5 Paper - Load Blinder
5 Paper - Load Blinder
In today’s modern power systems, the radial approach Typical sub-transmission protection schemes often
to generation is rapidly being supplemented with a more employ plain distance protection without any channel
meshed / bi-directional topology. Power generation is aided schemes for clearing all line faults. Intertripping is
moving closer to the load centres at the distribution end frequently used to open the LV breaker of the load
of the system and introducing numerous problems in the transformer to prevent any back-feed from the embeded
process. A major issue facing the Distribution Network generation and the adjacent unfaulted line. The DOC
Operators (DNO’s) is the reverse load flow that occurs protection provides back-up against HV faults if the
when the embedded generation exceeds the local intertripping scheme fails to operate due to an
demand. Excess generation forces reverse load current interruption in communications. Generally a DOC
to flow back on to the sub-transmission network setting of 0.5IN ensures adequate sensitivity for faults at
(typically 132kV), which has an impact on the back-up the remote feeding ends near to CB1 and CB2 (see
DOC relays situated on the transformer LV side. Failure Figure 1).
to raise the current threshold of the DOC relay will
Figure 1 clearly illustrates the protection philosophy
inevitably result in a mal-operation of the protection
commonly employed by the DNO’s for their 132kV
when the reverse load is excessive. However, increasing
lines. It can be seen that a fault at F1 would be cleared
the current threshold compromises the sensitivity of the
by the main protection relays at CB1 and CB2, with the
back-up protection that the DOC relays provide,
intertripping scheme providing the LV clearance of the
resulting in potential “blind-spots” for distant faults on
back-feed via CB4. The protection and intertripping
the sub-transmission network.
scheme associated with CB2 and CB4 is also replicated
One solution currently being employed by some DNO’s on CB1, thus completing the scheme for a single 132kV
is to limit the reverse load flow on to the sub- feeder.
transmission network by means of multi-stage
intertripping. Each stage is associated with a level of
reverse power flow, the first of which may be an alarm
to warn the supplier to curtail the generation. The
second stage would be configured as a time delay trip
should the generation remain unchanged.
Whilst this approach eliminates the problem from a
protection perspective, it does restrict the export
generation to areas further afield. This may be
1
particularly for faults at the extremities of the 132kV
line. In extreme circumstances the fault current
CB1 132kV Network CB2 magnitudes, when back-fed through the parallel
Bulk Supply transformers, can be as low as full load current,
MAIN Point particularly if the fault is not solid in nature. It is for
PROT
Overload
Embedded Time Characteristic
LV Load Inter-connector generation
Fault
Figure 3- Effects of reverse load flow from Characteristic
embedded generation on DOC relays
Current
K.Is Is
5. BENEFITS OF LOAD BLINDING ON DOC Time
RELAYS DURING REVERSE LOAD FLOW Min. IF Max. IF
CONDITIONS K
3
Both techniques described above provide adequate To prevent operation of the DOC protection during
back-up protection providing the user is comfortable heavy export conditions, MiCOM AGILE relays
with the idea of abandoning the conventional DOC employ a load blinder which is based upon the
protection. The following section introduces a method measured positive sequence impedance (Z1 = V1/I1).
that permits conventional DOC setting procedures to be The resulting measurement is compared with a settable
maintained, whilst maintaining the performance characteristic to ascertain the location of the impedance.
advantages of the DVCO protection above. Directional overcurrent protection will be inhibited if
Z1 falls with the load portion of the characteristic
5.2 Load blinding defined by two settings. One setting defines the
minimum load impedance (ZMIN) and the second defines
Load blinding is a technique that most engineers the maximum load angle (), which is dictated by the
experienced in setting distance protection relays will be power factor of the load. Whilst this application only
familiar with. The principle relies upon the change in requires the DOC protection to be inhibited in the
impedance measured by the relay during load and fault export region, MiCOM AGILE relays also replicates the
conditions. Under normal load conditions the measured characteristic in the import region if required. Figure 6
impedance resides in one of two regions, depending clearly illustrates the load blinder characteristic and its
upon whether power is being imported or exported associated settings.
through the relaying point. Referring to Figure 5 below,
it can be seen that during periods of imported power the
system impedance will be situated in the load locus on jX
the left hand side. Conversely, during export periods the
impedance will be situated in the locus on the right hand
side. It can also be seen that for a fault at F1 the ZMIN
impedance quickly migrates from one of the load loci to Load Load
a position equal to ZT-B plus ZLINE-B, as denoted in the Locus Locus
R
diagram. It is this migration of impedance, together with (Import) (Export)
the direction of current flow during import and export
conditions, which form the basis of the load blinding
principle.
ZLINE-A
the fault, the voltage collapse is primarily governed by ZLINE-B Bulk Supply
the ratio between the impedances in front and behind Point (ZSHV)
the relay. These ratios will vary depending upon the
ZT-A ZT-B F1
strength of the embedded generation; hence to select the
most appropriate voltage threshold (V<) we must
consider two different scenarios:
1) Back fed HV fault with no embedded DOC
generation CB3
2) Back fed HV fault with maximum embedded Embedded
generation LV Network generation
(ZSLV)
It must be noted that the derivation of the fault voltage
(VF) and current (IF) under both of these conditions Inter-connector
assumes that the faulted line has been tripped on the HV
side and the fault is being back fed via the LV. Figure 9
ZSHV ZLINE-A ZT-A ZT-B ZLINE-B
illustrates the equivalent circuit for calculating the fault
voltage (VF) and current (IF) at the relaying point. The
equivalent circuit gives the following equations for VF ZA
and IF for a three phase fault at F1:- ZSLV F1
VS (pu)
I F I BASE- LV
ZA //ZSLV ZTB ZLINE
ZTB ZLINE ZA
VF VS (pu) VBASE- LV
ZA //ZSLV ZTB ZLINE
ZT-B ZLINE-B
ZSLV
IF
Where: VS
VF
VS (pu) = Per unit source voltage
IBASE-LV = Base current on LV side
Figure 9- Equivalent circuit for HV 3ph fault at F1
VBASE-LV = Base voltage on LV side
with CB1 and CB2 open
Impedances = All in (pu), see Figure 9 for details
6
6.3 Problems with under voltage threshold during To ensure the load blinder is inhibited at I S or above we
unbalanced faults must assume that IS = IF.
To ensure that the relay disables the load blinder at a Where: a = 1120° = - 0.5 j 3
value of current greater than or equal to the DOC 2
threshold (IS), the analysis will evaluate the negative a2 = 1240° = - 0.5 j 3
sequence as a multiple of IS for the above conditions, 2
taking in to account a 30° vector shift through the Hence:
transformer. The negative sequence threshold must then
be set to the lowest value calculated for the above three IS = I1(1240° x 1-30° + 1120° x 1210°)
fault types.
IS = I1(1210° + 1-30°)
6.4.1 Phase to ground: IS = I1 3 j0.5 3 j0.5 = -jI1
2 2
During phase to ground faults it can be shown that the
positive (I1), negative (I2) and zero sequence (I0) and |I1| = |I2|
currents are of equal magnitude and phase [3].
However the delta / star transformer, between the relay Hence for phase to phase faults the I2 threshold must be
and the fault, effectively eliminates the I0 component set to:-
and causes the I1 and I2 components to shift by 30° in
opposite directions. This results in the following :- I2 threshold = IS
I1 at relaying point, I1R = I1-30° = I1 3 j0.5 However, since this is greater than the value calculated
2 for the phase to ground fault condition, the phase to
I2 at relaying point, I2R = I2+30° = I2 3 j0.5
ground value of 0.577IS should be selected, to ensure
2 operation for both of the above fault conditions. Now
7
let us consider the impact of double phase to ground Referring to Figure 10, it is clear that the negative
faults. sequence current I2 magnitude is heavily dependent
upon Z0. Assuming the embedded generation is
6.4.3 Phase to phase to ground: disconnected (ZSLV = ∞) and that the two transformers
impedances dominate, it can be shown that the Z2 will
Unlike the previous two fault conditions, the negative
be approximately 2Z0. This results in a minimum I2
sequence current threshold requirement is no longer a
component of approximately 1/3∙I1, with the ratio
fixed proportion of the fault current when a double
increasing as the fault resistance RF gets larger.
phase to ground fault is considered. This is consequence
of the split of currents between the negative and zero
I2 = 1/3∙I1180° hence: |I1| = |3I2|
sequence networks, which is governed by the ratio of Z2
and Z0, together with any intervening arc resistance RF.
I1 at relaying point, I1R = I1-30° = 3I2 3 j0.5
ZLINE-A 2
132kV Network
= I2 3 3 j1.5
CB1 CB2
8
6.5 Summary of load blinder settings and DOC
settings
8. REFERENCES