The document contains settings for configuring an inverter according to different standards and grid codes. It lists protection parameters including voltage, frequency, and fault ride-through settings. Additional parameters related to reactive power support and active power limitation are also included.

Uploaded by

West Point
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
223 views4 pages

FRT Settings STP60 - Customer Setting-En-43

The document contains settings for configuring an inverter according to different standards and grid codes. It lists protection parameters including voltage, frequency, and fault ride-through settings. Additional parameters related to reactive power support and active power limitation are also included.

Uploaded by

West Point
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

Customer specific setting for STP 60-10 / STP 60-10-US

Plant name:
Contact data Name Date
Telephone
Email-Address Signature

Inverter model STP 60-10 STP 60-10-US

SW version Newest Other

Parent standard IEC 61727 BDEW G59/3 AS 4777 IEEE 1547 Other

The STP 60-10 can be configured in accordance with many country specifications. You can select the appropiate standard during the
commisioning of the inverters. However, if you want to get a specific plant setting, you need to fill out this form and send it to us
before commissioning.
First choose the standard that must be used as reference and then fill out the form only with the different values. The other values
will be set as in the parent standard. Please refer to the document "STP60-10-Parameter-TI" available in our website.
Contact your grid operator for the approval of the inverters with the specific setting. Otherwise you may face problems during the
commisioning. SMA Solar Technology AG is not responsible of the approval of specific settings.

Protection Settings
Short description of parameter Range / step size Parameter ID Value
Nominal grid voltage 220 - 277 / 1 [V] UNOM
Nominal grid frequency 50/60 [Hz] FNOM
Under voltage stage 2 (far) 23 - UMIN1 / 0.1 [V] UMIN2
Trip time for under voltage stage 2 0 - TUMIN1 / 0.01 [s] T_UMIN2
Voltage disconnection

Under voltage stage 1 (near) 23 - UNOM / 0.1 [V] UMIN1


Trip time for under voltage stage 1 0 - 600 / 0.01 [s] T_UMIN1
10 min. mean (EN 50160) UNOM - 350 / 0.1 [V] U10M_AVG
Trip time for 10 min. Mean 0 - 600 / 0.01 [s] T_U10M_AVG
Over voltage stage 1 (near) UNOM - 350 / 0.1 [V] UMAX1
Trip time for over voltage stage 1 0 - 600 / 0.01 [s] T_UMAX1
Over voltage stage 2 (far) UMAX1 - 350 / 0.1 [V] UMAX2
Trip time for over voltage stage 2 T_UMAX1 - 600 / 0.01 [s] T_UMAX2
Under frequency stage 2 (far) 45/54 - FMIN1 / 0.01 [Hz] FMIN2
Frequency disconnection

Trip time for under frequency stage 2 0 - T_FMIN1 / 0.01 [s] T_FMIN2
Under frequency stage 1 (near) 45/54 - 50/60 / 0.01 [Hz] FMIN1
Trip time for under frequency stage 1 0 - 6000 / 0.01 [s] T_FMIN1
Over frequency stage 1 (near) 50/60 - 55/66 / 0.01 [Hz] FMAX1
Trip time for over frequency stage 1 0 - 6000 / 0.01 [s] T_FMIN1
Over frequency stage 2 (far) FMAX1 - 55/66 / 0.01 [Hz] FMAX2
Trip time for over frequency stage 2 T_FMAX1 - 600 / 0.01 [s] T_FMAX2
Connection / Re-connection time (>T_SHT_INT) 0 - 1200 / 0.01 [s] T_CON
Re-connection time (<T_SHT_INT) 0 - 1200 / 0.01 [s] T_RECON
(re-) Connection

Maximum time for a short interupt 0 - 1200 / 0.01 [s] T_SHT_INT


Connection/reconnection ramp rate 0.6 - 1200 / 0.01 [%/min] RmpIncTmm_ONLINE
Minimum connection voltage UMIN1 - UNOM / 0.1 [V] UMIN_CON
Maximum connection voltage UNOM - UMAX1 / 0.1 [V] UMAX_CON
Minimum connection frequency FMIN1 - FNOM / 0.01 [Hz] FMIN_CON
Maximum connection frequency FNOM - FMAX1 / 0.01 [Hz] FMAX_CON
Active frequency shift (1: on, 0: off) [bool] LOM_F_SHF_K0 / _K1
Loss Of
Mains

Rate of Change of Frequency 0.1 - 5 / 0.01 [HZ/s] LOM_ROC


Trip time for RoCoF 0 - 1200 / 0.01 [s] T_LOM_ROC
RoCoF threshold 0 - 5 / 0.01 [Hz] LOM_ROC_THR

v 4.2 SMA Solar Technology AG 1/4


Auxiliary Support Settings
Short description of parameter Range / step size Parameter ID Value

FRT mode (0:off, 1:zeroCurrent, 2:Q_CurrentOnly,


3:P_CurrentOnly, 4:fullCurrent_Q_Priority, 5: [int] FRT_MODE
fullCurrent_P_Priority)
Fault Ride Through

FRT dI/dU gain (k-factor) for Positive Sequence in HVRT 0 - 10 / 0.1 [/] FRT_DIDU_POS_HVRT
FRT dI/dU gain (k-factor) for Positive Sequence in LVRT 0 - 10 / 0.1 [/] FRT_DIDU_POS_LVRT
FRT reactive current curve type (0: BDEW, 1: SDL-Wind) [int] FRT_IQ_MODE
FRT blocking zone time 0 - 10 / 0.01 [s] FRT_T_BLK
FRT transition time 0 - 10 / 0.01 [s] FRT_T_TRANS
FRT lower threshold voltage 10 - 100 / 0.01 [%] FRT_ULOW
FRT upper threshold voltage 100 - 130 / 0.01 [%] FRT_UUP
FRT power recovery time 0 - 10 / 0.01 [s] FRT_T_P_RECOV
Mode Select (1: Q(U), 2: Q(P), 3: Q(S), 4: Q(T), 5: Qext, 6: PF(P),
[int] ModeSelect
Basic Settings

7: PF(U), 8: PF(T), 9: PFext )


Night mode selection (0:false, 1:true) [bool] NightMode
Active power limitation for reactive power support 80 - 100 / 0.01 [%] P_LIM_IF_Q
Nominal apparent power at point of common coupling 60 - 2400 / 0.1 [kVA] Sgrid_nom
Voltage drop between PCC and generator 0 - 1000 / 0.1 [V] UNOMOffset
Maximum reactive power reduction rate -1200 - 0.6 / 0.01 [%/min] RmpDecTmm_Q
Immediate Controls

Maximum reactive power increase rate 0.6 - 1200 / 0.01 [%/min] RmpIncTmm_Q
Reduction rate of power after external setpoint change -1200 - 0.6 / 0.01 [%/min] RmpDecTmm_EXT
Increase rate of power after external setpoint change 0.6 - 1200 / 0.01 [%/min] RmpIncTmm_EXT
Maximum active power 0 - 100 / 0.01 [%] P_ref
Maximum reactive power -100 - 100 / 0.01 [%] Q_ref
Maximum power factor -0.8…1...0.8 / 0.01 [/] PF_ref
Maximum apparent power 0 - 100 / 0.01 [%] S_ref
Activation of the Fallback function (0=disable, 1=enable) 0-1 [int] FallbackEnabled
Activation time after a communication loss 2 - 20 [s] FallbackDelay
function
Fallback

Duration of the fallback function 0 - 604800 [s] FallbackMaxDuration


P reference 0 - 100 / 0.01 [%] FallbackPref
Q reference 0 - 100 / 0.01 [%] FallbackQref

Reactive Power Modes


The time of the PT1 low pass filter 0.6 - 3600 / 0.01 [s] RmpTmsPT1_UQ
Limit of active power for activation of Q(U) 0 - 100 / 0.01 [%] lock_in_UQ
Reactive power as a function of voltage

Limit of active power for deactivation of Q(U) 0 - 100 / 0.01 [%] lock_out_UQ
Curve of Q(U) for decreasing U (hysteresis) Q range : -60 to 60 % / 0.01
Curve of Q(U) for increasing U U range: 80 to 120 % / 0.01
Q_of_U_dec Q_of_U_inc 60
Mode #1

40
20
0
80 90 100 110 120
-20
-40
-60
Mode #2 Reactive power as a function of active power. Contact us if you want to use this mode
Mode #3 Reactive power as a function of apparent power is editable via the ramps and reference points given under Immidiate
Mode #5 Constant reactive power is editable via the ramps and reference points given under Immidiate Controls

v 4.2 SMA Solar Technology AG 2/4


The time of the PT1low pass filter. 0.6 - 3600 / 0.01 [s] RmpTmsPT1_PPF
Grid voltage limit for activation of PF(P) support 80 - 120 / 0.01 [%] lock_in_PPF
Grid voltage limit for deactivation of PF(P) support 80 - 120 / 0.01 [%] lock_out_PPF
Power factor as a function of power

Curve of PF(P) for decreasing P (hysteresis) PF range: +- 0.8 to 1 / 0.0001


Curve of PF(P) for increasing P P range: -100 to 100 % / 0.01
PF_of_P_dec PF_of_P_inc
0,2
0
Mode #6

0
0,1 0
0
0 0
-100 -50 0 50 100
0
0
-0,1
0
0
-0,2 0
Mode #7 Power factor as a function of voltage. Contact us if you want to use this mode.
Mode #9 Constant power factor is editable via the ramps and reference points given under Immidiate Controls

Active Power control


The time of the PT1low pass filter. 0.6 - 3600 / 0.01 [s] RmpTmsPT1_UP
Power reduction in responce to changes in voltage -1200 - 0.6 / 0.01 [%/min] RmpDecTmm_UP
Power increasing in responce to changes in voltage 0.6 - 1200 / 0.01 [%/min] RmpIncTmm_UP
Active power as a function of voltage

Curve for decreasing power - voltage P range: -100 to 100 % / 0.01


Curve for increasing power - voltage U range: 80 to 120 % / 0.01
P_of_U_dec P_of_U_inc 100

50

0
80 90 100 110 120
-50

-100
Max. active power reduction rate if f change 0.6 - 3600 / 0.01 [%/min] RmpIncTmm_FPReg
Delay between disturbance and start of P increase 0 - 600 / 0.01 [s] tdelay_off
Delay between disturbance and start of P decrease 0 - 2 / 0.01 [s] tdelay_on
Active power as a function of frequency

Modeselector for rate limit [bool] variable


Curve of P(f) for decreasing f (response) P range: 0 to 100 % / 0.01
Curve of P(f) for increasing f (response) f range: 47.5 to 52 Hz / 0.01
FP_of_f_dec FP_of_f_inc 100

80

60

40

20

0
47,5 48,5 49,5 50,5 51,5

v 4.2 SMA Solar Technology AG 3/4


Combination 0 to 31 Combination 32 to 63

Re y 1
Re y 2
Re y 3
Re y 4
Re y 5
6

Re y 1
Re y 2
Re y 3
Re y 4
Re y 5
6
lay

lay
P Q PF P Q PF
la
la
la
la
la

la
la
la
la
la
Re

Re
0 0 0 0 0 0 0 32 1 0 0 0 0 0
1 0 0 0 0 0 1 33 1 0 0 0 0 1
2 0 0 0 0 1 0 34 1 0 0 0 1 0
3 0 0 0 0 1 1 35 1 0 0 0 1 1
4 0 0 0 1 0 0 36 1 0 0 1 0 0
5 0 0 0 1 0 1 37 1 0 0 1 0 1
6 0 0 0 1 1 0 38 1 0 0 1 1 0
7 0 0 0 1 1 1 39 1 0 0 1 1 1
8 0 0 1 0 0 0 40 1 0 1 0 0 0
9 0 0 1 0 0 1 41 1 0 1 0 0 1
10 0 0 1 0 1 0 42 1 0 1 0 1 0
11 0 0 1 0 1 1 43 1 0 1 0 1 1
12 0 0 1 1 0 0 44 1 0 1 1 0 0
13 0 0 1 1 0 1 45 1 0 1 1 0 1
PLA option

14 0 0 1 1 1 0 46 1 0 1 1 1 0
15 0 0 1 1 1 1 47 1 0 1 1 1 1
16 0 1 0 0 0 0 48 1 1 0 0 0 0
17 0 1 0 0 0 1 49 1 1 0 0 0 1
18 0 1 0 0 1 0 50 1 1 0 0 1 0
19 0 1 0 0 1 1 51 1 1 0 0 1 1
20 0 1 0 1 0 0 52 1 1 0 1 0 0
21 0 1 0 1 0 1 53 1 1 0 1 0 1
22 0 1 0 1 1 0 54 1 1 0 1 1 0
23 0 1 0 1 1 1 55 1 1 0 1 1 1
24 0 1 1 0 0 0 56 1 1 1 0 0 0
25 0 1 1 0 0 1 57 1 1 1 0 0 1
26 0 1 1 0 1 0 58 1 1 1 0 1 0
27 0 1 1 0 1 1 59 1 1 1 0 1 1
28 0 1 1 1 0 0 60 1 1 1 1 0 0
29 0 1 1 1 0 1 61 1 1 1 1 0 1
30 0 1 1 1 1 0 62 1 1 1 1 1 0
31 0 1 1 1 1 1 63 1 1 1 1 1 1
Backup value
IO select (off:0 on:1) 0 [bool]
Fallback if connection to IO box is lost

v 4.2 SMA Solar Technology AG 4/4