uma)
IEC-320-C19 . Cada tomada possui um LED verde que se acende quando a tomada está energizada.
(O recurso de travamento é compatível com os cabos de entrada com trava da APC e com os cabos
jumper com trava da APC.)

Display. O display de cristal líquido (LCD)  e os botões de entrada  permitem monitorar medições
de corrente, potência e tensão da PDU para rack. A comunicação local pode ser estabelecida através da
porta serial  e a comunicação remota através da porta de rede . As portas USB  e CAN 
permitem a transferência de dados para futuras opções de expansão. A porta do sensor ambiental 
permite o monitoramento de temperatura e umidade da sala ou do gabinete.

Cabo de energia. Um cabo de energia C19-para-IEC-309 removível de 3,0 m, 16 A, 3 pinos  é


fornecido. A PDU para rack possui 1 (uma) entrada IEC-320-C20 .

Montagem sem ferramentas. A PDU para rack possui dois prendedores para montagem sem
ferramentas  que permitem a montagem 0 U em um rack ou gabinete.
Menu
Ma in

Scroll

Select

Ma in
Me nu

Scro ll

Sele ct
Lin k - Rx /Tx

Temp /Hu midity


Link - Rx/Tx

1 00
10 /
In

Ou t
Temp/Hu midity

Ser ial Port

USB
100
1 0/
In

Out
Serial Port

USB

pdu0486a

PDU para Rack Comutada — Visão Geral e Especificações 17


Especificações

Elétricas

Tensão de entrada aceitável 100 a 240 VCA +6%, -10%

Corrente máxima de entrada (fase) 16 A UL (reduzida à capacidade nominal)


16 A VDE
20 A PSE

Frequência de entrada 50/60 Hz

Conexão de entrada IEC-320-C20

Cabo de energia C19-para-IEC-309 removível de 16 A e 3 pinos


fornecido

Potência de entrada 3,3 kVA UL


3,7 kVA VDE
4,0 kVA PSE

Tensão de saída 100 a 240 VCA

Corrente máxima de saída (tomada) IEC-320-C13: 12 A; IEC-320-C19: 16 A UL


(reduzida à capacidade nominal)
IEC-320-C13: 10 A; IEC-320-C19: 16 A VDE
IEC-320-C13: 15 A; IEC-320-C19: 20 A PSE

Corrente máxima de saída (fase) 16 A UL (reduzida à capacidade nominal)


16 A VDE
20 A PSE

Conexões de saída 7 (sete) IEC-320-C13; 1 (uma) IEC-320-C19

Físicas

Dimensões (A x L x P) 99,1 x 5,6 x 4,6 cm


(a profundidade não inclui os prendedores para
montagem sem ferramentas)

Comprimento do cabo de energia 3,0 m

Dimensões para transporte (A x L x P) 112,4 x 16,5 x 11,4 cm

Peso/peso para transporte 3,9 kg / 5,5 kg

Ambientais

Altitude máxima (acima do nível médio do mar)


Operação/armazenamento 0–3.000 m / 0 a 15.000 m

Temperatura
Operação/armazenamento –5 a 45°C / –25 a 65°C

Umidade
Operação/armazenamento 5–95% Umidade relativa, não condensante

Conformidade

Verificação EMC FCC Parte 15 Classe A, ICES-003 Classe A, VCCI-A,


EN 55022 Classe A, EN 55024, EN 61000-3-2, EN 61000-3-3

Verificação de segurança UL, VDE, PSE

Informações sobre o Serviço de Atendimento ao Cliente e sobre garantia estão disponíveis no site da Web da 990-3445
APC, www.apc.com. 12/2009

© 2009 APC by Schneider Electric. Todas as marcas comerciais são propriedade da Schneider Electric Industries
S.A.S., American Power Conversion Corporation ou de suas empresas controladas.
Zarządzana listwa zasilająca do montażu w szafie
przemysłowej (AP8958EU3)

Przegląd i specyfikacja

Me nu
Main

Sc ro ll

Select
Link - Rx/ Tx

Temp/ Humidity
10 0
10/
In

O ut
Se rial Port

USB

pdu0485a
Dane ogólne

Zarządzana listwa zasilająca (PDU) do montażu w szafie przemysłowej marki APC by Schneider
Electric zapewnia dystrybucję zasilania do urządzeń w szafie. Jest ona wyposażona w czujnik, który
mierzy prąd zużywany przez samą listwę i podłączone do niej urządzenia. Działanie listwy może być
monitorowane za pośrednictwem interfejsu bazującego na sieci Web, usłudze Telnet, protokole SNMP,
SSH lub kontrolerze InfraStruXure® Central.

Gniazda. Listwa zasilająca do montażu w szafie jest wyposażona w siedem (7) gniazd IEC-320-C13
oraz jedno (1) gniazdo IEC-320-C19; gniazda są wyposażone w blokady . Gdy gniazdo jest pod
napięciem, świeci się odpowiadająca mu zielona dioda LED. (Blokady gniazd są kompatybilne z
wejściowymi przewodami zasilającymi APC z blokadami oraz z przewodami połączeniowymi APC z
blokadami).

Wyświetlacz. Wyświetlacz ciekłokrystaliczny (LCD)  oraz przyciski wejść  umożliwiają


monitorowanie prądu, mocy i napięcia na listwie zasilającej. Możliwe jest nawiązanie komunikacji
lokalnej przez port szeregowy  oraz komunikacji zdalnej przez port sieciowy . Porty USB  i
CAN  umożliwiają przesyłanie danych do/z opcjonalnych urządzeń dodatkowych, jakie mogą zostać
wprowadzone w przyszłości. Port czujnika warunków otoczenia  umożliwia monitorowanie
temperatury i wilgotności w pomieszczeniu lub w obudowie.

Przewód zasilający. Zestaw zawiera odłączalny przewód zasilający o długości 3,0 m, zakończony z
jednej strony 3-stykowym złączem C19, a z drugiej IEC-309, o prądzie znamionowym 16 A . Listwa
zasilająca jest wyposażona w jedno (1) gniazdo wejściowe IEC-320-C20 .

Montaż bez użycia narzędzi. Listwa zasilająca do montażu w szafie jest wyposażona w dwa kołki do
mocowania bez użycia narzędzi ; umożliwiają one zamontowanie listwy w szafie lub obudowie w taki
sposób, aby nie zajmowała miejsca na sprzęt (0 U).
Menu
Main

Scroll

Select

Ma in
Me nu

Scroll

Select
Link - Rx /Tx

Temp /Humidity
100
Link - Rx/Tx

10 /
In

Ou t
Temp/Humidity

Serial Por t

USB
100
10 /
In

Ou t
Seri al Port

USB

pdu0486a

20 Zarządzana listwa zasilająca (PDU) do montażu w szafie — przegląd i specyfikacja


Dane techniczne

Parametry elektryczne

Dopuszczalne napięcie wejściowe 100-240 VAC +6%, -10%

Maksymalny prąd wejściowy (faza) 16 A UL (zredukowany znamionowy)


16 A VDE
20 A PSE

Częstotliwość na wejściu 50/60 Hz

Połączenie wejściowe IEC-320 C20

Na wyposażeniu odłączalny przewód zasilający o


obciążalności 16 A, zakończony z jednej strony 3-stykowym
złączem C19, a z drugiej IEC-309.

Zasilanie na wejściu 3,3 kVA UL


3,7 kVA VDE
4,0 kVA PSE

Napięcie na wyjściu 100–240 VAC

Maksymalny prąd na wyjściu (gniazda) IEC-320-C13: 12 A; IEC-320-C19: 16 A UL (zredukowany


znamionowy)
IEC-320-C13: 10 A; IEC-320-C19: 16 A VDE
IEC-320-C13: 15 A; IEC-320-C19: 20 A PSE

Maksymalny prąd na wyjściu (faza) 16 A UL (zredukowany znamionowy)


16 A VDE
20 A PSE

Połączenia wyjściowe Siedem (7) IEC-320-C13; jedno (1) IEC-320-C19

Parametry fizyczne

Wymiary (W x S x G) 99,1 x 5,6 x 4,6 cm (39,0 x 2,2 x 1,8 cala)


(głębokość bez uwzględnienia kołków do mocowania)

Długość przewodu zasilającego 3,0 m (10 stóp)

Wymiary transportowe (W x S x G) 112,4 x 16,5 x 11,4 cm (44,3 x 6,5 x 4,5 cala)

Ciężar/ciężar transportowy 3,9 kg (8,7 funta) / 5,5 kg (12,1 funta)

Parametry środowiska

Maksymalna wysokość (n.p.m)


Eksploatacja/Przechowywanie 0–3 000 m (0–10 000 st.) / 0–15 000 m (0–50 000 st.)

Temperatura
Eksploatacja/Przechowywanie Od –5 do 45°C (od 23 do 115°F) / od –25 do 65°C (od –13 do
149°F)

Wilgotność
Eksploatacja/Przechowywanie 5–95% — wilg. względna, bez kondensacji

Zgodność z normami

Atesty kompatybilności elektromagnetycznej (EMC) FCC Part 15 klasa A, ICES-003 klasa A, VCCI-A,
EN 55022 klasa A, EN 55024, EN 61000-3-2, EN 61000-3-3

Atesty bezpieczeństwa UL, VDE, PSE

Informacje dotyczące gwarancji oraz pomocy technicznej znajdują się na stronie internetowej 990-3445
firmy APC: www.apc.com. 12/2009

© 2009 APC by Schneider Electric. Wszystkie znaki towarowe są własnością Schneider Electric
Industries S.A.S., American Power Conversion Corporation lub ich przedsiębiorstw afiliowanych.
Управляемое устройство распределения
электропитания для монтажа в стойку (AP8958EU3)

Описание и характеристики

Me nu
Main

Sc ro ll

Select
Link - Rx/ Tx

Temp/ Humidity
10 0
10/
In

O ut
Se rial Port

USB

pdu0485a
Обзор

Устройство Switched Rack PDU APC компании Schneider Electric предназначено для
распределения электропитания между устройствами, смонтированными в стойке. Оно оснащено
датчиком, который измеряет ток, используемый данным блоком и подключенными к нему
устройствами. Мониторинг блока распределения питания можно осуществлять посредством веб-
интерфейса, а также с помощью интерфейсов Telnet, SNMP, SSH или InfraStruXure® Central.

Разъемы. Устройство Rack PDU имеет семь (7) разъемов IEC-320-C13 и один (1) IEC-320-C19
запорный разъем . Каждому разъему соответствует зеленый индикатор; он загорается при
активировании разъема. (Функция запирания совместима с запорными входными шнурами APC,
а также с запорными соединительными шнурами APC.)

Дисплей. Жидкокристаллический дисплей (LCD)  и клавиши ввода  позволяют отслеживать


значения тока, мощности и напряжения в устройстве Rack PDU. Локальное соединение можно
установить через последовательный порт , а удаленное соединение – через сетевой порт .
Порты USB  и CAN  обеспечивают возможность передачи данных в случае расширения
функций. Порт датчиков окружающей среды  позволяет отслеживать температуру и влажность
помещения или монтажного шкафа.

Кабель питания. Отсоединяемый кабель питания 3,0 м, 16 A, 3-контактный C19-to-IEC-309  в


комплекте. Устройство Rack PDU имеет один (1) ввод IEC-320-C20 .

Монтаж без применения инструментов. В устройстве Rack PDU есть два монтажных
ограничителя  для монтажа в шкаф или стойку 0 U.
Menu
Main

Scroll

Select

Ma in
Menu

Scro ll

Sele ct
Link - Rx /Tx

Temp /Humidity
Link - Rx/Tx

100
10 /
In

Out
Temp/Humidity

Serial Port

USB
100
1 0/
In

Ou t
Seri al Port

USB

pdu0486a

Устройство Switched Rack PDU – описание и характеристики 23


Технические характеристики

Электрические компоненты

Допустимое входное напряжение 100-240 В переменного тока +6%, -10%

Максимальный входной ток (по фазам) 16 A UL (с пониженными характеристиками)


16 A VDE
20 A PSE

Частота 50/60 Гц

Входное соединение IEC-320-C20

Отсоединяемый кабель питания 16 А, 3-контактный


C19-to-IEC-309

Входная мощность 3,3 кВА UL


3,7 кВА VDE
4,0 кВА PSE

Выходное напряжение 100-240 В переменного тока

Максимальный выходной ток (разъем) IEC-320-C13: 12 A; IEC-320-C19: 16 A UL (с пониженными


характеристиками)
IEC-320-C13: 10 A; IEC-320-C19: 16 A VDE
IEC-320-C13: 15 A; IEC-320-C19: 20 A PSE

Максимальный выходной ток (по фазам) 16 A UL (с пониженными характеристиками)


16 A VDE
20 A PSE

Выходные соединения Семь (7) IEC-320-C13; одно (1) IEC-320-C19

Физические параметры

Габариты (В x Ш x Г) 99,1 x 5,6 x 4,6 см


(глубина без учета штифтов для монтажа без
инструментов)

Длина кабеля питания 3,0 м

Габариты при транспортировке (В x Ш x Г) 112,4 x 16,5 x 11,4 см

Вес/вес в упаковке 3,9 кг / 5,5 кг

Окружающая среда

Максимальная высота (над средним уровнем моря)


При эксплуатации/При хранении 0–3 000 м / 0–15 000 м

Температура
При эксплуатации/При хранении –5 – 45°C / –25 – 65°C

Влажность
При эксплуатации/При хранении 5–95% Относительная влажность, без конденсации

Соответствие стандартам

Подтверждение EMC Часть 15 правил FCC, Класс A, ICES-003, Класс A, VCCI-A


EN 55022 класс A, EN 55024, EN 61000-3-2, EN 61000-3-3

Подтверждение эксплуатационной безопасности UL, VDE, PSE

Техническую поддержку и сведения о гарантийном обслуживании можно получить на 990-3445


веб-сайте компании APC по адресу www.apc.com. 12/2009

© 2009 APC, компания Schneider Electric. Все товарные знаки являются собственностью компании Schneider
Electric Industries S.A.S., American Power Conversion Corporation и их аффилированных компаний.
Anahtarlı Kabin İçi Dikey Montajlı Güç Dağıtım Birimi
(AP8958EU3)

Genel Bakış ve Teknik Özellikler

Me nu
Main

Sc ro ll

Select
Link - Rx/ Tx

Temp/ Humidity
10 0
10/
In

O ut
Se rial Port

USB

pdu0485a
Genel Bakış

APC by Schneider Electric Anahtarlı Kabin İçi Dikey Montajlı Güç Dağıtım Birimi (PDU) kabin
içindeki cihazlara güç dağıtır. Kendisinin ve ona bağlı cihazların kullandığı akımı ölçen bir sensöre
sahiptir. Web, Telnet, SNMP veya InfraStruXure® Central arabirimlerinden de takip edilebilir.

Çıkışlar. Kabin İçi Dikey Montajlı PDU’da yedi (7) adet IEC-320-C13 ve bir (1) adet IEC-320-C19
kilitli çıkış  bulunmaktadır. Çıkışa voltaj geldiğinde ilgili yeşil LED yanar. (Kilitleme özelliği APC
kilitli giriş kabloları ve APC kilitli jumper kablolarıyla uyumludur.)

Görüntü arabirimi. Likit kristal ekran (LCD)  ve giriş düğmeleri  Kabin İçi Dikey Montajlı
PDU'nın akım, güç ve voltaj değerlerini takip etmenizi sağlar. Seri port  aracılığıyla yerel iletişim ve
ağ portu  aracılığıyla uzaktan iletişim kurulabilir. USB  ve CAN  portları sonraki genişletme
seçenekleri için veri transferi sağlar. Ortam sensörü portu  odanın veya dolabın sıcaklık ve nem
değerlerinin takip edilmesini sağlar.

Güç kablosu. Çıkarılabilir 3,0 m (10 ft), 16 A, 3-pim C19-IEC-309 güç kablosu  ürünle birlikte
verilmektedir. Kabin İçi Dikey Montajlı PDU'da bir (1) adet IEC-320-C20 giriş  bulunmaktadır.

Aletsiz montaj. Kabin İçi Dikey Montajlı PDU'da iki adet aletsiz montaj mandalı bulunmaktadır  bu
mandallar raf veya dolaba 0 U montaj içindir.
Menu
Main

Scroll

Select

Main
Menu

Scroll

Select
Link - Rx /Tx

Temp/Humidity
Link - Rx/Tx

100
10/
In

Out
Temp/Humidity

Serial Port

USB
100
10/
In

Out
Serial Port

USB

pdu0486a

26 Anahtarlı Kabin İçi Dikey Montajlı PDU—Genel Bakış ve Teknik Özellikler


Teknik Özellikler

Elektriksel

Uygun giriş gerilimi 100–240 VAC +%6, -%10

Maksimum giriş akımı (faz) 16 A UL (düşürülmüş)


16 A VDE
20 A PSE

Giriş frekansı 50/60 Hz

Giriş bağlantısı IEC-320-C20

Çıkarılabilir 16 A, 3-pim C19-IEC-309 güç kablosu ürünle


birlikte verilmektedir

Giriş gücü 3,3 kVA UL


3,7 kVA VDE
4,0 kVA PSE

Çıkış voltajı 100–240 VAC

Maksimum çıkış akımı (çıkış) IEC-320-C13: 12 A; IEC-320-C19: 16 A UL (düşürülmüş)


IEC-320-C13: 10 A; IEC-320-C19: 16 A VDE
IEC-320-C13: 15 A; IEC-320-C19: 20 A PSE

Maksimum çıkış akımı (faz) 16 A UL (düşürülmüş)


16 A VDE
20 A PSE

Çıkış bağlantıları Yedi (7) adet IEC-320-C13; bir (1) adet IEC-320-C19

Fiziksel

Boyutlar (Y x G x D) 99,1 x 5,6 x 4,6 cm (39,0 x 2,2 x 1,8 inç)


(derinlik aletsiz montaj mandallarını içermez)

Güç kablosu uzunluğu 3,0 m (10 ft)

Nakliye boyutları (Y x G x D) 112,4 x 16,5 x 11,4 cm (44,3 x 6,5 x 4,5 inç)

Ağırlık/nakliye ağırlığı 3,9 kg (8,7 lb) / 5,5 kg (12,1 lb)

Çevresel

Maksimum yükseklik (Ortalama deniz seviyesinin


üzerinde)
Çalışma/Depolama 0–3000 m (0–10.000 ft) / 0–15.000 m (0–50.000 ft)

Sıcaklık
Çalışma/Depolama -5 – 45°C (23 – 115°F) / -25 – 65°C (-13 – 149°F)

Nem
Çalışma/Depolama %5–95 Bağıl nem, yoğunlaşmayan

Uyum

EMC onayı FCC Bölümü 15 A Sınıfı, ICES-003 A Sınıfı, VCCI-A


EN 55022 A Sınıfı, EN 55024, EN 61000-3-2, EN 61000-3-3

Güvenlik normları UL, VDE, PSE

Müşteri desteği ve garanti bilgisine APC web sitesinden, www.apc.com, ulaşabilirsiniz. 990-3445
12/2009
© 2009 APC by Schneider Electric. Bütün ticari markalar Schneider Electric Industries S.A.S.,
American Power Conversion Corporation veya bağlı kuruluşlarına aittir.