DOUBLE CHECK VALVE DC
TECHNICAL DATA
Nominal diameter: DN 50 - DN 600
Face-to-face: EN 558-1
ISO 5752
Flange accommodation: EN 485 PN 10/16
ASME Class 150
Flange Surface Design: EN 1092 Form A/B
ASME RF, FF
Marking: EN 19
Operating pressure: 16 bar ≤ DN 250
10 bar ≥ DN 300
Tightness check: EN 12266 (Leakage Rate A)
ISO 5208, Category 3
Temperature range: 0°C to +130°C (depending on
pressure, medium and temperature)
Standard construction:
TYP DC 1 DC 2 DC 3 DC 4 DC 5
Body EN-JS EN-JS 1.4408 Alu-Bronze EN-JS
1030 1030 C954 1030
Disc Alu-Bronze 1.4408 1.4408 Alu-Bronze EN-JS
C954 C954 1030
Shafts 1.4301 1.4301 1.4404 Alu-Bronze 1.4301
C954
FEATURES Springs 1.4571 1.4571 1.4401 2.4816 1.4571
Bearing NBR EPDM EPDM NBR EPDM
- Maintenance-free wafer double check valve
operating
- Can be disassembled, material-specific recycling possible
Lager PTFE PTFE PTFE PTFE PTFE
PRESSURE LOSS DIAGRAM DN 50 - DN 300
The values given in the diagram are valid for water
at 20°C. They result of measurements at valves
which are mounted in a horizontal conduction.
For the ascertainment of pressure losses for other
media, the water flow amount has to be calculated
0
0
0
0
0
50
15
30
80
10
20
25
with the following formular:
DN
DN
DN
DN
DN
DN
DN
Pressure loss p (mWs)
Wäp = √ YB x QB
1000
Wäp = equivalent water flow in m³/h
YB = flow amount of the media in its operating
conditions kg/m³
QB = volume of flow in operating condition (m³/h)
Volume of flow (I/sec)
DC 8.2
DOUBLE CHECK VALVE DC
INSTALLATION
vertical
horizontal
B
ØC right wrong
ØA
Double check valve DC
Dimensions [mm]
DN Size min. opening pressure Kv Weight
A B C R
[mm] [in] [mbar] [m³/h] [kg]
50 2 107 43 65 29 20 63 1,5
65 2½ 127 46 80 36 20 109 2,4
80 3 142 64 94 43 20 172 3,6
100 4 162 64 117 53 20 289 5,7
125 5 192 70 145 66 20 476 7,3
150 6 218 76 170 79 20 750 9,0
200 8 273 89 224 104 20 1550 17,0
250 10 328 114 265 127 20 2880 26,0
300 12 378 114 310 148 20 4100 42,0
350 14 438 127 360 172 30 5274 55,0
400 16 489 140 410 197 30 8250 75,0
450 18 539 152 450 218 30 10550 101,0
500 20 594 152 505 241 30 14500 111,0
600 24 695 178 624 295 30 24000 172,0
Installing the check valve on top of a pump please ensure that neither the valve is Subject to change without notice
mounted directly on the pump flange or the following bend or a smoothing section
of less than 5 x DN is observed.
For tight sealing of the DC a back pressure of not less than 1 bar is required.