Fresh HDO Storage Tank
Fresh HDO Storage Tank
DESIGN CALCULATIONS
CLIENT
PROJECT
JOB NO.
FIELD FABRICATED, VERTICAL TANK, FLAT BOTTOM,
TANK DESCRIPTIO SUPPORTED CONE ROOF WITH CENTRAL COLUMN.and
2 -GIRDER RING
ITEM NO
Rev. Description Prepared ReviewedApproved Date
0 Mechanical Calculation H.M H.M M.B 25/2/2013
1 .1 TANK
Item number : 0
Roof ( Open/Close ) : Close
Type of roof ( Cone-roof / Dome-roof / Flat-roof / NA ) : Fixed cone w/col,s
Roof slop 1 : 6
Inside diameter , Di (corr. diameter38203.2 )mm = 38,200 mm
Nominal diameter, Dn = 38,212 mm
Tank height ,H = 9,144 mm
Free Board = 604 mm
Specific gravity of operating liquid , S.G. (Design) = 0.900
Maximum design liquid level, HHL = 8,540 mm
Min.Design Liquid level ,LLL = 250 mm
Insulation thickness = 50 mm
Bottom Slope 1 : 120
Depth of liquid outside level indicator scale = = 159 mm
12 LOADS
Wind Speed (Fatest mile wind speed ) = 145 kmph
Max.Design Wind Speed (3 seconds gust Wind ) = 145 kmph
Live Load , @ LL = 120 kg/m2
Rain Rates @ Misc.loads = 20 mm/hr
13 SEISMIC (UBC)
Tank Location (Elmadina)
Zone Factor = 0.75
Importance Factor = 1.3
Site coefficient = 1.5
Site Class = D
15 PUMPING RATE
Pumping in = 1500 m³/hr
pumping out = 1500 m³/hr
16 CAPACITYS
Nominal capacity , V = 10,480 m³
Net capacity (based on LLL) = 9,501 m³
Operating Capacity (based on Operating level only) = 9,788 m³
Under Reading Level indicator Capacity = 124 m³
17 MATERIAL & MECHANICAL PROPERTIES
18 STEEL PLATESPROPERTIES
1) Material HIC NO
2) Material Impact test NO
3) Material PWHC NO
4) Material ARAMCO APPROVED NO
5) Material PMI NO
SHELL THICKNESS CALCULATION BY ONE-FOOT METHOD
2 .0 SHELL DESIGN
2 .1 GEOMETRIC DATA
Plate size used : 2,480 mm
Shell plate min. width as per API 650 : 1,870 mm
No Material Specified Specified Yield stress Max. allow Max. allow Corrosion
used min. tensile min. yield reduction fac design hydro.test allowance
stress stress ( App. M ) stress stress
St (N/mm²) Sy (Nmm²) k Sd (N/mm²) St (N/mm²) c.a (mm)
1 ASTM A516 Gr60 485.00 260.00 1.000 173 195.00 1.60
2 ASTM A516 Gr60 485.00 260.00 1.000 173 195.00 1.60
3 ASTM A516 Gr60 485.00 260.00 1.000 173 195.00 1.60
4 ASTM A516 Gr60 485.00 260.00 1.000 173 195.00 1.60
5 - - - - - - -
6 - - - - - - -
7 - - - - - - -
8 - - - - - - -
9 - - - - - - -
- - - - - - -
- - - - - - -
- - - - - - -
2 .3 SPECIFIED MINIMUM SHELL THICKNESS
Specification API 650 11th Edition & 32-SAMS-05 :
Minimum thickness as per API 650 cl 5.6.1.1 = 8.00 mm
Minimum thickness provided = 8.00 mm
2 .4 SHELL THICKNESS CALCULATION BY ONE-FOOT METHOD ( CLAUSE 5.6.3.1 )
SI METRIC UNIT :-
Design shell thickness, ( in mm )
4.9Dn ( [H+Hi] - 0.3 ).G
td = + c.a
Sd
Hydrostatic test shell thickness , ( in mm )
4.9Dn ( H - 0.3 )
tt =
St
Gravitational force = 9.81 m/s
height 9.144 m
inclined angle 41 deg.
step 195 mm
width of tread 245 mm
No.of tread 47
total weight of tread 469 kg
Flat Bars 437.65 kg
No.of Plat,grating 2
Platforms and grating 252.36587 kg
W,t of pipes if duble handrails 223.0043236 kg
Total weight of stair 1381.94 kg 1,381.94 ton Stair length 13.94 m
###
(iii) Platforms Y
Platforms Claculations
Width of platform = 750 mm
We select grating type 32x5 mm
Unit w,t of Grating = 48.8 kg/m^2
total length of platform = 120 m
Supportes channels-UPN 160 = 1,355 Kg
Platform Skech
BOTTOM & ANNULAR PLATE DESIGN
3 .0 BOTTOM PLATE & ANNULAR PLATE DESIGN
Annular plate used ? ( yes/no ) : YES
BOTTOM PLATE
(i) Minimum thickness as per API 650 Clause 5.4.1 = 6.00 mm
Minimum thickness required ( 1.60 mm c.a ) = 7.60 mm
Therefore, use thickness of 8.00 mm (tb) is satisfactory.
Detail -b
SI METRIC UNIT :-
Shell Shell Actual Transposed Since H1 > H2, therefore the intermediate
course thickness width width wind girder is/are Not required
tsc.cor W Wtr
(mm) (mm) (mm) Minimum number of intermediate wind
1 10.40 2,480 737 girders required,
2 8.40 2,480 1,257 = 0
3 8.40 2,204 1,117
4 8.40 1,980 1,003 Location of intermediate wind girders from
top of tank,
L1 = - mm
L2 = - mm
L3 = - mm
L4 = - mm
L5 = - mm
(a) Required minimum section modulus of intermediate wind girder ( clause 5.9.7.6 )
SI METRIC UNIT :-
tsc.cor = 8.40 mm
D= 38214 mm
20 mm 200 mm
X
C1
20 2
L1=16.tsc.cor = 134 mm
200 m
m 3
1
X
A Y AY h A.h² I = (bd³)/12
(mm²) (mm) (mm³) (mm) (mm4) (mm4)
1 2257.92 4.20 9483.264 4.2 39829.7088 13,277
2 4000 108.4 433600 108.4 47002240 13333333.33
3 4,000 218.40 873,600 90.04 32,430,446 133,333
TOTAL 10,258 1,316,683 79,472,516 13,479,943
Neutral axis of combined section, C1 = 128 mm
Moment of inertia of section , Ix-x = 92,952,459 mm4
Section modulus available, Za = 724,167 mm³
Since Za > Zmin , therefore the angle size selected is satisfactory.
Girder stiffened as per clause 5.9 NO
at distance 4800 mm & No.of stiffeners = 25 stiffener
Wind Girder Weight @Stiffen= 9926 kg
Clean Out Door Calculations
Clean Out Door Size 36 in 48 in
1 )- Claculations of shell reinforced plate
As per clause 5.7.7.4 required cross -section area of the reinforcement
Over the top of the opening
Acs <=K1*h*t/2 6364.8
where
Acs =cross-sectional area of the reinforcement over the top of the opening ,in mm^2
k1= area of coefficient from fig. 1.36
h =Vertical height of Clear Opening ,in mm 900 mm
b=horizontal width of clear opening ,in mm 1200 mm
t= Calculated thickness of the lowst shell course exclusive of any corr. All. 10.40 mm
computing for vertical axis in fig. 0.5
(H+8.8)D+71.5 123 t
1.408 h 4.9D (H-0.3) 0.5
Where
H= Max.design liquid level 9m
D= Nominal tank diameter 38 m
G=sp. gravity not less than 0.90
Unite scale horiz.=0.004
therefore
Value of K1 from FIG .5-11 1.36
Min.Cross -Sectional area ,Acs 6364.8 mm^2
as per clause 3.7.7.5 max .height of reinf 1350 mm
Dimension of reinforcing plate (RF) Provided
Ap =tpx(L-h)
Where tp=thickness of RF plate = 16.00 mm
L=hieght of RF Plate = 1350 mm
h=height of clear opening = 900 mm
Ap 7200 mm^2 safe area
Calculation of bottom reinforcing plate
As per clause 5.7.7.6 required min.thickness of bottom reinforcing plate
tb =( h^2/360000)+( b/170)*sqrt(HG) 22.5 mm
Provide thickness 24.0 mm
Clean Out Door Wight Clean Out Door Weight 7,906 kg
8,0 ROOF Design
8,1 EVALUATION OF ROOF THICKNESS
(i) Tank
Tank Raduis = 19 m
Roof slop 1 : 6
Roof thickness = 6.00 mm
Center column Cap diameter ,Dcap = 2100 mm
RRoof slope, ß° = 9.4695343 °
Roof height , Hr = 3,187 mm
Insulation thickness, ti = 50 mm
Momen arm of uplift Wind force on Roof =OD/2 = 9.55 m
Plan proj.area of Roof for wind Moment = π* R 2 = 286.5211 mm²
(ii) No.of Rafters = 70 Nos.
Max spacing bet,n rafters ,L =Tank primeter / No.of R = 1714.41 mm
Max spacing between rafter as per clause 5.10.4.4 = 1916.38 mm Safe
Min.thk.of Roof Plates as per 5.10.2.2 = 4.78 mm
Min.thk.of Roof Plates including corrosion = 4.78 mm
(iii) Roof Loads per appendix R
* Dead Load DL = 104.10 kg/m2 = 21.332 psf
* Vaccum PE = 25.49 kg/m2 = 5.22396 psf
* Live Load LL = 123.00 kg/m2 = 25.2049 psf
* Wind Load WL = 8 kg/m2 = 1.59825 psf
* Internal Pressure
PI ,DL4 = 210.87727 kg/m2 = 43.2126 psf
Loads combinations
### DL+PE+LL 252.59 Kg/m2 51.7608 psf
### DL+PI+WL 114.58 Kg/m2 23.4788 psf
### DL+PI+WL+LL 8.42 Kg/m2 1.72608 psf
### DL+LL+PI 16.22 Kg/m2 3.32433 psf
### DL+LL+PE 252.59 Kg/m2 51.7608 psf
### Misc. 20% 50.52 Kg/m2 10.3522 psf
### Max.load 303.11 Kg/m2 62.113 psf
Max. bending moment assumed simply supported from one side and continous from other side
M= UT*L2/10 = 8909.08 Kg.cm/m
As per 5.10.3.1 .stress should not exceed limitations specified in AISC
Fa =0.75 Fy = 1988.4462 Kg/cm2
Req.Plate thickness of Roof ,tr =(6*M /(B*Fb))0.5= 5.1848368 mm
where i
* Plate width B = 100 cm
* Corrosion allowance = 0.00 mm
Min.thickness including corrosion allowance = 5.2 mm
Provided thickness of Roof Plates = 6.0 mm
(iv) ROOF PLATES JOINTS& WIGHT
DR =Ring Rafter
19.1 m
Center Col. UPN 200
Pipe 36 "ØSCH 40 35 nos.
No. of Rafters
Diameter of the tank, in m (D) = 38.21 m
Diameter of the ring, in m (DR) = 19.11 m
Total no. of rafters on the circumference of the shell, (nM+nS) = 70.00 Nos
Provided rafter center line spacing, in m = 1.715 m <= 1.916 m O.K.
Span L = 9.68 m
Spacing at shell = Л *D/(ns+nM) S = 1.715 m
Spacing at ring Sr = 0.857 m
Average uniform distributed load = wunif. * (S+Sr)*UT/ = 390 kg/m
Using 35 Nos IPE 360
Self weight = 57.1 kg/m
Beam flange Depth = 360 mm
Total uniform load acting on the beam including self weight, ws
ws = 447 kg/m
Sectional modulus Z = 713.16 cm³
Moment of Inertia Ix = 12836.91 cm4
As per AISC for uniformly distributed load
Maximum bending moment acting on the beam M = ws*L²/8 5240.62 = kg-m
Allowable bending stress of A36 = 0.66Fy ,= 173 Mpa
fall. = 1177 kg/cm2
Modulus of Elasticity E = 200000 Mpa
Max.Bending stress , fb.max. = M/Z = 734.84 kg/cm2 Safe
Sectional modulus req., in cm³ Z = M*100/f all. = 445.19 cm³ > 713.16 cm³Safe
Use 35 NOS. IPE 360 As secondary rafters.
Beam deflection = 5*ws*L4 / (384*E*Ix) = 1.899 cm Actual
Max.Deflection Allowable = L/360 = 2.690 cm Accepted
Total compressive load acting on the column including self weig = 217793 kgs
As per AISC, Slenderness ratio,K L/r, max = 18 = 39.0 < 180 O.K.
Fy = Yield stress of the pipe column = 1177 kg/cm²
= 115 Mpa
Calculations Max. allowable stress for Central Column
P=total Roof Load Supported by column = 212602 kg
Fa =Allowable Compressive Stress (per API -650 5.10.3.4 )
Per API 650 5.10.3.3
As per AISC, Slenderness ratio,K =L/r, max = 180
Raduis of Gyration of Column required = 68.504473 mm
Raduis of Gyration of Column = 316.50 mm >>>>>>>>Accepted
Cc = Column Selenderness Ratio = SQRT (2 ∏^2 x E / Fy )
Where :
E=Modulus of Elasticity for Column material at design tempreature = 199000 Mpa
Fy= Yield stress for cloumns material at design tempreature = 115 Mpa
Selendreness Ratio ,K = 38.959695
Cc = 184.5
Fs = Factor Saf5/3 + 3 * k /(8*(Cc))-k ^3/(8*(Cc)^3) = 1.7
Using AISC specification Formulas Section E 2 , let K=1
k = 39.0 Since KL/r < Cc : Equation (1)>>>Applicable
F =Actual induced Stress for the Column =(P + Column self weight) / A
Fa =(([1-K 2/ (2*Cc^2) ]* FY) / F.S) = 64.7 Mpa--------------(1)
Fa =(12 π 2*E ) / ( 23 * K ^2) = 675.1 Mpa--------------(2)
F = 40.0 Mpa >>>>>Safe
Using Central CPipe 36 "ØSCH 40 Safe
Sizing of Col.Cap
Cap Diameter 2m
Stiffeners of Cap 713 mm X 356.5 x 15 mm
Top Beams w,t = 7.968 kg
Weight of Cap = 1860.4982 kg
(v) Sizing of Center Column Base Plate
Maximum load on the column = 217793 kgs
Considering center column is resting on concrete foundation
Ultimate strength of concrete (28 day) = 300 kg/cm²
Allowable compressive strength, fc = 90 kg/cm²
Using base plate 1014 X 1014 X ###mm
Actual bearing perssure on concrete = Load / ba = 26.98 kg/cm² < 90
Outside diameter of the column = 914 mm Safe
Overhanging of the base plate, = 5 cm
Considering section of unit width, = 1 cm
Maximum bending moment , M =b.w.L2 / 2= 337.29 kg.cm
= 6.62626325 in2
Sa=allo. stress for tension and compression rings (table 4 and 5) = 15,000.0 psi
Safe
Cap = 1,860.5 kg
Col. = 5,191.3 kg
BasePlate+Guide angles = 187.8 kg
Rafters = 77,811.8 kg
Connections = 945.1 kg
Bracing = 689.1 kg
PLATES = 56,869.5 kg
Total w,t = ### kg
11 HEATING COIL Reff. Pressure Vessel Manual,procedure 6-8 & ASME
1.0
Stem in
Condensate
Steam Coil Data
1.1 Operating Pressure 4 ata
1.2 Pressure at inlet of Coil heater 4 ata
1.3 Steam temp.at design pressure of coil 168 0
C
Wind l H
shell, FS
where:
Mpi = Moment about the shell-to-bottom joint from design internal pressure
= Uplift thrust on roof due to internal pressure x 1/2 tank diameter
= ( 1/4 p. D2. Pi ). 1/2. D = 45,311,634,378 Nmm
MDL = Moment about the shell-to-bottom joint from the weight of the
shell and the roof supported by the shell.
= 0.5. D. WDL = 16,171,503,154 Nmm
MF = Moment about the shell-to-bottom joint from liquid weight (wa) = 2,329,647,053,663 Nmm
= (wa. p D). D
1000 2
I
Ai = 2.5 Q Fa So = 0.09
Rwi
When Tc ≤ TL
Ts I
c= 2.5 K Q Fa So ≤ Ai = -
Tc Rwc
When Tc > TL
Ts .TL I
c= 2.5 K Q Fa So ≤ Ai = 0.008656886
Tc 2
Rwc
where
Q = Scaling factor = 1
K = Coefficient to adjust the spectral damping from 5% - 0.5% = 1.5
Fa = Acceleration based site coefficient as per Table E-1 = 1.2
Fv = Velocity-based site coefficient as per Table E-2 = 2.152
So = Substitution for seismic peak ground acceleration Sp = 0.1
Rwi = Force reduction coefficient for impulsive mode as per Table E-4= 4
Rwc = Force reduction coefficient for convective mode as per Table E-= 2
TL = Regional dependent transition period for longer period = 4s
ground motion
Tc = First mode sloshing wave period for convective mode = 7.82 s
Ts = Fv. S1/ Fa. Ss = 0.51
7 .1.3CONVECTIVE (SLOSHING ) PERIOD
The first mode sloshing wave period,
Tc = 1.8 Ks √ D = 7.82 s
where,
Ks = sloshing period coefficient
0.578
Ks = 3.68 H = 0.70
tanh
D
Fv . S1
Ts =
Fa . Ss
= 0.51
where,
Fa = Acceleration based site coefficient (at 0.2 sec perios)
as per Table E-1 = 1.2
Fv = Velocity-based site coefficient (at 1 sec. period) as per Table E- = 2.1520
Since /H > 1.333 , effective impulsive portion of the liquid weight, Wi = ### N
D 3.67H
Wc = 0.230 tanh . Wp = ### N
H D
7 .2.2CENTER OF ACTION FOR EFFECTIVE LATERAL FORCES
The height from the bottom of the Tank Shell to the center of action of the lateral
seismic forces related to the impulsive liquid force for ringwall moment,
Xi = 0.375H = 3202.5 mm
D
Xi = 0.5 - 0.094 .H = 0 mm
H
The height from the bottom of the Tank Shell to the center of action of the lateral
seismic forces related to the convective liquid force for ringwall moment,
3.67 H
cosh -1
D
c = 1.0 - .H = 4,494.44 mm
3.67H 3.67 H
sinh
D D
7 .2.3OVERTURNING MOMENT
The seismic overturning moment at the base of the tank shell shall be the SRSS summation of the
impulsive and convective components multiplied by the respective moment arms to the center of action of
the forces.
Ringwall moment,
Mrw = [Ai ( Wi. Xi + Ws. Xs + Wr. Xr)]2 + [Ac (Wc. Xc)]2 = 9102868542 Nmm
= 9102868.542 Nm
7 .2.4SHEAR FORCE
The seismic base shear shall be defined as the SRSS combination of the impulsive and convective components.
Anchorage Ratio, J
Mrw
J= = 0.09
D ( Wt (1 - 0.4 Av) + Wa )
2
where,
Av = Vertical earthquake acceleration coefficient = 0.7
Wt = Tank and roof weight acting at base of shell = 35.92 N/mm
wa = Resisting force of the annulus = 47.50 N/mm
If the thickness of the bottom plate under the shell is thicker than the remainder
of the bottom, then the minimum radial width of the bottom plate,
Fy
L= 0.01723 ta = 1,344.49 mm
H. Ge
The maximum width of annulus for determining the resisting force, 0.035 = 1,337.00 mm
When Tc > 4
Af = K. SD1. I. 4 2.5 K Q Fa So 4Ts = 0.02
=
Tc 2 Tc 2
For SUG III
When Tc ≤ TL
Af = K. SD1 1 2.5 K Q Fa So Ts = 0.03
=
Tc Tc
When Tc > TL
Af = K. SD1 TL 2.5 K Q Fa So Ts. TL = 0.02
=
Tc 2 Tc 2
d b
twdt
a e
h hg tm
g ta
J
9 7 ANCHOR CHAIR DESIGN
AISI 'Steel Plate Engr Data' Dec. 92, Vol. 2, Part VII
stresses at the Top Plate including axial stress due to chair height as per AISI
Top Plate stress =P*e/ tm 2 *K
where K= 1.32 * Z / [(1.43*a*h2 / R*tm ) +(4*a*h2)0.333] + 0.031/(R*tm)0.5
Z = 1/ [ 0.1777*a*ta / (R*tm )0.5 + (ta /tm )2 +1]
Z =0.40107349
K =0.00200643
Top Plate stress σ th = 2.2973901 kpa
pass
t min.
=1.23 (SI *HTS*PS )0.4 *Dc0.6/E0.4 t min.corr. = 0.27 in
Min shell thickness req.at corroded condtions t min.corr. = 7 mm
Min.shell thickness (corroded)Provided tsmin. = 6.40 mm
t min.corr. > tsmin.
Wstiff.
Radial Load (V1)
as per postion of stiffener (far from bottom & roof) we consider Xshell/X cone =0
A stiff. = 85 mm2
We consider Stiffener section L 150 X 150 X 15
AL = 4275 mm2
Pass
6 8 VENT CALCULATION
We Assume the is fully air tighted and there is must be created apressure in the tank during the filling of liquid
.since the tank is fully closed.this pressure might be caused to lift the roof plate from tank
so we consider to provide engough vent opening so that the pressure inside tank would be lesser
than of roof acting Dead Load acting on roof plate
ITEM NO : 0
1 GENERAL
Design Type of roof
code : API 650 11th Edition fixed
: conical w/col,s
Inside Tank height
diameter : 38,200 mm : 9,144 mm
Steel density Roof plates lapping Annular/Bottom plates lapping
Shell / Btm : 7,850 kg/m³ factor : 25mm factor : 25 mm
Roof : 7,850 kg/m³
2 SHELL COURSES
3 BOTTOM PLATES
ANNULAR RING Y
Material Thickness Width Weight
(mm) (mm) (kg)
ASTM A516 Gr60 12.00 1,100 6,297 = 6,297 kg
BOTTOM PLATES
Material Thickness Outside Dia. Weight
(mm) (mm) (kg)
ASTM A516 Gr60 8.00 37,244 70,127.1 = 70,127 kg
7 NOZZLES Y
Total weight of nozzles 2,500 = 2,500 kg
11 PLATFORMS Y
Platform Weight 5,860.11 Kg 5,860 = 5,860 kg
12 ROOF HANDRAILS
Handrails weight 1,987.39 Kg 1,987 = 1,987 kg
13 ROOF STRUCTURE `
(i) ROOF RAFTERS
Material Weight (kg)
ASTM A36 77,812 = 77,812 kg
(iv) CENTER COL,S W/END CAPS AND BASE PLATES Y
Material Size Weight (kg)
ASTM 106 GR BPipe 36 "ØSCH 40 7239.54 = 7,240 kg
14 ROOF PLATES
Material Thickness Weight
(mm) (kg)
ASTM A516 Gr60 6.00 56,869 = 56,869 kg
15 MANHOLES ( FABRICATED PLATES) Y Weight
Material QTY (kg)
ASTM A516 Gr60 1 275 275 kg
16 BOLTS Y
Material QTY (kg)
ASTM A 193GR B7 /A194 GR 2H H. 2500 0.25 625 kg
18 CLEAN OUT DOOR Y
ASTM A516 Gr60 (kg)
7,905.74 7,906 kg
20 ANCHOR BLOTS QTY N (kg)
0 1 0 kg
22 SUMP DRAIN Y
QTY (kg)
1 375.00 375 kg
23 EXTERNAL PIPES (INTAK & OVER FLOW) N
(kg)
2,500 - kg