Basics of Se Engineering
Basics of Se Engineering
D = 6.0 kips
L = 3.0 kips
For the required “design strength” check, both Equations (12-17) and (12-18) must be
checked.
P = 1.2 D + f 1 L + E m (12-17)
Commentary
For allowable stress design, the timber column must be checked for a compression
load of 28.3 kips and a tension load of 14.2 kips . In making this “design strength”
check, §1630.8.2.1 permits use of an allowable stress increase of 1.7 and a resistance
factor, φ , of 1.0 . The 1.7 increase is not to be combined with the one-third increase
permitted by §1612.3.2, but may be combined with the duration of load increase
C D = 1.33 given in Table 2.3.2 of Chapter 23, Division III. The resulting “design
strength” = (1.7 )(1.0)(1.33) (allowable stress). This also applies to the mechanical
hold-down element required to resist the tension load.
The purpose of the “design strength” check is to check the column for higher and,
hopefully, more realistic loads that it will be required to carry because of the
discontinuity in the shear wall at the first floor. This is done by increasing the normal
seismic load in the column, E h , by the factor Ω o = 2.8 .
&-
7 , $%(4'3'(
Foundation reports usually provide soil bearing pressures on an allowable stress
design basis while seismic forces in the 1997 UBC, and most concrete design, are on
a strength design basis. The purpose of this example is to illustrate footing design
under this situation.
A spread footing supports a reinforced concrete column. The soil classification at the
site is sand (SW). The following information is given:
P
Zone 4 Grade
M
ρ = 1.0 for structural system V
PD = 80 k M D = 15 k - ft 4'
2'
PL = 30 k M L = 6 k - ft
PE = ± 40 k V E = 30 k M E = ± 210 k - ft
Snow load S = 0
E
D+L+ (12-13)
1.4
E
0.9 D ± (12-16-1)
1.4
Because foundation investigation reports for buildings typically specify bearing
pressures on an allowable stress design basis, criteria for determining footing size are
also on this basis.
E = ρE h + E v (30-1)
E = ρE h = (1.0 ) E h
Table 18-1-A of §1805 gives the allowable foundation pressure, lateral bearing
pressure, and the lateral sliding friction coefficient. These are default values to be
used in lieu of site-specific recommendations given in a foundation report for the
building. They will be used in this example.
For the sand (SW) class of material and footing depth of 4 feet, the allowable
foundation pressure p a is
E P 40
Pa = D + L + = PD + PL + E = 80 + 30 + = 138.6 kips (12-13)
1.4 1.4 1.4
E M 210
Ma = D + L + = M D + M L + E = 15 + 6 + = 171.0 k - ft (12-13)
1.4 1.4 1.4
BL2 9 3
A = BL = 81 ft 2 , S= = = 121.5 ft 3
6 6
Pa M a 138.6 171.0
p= + = + = 1.71 + 1.41 = 3.12 ksf
A S 81 121.5
P
= 0.9 PD ± E = 0.9 (80) ±
E 40
Pa = 0.9 D ± = 100.6 kips or 43.4 kips (12-16-1)
1.4 1.4 1.4
M
= 0.9 M D ± E = 0.9 (15) ±
E 210
M a = 0.9 D ± = 163.5 k - ft or 136.5 k - ft
1.4 1.4 1.4
(12-16-1)
M a 163.5 k - ft 136.5 k - ft
Eccentricity e = = = 1.63 ft, or = .15 ft, ∴ e = 3.15 ft governs.
Pa 100.6 43.4
L 9 L
e> = = 1.5 ft (where is the limit of the kern area)
6 6 6
Since e = 3.15 > 1.5, there is partial uplift, and a triangular pressure distribution is
assumed to occur.
Center line
4.5' 4.5'
For the footing free-body:
Pa = R p = (3a )B
p e a
2 Pa
R p must be co-linear with Pa
such that the length of the
triangular pressure distribution
is equal to 3a . p
R p = Pressure resultant
a
Rp
3a
E
The load combination 0.9 D − , with Pa = 43.4 kips and M a = 136.5 k - ft (12-10)
1.4
governs bearing pressure
B
a= − e = 4.5 − 3.15 = 1.35 ft
2
Pa =
p
(3a ) B
2
or
2 1 2
= (43.4 )
1
p= Pa = 2.38 ksf < 1.33 p a = 3.20 ksf o.k.
3 aB 3 (1.35)(9.0)
If p had been greater than 1.33 p a , the footing size would have to be increased.
Finally, check the gravity load combination (12-12) for p < p a = 3.2 ksf .
M a = D + L = M D + M L = 15 + 6 = 21 k - ft (12-12)
Pa M a 110 21
p= + = + = 1.53 ksf < 3.2 ksf, o.k.
A S 81 121.5
All applicable load combinations are satisfied, therefore a 9ft x 9ft footing is
adequate.
Lateral bearing resistance p L = 150 psf × depth below grade Table 18-1-A
Assume the footing is 2 feet thick with its base 4 feet below grade. Average
300 + 600
resistance on the 2 feet deep by 9 feet wide footing face is = 450 psf .
2
2'
lateral loads to be used in the sliding
resistance calculations are: 600 psf
V E 30
Lateral load = = = 21.4 kips
1.4 1.4
The total resistance is then the sum of the resistance due to friction and the resistance
due to lateral bearing pressure.
∴ No sliding occurs
The section design must have the capacity to resist the largest moments and forces
resulting from these load combinations.
f1 = 0.5 §1612.2.1
Pu = 1.2 PD + 1.0 PE + 0.5PL = 1.2 (80) + 1.0 (40) + 0.5 (30) = 151 kips (12-5)
M u = 1.2 M D + 1.0 M E + 0.5M L = 1.2 (15) + 1.0 (210) + 0.5 (6) = 231 k - ft (12-5)